Blaupunkt F.01U.512.629 Datasheet

Communications Systems | LBB 1956/00 Plena Voice Alarm Call Station
LBB 1956/00 Plena Voice Alarm Call Station
www.boschsecurity.com
u Stylish six-zone call station for the Plena Voice
Alarm System
PTT-key for calls
u Selectable gain, speech filter, limiter, and output
level for improved intelligibility
u LED indications for zone selection, fault, and
emergency state
u Call station extension provides seven additional
zone and zone group keys
The Plena call station is a stylish, high-quality call station with a stable metal base design, a flexible microphone stem and a unidirectional condenser microphone. It can make calls to selected zones (one to six and all-call) in a public address system built with the Plena Voice Alarm System. In addition to tabletop use, the special design allows it to be neatly flush­mounted in desktops. The Plena Voice Alarm Keypad (LBB 1957/00) is an extension adding seven additional keys.
Functions
Each call station supports six zone selections. The number of selectable zones or zone groups can be increased by connecting call station keypads (LBB 1957/00). Up to eight keypads can be added with each keypad adding seven zone or zone-group keys.
This call station features selectable gain, a selectable speech filter, and a limiter for improved intelligibility. The call station has a balanced line level output, making it possible to position it up to 1000 meters
from the controller, using CAT-5 extension cables. With shielded cable, the call station can also be used in an EMC level 5 (heavy industry) environment.
DIP switches at the base of the call station select different microphone gain levels, the call station ID, and the speech filter. A service accessible rotary control provides microphone level attenuation. LEDs on the call station show which zones have been selected. Three additional LEDs give visible feedback on the active state of the microphone and the system. Green flashing means standby (chime is sounding). Green indicates microphone active. Amber indicates that the system has detected a fault, and red indicates that the system is in the emergency state.
Controls and indicators
• Four status LEDs
• PTT-key
• PTT status LED
• Six zone selection keys
• Six zone selection LEDs
• All-call key
• Eight DIP switches
2 | LBB 1956/00 Plena Voice Alarm Call Station
• Rotary volume control
Interconnections
• Two RJ45 jacks
• 24 VDC input
• Keypad connector
Certifications and approvals
Safety acc. to EN 60065
Immunity acc. to EN 55103-2
Emission acc. to EN 55103-1
Region Certification
Europe CE Declaration of Conformity
Parts included
Quantity Components
1 LBB 1956/00 Plena Voice Alarm Call Station
1 Cable terminated with a lockable CAT-5 connector
Technical specifications
Electrical
Mechanical
Base dimensions 40 x 100 x 235 mm
(1.57 x 3.97 x 9.25 in)
Weight Approx. 1 kg
Mounting Standalone
Color Charcoal with silver
Stem length with mic 390 mm (15.35 in)
Cable length 5 m (16.4 ft)
Environmental
Operating temperature -10 ºC to +45 ºC (14 ºF to +113 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity <95%
Ordering information
LBB 1956/00 Plena Voice Alarm Call Station
metal base design, a flexible microphone stem and a unidirectional condenser microphone. It can make calls to selected zones (one to six and all-call)
Order number LBB1956/00
Power Supply
Voltage range 24 VDC supplied by LBB 1990/00
(or 18 to 24 VDC or VAC external power supply)
Current consumption <30 mA (plus <15 mA per keypad)
Performance
Nominal sensitivity 85 dB SPL (gain preset 0 dB)
Nominal output level 700 mV
Input sound level (max) 110 dB SPL
Gain preset +6 / 0 / -15 dB
Limiter threshold 2 V
Compression ratio limiter 1:20
Distortion <0.6% (maximum input)
Input noise level (equiv.) 25 dB SPLA
Frequency response 100 Hz to 16 kHz
Speech filter -3dB at 315 Hz, high-pass, 6 dB/oct
Output impedance 200 ohm
Selections
Chimes Any wave file
Priorities 7
Loading...