Beckhoff KL3041, KL3051, KL3042, KL3052, KL3044 Documentation

...
Documentation
KL304x, KL305x
Single-, Dual- and Four-Channel Analog Input Terminals, Measuring range: 0...20 mA and 4...20 mA, Single ended
Version: Date:
4.0 2017-10-06
Table of contents
1 Foreword ....................................................................................................................................................5
1.1 Notes on the documentation........................................................................................................... 5
1.2 Safety instructions .......................................................................................................................... 6
1.3 Documentation issue status............................................................................................................ 7
2 Product overview.......................................................................................................................................8
2.1 KL3041, KL3051 – Introduction ...................................................................................................... 8
2.2 KL3042, KL3052 – Introduction ...................................................................................................... 9
2.3 KL3044, KL3054 – Introduction .................................................................................................... 10
2.4 KL304x, KL305x - Technical data................................................................................................. 11
2.5 Basic function principles ............................................................................................................... 11
3 Mounting and wiring ...............................................................................................................................13
3.1 Instructions for ESD protection ..................................................................................................... 13
3.2 Installation on mounting rails ........................................................................................................ 13
3.3 Installation instructions for enhanced mechanical load capacity .................................................. 17
3.4 Connection.................................................................................................................................... 17
3.4.1 Connection system...........................................................................................................17
3.4.2 Wiring...............................................................................................................................19
3.4.3 Shielding ..........................................................................................................................20
3.5 KL3041, KL3051 - Connection and LED description .................................................................... 21
3.6 KL3042, KL3052 - Connection and LED description .................................................................... 22
3.7 KL3044, KL3054 - Connection and LED description .................................................................... 23
3.8 ATEX - Special conditions (standard temperature range) ............................................................ 24
3.9 ATEX - Special conditions (extended temperature range) ........................................................... 25
3.10 ATEX Documentation ................................................................................................................... 26
4 Configuration Software KS2000.............................................................................................................27
4.1 KS2000 - Introduction ................................................................................................................... 27
5 Access from the user program ..............................................................................................................29
5.1 Terminal configuration .................................................................................................................. 29
5.2 Mapping in the Bus Coupler ......................................................................................................... 30
5.2.1 KL3041 and KL3051 ........................................................................................................30
5.2.2 KL3042 and KL3052 ........................................................................................................31
5.2.3 KL3044 and KL3054 ........................................................................................................32
5.3 Register overview ......................................................................................................................... 33
5.4 Register description ...................................................................................................................... 35
5.5 Control and status byte................................................................................................................. 39
5.5.1 Process data exchange ...................................................................................................39
5.5.2 Register communication...................................................................................................40
5.6 Examples of Register Communication.......................................................................................... 41
5.6.1 Example 1: reading the firmware version from Register 9 ...............................................41
5.6.2 Example 2: Writing to an user register.............................................................................42
6 Appendix ..................................................................................................................................................45
6.1 Support and Service ..................................................................................................................... 45
KL304x, KL305x 3Version: 4.0
KL304x, KL305x4 Version: 4.0
Foreword

1 Foreword

1.1 Notes on the documentation

Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the documentation and the following notes and explanations are followed when installing and commissioning these components. It is the duty of the technical personnel to use the documentation published at the respective time of each installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany. The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
KL304x, KL305x 5Version: 4.0
Foreword

1.2 Safety instructions

Safety regulations
Please note the following safety instructions and explanations! Product-specific safety instructions can be found on following pages or in the areas mounting, wiring, commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Description of symbols
In this documentation the following symbols are used with an accompanying safety instruction or note. The safety instructions must be read carefully and followed without fail!
DANGER
WARNING
CAUTION
Attention
Note
Serious risk of injury!
Failure to follow the safety instructions associated with this symbol directly endangers the life and health of persons.
Risk of injury!
Failure to follow the safety instructions associated with this symbol endangers the life and health of persons.
Personal injuries!
Failure to follow the safety instructions associated with this symbol can lead to injuries to persons.
Damage to the environment or devices
Failure to follow the instructions associated with this symbol can lead to damage to the en­vironment or equipment.
Tip or pointer
This symbol indicates information that contributes to better understanding.
KL304x, KL305x6 Version: 4.0
Foreword

