BERG BME461, BME252, BME251, BME362, BME332 Operating Instructions Manual

...
Page 1
Berg GmbH Frauenhoferstraße 22 82152 Martinsried, Germany Phone +49 379 160 - 0 Fax +49 379 160 - 199 E-Mail info@berg-energie.de www.berg-energie.de
Operating Instructions
3/8.18
Edited in Germany • Subject to change without notice • PDF version available on the Internet
Electronic Energy Meters
Efficio Certified
Direct Meter BME Transformer Meter BME
1Scope of Delivery
1Energy meter 2 Operating instructions (German and English)
Operating instructions can be found at www.berg-energie.de
2 Safety Precautions – Symbols
– Check the specified nominal voltage on the serial
plate before placing the instrument into service. – Observe maximum pulse output voltage. – When wiring the instrument, make sure the connec-
tor cables are not damaged, and that they are volt-
age-free. – If it can be assumed that safe operation is no longer
possible, the instrument must be immediately
removed from service (disconnect input voltage!).
Safe operation can no longer be relied upon if the
instrument demonstrates visible damage.
The device may not be placed back into operation
until troubleshooting and repair have been per-
formed, and calibration and dielectric strength have
been tested and approved at our factory or an autho-
rized service center. – Voltage conducting parts may be exposed if the
cover is opened.
If balancing, maintenance or repair of a live open
instrument is required, this may only be carried out by
trained personnel who are familiar with the dangers
involved. – When connecting measuring current, it is important
to provide for low-ohmic contact and to select an
appropriate conductor diameter.
Meanings of Symbols on the Instrument
DE MTP 18 B 004 MI-003 (Direct Meter) DE MTP 18 B 005 MI-003 (Transformer Meter)
Prototype test certificate
Total insulation, protection class II device
Warning concerning a point of danger (attention, observe documentation!)
This device may not be disposed of with the trash. Further information can be accessed on the Internet at www.berg-energie.de.
Metrology mark with indication of year (M18) and register no. of the notified body for module D, country-specific calibration validity period
Marking with stamp of the federally approved test laboratory
(for recalibration only)
Tamper-Proof Sealing – Opening the Meter / Repairs Tamper-Proof Calibration Sealing
with Manufacturer’s Seal (at the side) If the manufacturer’s seal is damaged or removed, all guarantee claims are rendered null and void. The meter may only be opened by authorized, trained per­sonnel in order to ensure flawless operation and to assure that the guarantee is not rendered null and void. If it can be ascertained that the
meter
has been opened by unauthorized personnel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any consequential damages. Tamper-proof sealing for the terminal cover may be attached either to the left or the right of the terminal cover.
3 Rating Plate Entries
4 Connector Pin Assignments and Wire Gauge
Note: Observe the wiring diagrams in the top and bot-
tom terminal covers.
Meas. Inputs, Direct Meter (top & bottom terminals)
Meas. Inputs, Transformer Meter (bottom terminals)
Connections (top terminals)
5 Pulse Output
Default setting: active energy Terminal 23 (S01) import, terminal 25 (S02) export
* Type of energy can also be selected with feature Impuls.
Underlined values are default values.
* Pulse rates are based on secondary side
!
M18
1948
EBY
8
18
Connections Direct Meter Transformer Meter
Current input Solid wire 16 sq. mm
Fine wire 25 mm
2
or
16 mm2 with wire end ferrule Tightening torque: 3-4 Nm
Solid wire 4 sq. mm Tightening torque: 0,5-0,6 Nm
Voltage input
N: solid wire ≤ 2.5 sq. mm Tightening torque: 0,4 Nm
Solid wire 4 sq. mm Tightening torque: 0,5-0,6 Nm
SØ pulse output Bus output, tariff input (power utility pulse)
Solid wire 2.5 sq. mm Tightening torque: 0,4 Nm
Solid wire 2.5 sq. mm Tightening torque: 0,4 Nm
TCP/IP
RJ45 (8P8C)
Prototype test certificate
Accuracy class / operating temperature
Energy export / energy import
Nominal voltage Imin - In (Imax.) / nominal frequency
Warning
Protective insulation
Symbol for system type
Yea r of man uf act ure
Metrology mark
LED constant
2D code
EBY
8
18
Serial number
Up key
Enter key
Anti-reversing for
the registers in both energy directions
Bidirectional meter
L2
L1
L3
Voltage Voltage
Current Current Current
Voltage
CurrentCurrent Current
N
Voltage Voltage Voltage
Current Current Current
L3
L2L1 N
Current
CurrentCurrent
Tar if f
Connections
W1: LON W2: M-Bus W4: TCP/IP W7: Modbus RTU V1 ... 9: SØ pulse output
Tb Tn Ta
TCP/IP
Pulse Rates programmable V2 Direct Meter
1 1000
Imp/kWh
Transformer * CT, VT progr.
