Bosch F220-B6PS, F220-B6PM Specsheet

Fire Alarm Systems | F220‑B6PS/M Addressable Detector Bases with POPITs
F220‑B6PS/M Addressable Detector Bases with POPITs
www.boschsecurity.com
u POPITs provide individual addresses on the control
panel data expansion circuit
The F220‑B6PM 24 VDC Four-wire Addressable Multiple Base and F220‑B6PS 12/24 VDC Four-wire Addressable Single Base, with their built‑in POPITs, provide individual addresses on the FACP data expansion circuit. These bases accept the F220 Family Photoelectric Smoke and Heat Detector Heads. When using these bases with one of the F220 Detectors, they provide a Chamber Check trouble indication to the control panel through the POPIT Bus. The trouble indication appears at the keypads and annunciators as a Fire Trouble. These bases are compatible with addressable systems controlled by D9412G Series or D7412G Series or newer control panels with a D8125 POPEX Module and 12 V or 24 V auxiliary power or a D9124 24 V Fire Alarm Control Panel (FACP).
detectors
u Chamber Check with F220 family detectors
u DIP switch address setting
u Compatible with PAM‑4 Relay Module
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
FM F220-B6P Family
CSFM see our website
NYC­MEA
(UL268 and A), UROX7: Smoke - Auto­matic Fire Detectors Certified for Cana­da (CAN/ULC-S529)
117-05-E
Installation/configuration notes
Compatibility Information
The following products are compatible with both the F220‑B6PM and the F220‑B6PS detector bases:
Category Product ID Product Description
Control Panels
D9124 Addressable FACP
G Series
1
12 V Addressable Control Panels
2 | F220‑B6PS/M Addressable Detector Bases with POPITs
Can be used as replacement bases on systems using
other Bosch Security Systems, Inc. control panels (versions B1 or earlier)
Detector Heads
F220‑135 Rate‑of‑Rise and fixed temperature
heat detector (+135°F [+57°C])
F220‑135F Fixed temperature heat detector
(+135°F [+57°C])
F220‑190F Fixed temperature heat detector
(+190°F [+88°C])
F220‑P Photoelectric smoke detector head
F220‑PTH Photoelectric smoke detector head
with fixed‑temperature (+135°F [+57°C]) heat sensor
F220‑PTHC
2
Photoelectric smoke detector head with fixed‑temperature (+135°F [+57°C]) heat sensor and carbon monoxide sensor enhancement
1
Modules PAM‑4 Relay module
1
Includes the D7412G (and newer) Series and
D9412G (and newer) Series control panels
2
The F220‑PTHC detects carbon monoxide (CO) as a component of a fire. It is not a CO detector and cannot activate an alarm in the presence of CO only. The following products are also compatible with the F220‑B6PM Multiple Detector Base:
Category Product ID Product Description
Detector Bases F220‑B6 Two‑wire detector base
Mounting
The F220‑B6PM and F220‑B6PS bases mount directly on single‑gang switch boxes or on four‑inch square or octagonal back boxes. They can mount directly on a surface using anchors, mollies, or wing nuts.
Wiring
The B6PS/M bases can accept any solid wire size from 12 AWG to 24 AWG (ISO 4 mm2 to 0.2 mm2). The minimum wire size required by the bases is determined by the maximum number of bases used and the maximum distance from the FACP to the most remote base. For specific wiring instructions and specifications, see the F220-B6PS/M Installation Instructions.
Parts included
Quant. Component
1 Detector base with POPIT
1 Literature pack
Technical specifications
Electrical (B6PM)
Current (Alarm)
B6PM with Head3: 39 mA
B6PM with PAM‑4 Relay Module and
55 mA
Head3:
Current (Idle)
B6PM with Head3: 13 mA
B6PM with PAM‑4 Relay Module and
29 mA
Head3:
Auxiliary Power Voltage Range
B6PM with Head3: 18.9 VDC to 28 VDC
B6PM with PAM‑4 Relay Module and
18.9 VDC to 28 VDC
Head3:
3
Current ratings are based on a B6PM with 19 detectors. The B6PM base and the PAM‑4 Relay Module operate at 24 VDC nominal.
Electrical (B6PS)
Current (Alarm)
B6PS with Head4: 35 mA
B6PS with PAM‑4 Relay Module and
51 mA
Head:
Current (Idle)
B6PS with Head4: 2.5 mA
B6PS with PAM‑4 Relay Module and
18.5 mA
Head:
Auxiliary Power Voltage Range
B6PS with Head4: 9.6 VDC to 28 VDC
B6PS with PAM‑4 Relay Module and
9.6 VDC to 28 VDC
Head:
4
The B6PS base can operate at 12 VDC nominal or 24 VDC nominal.
Ordering information
F220‑B6PM 24 VDC Four‑wire Addressable Multiple De­tector Base
The multiple detector base provides an address on the FACP data expansion circuit for its detector and up to an additional 19 detectors. It accepts the F220 Photoelectric Smoke Detector Heads and Heat Detector Heads.
Order number F220-B6PM
Loading...
+ 1 hidden pages