1.3 Documentation issue status

Version Comment
4.0 • Migration
• Update Technical data
• Structure update
• Chapters KS2000 configuration software and Access from the user program added
Firmware (FW) and hardware (HW) versions
Documen­tation, Version
4.0 3C 08 3C 07 3B 04 3C 07 3C 07 3B 04
The firmware and hardware versions (delivery state) can be found in the serial number printed on the side of the terminal.
Syntax of the serial number
Structure of the serial number: WWYYFFHH
KL3041 KL3042 KL3044 KL3051 KL3052 KL3054
FW HW FW HW FW HW FW HW FW HW FW HW
WW - week of production (calendar week) YY - year of production FF - firmware version HH - hardware version
Example with ser. no.: 35 04 1B 01:
35 - week of production 35 4 - year of production 2004 1B - firmware version 1B 1 - hardware version 1
KL304x, KL305x 7Version: 4.0
Product overview

2 Product overview

2.1 KL3041, KL3051 – Introduction

Fig.1: KL3041, KL3051
The job of the KL3041 and KL3051 analog input terminals is to supply power to measuring transducers located in the field, and to transmit analog measurement signals with electrical isolation to the automation device. The KL3041 terminal processes signals in the range from 0mA to 20mA. The KL3051 terminal processes signals in the range from 4mA to 20mA. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a power feed terminal (KL9xxx) with electrical isolation. The input electronics is independent of the supply voltage of the power contacts. The 0 V rail is the reference potential for the inputs. The Run LEDs indicate the exchange of data with the Bus Coupler, while the Error LEDs indicate overload and wire breakage.
KL304x, KL305x8 Version: 4.0

2.2 KL3042, KL3052 – Introduction

Product overview
Fig.2: KL3042, KL3052
The job of the KL3042 and KL3052 analog input terminals is to supply power to measuring transducers located in the field, and to transmit analog measurement signals with electrical isolation to the automation device. The KL3042 terminal processes signals in the range from 0mA to 20mA. The KL3052 terminal processes signals in the range from 4mA to 20mA. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a power feed terminal (KL9xxx) with electrical isolation. The input electronics is independent of the supply voltage of the power contacts. The 0 V rail is the reference potential for the inputs. The Run LEDs indicate the exchange of data with the Bus Coupler, while the Error LEDs indicate overload and wire breakage.
KL304x, KL305x 9Version: 4.0
Product overview

2.3 KL3044, KL3054 – Introduction

Fig.3: KL3044, KL3054
The job of the KL3044 and KL3054 analog input terminals is to transmit analog measurement signals with electrical isolation to the automation device. The KL3044 terminal processes signals in the range from 0mA to 20mA. The KL3054 terminal processes signals in the range from 4mA to 20mA. The input electronics is independent of the supply voltage of the power contacts. The ground connection is the reference potential for the inputs. The error LEDs indicate an overload condition. The KL3044 and KL3054 combine four channels in a single housing.
KL304x, KL305x10 Version: 4.0
Product overview

2.4 KL304x, KL305x - Technical data

Technical data KL3041 KL3051 KL3042 KL3052 KL3044 KL3054
Number of inputs 1 2 4
Power supply for the sensors 24VDC via the power contacts
Signal current 0mA to
Technology Single-ended
Internal resistance 80Ω + diode voltage 0.7V
Surge voltage resistance 35V max.
Resolution 12bit
Conversion time ~1ms ~2ms ~4ms
Measuring error (total mea­suring range)
Electrical isolation 500V (K-Bus / signal voltage)
Power supply for the electron­ics
Current consumption from the K-bus
Bit width in the K-bus I/O Input: 1 x 16bits of data (1 x
Configuration No address or configuration settings
Weight approx. 70g
Dimensions (W x H x D) approx. 15mmx100mmx70mm (width aligned: 12mm)
Mounting [}13]
Permissible ambient tempera­ture range during operation
Permissible ambient tempera­ture range during storage
Permissible relative air hu­midity
Vibration/shock resistance
EMC immunity/emission conforms to EN61000-6-2/ EN61000-6-4
Protection class IP20
Installation position variable
Approval
20mA
<±0.3% of the full scale value
via the K-Bus
typically 65mA
8bit control/status optional)
on 35mm mounting rail conforms to EN60715
0°C ... + 55°C -25°C ... +60°C (extended
-25°C ... + 85°C -40°C ... +85°C -25°C ... + 85°C -40°C ... +85°C
95%, no condensation
conforms to EN60068-2-6/ EN60068-2-27, see also Installation instructions for enhanced mechanical
load capacity [}17]
CE, cULus, ATEX [}24],GLCE, cULus, ATEX [}25],GLCE, cULus, ATEX
4mA to 20mA
0mA to 20mA
<±0.30% (at 0°C to +55°C) <±0.75% (when the ex­tended temperature range is used)
Input: 2 x 16bits of data (2 x 8bit control/status op­tional)
temperature range)
4mA to 20mA
-
0mA to 20mA 4mA to 20mA
<±0.3% of the full scale value
Input: 4 x 16bits of data (4 x 8bit control/sta­tus optional)
0°C ... + 55°C -25°C ... +60°C (ex-
[}24], GL
<±0.30% (at 0°C to +55°C) <±0.75% (when the extended temperature range is used)
tended temperature range)
CE, cULus, ATEX [}25], GL

