Bosch F220-135, F220-190F, F220-135F Specsheet

Fire Alarm Systems | F220 Heat Detectors
F220 Heat Detectors
www.boschsecurity.com
u Two-wire or four-wire bases
u 50 ft (15.2 m) maximum spacing between detectors
u Visible identification of model: F220‑135 = no ring,
The F220 Heat Detectors include:
• F220‑135: An electronic rate-of-rise, fixed temperature heat detector that initiates an alarm when the ambient temperature exceeds +135°F (+57°C) or when the ambient temperature increases by +15°F (+8.3°C) or more in less than 1 minute
• F220‑135F: An electronic fixed temperature heat detector that initiates an alarm when the ambient temperature reaches +135°F (+57°C).
• F220‑190F: An electronic fixed temperature heat detector that initiates an alarm when the ambient temperature reaches +190°F (+88°C).
The detectors use low current electronic circuitry, so they can connect to 12 VDC nominal or 24 VDC nominal power source circuits. When mounted on the appropriate F220‑B6 Series Mounting Base, the F220 Heat Detectors provide general property protection from fire.
Notice
Heat detectors are not life safety devices.
u Tamper detection
u Dual color LED
Functions
Compatible Bases
Configure the detectors as either two-wire or four-wire depending on the mounting base selected. These detectors are compatible with any of the F220‑B6 bases:
• F220‑B6 12/24 VDC Two-wire Mounting Base
• F220‑B6R Standard 12/24 VDC Four-wire Mounting Base
• F220‑B6RS 24 VDC Four-wire Mounting Base with Sounder
• F220‑B6C 12/24 VDC Four-wire Mounting Base with Auxiliary Form C Relay
• F220‑B6E 12/24 VDC Four-wire Power Supervision Mounting Base
• F220‑B6PM 24 VDC Four-wire Addressable Master Base
• F220‑B6PS 12/24 VDC Four-wire Addressable Base
Dual-color LED
To verify the detector has power and the heat detection circuitry functions, a dual-color LED indicator flashes green every 8 sec when operating normally. It flashes once every 4 sec when a trouble condition exists. The LED latches on red if an alarm
2 | F220 Heat Detectors
occurs, allowing the user to easily verify individual detector alarms. Clear the alarm condition by interrupting power to the detector.
Tamper Detection
When detector heads are correctly installed in any of the F220‑B6 bases, the control panel initiates a trouble signal if a detector is removed from its base. A mechanical tamper lock comes with each base to inhibit unauthorized head removal.
Supervision
The control panel supervises two-wire systems. Supervision of four-wire system power is provided by an end-of-line (EOL) power supervision device such as a D275 or PAM-4, or an F220‑B6E Power Supervision Mounting Base and an EOL resistor as specified by the control panel manufacturer.
Certifications and approvals
Region Certification
Europe CE 89/336/EEC, EN50130-4/A Sept 1998,
USA UL UQGS: Heat - Automatic Fire Detectors
FM F220 Heats
CSFM see our website
NYC­MEA
MSFM 2200 Sep 2008
Hong Kong HKFSD J-002/C/067
EN61000-6-3 Oct 2001
(UL521)
117-05-E
Installation/configuration notes
Compatible Control Panels
Addressable Systems: These detectors are compatible with addressable systems controlled by D9412GV2, D7412GV2, D9412G, or D7412G Control Panels or the D9124 Fire Alarm Control Panel when used with the F220‑B6PM or F220‑B6PS Addressable Detector Bases. Two-wire: Bosch Security Systems, Inc. makes no claim written, oral, or implied that these detectors work with any two-wire control panels except those specified in the Control Panel Compatibility chart in the Technical Service Note (P/N: 4998148185). Four-wire: Thes detectors are compatible with all UL Listed four‑wire control panels. For proper end-of-line (EOL) resistor selection, see the control panel's installation instructions.
Mounting the Bases
Depending on local regulations, the bases can be surface mounted directly on four-inch square or octagonal electrical boxes and single-gang switch boxes.
Notice
The volume of any electrical box used should be adequate to accommodate the number and size of conductors as specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).
End-of-Line Power Supervision
Loop supervision requires one D275 or PAM-4 or F220‑B6E per loop when using F220‑B6R/B6C bases and is accomplished by the control panel.
Wiring the Bases
For detailed wiring instructions, see the F220 Series Detectors with F220‑B6/C/E/R Bases Installation Instructions, the F220 Series Detectors with F220‑B6RS Bases Installation Instructions, or the F220‑B6PS/M Installation Instructions.
Parts included
QuantityComponent
1 Detector head with dust cover
Technical specifications
Electrical
Current (alarm): (detector head only)
Current (start‑up \standby):
Maximum RMS Ripple: 25% of DC input
Power-up Time: 22 sec maximum
Voltage (standby)
F220‑B6: 8.5 VDC to 32.0 VDC
F220‑B6C/‑B6R/‑B6E: 10.0 VDC to 30.0 VDC
F220‑B6RS: 16.0 VDC to 30.0 VDC
F220‑B6PM: 18.9 VDC to 28.0 VDC
F220‑B6PS: With D299: 18.9 VDC to 28.0 VDC
20 mA minimum at 8.5 VDC; 35 mA maximum at 32 VDC
0.12 mA maximum at 35 VDC
Without D299: 9.6 VDC to 28.0 VDC
Environmental
Relative Humidity: 0% to 95% non-condensing
Notice
Consult NFPA 72 for proper detector placement.
Temperature (normal operating):
Note: The normal environment where these detectors are installed should be within the specified normal operating temperature limits.
+32°F to +100°F (0°C to +38°C)