Bosch FLM-325-I4-AI, FLM-325-I4-A Specsheet

Fire Alarm Systems | FLM-325-I4-A Contact Monitors
FLM-325-I4-A Contact Monitors
www.boschsecurity.com
u Monitors Normally Open (NO) or Normally
Closed (NC) contacts
u Monitored Normally Closed (NC) contacts can be
The FLM-325-I4-A and FLM-325-I4-AI modules are used to connect standard Normally Open or Normally Closed dry contact types of fire alarm devices such as pull stations or water flow devices. The modules are mounted to a cover plate for a 4‑inch square or double‑gang electrical back box. A bi‑colored LED provides the module status.
Functions
Address Range
Contact Monitor modules must be programmed with a unique address. All devices connected to module appear only as one single address at the fire panel. The modules are compatible with 254 addresses.
Status Conditions
The module supervises the wiring to the contact with an EOL resistor. If a fault condition occurs, the module sends a trouble signal to the fire panel. If a status change occurs, the module sends an interrupt signal to the fire panel indicating that an alarm has occurred.
u Module address programming with the D5070
Analog Device Programmer
u Bi‑colored LED provides module status
u Digital data communications and power over a
two‑wire circuit
Certifications and approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864)
CSFM see our website
FDNY-
#6101
CoA
Installation/configuration notes
Compatibility Information
The following products are compatible with the modules:
Category Product ID Product Description
Fire Panels FPA‑1000
Analog Addressable Fire Panels
series
Programmer D5070 Analog Device Programmer
Data Circuit Length
Data (or polling) circuit length is the distance over the circuit wire from the connection at the fire panel to the most distant device and back to the fire panel. Data circuit length must include the distance to any
2 | FLM-325-I4-A Contact Monitors
device connected to the circuit in a T‑tap. The screw terminals can accept 14 AWG (ISO 2.5 mm2) wire; thinner wire can be used, but this reduces the allowable length of the circuit.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL listed Normally Open (NO) contact closure devices. Device circuit wiring must not exceed 50 Ω. Install contact closure devices according to the manufacturer’s installation instructions. All wiring must be supervised and power-limited.
Notice
Do not mix fire alarm initiating and supervisory devices on the same module.
Parts included
Quant. Component
1 FLM‑325‑I4-A Family Contact Module
1 EOL resistor, 10 kΩ
1 Wall plate
1 Hardware pack
1 Literature pack
Ordering information
FLM-325-I4-A Contact Monitor 4-inch Class A
Can be wired for Class A or Class B circuits; mounted to a cover plate for a 4‑inch square or double gang electrical back box; bi‑colored LED provides module status; compatible with 254 addresses
Order number FLM-325-I4-A
FLM-325-I4-AI Contact Monitor 4-inch Class A with Isola­tor
Can be wired for Class A or Class B circuits; has built‑in short circuit isolator circuitry; mounted to a cover plate for a 4‑inch square or double gang electrical back box; bi‑colored LED provides module status; compatible with 254 addresses
Order number FLM-325-I4-AI
Technical specifications
Power Requirements
Input Voltage 25.3 VDC to 39 VDC
Current Consumption
• Nominal: 0.63 mA
• Maximum: 6.3 mA
Resistance
• End of Line Device 10 kΩ, 0.25 W per resistor
• Initiating Device Circuit
Less than 50 Ω
Mechanical Properties
Dimensions (H x W x D): 4.7 in. x 4.2 in. x 1.4 in.
Weight 20 oz (567 g)
Color Ivory
Material ABS Blend
Response Time 2 sec
(11.9 cm x 10.7 cm x 3.6 cm)
Environmental Considerations
Operating Temperature +32°F to +120°F (0°C to +49°C)
Relative Humidity Up to 90 %, non‑condensing
3 | FLM-325-I4-A Contact Monitors
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2699165195 | en, V9, 31. Jul 2014
Loading...