1
...
1000
...
50000Imp/kWh
R
L
+
24
23/25
U
t
Energy type*
Max. 40 V
24 V DC
I = max. 27 mA
U
External Voltage Source
Standard pulse duration: 30 ms + 5%, interpulse period: > 30 ms V7/V8 pulse duration: 130 ms + 5%, interpulse period: > 130 ms
6 Display and Control Panel
6.1 Test LEDs
The
test LEDs
are located above the control keys. The left­hand LED indicates energy export, and the right-hand LED energy import. LED blinking frequency increases along with measured power. If all currents are smaller than start­ing current, both LEDs light up continuously.
LED Constant
Direct Meter: 10,000 pls/kWh Transformer Meter: 100,000 pls/kWh
6.2 Resolution, Main Display (large characters) Energy Import
Intern wird mit erhöhter Auflösung gezählt. Hierdurch kann bei Mehrtarifnutzung das Gesamtregister in der letzten Stelle einige Digit über der Summe der Einzelregister liegen.
* An additional place to the right of the decimal point is included
for the calibration display in the case of a main display which can be calibrated. And thus the leading digit is eliminated in the case of an 8-place display.
** Due to programmable CT, VT only the secondary display can be
calibrated. Therefore, display overflow is based on the secondary display. The normal display is shifted one place to the left if neces­sary.
6.3 Meanings of Symbols at the LCD
u Main display
, not calibrated (programmable CT/VT, see section 6.2). T1 ... T8: active tariff
Display of instantaneous power in 4 quad­rants: positive or negative active power P, positive or negative reactive power Q.
Correct connection: Continuous illumination of the phase symbols where P
0
Phase failure:
Symbol for affected phase is cleared from the display.
Incorrect phase sequence:
Phase symbols blink in following order: 3 - 2 - 1.
Negative power:
Respective phase symbol blinks.
For bus connection: appears when the meter transmits a data packet.
Key symbols for parameters configuration (see next column)
Key Symbols for Parameters Configuration
for Feature Q1 and V2:
Key and 2nd key bit blanked: Parameter CT, VT and SØ configurable according to features, disabling with enable key. Key displayed with one bit: Parameter CT, VT and SØ disabled, change after activating the enable key.
6.4 LCD Background Illumination
Background illumination is activated each time a key is activated. Background illumination goes off after about 2 minutes. Background illumination colors indicate various display menus: – White: query menus – Red: display of firmware version – Pink: parameters display and setting menu – Blinking red: in case of error
6.5 Key Operation
Querying Parameter Values
In addition to the LCD test, the UP and ENTER keys also make it possible to query currently set parameter val­ues, as well as to change parameters for certain fea­tures after first pressing the enable key (located behind the top cover).
If no keys are pressed for a period of 1 minute, the meter is returned automatically to its standard display.
Parameters can be changed for the following meters:
Parameters CT and VT for Transformer Meter, Parameter SØ for Pulse Meter. Further parameters in accordance with interface descri­tion.
a) Enabling Parameter Changes
The enable key makes it possible to enable or disable parameter changes. It’s located underneath the top ter­minal cover between terminals 21 and 22 and is acti­vated with a pointed o bject (e.g. a ballpoint pen). Pressing the enable key activates the “change parame­ters” operating mode (key off):
Pressing the enable key again disables the “change parameters” operating mode (key on):
If no keys are pressed for a period of about 2 minutes, the “change parameters” operating mode is exited auto­matically and disabled (key on).
b) Changing Parameter Values
Briefly press the enabling key as described in point
a) above (this activates the “change parameters” operating mode).
