Bosch F220, F220-B6RS User Manual

F220 Series Detectors with F220-B6RS Base
Installation Manual
en English manual
2 en | Legal F220 Series Detectors with F220-B6RS Bases
1Legal
CleanMe® is a registered trademark of GE Interlogix in the United States and/or other countries.
Chamber Check Systems, Inc. in the United States. Chambermaid™ is a trademark of Bosch Security Systems, Inc. in the United States. ENVI-RO-TECH™ is a trademark of Tech Spray L.P.
TECHSPRAY
1.2 Required Maintenance and Testing
Keep the detector calibrated for proper operation. NFPA 72, The National Fire Alarm Code, recommends performing calibration tests at installation, then every other year. Depending on local regulations, calibration testing might be required more than once a year.
Perform functional testing yearly.
®
is a registered trademark of Bosch Security
®
is a registered trademark of Tech Spray L.P.
NOTE! Notify all concerned parties before any maintenance or testing of the fire alarm system and upon
i
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
completion of these activities.
Test the calibration (to meet NFPA 72) using either the magnet test or measuring the calibration with a calibrated product from No Climb Products Ltd. Quickly determine the calibration by a visual inspection of the detector’s LED (refer to Section 4.4 Flash Rate and Trouble Indication on page 24). These tests confirm whether or not the detector is within its factory marked calibration range. At least once a year vacuum or wipe the external part of the detector clean. Pay particular attention to the detector screens in areas of heavy insect activity or dust. To clean the chamber,
F220 Series Detectors with F220-B6RS Bases General Information | en 3
use a can of clean, dry compressed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores. Shorten the plastic tube that comes with the compressed air to about 2 in. (5 cm). Place the tube or needle valve through the Chambermaid valve in the bottom of the detector (refer to Figure 2.2 on page 6).
NOTE! Do not paint the detectors. Paint or other foreign
i
matter covering the detector can prevent smoke detection.
2 General Information
This document covers mounting, wiring, power requirements, testing, and maintenance for the F220-B6RS Detector Bases and the F220 Series Heat and Photoelectric Smoke Detectors. Install them according to NFPA 72.
NOTE! For proper system installation, read and understand NFPA 72 before installation.
i
For installation guidelines, refer to Installation Considerations for Smoke and Fire Detectors (P/N: 26715).
2.1 F220-B6RS Detector Bases
The F220-B6RS is a four-wire base with a Form A alarm relay and a built-in sounder. Other bases (two-wire and four-wire without built-in sounders) are available. Refer also to the F220 Series Detectors with F220-B6/C/E/R Installation Instructions (P/N: 4998138694) and the F220-B6PS/M Installation Instructions (P/N: 4998149982).
2.1.1 Compatible Control Panels
The F220-B6RS is a four-wire base compatible with all UL Listed four-wire control panels. Refer to the control panel
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
4 en | General Information F220 Series Detectors with F220-B6RS Bases
manufacturer’s installation instructions for proper end-of-line (EOL) resistor selection.
2.1.2 Base Features
13
12
11
10
14
12
15
8
13
7
4
5
4
D I P
3
2
3
2
1
O N
1
9
13
12
6
12
13
1. Terminal 1
2. Terminal 2
3. Terminal 3
4. Terminal 4
5. Terminal 5
6. DIP Switches
7. Resettable Auxiliary Power Positive (+) In and Out Terminals (b1 and b2)
9. Remote Terminal (c)
10. Tamper Tab (Locking Bar)
11. Tamper Tab (Locking Bar Mount)
12. Alignment Key (4 places)
13. Snap Lock (4 places)
14. Sounder
15. Earth Shield Terminal (optional)
8. Resettable Auxiliary Power Negative (-) In and Out Terminal (a1/a2)
Fig. 2.1 Base Features
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases General Information | en 5
2.2 F220 Series Detectors
2.2.1 About F220 Series Detector Heads
The F220 Series Detector Heads listed inTable 2.1 each require an F220-B6 Series Base.
WARN ING ! The F220-PTHC detects carbon monoxide
!
