FOR USE WITH RANGEMASTER HOODS AND ECLIPSE DOWNDRAFT VENTILATORS
Page Lm1
READ AND SAVE THESE INSTRUC
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY
TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment
manufacturer's guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall, or ceiling, do not damage
electrical wiring or other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce risk of fire, use only metal ductwork.
8. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive material and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
3. Please read specification label on product for further information and requirements.
4. Electrical circuit, including speed control, (if used), must be
rated 6 AMPS minimum for Model 332H or 3 AMPS minimum
for Model 331H.
1. Locate the blower so the length of the duct run and number of
Please note - when using blower with the Broan Eclipse
ALL INSTALLATIONS
elbows and transitions needed are kept to a minimum.
Downdraft: The downdraft has a 3¼" x 10" discharge. Transitions are available to connect it to the 10" round inlet on
this exterior-mounted blower.
TYPICAL ROOF MOUNTED INSTALLATION
(Vertical discharge)
INSTALLER: Leave This Manual With The Homeowner
HOMEOWNER: Use And Care Information On Page 3
TYPICAL WALL MOUNTED INSTALLATION
(Vertical discharge - elbow to horizontal)
2. Where possible, blower should be centered between wall studs
or roof rafters.
3. Avoid pipes, wires, or other ductwork that may be running
through the wall.
4. Be sure that there is enough space for any transitions that may
be needed between the blower and the connecting ductwork.
5. For best performance, locate transitions nearest to ventilator
(i.e. downdraft).
NOTE: Horizontal discharge requires relocation of the duct opening
cover plate. See hood manual for instructions.
TYPICAL WALL MOUNTED INSTALLATION
(Horizontal discharge)
11" dia.
hole
7¼"
1¼"
dia. hole
91/8"
10¾"
24¾"
28¼"
Wall Stud
127/8"
Wall Stud
REMOVE
SIDING
8½"
Pilot
Hole
Pilot
Hole
OUTSIDE - WALL VIEW
6¾"
2"
28¼ "
24 ¾"
2"
20½"
103/8"
8½"
20¾"
7¼"
1¼"
dia. hole
91/8"
Roof Rafter
REMOVE
SHINGLES
11"
dia.
hole
Roof Rafter
Pilot
Hole
Pilot
Hole
OUTSIDE - ROOF VIEW
PREPARE THE INSTALLATION
LOCATION
PREPARE THE INSTALLATION
LOCATION
2
ROOF INSTALLATIONS
1. Locate the blower on the rear slope of the roof.
Place it in a location to minimize duct run. The
location should be free of obstacles (T.V. leads,
electrical lines, etc.). Bear in mind, if the blower
top is level with the roof peak, it will not be seen
from the street. Keep this approximate location in
mind as you work from within the attic.
Figure 1
WALL INSTALLATIONS
1. Choose a position on the outside wall. Make sure
that no wall studs, pipes or wires run through the
opening area.
Figure 3
From inside the attic space:
2. Drill a PILOT HOLE up through the roof, 8½" from
the inside edge of a ROOF RAFTER.
From outside - on the roof:
3. Measure and mark the 20¾" x 20½" rectangle.
Cut and remove only the shingles inside this
rectangle.
4. Measure and mark the 11" DIAMETER HOLE
and the 1¼" DIAMETER HOLE. Cut these holes
all the way through the roof.
Figure 2
5. For flat roof installations, build a curb that will mount
the blower at a minimum pitch of 2/12. See Figure
2. Discharge end of the blower should be pointed
away from prevailing winds.
From inside the wall:
2. Drill a PILOT HOLE through the wall, 8½" from
the inside edge of a WALL STUD.
From outside - on the wall:
3. Measure and mark the 24¾" x 28¼" rectangle. Cut
and remove only the siding inside this rectangle.
4. Measure and mark the 11" DIAMETER HOLE and
the 1¼" DIAMETER HOLE. Cut these holes all
the way through the wall.