See the operating overview on the back with regard
to changing the parameters.
Press and hold the ENTER key until the firmware ver-
sion appears (red background).
Press the UP key. The display test appears.
Briefly press and hold the ENTER key in order to dis- play two further test patterns.
Then repeatedly press the UP key until the parame-
ter to be changed appears at the display.
Briefly press the ENTER key in order to access the
setting menu.
The input cursor blinks at the leftmost entry posi-
tion. Each tine the ENTER key is pressed the cursor is advanced to the next position to the right. The value of the blinking digit can be increased by pressing the UP key. When the rightmost digit is ac­knowledged by pressing the ENTER key, the se­lected value is accepted and SAVinG appears briefly at auxiliary display 2. If no keys are pressed for a period of about one minute, the setting menu is exited.
Press and hold the ENTER key or wait for one minute
in order to change to the normal display.
Press the enable key once again. This disables the
“change parameters” operating mode. Disabling takes place automatically after 2 minutes.
Meter CTxVT
min.
CTxVT max.
Normal dis­play
Calibration display *
Unit
Direct Meter
— 123456,78 23456,789 kWh
Trans
for­mer
meter
Q1 **
1 4 u12345,67 ** kWh
5 40 u123456,7 ** kWh
41 400 u1234567 ** kWh
401 4000 u12345,67 ** MWh
4001 40000 u123456,7 ** MWh
40001 100000 u1234567 ** MWh
Main display
(active energy* in kWh or MWh)
Auxiliary display 1 (active power* in kW or MW)
* Transformer meter: CT and VT are taken into account
Auxiliary display 2 (e.g. IN, OUT for import or export) In case of error: error code alternates with current display
(reactive energy* in kVArh or MVArh)
(reactive energy or power in kVAr(h) or MVAr(h)*)
Power: negative sign for export
Enable Key
Repair and Replacement Parts Service Recalibration
Recalibration can be conducted at any time by our fed­erally approved test laboratory.
Page 2
7 Switching Amongst Tariffs
Hardware Controlled
Tariff inputs Ta and Tb are each connected with refer­ence to Tn. Level 0: < 12 V Level 1: > 45 V (max. 265 V permissible!)
Software Controlled (not included in MID scope of approval)
In the case of meters with bus connection, four further tariffs can be selected (software controlled).
8 Overview of Bus Systems
LON-Bus –M-Bus – TCP/IP (BacNet IP/Modbus TCP) –Modbus RTU
Interface descriptions for energy meters with bus connection can be found on the Internet at www.berg-energie.de.
9 Error Messages – Reset
Display
If an error occurs, the respective error code and active energy or instantaneous power are displayed alter­nately.
LOVoLt e rror
In case of LOVoLt error (phase voltages too low), back­ground illumination, and if applicable the bus connec­tion, are deactivated. The load profile (feature load pro­file) cannot be viewed as long as the error is pending.
10 Repair and Recalibration
Note for Test Laboratories Direct measuring meter: Testing is only possible with
source which supply currents superimposed on volt­ages.
Calibration Display
Display of energy values with increased resolution can be selected for testing or calibration purposes. Press and hold the ENTER key once to this end. The
firmware version is displayed with a red back­ground.
Press the UP key twice. The calibration display ap-
pears with a pink background. Resolution depending on display, see section 6.2. Recalibration can be conducted at any time by a feder-
ally approved test laboratory (e. g. EB-8) (see repair and service address on the back of the folder). Calibration capability is valid for 8 years in Germany.
11 Manufacturer’s Guarantee
The energy meters are guaranteed for a period of 3 years after shipment. The manufacturer’s guarantee covers materials and workmanship. Damages resulting from use for any other than the intended purpose or operating errors, as well as any and all consequential damages, are excluded.
12 Ambient Conditions
13 Return and Environmentally Sound Disposal
The BME meter is a category 9 product (monitoring and control instrument) in accordance with ElektroG (Ger­man electrical and electronic device law). This device is subject to the RoHS directive. We identify our electrical and electronic devices in accordance with WEEE 2012/19/EU and ElektroG using the symbol shown at the right per DIN EN 50419. These devices may not be disposed of with the trash. Please contact our service department regarding the return of old devices.