(CO) as a component of a fire. Do not use the F220-PTHC as a stand-alone CO detector.
F220-135
F220-135F
F220-190F
F220-P Photoelectric smoke detector
F220-PTH
F220-PTHC
Tab le 2. 1 F220 Series Detector Heads
Electronic heat detector 135°F (57°C), fixed temperature and rate-of-rise
Electronic heat detector 135°F (57°C), fixed temperature only
Electronic heat detector 190°F (88°C), fixed temperature only
Photoelectric smoke detector with integral 135°F (57°C) heat sensor
Photoelectric smoke detector with integral 135°F (57°C) heat sensor and CO enhanced smoke detection
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
6 en | General Information F220 Series Detectors with F220-B6RS Bases
2.2.2 F220 Series Detector Features
1
2
6
5
3
1. Front of detector
2. Light-emitting diode (LED)
3. Thermistor (heat detectors only)
Fig. 2.2 Detector Features
4
4. Unlocking port
5. Back of detector
6. Chambermaid location
2.2.3 F220 Series Heat Detector Heads
The F220 Heat Detector Heads can be identified by color coding (refer to Table 2.2).
F220-135 No circle around the thermistor F220-135F A gray circle around the thermistor F220-190F A black circle around the thermistor
Tab le 2. 2 Distinguishing Heat Detectors
WARNING ! The F220-135, F220-135F and F220-190F are
!
not life safety devices. Use them with F220-B6 Series bases to provide general property protection.
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases General Information | en 7
2.2.4 F220 Series Smoke Detector Heads
The F220 Series Smoke Detector Heads are UL Listed, open­area photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to Section 2.1 F220-B6RS Detector Bases on page 3). To verify power to the detector and a functioning smoke sampling circuitry, a dual color LED indicator flashes green every eight seconds when operating normally. It flashes once every four seconds when a trouble condition exists. If the detector determines an alarm condition exists, the LED changes from flashing green to steady red. The detector returns to normal after the alarm condition is cleared and power is interrupted. Throughout its normal life cycle, the smoke detector monitors and periodically adjusts itself to keep the sensitivity at its factory calibrated level. When excessively dirty, the detector’s LED flash rate changes from an eight second flash rate to a four second rate. If CleanMe is selected, the detector sends a CleanMe signal to the compatible control panel to indicate a dirty smoke detector. Refer to Section 4.3 Set CleanMe Feature on page 24.
2.3 Technical Specifications
2.3.1 General Specifications
Air Velocity 4000 ft/min (1200 m/min) maximum Operating
Temperature Relative
Humidity
Tab le 2. 3 Specifications - Detectors and Bases
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
+32°F to 100°F (0°C to 38°C)
0% to 95% (non-condensing)
8 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
2.3.2 Base Specifications
Alarm Current (only base current, detector current excluded)
F220-B6RS (with steady sounder and relay): F220-B6RS (with separately powered sounder only):
NAC Current 30 mA at 24 VDC Standby Current 10 mA maximum at 30 VDC Voltage 10.0 VDC to 30.0 VDC
Tab le 2. 4 F220-B6RS Detector Base Specifications
45 mA at 24 VDC 50 mA maximum at 30 VDC
30 mA at 24 VDC 35 mA maximum at 30 VDC
2.3.3 Detector Specifications
Current
Alarm: 35 mA maximum at 32 VDC Standby: 0.12 mA maximum Startup: 0.12 mA maximum
Powerup Time 22 second maximum Rate of Rise
F220-135: 15°F/min (9°C/min) or greater
Tab le 2. 5 F220 Series Detector Heads Specifications
2.4 Electrical Supervision
When the F220-B6RS Bases are wired according to the instructions in this document, the control panel initiates a trouble signal when a detector is removed from its base, providing tamper protection. An EOL power supervision module, such as a D275 or an F220-B6E Power Supervision Base and an EOL resistor as specified by the control panel manufacturer, supervises power.
3 Install the Bases
3.1 Mount the Bases
With the exception of the F220-B6E base, all four-wire bases can be used in any combination within a loop. One F220-B6E
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 9
Power Supervision Base can be used as the last base on a loop in four-wire systems to provide power supervision.