2.5 Basic function principles

The analog input terminals KL304x process signals in the range from 0mA to 20mA KL305x process signals in the range from 4mA to 20mA with 12-bit resolution (4095 steps). The terminal inputs are single-ended inputs. The KL3041, KL3042, KL3051 and KL3052 can supply the sensors with voltage supplied via the power contacts. The KL3044 and KL3054 have no power contacts. The power contacts can optionally be supplied via the standard supply or via a power feed terminal with electrical isolation.
The LEDs indicate the operating state of the associated terminal channels.
• green Run LED (omitted for KL3044 and KL3054):
◦ On: Normal operation
◦ Off: Watchdog-timer overflow has occurred. If no process data are transmitted by the Bus
Coupler for 100ms, the green LEDs go out.
• red Error LED:
KL304x, KL305x 11Version: 4.0
Product overview
◦ On: The limit stop of the A/D converter has been reached. The current is greater than 21.5mA.
◦ Off: Normal operation
Process data output format
In the delivery state the process data are shown in two's complement form (integer -1 corresponds to 0xFFFF). Other presentation types can be selected via the feature register (R32) [}37] (e.g.signed amount
representation, Siemens output format).
Measured value Output
KL304x KL305x dec hex
0mA 4mA 0 0x0000
10mA 12mA 16383 0x3FFF
20mA 20mA 32767 0x7FFF
Calculation of process data
The terminal continuously takes measured values and stores the raw values of its A/D converter in register R0 [}35] (RAM ). The calculation of the correction with the calibration values takes place after each
sampling of the analog signal. This is followed by manufacturer and user scaling:
The process data that are transferred to the Bus Coupler are calculated using the following equations:
Y_a = (B_a + X_adc) * A_a Y_aus = Y_a
Y_1 = B_h + A_h * Y_a Y_aus = Y_1
Y_2 = B_w + A_w * Y_a Y_aus = Y_2
Y_1 = B_h + A_h * Y_a Y_2 = B_w + A_w * Y_1 Y_aus = Y_2
(1.0) Neither user nor manufacturer scaling is active.
(1.1) Manufacturer scaling active: (Default setting)
(1.2) User scaling active
(1.3) (1.4)
Manufacturer and user scaling active
Key
Name Name Register
X_adc Output value of the A/D converter -
Y_aus Process data for controller -
B_a Vendor calibration: Offset
A_a Vendor calibration: Gain
B_h Manufacturer scaling: Offset
A_h Manufacturer scaling: Gain
B_w User scaling: Offset
A_w User scaling: Gain
R17 [}36]
R18 [}36]
R19 [}36]
R20 [}36]
R33 [}37]
R34 [}37]
The equations of the straight line are enabled via register R32 [}37].
Fig.4: KL304x, KL305x - Data flow
KL304x, KL305x12 Version: 4.0

3 Mounting and wiring

3.1 Instructions for ESD protection

Destruction of the devices by electrostatic discharge possible!
The devices contain components at risk from electrostatic discharge caused by improper
Attention
handling.
ü Please ensure you are electrostatically discharged and avoid touching the contacts of
the device directly.
a) Avoid contact with highly insulating materials (synthetic fibers, plastic film etc.).
b) Surroundings (working place, packaging and personnel) should by grounded probably,
when handling with the devices.
c) Each assembly must be terminated at the right hand end with an EL9011 bus end cap,
to ensure the protection class and ESD protection.
Mounting and wiring
Fig.5: Spring contacts of the Beckhoff I/O components

