Fire Alarm Systems | GC Ceiling mount, Field selectable Strobes and Horn Strobes
GC Ceiling mount, Field selectable Strobes
and Horn Strobes
www.boschsecurity.com
The Commander4 Series Ceiling mount Strobes and Horn Strobe combinations offer dependable audible and visual alarms, low current draw, and a minimum flash rate of 1 Hz regardless of the input voltage.
These models offer field selectable options of 15 cd, 30 cd, 75 cd, 95 cd, 115 cd, and 150 cd.
The horns provide a selection of high or low dBA and a selection of 2400 Hz (remote signaling) or a low frequency broad band from 1500 Hz to 3000 Hz mechanical sounding (evacuation) tone where doors could be a problem. These models are easily field changeable from Temporal Code 3 to a continuous tone.
These devices come standard with a 4 in. (10.2 cm) mounting plate, and incorporate the popular SuperSlide feature that allows you to easily test for supervision.
Certifications and approvals
Gentex Corporation holds these Listings and Approvals:
uField selectable candela options (15 cd, 30 cd, 75 cd, 95 cd, and 115 cd)
uSeparate horn and strobe functions; silence horn while strobes remain flashing
uStrobe, horn, or both can be synchronized using the AVS Series Synchronization Modules
uSilence horn while strobes remain flashing
uSwitch selection for high or low dBA, high or low frequency, and for Temporal Code 3, Chime, or Whoop tones
Region |
Certification |
|
|
|
|
USA |
UL |
ULSZ: Audible Signal Appliances |
|
|
(UL464), ULSZ7: Audible Signal Appli- |
|
|
ances Certified for Canada, and UUKC: |
|
|
Signaling Appliances and Equipment for |
|
|
the Hearing Impaired (ANSI/UL 1971) |
|
|
(GCC24-C models) |
|
UL |
UUKC: Signaling Appliances and Equip- |
|
|
ment for the Hearing Impaired (ANSI/UL |
|
|
1971) and UEES7: Visual-signal Appli- |
|
|
ances Certified for Canada [CAN/ULC- |
|
|
S526 (1987)] (GCS24-C models) |
|
FM |
|
|
CSFM |
see our website |
|
|
|
Installation/configuration notes
Mounting Considerations
These strobes are equipped with a 4 in. square mounting plate that can be mounted on the indicated back boxes for the indicated applications:
2 | GC Ceiling mount, Field selectable Strobes and Horn Strobes
|
Conduit |
Surface |
Flush |
|
Applications |
Mounted |
Mounted |
4 in. square |
|
• |
• |
GSB |
• |
• |
|
Synchronization
Although the AVS44 modules can be used with these devices, the AVSM modules are recommended in loops where no HS24 or ST24 devices are used.
Wiring
Notice
Do not use these strobe units in coded or pulsed signaling circuits.
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1Horn Strobe
1Mounting plate with terminal block
1Jumper card
2Hardware packs
1Literature pack
Technical specifications
Electrical
Current (operating |
15 cd = 72 mA; 30 cd = 88 mA; |
|
strobe): |
75 cd = 176 mA; 95 cd = 200 mA; |
|
|
115 cd = 214 mA, 150 cd = 286 mA |
|
|
|
|
Regulated Voltage (input): |
24 VDC or FWR |
|
|
|
|
Environmental |
|
|
|
|
|
Temperature (Operating): |
|
+32°F to +120°F (0°C to +49°C) |
|
|
|
Mechanical |
|
|
|
|
|
Candela Selections: |
|
15 cd, 30 cd, 75 cd, 95 cd, 115 cd, or |
|
|
150 cd |
|
|
|
Dimensions (diameter x D): |
|
6.0 in. x 2.6 in. (15.2 cm x 6.6 cm) |
|
|
|
Horn Ratings
Temporal Code 3, 2400 MHz Mode
Audible Device Current |
22 mA RMS |
(maximum): |
45 mA FWR |
|
|
Sound Output (maximum |
High output: 83 dBA |
range) |
Low output: 75 dBA |
at 10 ft (3 m): |
|
|
|
Temporal Code 3 Mechanical Mode
Audible Device Current |
23 mA RMS |
(maximum): |
43 mA FWR |
|
|
Sound Output (maximum |
High output: 81 dBA |
range) |
Low output: 73 dBA* |
at 10 ft (3 m): |
|
|
|
*Operating the horn in this mode at this voltage does not meet the minimum UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Chime mode is only acceptable for private use.
Continuous 2400 MHz Mode
Audible Device Current |
22mA RMS |
(maximum): |
45 mA FWR |
|
|
Sound Output (maximum |
High output: 86 dBA |
range) |
Low output: 78 dBA |
at 10 ft (3 m): |
|
|
|
Continuous Mechanical Mode |
|
|
|
Audible Device Current |
23 mA RMS |
(maximum): |
43 mA FWR |
|
|
Sound Output (maximum |
High output: 84 dBA |
range) |
Low output: 76 dBA |
at 10 ft (3 m): |
|
|
|
Notice
The sound output for the temporal (Code 3) mode is rated lower because the time that the horn is off is averaged into the sound output rating. While the horn is producing a tone in Temporal mode, its sound pressure is the same as the Continuous mode.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
GCC24 CR Red Horn Strobe Unit
Red ceiling-mount horn strobe with field selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.
Order number GCC24-CR
GCC24 CW White Horn Strobe Unit
White ceiling-mount horn strobe with field selectable strobe intensities of 15, 30, 75, 95, 115, and 150 cd, 2400 Hz (remote signaling) or low frequency broad band from 1500 to 3000 Hz mechanical sounding (evacuation) tone, continuous or temporal (Code 3) horn tone, and high or low sound volumes.