NOTE! Follow NFPA 72 guidelines for mounting locations.
i
i
For commercial and industrial installations, 30 ft (9 m) spacing between smoke detectors is recommended.
1. Release the mounting skirt from the mounting base. Use a screwdriver at the location of the snap locks (refer to Figure 2.1, item 12, page 4) to release the mounting skirt.
2. Run all system wiring (refer to Section 3.2 Wire the Bases on page 10).
3. Mount the base using the two oblong mounting holes. Fits 4 in. square, octagon, AB, and single-gang back boxes.
NOTE! Depending on local regulations, you can surface mount the bases using anchors, mollies, or wing nuts, or you can mount directly on back boxes.
NOTE! The electrical box must be large enough to accommodate the number and size of conductors
i
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).
4. Tighten the base to the mounting surface. Tighten only until snug; not distorted.
10 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
3.2 Wire the Bases
CAUTION! When wiring bases, all terminal screws including those not wired must be tightened to prevent
!
3.2.1 Terminal Connections
loose screw heads from making intermitent electrical contact with the detector head.
WARNING ! Do not twist or loop the wires around the terminals. In and out wires for terminal connection must be cut, stripped, and inserted as individual ends.
!
NOTE! Bring the positive (+) wires in on terminal b2 and out from terminal b1. Use a consistent pattern, inputting
i
on b2 and outputting from b1. The negative (-) wires input and output from the same terminal (a1/a2).
3.2.2 EOL Resistors
Use the EOL resistors supplied or specified by the control panel manufacturer. This applies to all loop terminations including the D275 Module and the F220-B6E Power Supervision Base.
3.2.3 Loop Wiring Specifications
In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop meets the minimum voltage requirement of at least 16 V.
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 11
3.2.4 Four-wire Loop Termination
One D275 End-of-Line Module (refer to Figure 3.5 on page 19) or F220-B6E Power Supervision Base (refer to Figure 3.4 on page 18) is required for each loop when using four-wire bases.
3.3 Wire Optional Remote Annunciators
If using the optional DRA-5 Remote Alarm Indicator, connect the positive (red) wire to terminal b1 and the negative wire (white) to terminal c (refer to Figure 3.1).
1
DRA-5
b1b2
3
4
2
5
1. Red wire to Terminal b1 on base
Fig. 3.1 Optional DRA-5 Remote Annunciator Wiring
1
ca1/a2
2. White wire to Terminal c
2
on base
3.4 Wire F220-B6RS Sounder Bases
The F220-B6RS has a built-in sounder that can be set to operate in one of four ways through a combination of wiring and DIP switch settings (refer to Figure 3.2, Item 3 on page 14 and Table 3.2 on page 15).
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
12 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
3.4.1 NAC Configurations
In these configurations, the sounders are controlled and powered from the control panel’s NAC power circuit or a remote NAC power circuit. The positive (+) wire from the NAC or D132B Multi-use Reversing Relay Module connects to Terminal 5 and the negative (-) wire connects to Terminal 4 (refer to Figure 3.2, Item 3 on page 14). The sounders on the loop follow the NAC configuration programmed at the control panel. The DIP switches (refer to Figure 2.1, Item 15 on page 4) are set as shown in Table 3.1.
WARNING ! DIP switches 1 and 2 must be either both on
!
or both off. Having one on and the other off could result in incorrect operation including failure to alarm.
Position 1 and 2 off; 3 and 4 either both on or both off.
O N D I P
1234
Tab le 3. 1 NAC Configuration DIP Switch Settings
NAC Follower (Direct Wire) Configuration: The sounders
on the loop follow the signal on the NAC terminals as pro­grammed at the control panel. Refer to the control panel's installation manual for NAC configuration instructions. This configuration requires an extra pair of supervised wires for the sounder circuit (refer to Figure 3.2, Item 3 on page 14).
Reverse Polarity Configuration: Tthe sounders in a loop
activate due to reversed polarity on the power line. The output pattern is not controlled by the base in this operat­ing mode; it follows the signal on the head terminals as programmed at the controlpanel.