3.2 Installation on mounting rails

Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation,
WARNING
disassembly or wiring of the Bus Terminals!
KL304x, KL305x 13Version: 4.0
Mounting and wiring
Assembly
Fig.6: Attaching on mounting rail
The Bus Coupler and Bus Terminals are attached to commercially available 35mm mounting rails (DIN rails according to EN60715) by applying slight pressure:
1. First attach the Fieldbus Coupler to the mounting rail.
2. The Bus Terminals are now attached on the right-hand side of the Fieldbus Coupler. Join the compo­nents with tongue and groove and push the terminals against the mounting rail, until the lock clicks onto the mounting rail. If the Terminals are clipped onto the mounting rail first and then pushed together without tongue and groove, the connection will not be operational! When correctly assembled, no significant gap should be visible between the housings.
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting
Note
rail. At the installation, the locking mechanism of the components must not come into con­flict with the fixing bolts of the mounting rail. To mount the mounting rails with a height of
7.5mm under the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
KL304x, KL305x14 Version: 4.0
Mounting and wiring
Disassembly
Fig.7: Disassembling of terminal
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1cm away from the mounting rail. In doing so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved housing surfaces and pull the terminal out of the bus terminal block.
Connections within a bus terminal block
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24V) or for higher voltages via power feed terminals.
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Termi-
Note
PE power contact
nals must be taken account of, since some types (e.g. analog Bus Terminals or digital 4­channel Bus Terminals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx or EL91xx, EL92xx) interrupt the power contacts and thus rep­resent the start of a new supply rail.
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first when plugging together, and can ground short-circuit currents of up to 125A.
KL304x, KL305x 15Version: 4.0
Mounting and wiring
Fig.8: Power contact on left side
Attention
WARNING
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g. disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230V). For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In order to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at least 10mm from the group of terminals.
Risk of electric shock!
The PE power contact must not be used for other potentials!
KL304x, KL305x16 Version: 4.0
Mounting and wiring

3.3 Installation instructions for enhanced mechanical load capacity

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting,
WARNING
Additional checks
The terminals have undergone the following additional tests:
Verification Explanation
Vibration 10 frequency runs in 3 axes
Shocks 1000 shocks in each direction, in 3 axes
Additional installation instructions
disassembly or wiring of the Bus Terminals!
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
60.1Hz<f<500Hz acceleration 5g, constant amplitude
25 g, 6 ms
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is: 64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A distance of approx. 10 cm should be maintained to the cable duct.

3.4 Connection

3.4.1 Connection system

Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation,
WARNING
disassembly or wiring of the Bus Terminals!
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective application:
• The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection level in a single enclosure.
• The terminals of ESxxxx and KSxxxx series feature a pluggable connection level and enable steady wiring while replacing.
KL304x, KL305x 17Version: 4.0
Mounting and wiring
• The High Density Terminals (HD Terminals) include electronics and connection level in a single enclosure and have advanced packaging density.
Standard wiring (ELxxxx / KLxxxx)
Fig.9: Standard wiring
The terminals of ELxxxx and KLxxxx series have been tried and tested for years. They feature integrated screwless spring force technology for fast and simple assembly.
Pluggable wiring (ESxxxx / KSxxxx)
Fig.10: Pluggable wiring
The terminals of ESxxxx and KSxxxx series feature a pluggable connection level. The assembly and wiring procedure for the KS series is the same as for the ELxxxx and KLxxxx series. The KS/ES series terminals enable the complete wiring to be removed as a plug connector from the top of the housing for servicing. The lower section can be removed from the terminal block by pulling the unlocking tab. Insert the new component and plug in the connector with the wiring. This reduces the installation time and eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3 mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual connection wires when the connector is removed.
Conductor cross sections between 0.08mm2 and 2.5mm2 can continue to be used with the proven spring force technology.
The overview and nomenclature of the product names for ESxxxx and KSxxxx series has been retained as known from ELxxxx and KLxxxx series.
High Density Terminals (HD Terminals)
Fig.11: High Density Terminals
KL304x, KL305x18 Version: 4.0
Mounting and wiring
The Bus Terminals from these series with 16 terminal points are distinguished by a particularly compact design, as the packaging density is twice as large as that of the standard 12mm Bus Terminals. Massive conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal point without tools.
Wiring HD Terminals
The High Density (HD) Terminals of the ELx8xx and KLx8xx series doesn't support plug-
Note
Ultrasonically "bonded" (ultrasonically welded) conductors
gable wiring.
Ultrasonically “bonded" conductors
It is also possible to connect the Standard and High Density Terminals with ultrasonically
Note
"bonded" (ultrasonically welded) conductors. In this case, please note the tables concern­ing the wire-size width below!