PREPARE THE BLOWER
ALL INSTALLATIONS
1. Unpack the blower assembly.
2. Remove the cover and screws.
3. Remove and discard cardboard from blower wheel.
4. Remove the wiring box cover and screws.
5. Attach an appropriate CSA approved cable con-
nector in the hole at the rear of the wiring box.
INSTALL THE BLOWER
INSTALL THE BLOWER
3
ROOF INSTALLATIONS
1. Remove roofing nails from the upper 2/3 of the
shingles around the cutout area and carefully lift
the shingles to allow the back flashing sheet on the
blower housing to fit under them.
2. Center the blower ring in the 11" diameter hole,
making sure that the 1-1/4" diameter electrical wiring hole aligns with the hole in the wiring box.
3. Attach the blower to the roof with the six screws
provided. All six holes in the back panel must be
filled, or any moisture that may get inside the housing could leak into the house.
4. Using a good grade of roofing cement, seal all of
the shingles around the housing and flashing sheet
as well as the mounting screw heads.
5. Bring electrical wiring through the hole in the wiring
box and secure it according to local codes.
Figure 4
WALL INSTALLATIONS
1. Place a large bead of caulk on the back side of
the housing along the outer edge.
2. Center the blower ring in the 11" diameter hole,
making sure that the 1-1/4" diameter electrical
wiring hole aligns with the hole in the wiring box.
3. Attach blower to the wall with the six screws provided. All six holes in the back panel must be filled,
or any moisture that may get inside the housing
could leak into the house.
4. Using a good grade of caulk, seal all around the
mounting screw heads.
5. Bring electrical wiring through the hole in the wiring
box and secure it according to local codes.
6. Make the electrical connections with the proper
connector for the type of wire being used. Connect
white to white, black to black, and green or bare
wire to green. See Figure 4.
6. Make the electrical connections with the proper
connector for the type of wiring being used. Connect white to white, black to black, and the green
or bare wire to green. See Figure 4.
7. Replace wiring box cover and screws. Do not pinch
wiring under the cover.
7. Replace wiring box cover and screws. Do not pinch
wiring under cover.
8. Check for free movement of the damper before
installing housing cover and screws.
9. Turn on power and check operation of the blower.
10.Top and side flanges of the back plate may be
covered with trim strips. Do not block grille opening at bottom with trim. It will adversely affect
performance of the blower.
USE AND CARE
Disconnect electrical power supply and lock out service
panel before cleaning or servicing this unit.
CLEANING
Remove cover and carefully vacuum blower and inside of housing. Be careful not to bend or otherwise
damage blower wheel.
8. Check for free movement of the damper before
installing housing cover and screws.
9. Turn on power and check operation of the blower.
MOTOR LUBRICATION
The motor is permanently lubricated. Do not oil or
disassemble motor.
* Standard Hardware - May be purchased locally.
Always order replacement parts by Part No., not Key No.
6
10
17
4
3
1
4
8
5
15
11
19
18
18
Broan-NuTone warrants to the original consumer purchaser of its
products that such products will be free from defects in materials or
workmanship for a period of one year from the date of original purchase.
THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During this one-year period, Broan-NuTone will, at its option, repair
or replace, without charge, any product or part which is found to be
defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP
STARTERS AND TUBES. This warranty does not cover (a) normal
maintenance and service or (b) any products or parts which have
been subject to misuse, negligence, accident, improper maintenance
or repair (other than by Broan-NuTone), faulty installation or installation contrary to recommended installation instructions.
The duration of any implied warranty is limited to the one-year period
as specified for the express warranty. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation
may not apply to you.
BROAN-NUTONE’S OBLIGATION TO REPAIR OR REPLACE, AT
BROAN-NUTONE’S OPTION, SHALL BE THE PURCHASER’S
SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY.
BROAN-NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF
OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE.
Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may
not apply to you.
This warranty gives you specific legal rights, and you may also have
other rights, which vary from state to state. This warranty supersedes
all prior warranties.
To qualify for warranty service, you must (a) notify Broan-NuTone at
the address or telephone number below, (b) give the model number
and part identification and (c) describe the nature of any defect in
the product or part. At the time of requesting warranty service, you
must present evidence of the original purchase date.