Bosch GCC24-CR, GCC24-CW, GCS24-CR, GCS24-CW Specsheet

Fire Alarm Systems | GC Ceiling‑mount, Field‑selectable Strobes and Horn Strobes
GC Ceiling‑mount, Field‑selectable Strobes and Horn Strobes
www.boschsecurity.com
u Field‑selectable candela options (15 cd, 30 cd,
75 cd, 95 cd, and 115 cd)
The Commander4 Series Ceiling‑mount Strobes and Horn Strobe combinations offer dependable audible and visual alarms, low current draw, and a minimum flash rate of 1 Hz regardless of the input voltage. These models offer field‑selectable options of 15 cd, 30 cd, 75 cd, 95 cd, 115 cd, and 150 cd. The horns provide a selection of high or low dBA and a selection of 2400 Hz (remote signaling) or a low frequency broad band from 1500 Hz to 3000 Hz mechanical sounding (evacuation) tone where doors could be a problem. These models are easily field‑changeable from Temporal Code 3 to a continuous tone. These devices come standard with a 4 in. (10.2 cm) mounting plate, and incorporate the popular SuperSlide feature that allows you to easily test for supervision.
Certifications and approvals
Gentex Corporation holds these Listings and Approvals:
while strobes remain flashing
u Strobe, horn, or both can be synchronized using the
AVS Series Synchronization Modules
u Silence horn while strobes remain flashing
u Switch selection for high or low dBA, high or low
frequency, and for Temporal Code 3, Chime, or Whoop tones
Region
USA UL ULSZ: Audible Signal Appliances
Certification
(UL464), ULSZ7: Audible Signal Appli­ances Certified for Canada, and UUKC: Signaling Appliances and Equipment for the Hearing Impaired (ANSI/UL 1971) (GCC24-C models)
UL UUKC: Signaling Appliances and Equip-
ment for the Hearing Impaired (ANSI/UL
1971) and UEES7: Visual-signal Appli­ances Certified for Canada [CAN/ULC­S526 (1987)] (GCS24-C models)
FM
CSFM see our website
Installation/configuration notes
Mounting Considerations
These strobes are equipped with a 4‑in. square mounting plate that can be mounted on the indicated back boxes for the indicated applications:
2 | GC Ceiling‑mount, Field‑selectable Strobes and Horn Strobes
Conduit
Applications
4‑in. square
GSB
Surface Mounted
Flush Mounted
Synchronization
Although the AVS44 modules can be used with these devices, the AVSM modules are recommended in loops where no HS24 or ST24 devices are used.
Wiring
Notice
Do not use these strobe units in coded or pulsed signaling circuits.
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1 Horn Strobe
1 Mounting plate with terminal block
1 Jumper card
2 Hardware packs
1 Literature pack
Technical specifications
Electrical
Current (operating strobe):
Regulated Voltage (input): 24 VDC or FWR
15 cd = 72 mA; 30 cd = 88 mA; 75 cd = 176 mA; 95 cd = 200 mA; 115 cd = 214 mA, 150 cd = 286 mA
Environmental
Temperature (Operating): +32°F to +120°F (0°C to +49°C)
Mechanical
Candela Selections: 15 cd, 30 cd, 75 cd, 95 cd, 115 cd, or
Dimensions (diameter x D): 6.0 in. x 2.6 in. (15.2 cm x 6.6 cm)
150 cd
Audible Device Current (maximum):
Sound Output (maximum range) at 10 ft (3 m):
*Operating the horn in this mode at this voltage does not meet the minimum UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Chime mode is only acceptable for private use.
Continuous 2400 MHz Mode
Audible Device Current (maximum):
Sound Output (maximum range) at 10 ft (3 m):
Continuous Mechanical Mode
Audible Device Current (maximum):
Sound Output (maximum range) at 10 ft (3 m):
Notice
The sound output for the temporal (Code 3) mode is rated lower because the time that the horn is off is averaged into the sound output rating. While the horn is producing a tone in Temporal mode, its sound pressure is the same as the Continuous mode.
23 mA RMS 43 mA FWR
High output: 81 dBA Low output: 73 dBA*
22mA RMS 45 mA FWR
High output: 86 dBA Low output: 78 dBA
23 mA RMS 43 mA FWR
High output: 84 dBA Low output: 76 dBA
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
GCC24‑CR Red Horn Strobe Unit
Red ceiling-mount horn strobe with field‑selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.
Order number GCC24-CR
Horn Ratings
Temporal Code 3, 2400 MHz Mode
Audible Device Current (maximum):
Sound Output (maximum range) at 10 ft (3 m):
Temporal Code 3 Mechanical Mode
22 mA RMS 45 mA FWR
High output: 83 dBA Low output: 75 dBA
GCC24‑CW White Horn Strobe Unit
White ceiling-mount horn strobe with field‑selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.
Order number GCC24-CW
Loading...