3.4.2 Wiring

Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation,
WARNING
disassembly or wiring of the Bus Terminals!
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
Fig.12: Connecting a cable on a terminal point
Up to eight terminal points enable the connection of solid or finely stranded cables to the Bus Terminal. The terminal points are implemented in spring force technology. Connect the cables as follows:
1. Open a terminal point by pushing a screwdriver straight against the stop into the square opening above the terminal point. Do not turn the screwdriver or move it alternately (don't toggle).
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal point closes automatically when the pressure is released, holding the wire securely and permanently.
KL304x, KL305x 19Version: 4.0
Mounting and wiring
See the following table for the suitable wire size width.
Terminal housing ELxxxx, KLxxxx ESxxxx, KSxxxx Wire size width (single core wires) 0.08 ... 2.5mm Wire size width (fine-wire conductors) 0.08 ... 2.5mm Wire size width (conductors with a wire end sleeve) 0.14 ... 1.5mm
2
2
2
0.08 ... 2.5mm 0,08 ... 2.5mm
0.14 ... 1.5mm
2
2
2
Wire stripping length 8 ... 9mm 9 ... 10mm
High Density Terminals (HD Terminals [}18]) with 16 terminal points
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are released, as usual, using the contact release with the aid of a screwdriver. See the following table for the suitable wire size width.
Terminal housing High Density Housing Wire size width (single core wires) 0.08 ... 1.5mm Wire size width (fine-wire conductors) 0.25 ... 1.5mm Wire size width (conductors with a wire end sleeve) 0.14 ... 0.75mm Wire size width (ultrasonically “bonded" conductors) only 1.5mm
2
2
2
2
Wire stripping length 8 ... 9mm

3.4.3 Shielding

Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted
Note
paired wires.
KL304x, KL305x20 Version: 4.0
Mounting and wiring

3.5 KL3041, KL3051 - Connection and LED description

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting,
WARNING
disassembly or wiring of the Bus Terminals!
Fig.13: KL3041, KL3051 - Connection and LEDs
Connection of KL3041, KL3051
Terminal point No. Comment
+Input 1 1 + Input 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 0V (internally connected to terminal point 7 and negative power contact)
Shield 4 PE contact (internally connected to terminal point 8)
n.c. 5 not used
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 0V (internally connected to terminal point 3 and negative power contact)
Shield 8 PE contact (internally connected to terminal point 4)
KL3041, KL3051 - LED description
LED Color Description
Run1 LED green On: Normal operation
Off: Watchdog-timer overflow has occurred. If no process data is transmitted to the bus
Error1 LED red On: The limit stop of the A/D converter has been reached. The current is greater than
Off: Normal operation
coupler for 100ms, the green LEDs go out
21.5mA.
KL304x, KL305x 21Version: 4.0
Mounting and wiring

3.6 KL3042, KL3052 - Connection and LED description

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting,
WARNING
disassembly or wiring of the Bus Terminals!
Fig.14: KL3042, KL3052 - Connection and LEDs
Connection of KL3042, KL3052
Terminal point No. Comment
+Input 1 1 + Input 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 0V (internally connected to terminal point 7 and negative power contact)
Shield 4 PE contact (internally connected to terminal point 8)
+Input 2 5 + Input 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 0V (internally connected to terminal point 3 and negative power contact)
Shield 8 PE contact (internally connected to terminal point 4)
KL3042, KL3052 - LED description
LED Color Description
Run1 LED, Run2 LED
Error1 LED, Error2 LED
green On: Normal operation
Off: Watchdog-timer overflow has occurred. If no process data is transmitted to the bus
coupler for 100ms, the green LEDs go out
red On: The limit stop of the A/D converter has been reached. The current is greater than
21.5mA.
Off: Normal operation
KL304x, KL305x22 Version: 4.0
Mounting and wiring

3.7 KL3044, KL3054 - Connection and LED description

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting,
WARNING
disassembly or wiring of the Bus Terminals!
Fig.15: KL3044, KL3054 - Connection and LEDs
Connection of KL3044, KL3054
Terminal point No. Comment
+Input 1 1 + Input 1
GND 2 Internal ground (internally connected to terminal point 6)
+Input 3 3 + Input 3
GND 4 Internal ground (internally connected to terminal point 8)
+Input 2 5 + Input 2
GND 6 Internal ground (internally connected to terminal point 2)
+Input 4 7 + Input 4
GND 8 Internal ground (internally connected to terminal point 4)
KL3044, KL3054 - LED description
LED Color Description
Error1 LED, Error2 LED, Error3 LED, Error4 LED
red On: The limit stop of the A/D converter has been reached. The current is greater than
21.5mA.
Off: Normal operation
KL304x, KL305x 23Version: 4.0
Mounting and wiring