Control panel NAC circuit power is applied to the base to Terminals 4(+) and 5(-). The sounder follows the configuration of the NAC. The positions of switches 3 and 4 have no affect.
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 13
3.4.2 Local Configurations
In these configurations, the sounders are controlled and powered from the control panel’s power circuit (refer to Figure 3.2, Items 1 and 2 on page 14). The initiating device circuit (IDC) wires connect to Terminals 1 and 2 (refer to Figure 3.2, Items 3 and 4 on page 14). The DIP Switches are set for one of the following patterns: Temporal (Code 3), March Time, or Continuous Tone (refer to Table 3.2 on page 15). – Local Configuration: Each sounder is individually set and
activated (refer to Table 3.2 on page 15).
Interconnection Configuration: Up to five detectors can be
interconnected by a common wire (refer to Figure 3.2, Item 4 on page 14, Table 3.2 on page 15, and Figure 3.3 on page 17). All sounders within the group activate together. Set all units for the same output pattern (Temporal Code 3, March Time, or Continuous Tone). All interconnected detectors are synchronized with and sound the pattern of the originating detector.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
14 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
_
1
+
F220-B6RS
b2
4
+
3
_
+
2
_
1. Base Power: positive (+) and negative (-) resetta­ble auxiliary power input from the control panel or from a previous four-wire base.
2. Positive (+) and negative (-) initiating device circuit (IDC) input from the control panel or from a previous four-wire base.
3. Sounder Power (optional): positive (+) and negative (-) 24 VDC NAC power input from the control panel, a remote NAC, or from a previous four-wire base. This connection
Fig. 3.2 Wiring F220-B6RS Sounder Bases
b1
4
5
3
2
4. Optional interconnection
5. Alarm Loop Relay
_
1
+
4
5
C
NO
+
1
powers the sounders from the control panel so that all sounders follow the control panel’s NAC set­ting.
from one base to the next base for up to five F220­B6RS bases. If any of the interconnected detectors signals an alarm, all of the interconnected base sounders are synchronized to the same signalling pattern as the initiating detector’s base. Refer to Figure 3.3 on page 17.
3
_
+
2
_
ca1/a2
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 15
i
Position 1 and 2 on; 3 and 4 either both on
Sounder output configured for steady signal (continuous tone)
or both off.
O N D I P
234
1
Position 1, 2, and 3 on; 4 off.
O N D I P
1234
Position 1, 2, and 4 on; 3 off.
O N D I P
12
Tab le 3. 2 Local Configuration DIP Switch Settings
34
Sounder output configured for Temporal Code 3 signal
Sounder output configured for March Time signal
NOTE! Up to five interconnected units activate per circuit. If more than five units activate, only individual detectors are guaranteed to activate the correct output pattern. Additional interconnected units cannot activate the correct output pattern.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
16 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
+
+
_
+
_
_
6
5
D275
_
+
+
Common (-)
+ 24 VDC
+ 12 VDC
4
_
+
+
_
_
D275
5
_
+
+
Common (-)
+ 24 VDC
+ 12 VDC
4
_
_
+
c
a1/a2
F220-B6RS
+
+
b1
b2
_
_
First Interconnected Loop
c
a1/a2
F220-B6RS
_
+
3
b1
b2
1
1
2
3
4
5
_
_
++
1
2
3
4
5
_
+
2
c
a1/a2
F220-B6RS
+
_
++
_
+
Last Interconnected Loop
c
a1/a2
F220-B6RS
_
+
_
+
1
1
2
3
4
b1
b2
_
_
5
3
_
+
_
+
3
1
2
3
4
b1
b2
5
+
_
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 17
1. Positive (+) and negative (-) resettable auxiliary power either in parallel originating from the same power supply or run from separate power supplies.
