Fire Alarm Systems | F220‑B6 Conventional Detector Bases
F220‑B6 Conventional Detector Bases
www.boschsecurity.com
u Easy installation
u Interchangeable detector heads
u UL listed when used with a detector from the F220
family
The F220‑B6 Detector Bases work with the F220
Photoelectric Smoke and Heat Detectors. The F220‑B6
is a 12 V or 24 V base for two‑wire loops. The other
bases in this family are 12 V or 24 V bases for four‑wire
loops.
Certifications and approvals
Region Certification
USA UL UQGS: Heat - Automatic Fire Detectors
(UL521), UROX: Smoke - Automatic Fire
Detectors (UL268), UROX7: Smoke Automatic Fire Detectors Certified for
Canada (CAN/ULC-S529)
FM F220-B6 Family
CSFM see our website
NYC-
(117-05-E)
MEA
MSFM permit #2200 Sep 2008
Hong Kong HKFSD J-002/C/067
Installation/configuration notes
Compatibility Information
Two‑wire: Bosch Security Systems, Inc. makes no
claim written, oral, or implied that the F220‑B6
Detector Bases work with any two‑wire control panels
except those specified in the Two‑wire Detector/
Control Panel Compatibility List Technical Service
Note (P/N: 4998148185).
Four‑wire: Compatible with all UL Listed four‑wire
control panels. Refer to the control panel's Installation
Instructions for proper end‑of‑line (EOL) resistor
selection.
Detectors: Compatible with the following F220 Series
Detector Heads:
• F220‑P Photoelectric Smoke Detector
• F220‑PTH Photoelectric Smoke Detector with +135°F
(+57°C) Heat Sensor
• F220‑PTHC1 Photoelectric Smoke Detector with
+135°F (+57°C) Heat Sensor and Carbon Monoxide
Sensor Enhancement
1
• F220‑135 Electronic Rate‑of‑Rise, Fixed Temperature
+135°F (+57°C) Heat Detector
• F220‑135F Electronic Fixed Temperature +135°F
(+57°C) Heat Detector
• F220‑190F Electronic Fixed Temperature +190°F
(+88°C) Heat Detector
2 | F220‑B6 Conventional Detector Bases
1
The F220‑PTHC detects carbon monoxide (CO) as a
component of a fire. It is not a CO detector and cannot
activate an alarm in the presence of CO only.
Mounting Considerations
Depending on local regulations, surface mount the
bases using anchors, mollies, or wing nuts; or mount
the bases directly on four‑inch square or octagonal
electrical boxes or single‑gang switch boxes.
Notice
The electrical box must be large enough to
accommodate the number and size of conductors
specified by the National Electrical Code or any
local authorities having jurisdiction (AHJ).
Wiring Considerations
In a two‑wire system, the maximum loop length
depends on the number of detector bases on the loop,
the wire size, and the control panel specifications.
Refer to the control panel's installation instructions for
specific wiring information.
In a four‑wire system, the maximum loop length and
number of bases that can be placed on a loop depend
on the voltage drop on the power circuit. Use standard
voltage drop calculations to ensure that the last
detector on the loop has at least 10 V.
F220‑B6C 12/24 VDC Four‑wire Base with Auxiliary
Form C Relay
Four‑wire base with a normally‑open (NO) alarm loop
relay and a set of auxiliary contacts (Form C).
Order number F220-B6C
F220‑B6E 12/24 VDC Four‑wire Power Supervision Base
with End‑of‑line Power Monitoring Relay
Four‑wire base with a normally‑open (NO) alarm relay
and an EOL power supervision relay.
Order number F220-B6E
Parts included
Quant. Component
1 Detector base
1 Literature pack
Technical specifications
Environmental
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +100°F (0°C to +38°C)
Mechanical
Color: Off-white
Dimensions (diameter x D) 6 in. x 0.9 in. (15.2 cm x 2.3 cm)
Material: Fire‑resistant plastic
Ordering information
F220‑B6 12/24 VDC Two‑wire Base
Standard base for two‑wire (12 VDC or 24 VDC
system) applications.
Order number F220-B6
F220‑B6R Standard 12/24 VDC Four‑wire Base
Standard base for four‑wire (12 VDC or 24 VDC)
detector systems.
Order number F220-B6R