Bosch FLM325IM User Manual

Fire Alarm Systems | FLM‑325‑IM Contact Module
FLM‑325‑IM Contact Module
Digital data communications and power provided over
a two-wire circuit
Advanced digital communications protocol
compatible
Class B circuit for dry contact devices
Module address programming (1-254) with the D5070
Analog Device Programmer
The FLM‑325‑IM Contact Module provides a variety of fire alarm functions, such as monitoring manual pull stations, waterflow devices, or other dry contact fire alarm activation applications. The module allows for alarm, trouble, and supervisory conditions. The module is mounted inside of a single‑gang back box and is normally out of view.
The FLM‑325‑IM Contact Module allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit. The module has an eight‑bit microprocessor and communicates with the control panel (both power and data) over a two-wire polling circuit. The initiating device circuit (NFPA Style B) connected to the module can have up to 20 normally-open (NO) dry contact devices. Each module can monitor one normally-closed (NC) device (NC devices must be non­alarm applications).

Certifications and Approvals

Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864)

Installation/Configuration Notes

The following products are compatible with the FLM‑325‑IM Contact Module:
Category Product ID Product Description
Control Panels: FPA‑1000
Series
Pull Stations FMM‑325A Analog addressable manual pull
FMM‑325A‑D Analog addressable manual pull
Programmers: D5070 Analog device programmer
Analog addressable fire panels
station (single action)
station (double action)
www.boschsecurity.com
2 | FLM‑325‑IM Contact Module
Data Circuit Length
Data (or polling) circuit length is the distance over the circuit wire from the connection at the FACP to the most distant device and back to the FACP. Data circuit length must include the distance to any device connected to the circuit in a T tap. The screw terminals can accept up to 14 AWG (1.5 mm) wire, but this reduces the allowable length of the circuit.
Refer to the FPE‑1000‑SLC Installation Guide (P/N: F01U078099) for specific wire instructions and specifications for the FPA‑1000 series panels.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL­listed normally open (NO) contact closure devices. Device circuit wiring must not exceed 50 Ω. Install contact closure devices according to the manufacturer’s installation instructions. All wiring must be supervised and power-limited.
Note Do not mix fire alarm initiating and
supervisory devices on the same module.

Parts Included

Mechanical
Dimensions (H x W x D) 2.375 in. x 1.75 in. x 0.5 in.
(60.325 mm x 44.45 mm x 12.7 mm)
Weight 20 oz (0.567 kg)
Trademarks
Trademark names are used throughout this document. In most cases, these designations are claimed as trademarks or registered trademarks in one or more countries by their respective owners. Rather than placing a trademark symbol in every occurrence of a trademark name, Bosch Security Systems, Inc. uses the names only in an editorial fashion and to the benefit of the trademark owner with no intention of infringing the trademark.
Hochiki is a trademark of Hochiki America Corporation.

Ordering Information

FLM‑325‑IM Contact Module
FLM-325-IM
Allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit
Quant. Component
1 Point contact module
1 EOL resistor: Hochiki P/N 0400‑01046,. 10 kΩ, ¼ W, ¼ in.
1 Literature – Installation Guide

Technical Specifications

Electrical
SLC Applied Voltage (rated range): 25.3 VDC to 39 VDC
SLC Current Consumption: Standby: 0.339 mA
Alarm: 0.358 mA
Resistance
End of Line Device 10 kΩ, 0.25 W per resistor
Initiating Device Circuit Less than 50 Ω
Environmental
Environment: Indoor dry
Relative Humidity: Up to 90%, non‑condensing
Temperature: Operating: 0°C to +49°C (+32°F to +120°F)
Storage: -30°C to +70°C (-22°F to +158°F)
Americas:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
© Bosch Security Systems 2011 | Data subject to change without notice T7621673227 | Cur: en-US, V1, 25 May 2011
Europe, Middle East, Africa:
Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.asia
Represented by
Loading...