Installation Instructions
for the
PIR Motion Detector
with POPIT Interface
1.0 Specifications
• Input Power: Connect to the Zonex Bus of the
control panel.
• Current Draw: Less than 1.7 mA during alarm
condition.
• Standby Power: There is no internal standby battery.
Connect to DC power sources
capable of supplying standby power
if primary power fails. 1.7 mAh are
required for each hour of standby
time needed. Four hours
minimum is required for then UL
Listed requirements.
• Coverage:
Standard Broad 15 m by 15 m (50 ft by 50 ft)
Barrier (Optional): 24.4 m by 4.8 m (80 ft by 16 ft)
Long Range (Optional): 36.6 m by 3.1 m (120 ft by 10 ft)
• Sensitivity: Standard, Intermediate, or High
• Tamper: A tamper condition is signaled
through the Zonex Bus and displayed
at the keypads when the cover is
removed.
• Temperature: The storage and operating range is
-29°C to +49°C (-20°F to +120°F).
For UL Listed requirements, the
range is 0°C to +49°C
(+32°F to +120°F).
• Requirements: Compatible Bosch Security Systems
control panel with the POPEX Module
installed.
• Options: B328 Gimbal Mount Bracket,
B335 Low Profile Swivel Mount
Bracket, Ceiling Mount Bracket,
OMB77-3* Barrier Mirror,
OMLR77-3* Long Range Mirror, and
the TC6000 Test Cord.
* Shipped in packages of three.
Note: When using an optional mounting bracket, detector
misalignment can reduce range.
ï
Reading Bosch Security Systems, Inc. Product Date Codes
For Product Date Code information, refer to the Bosch Security
Systems, Inc. Web site at: http://www.boschsecurity.com/
datecodes/
2.0 Programming
Program the address DIP switches as described for the control panel
you are using.
Note: Place switch number 0 in the ON position when installing
the ZX776Z with a D7212B1, D8112, or D9112B1.
The recommended point type programming is:
• D8112 = 7571
• D9112B1/D7212B1 = Point type 2, point response 2, no ring
until restored
• D9412/D9112 = Point type 2, point response E, no ring until
restored
Avoid
Direct Hot and Cold Drafts, Windows,
Small Animals, Air Conditioner Outlets,
Heat Sources, Direct Sunlight
Remember
Does not detect through glass.
Best catch performance is across
When using two or more detectors,
cross patterns for best coverage.
the pattern.
3.0 Mounting
• Select a location that is most likely to intercept an intruder
moving across the coverage pattern. The recommended
mounting height range is 2.0 m to 2.6 m (6.5 ft to 8.5 ft).
Note: Ensure the mounting surface is solid and vibration free.
T-Strip
Program
Plugs
LED
0 1 2 3 4 5 6
Figure 1: Circuit Board Components
Address
Switches
DO
NOT USE
Noise
Voltage
Tamper
Switch
Corner
Mounting
Hole
Surface Mounting Hole
Bracket
Mounting Hole
Surface Mounting Hole
Figure 2: Detector Enclosure (Rear View)
Corner
Mounting
Hole
• Adjust by sliding the mirror forward or backward until the angle
adjustment markings are in line with the markers on each side
of the frame.
• Use Figure 3 to identify the correct vertical angle based on
mounting height (X), mirror type, and maximum range (Y).
• Adjust the mirror horizontally by rotating (aiming) it from side to
side.
• Walk test the unit as described in the Section 6.0 Setup and
Walk Testing.
4.0 Wiring
Only apply power after all connections are made and
inspected.
Connect wiring as shown in Figure 4.
POPEX MODULE
–
–
+
+
(+)
(–)
ZONE EXPANSION LOOP
TO OTHER POINTS
• Remove the cover. Insert a thin flathead screwdriver into the
notch at the bottom of the cover and pry up.
• Remove the circuit board/mirror unit from the enclosure. Push
the board/mirror unit toward the top of the enclosure until it
clears its four retainer tabs, then lift it out.
• Open the knockout wire entrance and route the wiring through.
3.1 Surface or Corner Mounting
• Open two holes for surface or corner mounting.
• Mark the location for the mounting screws. Use the enclosure
as a template. Pre-start the mounting screws.
• Firmly mount the detector.
• Replace the circuit board/mirror unit.
3.2 Mirror Alignment
Note: Touching the mirror surfaces can lead to performance
degredation.
For the best performance, the mirror must be adjusted vertically for
the maximum desired detection range (distance) and mounting
height. The angle adjustment markings are located on both sides of
the mirror (see Figure 3).
MIRROR
ANGLE
ADJUSTMENT
Y
X
X m(ft)
Y m(ft)
2.0 (6.5)
2.3 (7.5)
2.6 (8.5)
5
(16)7(23)9(30)11(36)13(43)15(50)
-10°
-15° -8° -7 ° -6° -5°
-16° -12° -10° -8° -7° -6°
-8°-9°-10°-12°-15°-17°
Figure 3: Mirror Alignment
2134
+IN+
OUT-IN-OUT
Figure 4: Wiring
4.1 Terminal Descriptions
1 (+), 2 (+), 3 (-), and 4 (-): Connect to the Zonex Bus of the control
panel. Use no smaller than 0.8 mm (#22 AWG) wire between the
detector and the control panel.
5.0 Program Jumpers
The LED is only for Walk T est. Disable the LED by turning
Switch 1 off for normal operation. Failure to turn off the
LED results in a Zonex malfunction.
The following functions are controlled by various settings of the
program jumpers:
• LED Operation:
- ON: Allows the LED to operate when activated by alarm.
- OFF: The LED does not operate on alarm.
• Sensitivity Mode:
- Standard: Recommended setting for maximum false alarm
immunity. Tolerates environmental extremes on this setting.
Not recommended for Long Range or Barrier type patterns.
The detector is shipped in Standard Sensitivity Mode.
- Intermediate: Recommended setting for any location where
an intruder is expected to cover only a small portion of the
protected area. Tolerates normal environments on this setting.
This setting improves your intruder catch performance.
- High: Setting for fast response to intruder signals. For use in
quiet environments where thermal and illumination transients
are not anticipated.
Page 2 © 2012 Bosch Security Systems, Inc. ZX776Z Installation Instructions