2. Positive (+) and negative (-) initiating device circuit (IDC) from the control panel or an existing circuit.
3. Interconnection circuit (connects Terminal 3 from base to base) for up to five bases on a common power supply circuit. Each power circuit must be terminated with an F220-B6E Power
Fig. 3.3 Interconnection Wiring
Wire Size Wire Length
18 AWG (1.2 mm) 300 ft (91 m) 16 AWG (1.5 mm) 450 ft (137 m) 14 AWG (1.8 mm) 750 ft (229 m)
Tab le 3. 3 Maximum Distance from First to Last Interconnected Units
Supervision Base or a D275 Power Supervision Module.
4. When connecting a D275, connect the positive (+) wire to the yellow input (24 VDC) and the negative (-) wire to Common (black). The red wire is not used.
5. The blue wires from the D275 Power Supervision Module provide power supervision.
6. An EOL resistor as specified in the control panel’s installation instructions.
NOTE! To ensure interconnected units can alarm, the line load after the last detector must not exceed 10 mA.
i
3.5 Wire Power Supervision Modules
3.5.1 Wire F220-B6E Power Supervision Base
The F220-B6E base is wired as shown in Figure 3.4 on page 18.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
18 en | Install the Bases F220 Series Detectors with F220-B6RS Bases
_
1
+
4
b1
b2
F220-B6E*
5
C
NO
3
4
5
C
2
NO
1
ca1/a2
6
+
2
_
1. Power input (positive [+] in on terminal b2; negative [-] in on terminal a1/a2) from the control panel or from a previous four-wire base.
2. Initiating device circuit (IDC) input (positive [+] to terminal 2 and negative [-] to terminal 1) from the control panel or from a
Fig. 3.4 Wiring F220-B6E Four-wire Power Supervision Bases
* The F220-B6E base has a normally-open alarm loop relay that activates when the unit is in alarm and a power supervision relay that activates when power is supplied. Separate power supervision devices, such as the D275, are unnecessary. Use only one F220-B6E per zone run. It must be the last base on the run.
3
previous four-wire base.
3. Jumper connecting terminals 2 and 3.
4. Place an appropriate EOL resistor (refer to the control panel’s installation instructions for resistor specifications) across Terminals 1 and 4.
5. Power Supervision Relay
6. Alarm Loop Relay
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 19
The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads.
CAUTION! Do not connect relays to inductive or
!
capacitive loads. Use with resistive loads only.
3.5.2 Wire D275 Power Supervision Module
When a D275 Module is used with 24 VDC systems, connect the yellow wire to the output terminal (b1 or b2). The red wire remains unconnected (refer to Figure 3.5 on page 19).
1
3
2
4
2
7
5
6
D275
+12 VDC
+24 VDC
Common (-)
1. EOL resistor (refer to the control panel’s installation instructions for specifications).
2. The positive (+) and negative (-) IDC wires (blue) from the D275.
3. Connect the positive (+) IDC wire through the EOL resistor to Terminal 2 and the negative (-) IDC wire
Fig. 3.5 Wiring a D275 Power Supervision Module as a Loop Terminator
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
to Terminal 1 on the last base on the loop.
4. Red wire is not used.
5. Yellow wire to Terminal b1 on last base on loop for 24 VDC systems.
6. Black wire (common) to Terminal a1/a2 on last base on loop.
7. Power loop
20 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases
4 Install the Detector Heads
4.1 Mount the Detector Heads
CAUTION! Before mounting detector heads, all terminal screws in the base including those not wired must be
!
i
i
4.1.1 Optional Locking Bar
tightened to prevent loose screw heads from making intermitent electrical contact with the detector head.
NOTE! When using F220-B6RS Sounder Bases, set the DIP switches for desired operation and sounder signal pattern before installing the detector heads.
Each base has a snap-off locking bar as part of the base molding. Engage the locking bar to prohibit unauthorized detector removal. To engage the locking bar, move it to the position shown in Figure 4.1.
1
X
X
1. Snap locking bar (X) off base molding
Fig. 4.1 Engaging the Locking Bar
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
2. Insert locking bar (X) into locking bar mount until fully engaged
2
X
X
F220 Series Detectors with F220-B6RS Bases Install the Detector Heads | en 21
CAUTION! When using the locking bar, before installing the detector head, open the unlocking port (refer to
!
Figure 4.2, Item 4) by poking through the plastic with a screwdriver.