3.8 ATEX - Special conditions (standard temperature range)

Observe the special conditions for the intended use of Beckhoff fieldbus components with standard temperature range in potentially explosive areas (directive 94/9/EU)!
WARNING
• The certified components are to be installed in a suitable housing that guarantees a protection class of at least IP54 in accordance with EN 60529! The environmental con­ditions during use are thereby to be taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured tempera­ture values!
• Observe the permissible ambient temperature range of 0 to 55°C for the use of Beck­hoff fieldbus components standard temperature range in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than 40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal sys­tem if the supply voltage has been switched off or if a non-explosive atmosphere is en­sured!
• The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with standard temperature range certified for potentially explosive areas bear one of the following markings:
II 3GKEMA 10ATEX0075 X Ex nA IIC T4 GcTa: 0…55°C
or
II 3GKEMA 10ATEX0075 X Ex nC IIC T4 GcTa: 0…55°C
KL304x, KL305x24 Version: 4.0
Mounting and wiring

3.9 ATEX - Special conditions (extended temperature range)

Observe the special conditions for the intended use of Beckhoff fieldbus components with extended temperature range (ET) in potentially explosive areas (directive 94/9/EU)!
WARNING
• The certified components are to be installed in a suitable housing that guarantees a protection class of at least IP54 in accordance with EN 60529! The environmental con­ditions during use are thereby to be taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured tempera­ture values!
• Observe the permissible ambient temperature range of -25 to 60°C for the use of Beck­hoff fieldbus components with extended temperature range (ET) in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than 40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal sys­tem if the supply voltage has been switched off or if a non-explosive atmosphere is en­sured!
• The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with extended temperature range (ET) certified for potentially explosive areas bear the following marking:
II 3GKEMA 10ATEX0075 X Ex nA IIC T4 GcTa: -25…60°C
or
II 3GKEMA 10ATEX0075 X Ex nC IIC T4 GcTa: -25…60°C
KL304x, KL305x 25Version: 4.0
Mounting and wiring

3.10 ATEX Documentation

Notes about operation of the Beckhoff terminal systems in potentially explo­sive areas (ATEX)
Note
Pay also attention to the continuative documentation
Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)
that is available in the download area of the Beckhoff homepage http:\\www.beckhoff.com!
KL304x, KL305x26 Version: 4.0
Configuration Software KS2000

4 Configuration Software KS2000

4.1 KS2000 - Introduction

The KS2000 configuration software permits configuration, commissioning and parameterization of bus couplers, of the affiliated bus terminals and of Fieldbus Box Modules. The connection between bus coupler/ Fieldbus Box Module and the PC is established by means of the serial configuration cable or the fieldbus.
Fig.16: KS2000 configuration software
Configuration
You can configure the Fieldbus stations with the Configuration Software KS2000 offline. That means, setting up a terminal station with all settings on the couplers and terminals resp. the Fieldbus Box Modules can be prepared before the commissioning phase. Later on, this configuration can be transferred to the terminal station in the commissioning phase by means of a download. For documentation purposes, you are provided with the breakdown of the terminal station, a parts list of modules used and a list of the parameters you have modified. After an upload, existing fieldbus stations are at your disposal for further editing.
Parameterization
KS2000 offers simple access to the parameters of a fieldbus station: specific high-level dialogs are available for all bus couplers, all intelligent bus terminals and Fieldbus Box modules with the aid of which settings can be modified easily. Alternatively, you have full access to all internal registers of the bus couplers and intelligent terminals. Refer to the register description for the meanings of the registers.
KL304x, KL305x 27Version: 4.0
Configuration Software KS2000
Commissioning
The KS2000 software facilitates commissioning of machine components or their fieldbus stations: Configured settings can be transferred to the fieldbus modules by means of a download. After a login to the terminal station, it is possible to define settings in couplers, terminals and Fieldbus Box modules directly online. The same high-level dialogs and register access are available for this purpose as in the configuration phase.
The KS2000 offers access to the process images of the bus couplers and Fieldbus Box modules.
• Thus, the coupler's input and output images can be observed by monitoring.
• Process values can be specified in the output image for commissioning of the output modules.
All possibilities in the online mode can be used in parallel with the actual fieldbus mode of the terminal station. The fieldbus protocol always has the higher priority in this case.
KL304x, KL305x28 Version: 4.0
Access from the user program

