Broan SP200 Installation Manual

MODELS SP100, SP140 & SP200 SINGLE-PORT IN-LINE VENTILATORS
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOW­ING:
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel­burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire
WARNING
Protection Association (NFPA), and the American Soci­ety for Heating, Refrigeration and Air Conditioning Engi­neers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbal­anced impellers, keep drywall spray, construction dust, etc. off power unit.
3. If ventilator is installed in an unconditioned space (such as an attic): Surround the ventilator with thermal insulation - to minimize possible condensation.
4. Please read specification label on product for furth er information and requirements.
PLAN THE INSTALLATION
Adequate ventilation requires that both intermittent and continuous contamination be controlled.
Intermittent ventilation must be provided in the bathroom and kitchen. The bathroom requires 8 air changes per hour. (Multiply bathroom sq. footage by 1.1 for proper fan sizing.) The kitchen requires a minimum of 150 CFM capacity (71 l/s) when a ducted range hood is used. If a kitchen fan is used, determine fan capacity by multiplying the room's sq. footage by 2. All are run intermittently to control pollution at the source.
Continuous ventilation, while the house is occupied, pro­vides the flow of fresh air for good indoor air quality.
RECOMMENDED VENTILATOR SIZING
DWELLING SIZE RANGE (Sq. Ftg.)
(include finished basement area)
MODEL SP100
SP140 SP200
*AC/HR = Air Changes per Hour. Based on 8' ceilings. Square Feet x .093 = Square Meters
.50 AC/HR* .35 AC/HR* .30 AC/HR*
1500 2140 2500 2100 3000 3500 3000 4285 5000
PLAN THE INSTALLATION
LOCATION OF DIFFUSERS & INLETS
FRESH AIR
STALE AIR
VENTILATOR
DIFFUSER
INLET
FRESH AIR
AIR FLOW IN TYPICAL INSTALLATION
VENTILATOR
The ventilator exhausts stale air. There are normally suffi­cient natural intake openings into a dwelling to admit fresh outside air to be drawn in to replace the stale air. For better control, fresh air inlets may be used.
SINGLE-STORY HOME
FRESH AIR INLETS
DUCTED KITCHEN RANGE HOOD
DIFFUSER
DUCTED
BATH FAN
FRESH AIR INLETS
The ventilator should be centrally located to keep ductwork as short as possible. Locations for the ventilator include: joists in an attic space or the basement, or a wall away from the living areas.
EXHAUST DIFFUSERS (Available separately)
Exhaust diffusers regulate the flow of fresh air drawn through the house.
Exhaust diffusers should be mounted in the ceilings or high on the wall.
For best performance, exhaust diffusers should be mounted in a central location. An exhaust diffuser should not be installed near a cooking area. (see figure)
FRESH AIR INLETS (Available separately)
For best control of fresh air in a room, install a fresh air inlet.
The number of inlets depend on the floor plan. Consider the rooms/areas through which fresh air should flow toward the exhaust diffuser(s).
COOKING AREA
Do not install above
or inside this area
45
Cooking
Equipment
45
Floor
Inlets should be located in outside walls, preferably near the ceiling. Each inlet should be approximately the same distance from a diffuser. Inlets should be separated from diffusers far enough to allow fresh air to mix with room air before being exhausted.
INSTALL FRESH AIR INLETS
CONNECT DUCTWORK
1. Mount all fresh air inlets in chosen locations during rough-in construction. Follow directions packed with inlets.
MOUNT THE VENTILATOR
CEILING JOISTS
2 X 4 FRAMING
OR
DUCT
FROM DIFFUSER
6" ROUND INSULATED FLEXIBLE DUCT
TAPE OR CLAMP
OUTLET SIDE
TO ROOF OR WALL CAP
1. Run 6" insulated, flexible ductwork from ventilator inlet to diffuser location(s) and from ventilator outlet to roof or wall cap. Outlet side is marked with a label.
2. To minimize condensation inside of ductwork in the at­tic, cover ductwork with additional insulation. Also, avoid forming condensation traps in the ductwork runs.
3. Seal ductwork to ventilator and roof or wall cap with duct tape or clamp (available separately)
CEILING JOISTS
2 X 4 FRAMING
1. Add framing to ceiling joists as shown.
2. Set ventilator in place and screw it to framing with screws provided. Ventilator may also be hung from ceiling joists or rafters with hanging straps (available separately).
WIRE THE VENTILATOR
WARNING: DISCONNECT POWER AT SERVICE ENTRANCE AND LOCK OUT SERVICE PANEL TO PREVENT POWER FROM BEING SWITCHED ON ACCIDENTALLY.
GROUND WIRE
BLACK
WHITE
GROUND (Green or Bare Wires)
120 VAC LINE IN
BLACK
BLACK
Use an ON/OFF switch to control the in-line ventilator. Accessory timers and humidity controls are also available.
1. Remove the wiring adapter plate.
2. Attach power cable to wiring adapter plate using U.L./ CSA approved connector.
3. Connect black to black, white to white, and green or bare wire to green ground screw.
4. Replace wiring adapter plate. Make sure tab on housing slides through slot in plate.
WIRING ADAPTER
PLATE
ON/OFF SWITCH
Loading...
+ 5 hidden pages