4.1.2 Mounting Skirt (Figure 4.2, Item 2)
Align the four alignment keys (refer to Figure 2.2, Item 12 on page 6 and to Figure 4.2, Item 5) and press the mounting skirt firmly down onto the mounting base (Figure 4.2, Item 3) to engage the snap locks .
6
1
4
2
5
3
1. Detector head (heat detector shown in exam­ple)
2. Mounting skirt
3. Mounting base
4. Locking port
5. Alignment keys (four places on the bottom of
Fig. 4.2 Part Orientation for Mounting
6. LED
7. Bar on mounting skirt
8. T mark on mounting skirt
9. Locking bar in locked position
7
8
5
5
5
9
the mounting skirt and four corresponding places on the base)
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
22 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases
4.1.3 Detector Head
CAUTION! The mounting skirts and detector heads are
!
keyed. Do not force them onto the mounting bases.
Install:
Install the detector head by lining up the LED on the detector head (refer to Figure 4.2, Item 6 on page 21) with the bar on the mounting skirt (refer to Figure 4.2, Item 7). Turn the detector head clockwise until the LED aligns with the T mark on the mounting skirt (refer to Figure 4.2, Item 8).
Remove:
Remove the detector ahead by turning it counter-clockwise. If the optional locking bar is used, refer to Figure 4.3.
2
1
1. Insert screwdriver through the locking port and depress the locking bar.
Fig. 4.3 Unlocking the Locking Bar
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
2. Hold the locking bar down while turning the head counter-clockwise until disengaged.
F220 Series Detectors with F220-B6RS Bases Install the Detector Heads | en 23
4.2 Set Detector Modes
The F220 Series Smoke Detectors feature a unique magnet-operated sensitivity mode and detector test mode.
4.2.1 Test Mode
Test the detector by placing the magnet next to the T mark on the mounting skirt for three consecutive flashes to cause an alarm.
4.2.2 Sensitivity Mode
If the magnet is next to the T mark for less than three flashes but more than one flash, the detector enters Sensitivity Mode.
1. Place the detector into Sensitivity Mode.
2. Wait for the first single green LED flash.
3. Count the number of red LED flashes that follow and refer to Table 4.1 on page 23 for sensitivity definitions.
Number of
Red Flashes
1 Malfunctioning smoke or heat detector 3 Normally operating smoke or heat detector with
4 to 6 Progressively more contamination 7 to 10 Trouble condition, very dirty but still
11 Sensitivity < 2.5%/ft (2.5%/ft = 0.36 db/m) 12 Sensitivity < 2.0%/ft (2.0%/ft = 0.287 db/m),
13 Sensitivity < 1.5%/ft (1.5%/ft = 0.214 db/m) 14 Sensitivity < 1.0%/ft (1.0%/ft = 0.143 db/m),
15 Sensitivity < 0.5%/ft (0.5%/ft = 0.071 db/m),
Tab le 4. 1 Red LED Flash Definition
4. The detector exits sensitivity mode and returns to one green LED flash every eight seconds.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
Sensitivity Definition (% Obscuration)
little or no dirt contamination
compensated to 3%/ft (3%/ft = 0.433 db/m); Sensitivity < 3% at 10 flashes.
chance of false alarm increases
chance of false alarm greatly increases
false alarm likely
24 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases
4.3 Set CleanMe Feature
The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level.
NOTE! When a CleanMe signal is sent to a control panel
i
that is not CleanMe compatible, the signal may be misinterprted as an alarm.
To activate the CleanMe feature:
1. Put the detector into sensitivity mode by placing a magnet next to the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 21). Remove the magnet after the first red LED flash and before the third red LED flash.
2. When the magnet is removed, the LED flashes green once and shows the first of two sensitivity displays.
3. When the LED next flashes red, replace the magnet near the T mark (refer to Figure 4.2, Item 8 on page 21).
4. Hold the magnet against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 21) until the green LED flashes twice and the red LED repeats the sensitivity indication.
5. The detector exits sensitivity mode. If CleanMe has been successfully enabled, the green LED flashes twice in rapid succession every eight seconds indicating that CleanMe is activated.