14 Declaration of Conformity, Direct Meter 15 Declaration of Conformity, Transformer Meter
Tariff Input Tb Ta
Tariff 1 0 0
Tariff 2 0 1
Tariff 3 1 0
Tariff 4 1 1
Error Code Meaning Cause / Remedy
0L0volt
Phase voltage < 75% Check connection
0VHi1
Maximum value for U1 exceeded
Check connection
0 VHi 2
Maximum value for U2 exceeded
Check connection
0 VHi3
Maximum value for U3 exceeded
Check connection
1Hi1
Maximum value for I1 exceeded
Check connection
1Hi2
Maximum value for I2 exceeded
Check connection
1Hi3
Maximum value for I3 exceeded
Check connection
0SYnc
Frequency measuring error
Meter connected to direct voltage
0C0m
Interface error
Check connection
EnErgY
Meter defective
Send device to repair serv ice
0cALib
Balancing required
0
AnALog
DC offset too high
!!!!!!!!!
!!!
Operating temperature range –25 ... +55 °C
Storage temperature range –25 ... +70 °C
Relative humidity < 75% annual average
Elevation to 2000 m
Deployment Indoors
mechanical classification M1
electromagnetical classification E2
Protection (built-in device) front panel: IP 51
Protection terminal area IP20
12345. 678
4567
kWh
W
1 n a
Calibration
Firmware
Normal display
Pulse rate
Pulse Duration
Feature V2/V4
Feature V2/V4
12345. 678
678
kVArh
VAr
1
n R
CT
VT
112345
.
6
7
8
4567
kWh
W
0 u t a-
12345
.
6
7
8
678
kVArh
VAr
0 u t R-
12345
.
6
7
8
1
2345.
678
kWh
kVArh
1 n
Reactive energy import, total
1 123
4
2 1
234
W
3 1
234
Active power / phase
1 230.0
2
230
.
4
V
3 230
.
4
Phase voltages
12345
.
6
7
8
1
2345.
678
kWh
kVArh
0 u t
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 0 u t
Export, total
Active energy import, total
Tariff (T1)
Tariff (T1)
Power displays
1 1234
2
1234
VAr
3 1234
1 1 234 2
1234
VA
3 1234
1234
1234
VA
VAr
1234
Reactive power / phase
Apparent power / phase
Total power
Mains monitor
12 400.4
23
400
.
4
V
31 : 400
.
4
Line-to-line voltage
Switching Between Active and Reactive Energy – Display Tests – Calibration Display – Setting Transformer and S0 Interface Parameters Switching Amongst Tariffs, Active and Reactive Energy, as well as Power Displays and Mains Monitor, Optional Display of the Load Profile
1
Total active power (kW) appears at auxiliary display 2
2
Not approved for billing purposes in Switzerland
Measuring Function
Feature
Measured Quantity Accuracy M3
2
Active energy (kWh) 1EP1...EP8, EPtot ±1%
Reactive energy (kVArh)
EQ1...EQ8, EQtot
±2%
Star voltage (V) U1N, U2N, U3N0.5% ±1 d
Delta voltage (V) U12, U23, U13 0.5% ±1 d
Current per phase (A) I1, I2, I3 0.5% ±1 d
N conductor current (A) I
N
1% ± 1 d, typ.
Active power (kW) P1, P2, P3, Ptot 1% ±1 d
Reactive energy (kVAr) Q1, Q2, Q3, Qtot 1% ±1 d
Apparent power (kVA) S1, S2, S3, Stot 1% ±1 d
Power fa ctor (cos phi)
PF1, PF2, PF3, PFtot
1% ±1 d
Frequency (Hz) f 0.05% ±1 d
RMS distortion value THD U1, U2, U3
THD I1, I2, I3
Blinking cursor
Identifies the current entry position. Position selection via ENTER. The value at the cursor position can be changed with the UP key (upward arrow ).
