Fire Alarm Systems | F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
F220‑B6RS 24 VDC Four‑wire Detector
Base with Sounder
Easy installation
▶
Interchangeable detector heads
▶
UL listed when used with F220 Series Detector Heads
▶
UL464 approved sounder driven by the detector head
▶
or the NAC circuit
The F220‑B6RS 24 VDC Four-wire Detector Base with
Sounder meets the requirements of UL464 for a notification
device and works with the F220 Series Photoelectric Smoke
and Heat Detectors. Power the sounder from the control
panel's NAC circuit or from auxiliary power.
Functions
Sounder Configuration
The output (sound pattern and synchronization) of the
sounders on a detection loop can be configured in four
different ways. Refer to the F220 Series Detectors
Installation Instructions (P/N: 4998138694) for instructions
on wiring and setting the F220‑B6RS detector base for
these configurations:
1. NAC Follower (Direct Wire) Configuration: In this
configuration, the sounders on the loop follow the
signal on the NAC terminals as programmed at the
control panel. Refer to the control panel's installation
manual for NAC configuration instructions. This
configuration requires an extra pair of supervised wires
for the sounder circuit.
2. Reverse Polarity Configuration: In this configuration
(not suitable for synchronized protocols; such as,
Cooper Wheelock, Gentex, or System Sensor), the
sounders in a loop activate due to reversed polarity on
the power line. The output pattern is not controlled by
the base in this operating mode; it follows the reversing
power signal on the detector head's terminals as
programmed at the control panel.
3. Local Annunciation Configuration: In this
configuration, each sounder is individually set for one
of the following patterns: Temporal (Code 3), March
Time, or Continuous Tone. Use a D275 Power
Supervision Module in this configuration to supervise
the detector loop.
4. Interconnection Configuration: In this configuration,
up to five detectors supervise the end of the detector
loop when interconnected by a common wire. All
sounders within the group activate together. Set all
units for the same output pattern (Temporal [Code 3],
March Time, or Continuous Tone). All interconnected
detectors are synchronized with and sound the pattern
of the originating detector.
The maximum wire length for connecting up to five units
is:
Wire Size Wire Length
18 AWG (1.2 mm) 300 ft (91 m)
16 AWG (1.5 mm) 450 ft (137 m)
14 AWG (1.8 mm) 750 ft (229 m)
Note To ensure interconnected units can signal an
alarm, the line load after the last detector on
www.boschsecurity.com
2 | F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
the interconnected detector loop must not
exceed 10 mA.
Certifications and Approvals
Region Certification
USA UL ULSZ: Audible Signal Appliances (UL464),
UROX: Smoke - Automatic Fire Dectectors
(UL268), UROX7: Smoke - Automatic Fire
Dectectors Certified for Canada (ULCS529)
FM
CSFM 1700-1615: 105
NYC-MEA (117-05-E)
Installation/Configuration Notes
Compatibility Information
Four‑wire: Compatible with all UL Listed four‑wire control
panels. Refer to the control panel's Installation Instructions
for proper end‑of‑line (EOL) resistor selection.
Detectors: Compatible with the following F220 Series
Detector Heads:
F220‑P Photoelectric Smoke Detector
•
F220‑PTH Photoelectric Smoke Detector with +135°F
•
(+57°C) Heat Sensor
•
F220‑PTHC1 Photoelectric Smoke Detector with +135°F
(+57°C) Heat Sensor and Carbon Monoxide Sensor
Enhancement
F220‑135 Electronic Rate‑of‑Rise, Fixed Temperature
•
+135°F (+57°C) Heat Detector
F220‑135F Electronic Fixed Temperature +135°F
•
(+57°C) Heat Detector
F220‑190F Electronic Fixed Temperature +190°F
•
(+88°C) Heat Detector
1
The F220‑PTHC detects carbon monoxide (CO) as a
component of a fire. It is not a CO detector and cannot
activate an alarm in the presence of CO only.
Mounting Considerations
Depending on local regulations, surface mount the bases
using anchors, mollies, or wing nuts, or mount directly on
four‑inch square or octagonal electrical boxes or
single‑gang switch boxes.
Note The electrical box must be large enough to
1
accommodate the number and size of
conductors specified by the National Electrical
Code or any local authorities having
jurisdiction (AHJ).
Wiring Considerations
In a four-wire system, the maximum loop length and number
of bases that can be placed on a loop depend on the voltage
drop on the power circuit. Use standard voltage drop
calculations to ensure that the last detector on the loop has
at least 16 V when all sounders and relays are powered.
Parts Included
Quant. Component
1 Detector base
1 Literature pack
Technical Specifications
Environmental Considerations
Relative Humidity: 0 to 95%, non‑condensing; 15% to 95%,
non‑condensing when used with CO sensor
model
Temperature (operating): +32°F to +100°F (0°C to +38°C)
Mechanical Properties
Color: Off-white
Dimensions (diameter x thickness)
Material: Fire‑resistant plastic
Outputs
Relay Type: Normally‑open (NO) Form A
Relay Rating: 0.5 A at 120 VDC or 120 VAC
Sounder Output: >85 dB at 10 ft (3 m)
Power Requirements
Voltage Range: 16.0 VDC to 30 VDC
Alarm Current
6-wire mode (4-wire base + two sounder power wires)
Relay: The relay draws 15 mA in alarm.
Steady Sounder: 24 VDC: 30 mA
4-wire mode
With Steady Sounder
and Relay:
Standby Current (base only): 30 VDC: 10 mA maximum
6 in. x 0.9 in. (15.2 cm x 2.3 cm)
30 VDC: 35 mA
24 VDC: 45 mA
30 VDC: 50 mA