Bosch GCC24-CR, GCC24-CW, GCS24-CR, GCS24-CW Specsheet

Bosch GCC24-CR, GCC24-CW, GCS24-CR, GCS24-CW Specsheet

Fire Alarm Systems | GC Ceiling mount, Field selectable Strobes and Horn Strobes

GC Ceiling mount, Field selectable Strobes

and Horn Strobes

www.boschsecurity.com

The Commander4 Series Ceiling mount Strobes and Horn Strobe combinations offer dependable audible and visual alarms, low current draw, and a minimum flash rate of 1 Hz regardless of the input voltage.

These models offer field selectable options of 15 cd, 30 cd, 75 cd, 95 cd, 115 cd, and 150 cd.

The horns provide a selection of high or low dBA and a selection of 2400 Hz (remote signaling) or a low frequency broad band from 1500 Hz to 3000 Hz mechanical sounding (evacuation) tone where doors could be a problem. These models are easily field changeable from Temporal Code 3 to a continuous tone.

These devices come standard with a 4 in. (10.2 cm) mounting plate, and incorporate the popular SuperSlide feature that allows you to easily test for supervision.

Certifications and approvals

Gentex Corporation holds these Listings and Approvals:

uField selectable candela options (15 cd, 30 cd, 75 cd, 95 cd, and 115 cd)

uSeparate horn and strobe functions; silence horn while strobes remain flashing

uStrobe, horn, or both can be synchronized using the AVS Series Synchronization Modules

uSilence horn while strobes remain flashing

uSwitch selection for high or low dBA, high or low frequency, and for Temporal Code 3, Chime, or Whoop tones

Region

Certification

 

 

 

USA

UL

ULSZ: Audible Signal Appliances

 

 

(UL464), ULSZ7: Audible Signal Appli-

 

 

ances Certified for Canada, and UUKC:

 

 

Signaling Appliances and Equipment for

 

 

the Hearing Impaired (ANSI/UL 1971)

 

 

(GCC24-C models)

 

UL

UUKC: Signaling Appliances and Equip-

 

 

ment for the Hearing Impaired (ANSI/UL

 

 

1971) and UEES7: Visual-signal Appli-

 

 

ances Certified for Canada [CAN/ULC-

 

 

S526 (1987)] (GCS24-C models)

 

FM

 

 

CSFM

see our website

 

 

 

Installation/configuration notes

Mounting Considerations

These strobes are equipped with a 4 in. square mounting plate that can be mounted on the indicated back boxes for the indicated applications:

2 | GC Ceiling mount, Field selectable Strobes and Horn Strobes

 

Conduit

Surface

Flush

 

Applications

Mounted

Mounted

4 in. square

 

GSB

 

Synchronization

Although the AVS44 modules can be used with these devices, the AVSM modules are recommended in loops where no HS24 or ST24 devices are used.

Wiring

Notice

Do not use these strobe units in coded or pulsed signaling circuits.

The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).

Parts included

Quant. Component

1Horn Strobe

1Mounting plate with terminal block

1Jumper card

2Hardware packs

1Literature pack

Technical specifications

Electrical

Current (operating

15 cd = 72 mA; 30 cd = 88 mA;

strobe):

75 cd = 176 mA; 95 cd = 200 mA;

 

115 cd = 214 mA, 150 cd = 286 mA

 

 

 

Regulated Voltage (input):

24 VDC or FWR

 

 

 

Environmental

 

 

 

 

 

Temperature (Operating):

 

+32°F to +120°F (0°C to +49°C)

 

 

 

Mechanical

 

 

 

 

 

Candela Selections:

 

15 cd, 30 cd, 75 cd, 95 cd, 115 cd, or

 

 

150 cd

 

 

 

Dimensions (diameter x D):

 

6.0 in. x 2.6 in. (15.2 cm x 6.6 cm)

 

 

 

Horn Ratings

Temporal Code 3, 2400 MHz Mode

Audible Device Current

22 mA RMS

(maximum):

45 mA FWR

 

 

Sound Output (maximum

High output: 83 dBA

range)

Low output: 75 dBA

at 10 ft (3 m):

 

 

 

Temporal Code 3 Mechanical Mode

Audible Device Current

23 mA RMS

(maximum):

43 mA FWR

 

 

Sound Output (maximum

High output: 81 dBA

range)

Low output: 73 dBA*

at 10 ft (3 m):

 

 

 

*Operating the horn in this mode at this voltage does not meet the minimum UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Chime mode is only acceptable for private use.

Continuous 2400 MHz Mode

Audible Device Current

22mA RMS

(maximum):

45 mA FWR

 

 

Sound Output (maximum

High output: 86 dBA

range)

Low output: 78 dBA

at 10 ft (3 m):

 

 

 

Continuous Mechanical Mode

 

 

 

Audible Device Current

23 mA RMS

(maximum):

43 mA FWR

 

 

Sound Output (maximum

High output: 84 dBA

range)

Low output: 76 dBA

at 10 ft (3 m):

 

 

 

Notice

The sound output for the temporal (Code 3) mode is rated lower because the time that the horn is off is averaged into the sound output rating. While the horn is producing a tone in Temporal mode, its sound pressure is the same as the Continuous mode.

Trademarks

All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.

Ordering information

GCC24 CR Red Horn Strobe Unit

Red ceiling-mount horn strobe with field selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.

Order number GCC24-CR

GCC24 CW White Horn Strobe Unit

White ceiling-mount horn strobe with field selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.

Order number GCC24-CW

Loading...