Abbreviations
ct Transformation ratio, current I
N
N conductor current (calculated) SØ SØ pulse output THD Distortion component (for voltage and current) vt Transformation ratio, voltage
Features
M3 Multifunctional variant:
measurement of U, I, P, Q, S, PF, f, THD, In, reactive energy Q1 Programmable transformation ratios V2 Programmable SØ W1 ... 7Bus connections
Keys
ENTER key (press briefly)
ENTER key (press and hold)
UP key (press briefly)
long
Pulse source
4 pulse sources for pulse outputs SØ1 and SØ2:
– Active energy import (+) kWh or export – kWh – Reactive energy import (+) kVAr or export – kVAr
2 states: SØ switch “
C l o s e d” or “0 p e n”
Operating Overview
W
Feature V2/V4
Transformation ratios (Transformer Meter only)
Feature bus connection: T5 ... T8
Active energy import
Active energy export
Fixed display and illumination – live values
12345
.
6
7
8
1
2345.678
kWh
kVArh
1 n
Active energy import, total
12345
.
6
7
8
1
2345.678
kWh
kVArh
0 u t
Active energy export, total
2 additional
Display test
Pulse rate
Number of pulses to be read out per kWh
Pulse duration
Duration of the pulse for the on state or the high value: at least 30 ms, e.g. 70 ms in case of processing problems
version
1 .0 0
2345. 6789
1234.5678
kWh
kWh
1234
W
2345. 6789
1234.5678
kWh
kWh
hold
10000
c t
10000
c t
set
1000
u t
1000
u t
set
50 1000
per kWh
50 1000
per kWh
set
50 0.100
sec
50 0.100
sec
set
50 srC1/2
+ / – kWh
50 srC1/2
+ / – kWh
set
SØ pulse output**
test patterns
8888:88:88
8888:88:88
kWh
kWh
88:88:88
Information for manufacturing
All Tariffs *
Active tariff (here T1)
Reactive energy import, total Reactive energy export, total
Reactive energy, capacitive Reactive power, capacitive
Active energy export Active power export
Reactive energy, inductive Reactive power, inductive
Active energy import Active power import
* Max. 4 tariffs with S0
or 8 tariffs with bus
T1 T1 T1 T1 T1T3 T1T3
T2T4 T2T4
long
** See corresponding interface description for additional menus in case of bus connections.
Transformer Meter: Programmable CT, VT
T1T3
T1T3
T1
T1
pf1 : 1
.
00
2
: 1. 00
3 : 1
.
00
Power factor / phase
pf : 1
.
00
50.00 H
z
Power factor
T1
T1
T1
T1
T1
T1
1 1
.
234
2
1. 234
A
3 1
.
234
1n1.234 A
50.00 hz
kW
dv1 : 0.120
2
: 0. 042
3 : 0
.
050
THD U1, U2, U3
d11 : 0
.
476
2
: 0. 120
3 : 0
.
092
THD I1, I2, I3
T1
T1
T1
T1
T1
T1
Phase currents
Line frequency
4-wire only4-wire only
4-wire only4-wire only4-wire only4-wire only
Active Tariff (here T1)
3/4-wire
2-wire
1234
1234
VA
VAr
1234
Apparent/reactive/active power
W
pf : 1
.
00
50.00 H
z
Power factor
T1
T1
123.4
1
.
234
V
A
50.00 H
z
Voltage/current/frequency
dv : 0
.
028
d1
: 0. 082
THD U, I
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 0 u t
Tariff (T2)
Tariff (T2)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 0 u t
Tariff (T3)
Tariff (T3)
T1
T1
long
12345
.
6
7
8
1
2345.
678
kWh
kVArh
t1 : 1 n
Reactive energy
12345
.
6
7
8
1
2345.
678
kWh
kVArh
t1 : 0 u t
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 0 u t
Tari ff ( T1)
Active energy
Tari ff ( T2)
Tari ff ( T2)
Feature bus connection: T5 ... T8
T1
T1
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 0 u t
Tari ff ( T3)
Tari ff ( T3)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 4 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 4 : 0 u t
Tari ff ( T4)
Tari ff ( T4)
T1
T1
T2T4
T2T4
Q1: secondary calibrated
Tariff (T1)
N current (4-wire only)
display
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.4
3.8.4
2.8.4
4.8.4
OBIS
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.0
3.8.0
2.8.0
4.8.0
Loading...