Multi-use Reversing Relay Module
D132B
en Installation Instructions
Multi-use Reversing Relay Module Table of Contents | en 3
1 |
Notices |
4 |
2 |
Device Description |
5 |
3 |
|
|
Installing the module |
6 |
|
4 |
|
|
Wiring the module |
7 |
|
4.1 |
Wiring to a D7022 FACP |
7 |
4.2 |
Wiring to a D7024 or an FPD-7024 FACP |
10 |
4.2.1 |
Two-wire configurations |
10 |
4.2.2 |
Four wire configurations |
12 |
4.2.3 |
Configurations using filtered power |
15 |
4.3 |
Wiring to a D8024, D9024, or D10024 FACP |
18 |
5 |
|
|
Specifications |
21 |
Bosch Security Systems, Inc. |
Installation Instructions |
2012.12 | 1.0 | F.01U.279.509 |
4 |
en | Notices |
Multi-use Reversing Relay Module |
|
|
|
These instructions cover the installation of the D132B Multi-Use Reversing Relay Module in a fire system supervised by a fire alarm control panel (FACP).
Install, test and maintain the D132B according to these instructions, NFPA 72, local codes, and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in failure of the detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible for improperly installed, tested or maintained devices.
Warning!
!Follow these instructions to avoid personal injury and damage to equipment.
Notice!
NFPA 72 requires a complete system wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system’s components, hardware, wiring, programming and software/firmware.
2012.12 | 1.0 | F.01U.279.509 |
Installation Instructions |
Bosch Security Systems, Inc. |
Multi-use Reversing Relay Module Device Description | en 5
The D132B is a multipurpose, fully configurable, smoke power-reversing module for activating detectors with local annunciation. The module will operate both two-wire and four-wire 24 V circuits, and also works with Class A or Class B initiating circuits.
An alarm latch connection is provided to allow an initiating loop to be held in alarm after the detector loop power has been reversed to activate any sounders.
The module does not affect compatibility between the FACP and detectors, or the FACP and notification appliance circuits (NACs).
The maximum current available from the FACP smoke power terminals or NACs limits the total number of reversible smoke detectors that can be connected to the module.
Consult the FACP’s installation instructions for compatibility with the D132B Multi-Use Reversing Relay Module.
Bosch Security Systems, Inc. |
Installation Instructions |
2012.12 | 1.0 | F.01U.279.509 |
6 en | Installing the module Multi-use Reversing Relay Module
The supplied screw and Snap Trac are required to mount the module. It can be mounted anywhere within the FACP’s enclosure using the supplied screw with double sided tape as a mounting aid. Several methods of wiring the module can be used.
Caution!
The voltage supplied to the NAC sounder power terminals must be compatible with the detector voltage requirements when in alarm (reverse polarity). Unfiltered NAC output power is
!typically not compatible with detector sounder power requirements. Use a source of filtered power (for example, smoke power) for NAC sounder power on panels with unfiltered NAC output power, and ensure that the total current draw for detector sounders does not exceed the panel’s rated filtered power output capacity.
Notice!
The D7022, D7024, D8024, D9024, and D10024 do not meet the requirements of UL864, 9th edition. For UL applications, use the FPD 7024.
2012.12 | 1.0 | F.01U.279.509 |
Installation Instructions |
Bosch Security Systems, Inc. |
Multi-use Reversing Relay Module Wiring the module | en 7
Warning!
!Maintain a ¼ in. (6.35 mm) minimum distance between power limited and non power limited wiring.
Warning!
Since full or auxiliary power is applied to loop output terminals TB 1 and TB 2 during an
!alarm, only connect reversing smoke detectors to these terminals. Do not connect pull stations, heat detectors or other such devices. Doing so will damage the D132B module and/or the FACP.
4.1 |
Wiring to a D7022 FACP |
Notice!
The D132B module must be mounted within the control panel enclosure for this application and the D7022 must be set for 24 V operation.
Bosch Security Systems, Inc. |
Installation Instructions |
2012.12 | 1.0 | F.01U.279.509 |
8 |
en | Wiring the module |
Multi-use Reversing Relay Module |
|
|
|
Figure 4.1: Wiring a D132B (2 wire, Class B) to a D7022 FACP
1 |
NAC output |
9 |
Class A |
|
|
|
|
2 |
Input point |
10 |
Latch |
|
|
|
|
3 |
Auxiliary power |
11 |
NAC |
|
|
|
|
4 |
Smoke power |
12 |
24 VDC |
|
|
|
|
5 |
Optional filtered power connections |
13 |
24 V 2 wire reversing detectors |
|
|
|
|
6 |
Unfiltered power; power limited but |
14 |
2.2 kΩ EOL (power limited and |
|
not supervised |
|
supervised); P?N: F.01U.034.504 |
|
|
|
|
7 |
Power limited and supervised |
15 |
24 V NACs |
|
|
|
|
2012.12 | 1.0 | F.01U.279.509 |
Installation Instructions |
Bosch Security Systems, Inc. |