Bosch F220-B6RS User Manual

Fire Alarm Systems | F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
Easy installation
Interchangeable detector heads
UL listed when used with F220 Series Detector Heads
UL464 approved sounder driven by the detector head
or the NAC circuit
The F220‑B6RS 24 VDC Four-wire Detector Base with Sounder meets the requirements of UL464 for a notification device and works with the F220 Series Photoelectric Smoke and Heat Detectors. Power the sounder from the control panel's NAC circuit or from auxiliary power.

Functions

Sounder Configuration
1. NAC Follower (Direct Wire) Configuration: In this configuration, the sounders on the loop follow the signal on the NAC terminals as programmed at the control panel. Refer to the control panel's installation manual for NAC configuration instructions. This configuration requires an extra pair of supervised wires for the sounder circuit.
2. Reverse Polarity Configuration: In this configuration (not suitable for synchronized protocols; such as, Cooper Wheelock, Gentex, or System Sensor), the sounders in a loop activate due to reversed polarity on the power line. The output pattern is not controlled by the base in this operating mode; it follows the reversing power signal on the detector head's terminals as programmed at the control panel.
3. Local Annunciation Configuration: In this configuration, each sounder is individually set for one of the following patterns: Temporal (Code 3), March Time, or Continuous Tone. Use a D275 Power Supervision Module in this configuration to supervise the detector loop.
4. Interconnection Configuration: In this configuration, up to five detectors supervise the end of the detector loop when interconnected by a common wire. All sounders within the group activate together. Set all units for the same output pattern (Temporal [Code 3], March Time, or Continuous Tone). All interconnected detectors are synchronized with and sound the pattern of the originating detector. The maximum wire length for connecting up to five units is:
Wire Size Wire Length
18 AWG (1.2 mm) 300 ft (91 m)
16 AWG (1.5 mm) 450 ft (137 m)
14 AWG (1.8 mm) 750 ft (229 m)
Note To ensure interconnected units can signal an
alarm, the line load after the last detector on
www.boschsecurity.com
2 | F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
the interconnected detector loop must not exceed 10 mA.

Certifications and Approvals

Region Certification
USA UL ULSZ: Audible Signal Appliances (UL464),
UROX: Smoke - Automatic Fire Dectectors (UL268), UROX7: Smoke - Automatic Fire Dectectors Certified for Canada (ULC­S529)
FM
CSFM 1700-1615: 105
NYC-MEA (117-05-E)

Installation/Configuration Notes

Compatibility Information Four‑wire: Compatible with all UL Listed four‑wire control
panels. Refer to the control panel's Installation Instructions for proper end‑of‑line (EOL) resistor selection.
Detectors: Compatible with the following F220 Series Detector Heads:
F220‑P Photoelectric Smoke Detector
F220‑PTH Photoelectric Smoke Detector with +135°F
(+57°C) Heat Sensor
F220‑PTHC1 Photoelectric Smoke Detector with +135°F (+57°C) Heat Sensor and Carbon Monoxide Sensor
Enhancement F220‑135 Electronic Rate‑of‑Rise, Fixed Temperature
+135°F (+57°C) Heat Detector F220‑135F Electronic Fixed Temperature +135°F
(+57°C) Heat Detector F220‑190F Electronic Fixed Temperature +190°F
(+88°C) Heat Detector
1
The F220‑PTHC detects carbon monoxide (CO) as a component of a fire. It is not a CO detector and cannot activate an alarm in the presence of CO only.
Mounting Considerations
Depending on local regulations, surface mount the bases using anchors, mollies, or wing nuts, or mount directly on four‑inch square or octagonal electrical boxes or single‑gang switch boxes.
Note The electrical box must be large enough to
1
accommodate the number and size of conductors specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).
Wiring Considerations
In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop has at least 16 V when all sounders and relays are powered.

Parts Included

Quant. Component
1 Detector base
1 Literature pack

Technical Specifications

Environmental Considerations
Relative Humidity: 0 to 95%, non‑condensing; 15% to 95%,
non‑condensing when used with CO sensor model
Temperature (operating): +32°F to +100°F (0°C to +38°C)
Mechanical Properties
Color: Off-white
Dimensions (diameter x thick­ness)
Material: Fire‑resistant plastic
Outputs
Relay Type: Normally‑open (NO) Form A
Relay Rating: 0.5 A at 120 VDC or 120 VAC
Sounder Output: >85 dB at 10 ft (3 m)
Power Requirements
Voltage Range: 16.0 VDC to 30 VDC
Alarm Current
6-wire mode (4-wire base + two sounder power wires)
Relay: The relay draws 15 mA in alarm.
Steady Sounder: 24 VDC: 30 mA
4-wire mode
With Steady Sounder and Relay:
Standby Current (base only): 30 VDC: 10 mA maximum
6 in. x 0.9 in. (15.2 cm x 2.3 cm)
30 VDC: 35 mA
24 VDC: 45 mA 30 VDC: 50 mA

Ordering Information

F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
Four-wire detector base with sounder for use with the F220 Series Photoelectric Smoke and Heat Detectors.
Accessories
D275 Power Supervision Module
Line supervision device for four-wire fire de­tection circuits
F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder | 3
F220-B6RS
D275
www.boschsecurity.com
4 | F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
Americas:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1750697227 | Cur: en-US, V12, 4 Jul 2010
Europe, Middle East, Africa:
Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.com
Represented by
Loading...