Fire Alarm Systems | FLM-325-NA4 Supervised Output Modules
FLM-325-NA4 Supervised Output Modules
www.boschsecurity.com
u Contacts are rated 2 A at 24 VDC
u Flexible application and quick response to
emergency conditions
u Can be alarmed or reset by zone or by individual
address
The modules provide a supervised polarity reversal
output used for audible and visual signaling devices or
to trigger a remote NAC power expander. They require
a 24 VDC auxiliary input voltage that can be provided
by the FPA‑1000 Analog Addressable Fire Panels or
other UL listed power supplies.
The modules provide a Class B Circuit rated for 2 A at
24 VDC. They fit into a standard 4‑inch square or
double‑gang electrical back box.
Functions
Evacuation Tones
The following programmable patterns are selectable:
• Steady
• Pulsing
• Temporal 3
Flexibility
The operating parameters for the modules are saved at
the integrated EEPROM and maintained by the module
so that during emergency situations no communication
with the fire panel is needed which provides flexibility
and quick response to emergency conditions. The fire
panel only broadcasts system conditions on the
Signaling Line Circuit (SLC) and each module
processes them according to its configuration.
u Module address programming with the D5070
Analog Device Programmer
u Bi‑colored LED provides module status
Status display
A bi‑colored LED flashes every time the module is
polled and can be switched on steady when the
module goes into active condition.
Short Circuit Isolation
Built‑in short circuit isolating (SCI) circuitry that, in
the event of a short circuit on the SLC line, will
prevent entire loop failure and send a short circuit
condition report to the FACP, and, upon removal of
the short circuit condition, automatically restore the
entire loop to normal operation.
Certifications and approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864)
CSFM see our website
Installation/configuration notes
Compatibility Information
The following products are compatible with the
modules:
2 | FLM-325-NA4 Supervised Output Modules
Category Product ID Product Description
Fire Panels FPA‑1000 Analog Addressable Fire Panels
Programmer D5070 Analog Device Programmer
Parts included
Quant. Component
1 FLM‑325‑NA4 Family Supervised Output Module
1 Wall plate
1 Literature pack
Technical specifications
Electrical
Voltage
Input: 25.3 VDC to 39 VDC
Auxiliary Input: 24 VDC
Current Consumption
• FLM‑325‑NA4: Typical: 0.22 mA
Maximum: 6 mA
• FLM‑325‑NAI4:Typical: 0.42 mA
Maximum: 6 mA
FLM-325-NAI4 Supervised Output Module (Class A and
B, with isolator)
Built-in short circuit isolator circuitry; can be wired for
Class A or Class B circuits; compatible with 254
addresses
Order number FLM-325-NAI4
Accessories
D5070 Analog Device Programmer
Used to program address settings on
EEPROM‑programmable analog devices
Order number D5070
• Maximum
2 A at 24 VDC, power‑limited
Output:
SCI
• Fault Detection
12 V typical
Threshold:
• Isolation
10 mA typical
Current:
Environmental
Operating
+32°F to +120°F (0°C to +49°C)
Temperature:
Relative Humidity: Up to 90 %, non‑condensing
Mechanical
Dimensions
(H x W x D):
4.7 in. x 4.2 in. x 1.4 in. (11.9 cm x 10.7 cm
x 3.6 cm)
Bicolored LED: Red and green
Ordering information
FLM-325-NA4 Supervised Output Module (Class A and
B)
Can be wired for Class A or Class B circuits;
compatible with 254 addresses
Order number FLM-325-NA4