To disable CleanMe, repeat this process and verify the double flash returns to a single flash.
4.4 Flash Rate and Trouble Indication
These detectors include the Chamber Check Automatic Trouble Indicator that verifies the detector’s calibration is within the factory listed range. NFPA guidelines for sensitivity testing can
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Test the Installation | en 25
be met by visually inspecting the detector and checking the flash rate of the LED.
NOTE! Perform the visual check before resetting power. After a reset the trouble indicators clear for 70 seconds.
i
After 70 seconds, if the detector is in a trouble condition, trouble indications begin again.
A unit with CleanMe activated double flashes (two flashes within a half second of each other) every eight seconds. A normally operating unit flashes once every eight seconds. If a detector is in a trouble condition due to a dirty lens or a sensor malfunction, it single or double flashes every four seconds. If enabled, the CleanMe trouble signal is sent. If the calibration is out of range for more than 24 hours, the green LED on the detector flashes approximately once every four seconds.
5 Test the Installation
5.1 Inspect the Installation
1. Check the wiring from the control panel to the last head on each run for proper polarity and continuity.
2. Terminate each run with an EOL resistor as specified by the control panel manufacturer.
3. Terminate four-wire runs with EOL power supervision modules or F220-B6E bases.
4. Apply power to the system. Check for alarms and troubles.
5. Note which detectors alarmed (if any), shut down the system, remove alarmed detectors from their bases, and recheck the bases for proper wiring.
6. If the problem persists, determine if the problem is caused by the detector or the base. Replace the affected detectors or bases with known good units.
7. If a system alarm occurs with no detector alarms present, remove all detectors and check the wiring at each base.
8. Check the wiring of each EOL resistor and EOL module.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
26 en | Test the Installation F220 Series Detectors with F220-B6RS Bases
9. When the system is alarm free, check each detector to ensure that the green LED indicator flashes approximately every eight seconds. This verifies the detector is receiving power and operating properly.
NOTE! If a heat detector LED flashes at a rate of 4 flashes/sec, the detector is either cold (below +32°F
i
[0°C]), out of sensitivity range, or defective. If a smoke detector flashes at a rate of 4 flashes/sec, it is either out of sensitivity range or defective.
5.2 Test Each Detector
Test each detector to ensure it causes a control panel alarm. Reset the control panel after each test.
5.2.1 Activate an Alarm at Each Detector
To cause heat detectors to alarm either:
Activate the internal reed switch by placing a magnet
horizontally against the T mark on the mounting skirt and holding it there for three consecutive LED flashes, or
Expose the thermistor to a heat source such as a hair dryer
or a shielded heat lamp until the detector alarms and the alarm LED lights .
To cause smoke detectors to alarm either:
Activate the internal reed switch by placing a magnet
horizontally against the T mark on the mounting skirt and holding it there for three consecutive LED flashes, or
Use a UL Listed aerosol smoke detector tester to simulate
an alarm. Follow the instructions provided with the aerosol smoke detector tester.
5.2.2 Reset the Control Panel
When a detector alarms, the red LED indicator activates and latches into the ON position. Clear the alarm by momentarily removing power before proceeding to the next detector.
F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc.
F220 Series Detectors with F220-B6RS Bases Test the Installation | en 27
5.3 Test the Alarm Loop
Checkthe voltage across the EOL resistor of each alarm loop to verify wiring losses do not exceed control panel manufacturer’s specifications.
5.4 Test any CO Sensors
Removing the detector head or resetting the detector’s power places the detector in a special test mode for 15 minutes. If over 35 ppm of CO is applied to the detector within this 15-minute period, the detector must alarm or it is defective.
WARN ING ! The F220-PTHC detects carbon monoxide
!
(CO) as a component of a fire. Do not use the F220-PTHC as a stand-alone CO detector.
5.5 Perform NFPA 72 Required Testing
Refer to Section 1.2 Required Maintenance and Testing on page 2.
Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096 Technical Support: (888) 886-6189
www.boschsecurity.us
© Bosch Security Systems, Inc., 2007
Loading...