Fire Alarm Systems | E90 Speaker-Strobes with Colored Lenses
E90 Speaker-Strobes with Colored Lenses
www.boschsecurity.com
u Choice of two strobe lens colors with range of
intensity options
u Field‑selectable voltages of 25 VRMS or 70 VRMS
and powers from 1/8 W to 2 W
The Wheelock E90 Colored‑lens Speaker Strobes are
effective for alerting personnel in industrial, military,
or government applications. They are ideal for mass
notification systems and for emergency, warning, or
trouble notification in many industrial operations. They
are not listed for fire alarm use but are built with the
same high‑quality circuits and parts used in
Wheelock's life safety speaker strobes.
These speaker strobes are available in amber or blue
lens colors and include a multi‑candela model with
four field‑selectable settings and a high‑candela
(110 cd) model. The speakers have field‑selectable
voltages (25 VRMS or 70 VRMS) and powers (1/8 W,
1/4 W, 1/2 W, 1 W, or 2 W). They are designed for
indoor use and can be ceiling mounted on standard
electrical boxes.
Certifications and approvals
Region Certification
USA UL UUMW: Speakers and Amplifiers for Fire
Protective Signaling Systems (UL1480,
UL1711, and UL2043) (MCC model)
u Ceiling mount on standard electrical boxes
u Operates from 16 V to 33 V at 1 flash/sec using
filtered or full-wave rectified DC voltage
u Synchronize with SM or DSM Synchronization
Modules
Installation/configuration notes
Compatible Products
The following products are compatible with these E90
Speaker Strobes:
Category Product ID Product Description
Control
D7022
1
Conventional FACP
Panels
D7024
2
Addressable FACP
D7024 Conventional FACP
D8024
D9124
D10024A
1
1
1
Analog FACP
Addressable FACP
Analog FACP
Modules SM‑12/24‑R Synchronization module (red)
DSM‑12/24‑R Dual synchronization module (red)
These speakers are compatible with Wheelock SAFEPATH4 Facility
Communication Systems and Bosch Voice Evacuation Systems.
1
For synchronization, use the SM or DSM modules
with these control panels. The synchronization module
must be set for 24 V operation. When used, the D7022
must be set for 24 VDC operation.
| E90 Speaker-Strobes with Colored Lenses
2
2
When used with a D7039 Multiplex Expansion
Module, the D7024 becomes an addressable fire alarm
control panel (FACP).
Mounting Considerations
Flush mount on indoor ceilings on a 4‑inch
square by 2 1/8‑inch deep electrical back box with a
1 1/2‑inch deep extension ring.
Wiring
Notice
Do not use these strobe units in coded or pulsed
signaling circuits.
The input terminals accept wires with diameters
between 18 AWG and 12 AWG (ISO 0.75 mm2 and
4 mm2).
Parts included
Quant. Component
1 Speaker Strobe
1 Hardware pack
1 Literature pack
24MCC Models: 15 cd: 80 mA RMS maximum
30 cd: 125 mA RMS maximum
75 cd: 205 mA RMS maximum
95 cd: 263 mA RMS maximum
Strobe Current at 33 V
Filtered DC Input
24110W Models: 110 cd: 145 mA RMS maximum
24MCC Models: 15 cd: 35 mA RMS maximum
30 cd: 52 mA RMS maximum
75 cd: 89 mA RMS maximum
95 cd: 118 mA RMS maximum
FWR Input
24110W Models: 110 cd: 270 mA RMS maximum
24MCC Models: 15 cd: 69 mA RMS maximum
30 cd: 99 mA RMS maximum
75 cd: 163 mA RMS maximum
95 cd: 218 mA RMS maximum
Environmental
Relative Humidity: Up to 85%, non‑condensing
Temperature (Operating): +32°F to +120°F (0°C to +49°C)
Technical specifications
Electrical
Voltage (Input): 24 VDC nominal;
16 VDC or FWR to 33 VDC or FWR
Strobe Current at 16 V
Filtered DC Input
24110W Models: 110 cd: 300 mA RMS maximum
24MCC Models: 15 cd: 68 mA RMS maximum
30 cd: 112 mA RMS maximum
75 cd: 211 mA RMS maximum
95 cd: 292 mA RMS maximum
FWR Input
24110W Models: 110 cd: 455 mA RMS maximum
24MCC Models: 15 cd: 112 mA RMS maximum
30 cd: 178 mA RMS maximum
75 cd: 310 mA RMS maximum
95 cd: 400 mA RMS maximum
Strobe Current at 24 V
Filtered DC Input
24110W Models: 110 cd: 195 mA RMS maximum
24MCC Models: 15 cd: 45 mA RMS maximum
30 cd: 72 mA RMS maximum
75 cd: 128 mA RMS maximum
95 cd: 171 mA RMS maximum
Mechanical
Candela Settings: 24110W models: 110 cd
Dimensions
(diameter x D):
Material: Molded plastic enclosure incorporating a Xenon
1
24MCC model settings are rated for clear lenses.
2
24MCC models1: 15 cd, 30 cd, 75 cd, 95 cd
7.25 in. x 2.9 in. (18.4 cm x 7.5 cm)
flashtube and Lexan lens.
Lower the candela rating by approximately 25% for
amber and 70% for blue.
2
When flush mounted the unit extends 0.4 in. (1.1 cm)
from the mounting surface.
Speaker Rating (dBA at 10 ft [3 m])
1/8 W: 75 dBA
1/4 W: 78 dBA
1/2 W: 81 dBA
1 W: 84 dBA
2 W: 87 dBA
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
FWR Input
24110W Models: 110 cd: 320 mA RMS maximum