5 Access from the user program

5.1 Terminal configuration

The terminal can be configured and parameterized via the internal register structure. Each terminal channel is mapped in the Bus Coupler. Mapping of the terminal data in the Bus Coupler memory may differ, depending on the Bus Coupler type and the set mapping configuration (e.g.Motorola/Intel format, word alignment etc.). For parameterizing a terminal, the control and status byte also has to be mapped.
BK2000 Lightbus Coupler
In the BK2000 Lightbus Coupler, the control/status byte is always mapped, in addition to the data bytes. This is always located in the low byte at the offset address of the terminal channel.
Fig.17: Mapping in the Lightbus coupler - example for KL3042 and KL3052
BK3000 Profibus Coupler
For the BK3000 Profibus coupler, the master configuration should specify for which terminal channels the control and status byte is to be inserted. If the control and status byte are not evaluated, the terminals occupy 2bytes per channel:
• KL3041 and KL3051: 2bytes of input data
• KL3042 and KL3052: 4bytes of input data
• KL3044 and KL3054: 8bytes of input data
Fig.18: Mapping in the Profibus coupler - example for KL3042 and KL3052
BK4000 Interbus Coupler
The BK4000 Interbus Coupler maps the terminals in the delivery state with 2bytes per channel:
KL304x, KL305x 29Version: 4.0
Access from the user program
• KL3041 and KL3051: 2bytes of input data
• KL3042 and KL3052: 4bytes of input data
• KL3044 and KL3054: 8bytes of input data
Parameterization via the fieldbus is not possible. If the control and status byte is to be used, the KS2000 configuration software is required.
Fig.19: Mapping in the Interbus coupler - example for KL3042 and KL3052
Other Bus Couplers and further information
Further information about the mapping configuration of Bus Couplers can be found in the Appendix of the respective Bus Coupler manual under Master configuration.
The chapter on Mapping in the Bus Coupler [}30] contains an overview of possible mapping configurations, depending on the configurable parameters.
Parameterization with KS2000
The KS2000 configuration software can be used for parameterizations via the serial inter­face of the Bus Coupler, independent of the fieldbus system.
Note

5.2 Mapping in the Bus Coupler

As already described in the Terminal Configuration section, each Bus Terminal is mapped in the Bus Coupler. This mapping is usually done with the default setting in the Bus Coupler / Bus Terminal. The KS2000 configuration software or a master configuration software (e.g.ComProfibus or TwinCAT System Manager) can be used to change this default setting. If the terminals are fully evaluated, they occupy memory space in the input and output process image. The following tables provide information about how the terminals map themselves in the Bus Coupler, depending on the parameters set.

5.2.1 KL3041 and KL3051

Default mapping for: CANopen, CANCAL, DeviceNet, ControlNet, Modbus, RS232 and RS485 coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: no Word alignment: any
0 Ch1 D1 Ch1 D0
1 - -
2 - -
3 - -
KL304x, KL305x30 Version: 4.0
Access from the user program
Default mapping for: Profibus and Interbus Coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: yes Word alignment: any
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: no
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: no
0 Ch1 D0 Ch1 D1
1 - -
2 - -
3 - -
0 Ch1 D0 Ch1 CB/SB
1 - Ch1 D1
2 - -
3 - -
0 Ch1 D1 Ch1 CB/SB
1 - Ch1 D0
2 - -
3 - -
Default mapping for: Lightbus & Ethernet coupler and Bus Terminal Controller (BCxxxx, BXxxxx)
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: yes
0 Res. Ch1 CB/SB
1 Ch1 D1 Ch1 D0
2 - -
3 - -
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: yes
0 Res. Ch1 CB/SB
1 Ch1 D0 Ch1 D1
2 - -
3 - -
Key
Complete evaluation The terminal is mapped with control and status byte.
Motorola format Motorola or Intel format can be set.
Word alignment The terminal is positioned on a word boundary in the Bus Coupler.
Ch n CB Control byte for channel n (appears in the process image of the outputs).
Ch n SB Status byte for channel n (appears in the process image of the inputs).
Ch n D0 Channel n, data byte 0 (byte with the lowest value)
Ch n D1 Channel n, data byte 1 (byte with the highest value)
"-" This byte is not used or occupied by the terminal.
Res. Reserved: This byte is assigned to the process data memory, although it has no function.

