Multiplex Point Programmer D5060
User’s Guide May 2004
1.0 Introduction
Use the multiplex point programmer (Figure 1 and
Table 1) to program multiplex bus points for the Bosch
Security Systems D9412G, D9412, D9112, D7412G,
D7412, D7212G, and D7212 Control Panels. In
addition to programming points, the D5060 can also
be used to program and read information from a
D8125MUX.
Figure 1: Multiplex Point Programmer
EXT.
POWER
INTERROGATION MODE
YES NO
DOWN
MULTIPLEX POINT PROGRAMMER
SERIAL PORT MUX
ON
(HOLD)
3
2
1
4 56
0
OFF
(HOLD)
(HOLD)
9
#
ENTER
7 8
*
CLEAR
INTERROGATE
POINTS
UP
2.0 Installation
1. If using external power, attach the flying leads of
the included power cable to the output terminals
of a 16.5 VAC transformer. Insert the plug end
into the jack labeled EXT. POWER on the
programmer. Refer to Figure 2, Figure 3, and
Figure 4.
2. For control panels, use the serial cable provided
to connect the D8125MUX to the D9412G,
D9412, D9112, D7412G, D7412, D7212G, or
D7212 Control Panel to the jack labeled SERIAL
PORT on the programmer.
3. For MUX devices without DIP switches, use the
multiplex programmer cable provided to connect
the point to be programmed to the port labeled
MUX POINTS as shown in Figure 2. Use the
appropriate connector, either the alligator clips or
the probes, to connect the programmer to a point.
For MUX devices with DIP switches, program
the point using the DIP switches. Connect the
programmer to the D8125 MUX as shown in
Figure 3, using the C318 serial cable (Figure 4) to
program the point number and point type into
the D8125MUX.
Figure 2: Wiring Diagram When Installing MUX
Points Without DIP Switches
Table 1: D5060 LED Display Definitions
Display Definition
Adr
A.dr
bAd
Err
Lob
noP
PnL
rSP
tYP
t.YP
Enter address
Enter address for Interrogation Mode
Battery voltage is below 15 V
Point was not programmed correctly
Battery voltage is below 16 V
No response from point
Communications with the D8125 failed
Point responds to address
Enter point type
Enter point type for Interrogation Mode
1
12V IN OUT GND
ZONEX BUS
EXT.
POWER
INTERROGATION MODE
RESET
FIREMANUAL
WALK TEST
SERIAL PORT MUX
2
PROG
+-+-+- +-
PORT
POWER A
MUX BUS A
POWER B
MUX BUS B
POINTS
4
1 - External power
2 - D8125 MUX
3 - MUX point without DIP switches (non-i
models)
4 - D5060 Multiplex Point Programmer
3
D5060
It is not necessary to connect a MUX
module to the D5060 to program MUX
points with programming DIP switches.
Figure 3: Wiring Diagram When Installing MUX
Points With DIP Switches
1
12V IN OU T GND
ZONEX BUS
EXT.
POWER
INTERROGATION MODE
RESET
FIREMANUAL
PROG
PORT
WALK TEST
SERIAL PORT MUX
3
2
+-+-+ -+-
POWER A
MUX BUS A
POWER B
MUX BUS B
POINTS
1 - External power
2 - D8125 MUX
3 - D5060 Multiplex Point Programmer
Figure 4: Cables Included with the Programmer
1
2
3.0 Programming Procedure
3.1 Powering the D5060
To turn the D5060 on, press and hold the [1] key until
the unit beeps. To turn the unit off, press and hold the
[#] and [*] keys simultaneously until the unit beeps.
After 5 min of inactivity, the programmer
powers down automatically to conserve
3.2 Programming the Points
1. The D5060 displays the prompt Adr after it is
2. If the MUX device has no DIP switches, connect
3. Enter the point’s three-digit address. The address
power.
powered on. This indicates that it is ready to
begin programming.
the D5060 to the point to be programmed (Figure
2). If the MUX device has DIP switches, program
the device using its DIP switches.
The point must be connected only to the
programmer and not to the D8125MUX or
the MUX bus.
If programming points for a Bosch
Security Systems control panel, and if the
MUX device has no DIP switches,
connect the D8125MUX and the MUX
device to be programmed to the D5060
for simultaneous programming (Figure 2).
If the MUX device has DIP switches,
program the device using its DIP
switches.
must be between 1 and 255. Press [#].
4. The programmer displays tyP. Enter the number
3
corresponding to the point type you are
programming (Table 2), then press [#]. The
programmer alternately displays the address and
the point type.
1 - C318 Serial Cable
2 - C319 External Power Supply Cable
3 - C320 Multiplex Programmer Cable
When programming a Mux Smoke point
(decimal value 4 or 5, as shown in Table
2), an 18-second timer starts counting. Do
not disconnect the Mux Smoke point until
after the timer counts down to zero.