5.2.2 KL3042 and KL3052

Default mapping for: CANopen, CANCAL, DeviceNet, ControlNet, Modbus, RS232 and RS485 coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: no Word alignment: any
0 Ch1 D1 Ch1 D0
1 Ch2 D1 Ch2 D0
2 - -
3 - -
KL304x, KL305x 31Version: 4.0
Access from the user program
Default mapping for: Profibus and Interbus Coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: yes Word alignment: any
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: no
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: no
0 Ch1 D0 Ch1 D1
1 Ch2 D0 Ch2 D1
2 - -
3 - -
0 Ch1 D0 Ch1 CB/SB
1 Ch2 CB/SB Ch1 D1
2 Ch2 D1 Ch2 D0
3 - -
0 Ch1 D1 Ch1 CB/SB
1 Ch2 CB/SB Ch1 D0
2 Ch2 D0 Ch2 D1
3 - -
Default mapping for: Lightbus & Ethernet coupler and Bus Terminal Controller (BCxxxx, BXxxxx)
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: yes
0 Res. Ch1 CB/SB
1 Ch1 D1 Ch1 D0
2 Res. Ch2 CB/SB
3 Ch2 D1 Ch2 D0
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: yes
0 Res. Ch1 CB/SB
1 Ch1 D0 Ch1 D1
2 Res. Ch2 CB/SB
3 Ch2 D0 Ch2 D1
Key
Complete evaluation The terminal is mapped with control and status byte.
Motorola format Motorola or Intel format can be set.
Word alignment The terminal is positioned on a word boundary in the Bus Coupler.
Ch n CB Control byte for channel n (appears in the process image of the outputs).
Ch n SB Status byte for channel n (appears in the process image of the inputs).
Ch n D0 Channel n, data byte 0 (byte with the lowest value)
Ch n D1 Channel n, data byte 1 (byte with the highest value)
"-" This byte is not used or occupied by the terminal.
Res. Reserved: This byte is assigned to the process data memory, although it has no function.

5.2.3 KL3044 and KL3054

Default mapping for: CANopen, CANCAL, DeviceNet, ControlNet, Modbus, RS232 and RS485 coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: no Word alignment: any
0 Ch1 D1 Ch1 D0
1 Ch2 D1 Ch2 D0
2 Ch3 D1 Ch3 D0
3 Ch4 D1 Ch4 D0
KL304x, KL305x32 Version: 4.0
Access from the user program
Default mapping for: Profibus and Interbus Coupler
Conditions Word offset High byte Low byte
Complete evaluation: no Motorola format: yes Word alignment: any
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: no
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: no
0 Ch1 D0 Ch1 D1
1 Ch2 D0 Ch2 D1
2 Ch3 D0 Ch3 D1
3 Ch4 D0 Ch4 D1
0 Ch1 D0 Ch1 CB/SB
1 Ch2 CB/SB Ch1 D1
2 Ch2 D1 Ch2 D0
3 Ch3 D0 Ch3 CB/SB
4 Ch4 CB/SB Ch3 D1
5 Ch4 D1 Ch4 D0
0 Ch1 D1 Ch1 CB/SB
1 Ch2 CB/SB Ch1 D0
2 Ch2 D0 Ch2 D1
3 Ch3 D1 Ch3 CB/SB
4 Ch4 CB/SB Ch3 D0
5 Ch4 D0 Ch4 D1
Default mapping for: Lightbus & Ethernet coupler and Bus Terminal Controller (BCxxxx, BXxxxx)
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: no Word alignment: yes
Conditions Word offset High byte Low byte
Complete evaluation: yes Motorola format: yes Word alignment: yes
0 Res. Ch1 CB/SB
1 Ch1 D1 Ch1 D0
2 Res. Ch2 CB/SB
3 Ch2 D1 Ch2 D0
4 Res. Ch3 CB/SB
5 Ch3 D1 Ch3 D0
6 Res. Ch4 CB/SB
7 Ch4 D1 Ch4 D0
0 Res. Ch1 CB/SB
1 Ch1 D0 Ch1 D1
2 Res. Ch2 CB/SB
3 Ch2 D0 Ch2 D1
4 Res. Ch3 CB/SB
5 Ch3 D0 Ch3 D1
6 Res. Ch4 CB/SB
7 Ch4 D0 Ch4 D1
Key
Complete evaluation The terminal is mapped with control and status byte.
Motorola format Motorola or Intel format can be set.
Word alignment The terminal is positioned on a word boundary in the Bus Coupler.
Ch n CB Control byte for channel n (appears in the process image of the outputs).
Ch n SB Status byte for channel n (appears in the process image of the inputs).
Ch n D0 Channel n, data byte 0 (byte with the lowest value)
Ch n D1 Channel n, data byte 1 (byte with the highest value)
Res. Reserved: This byte is assigned to the process data memory, although it has no function.

5.3 Register overview

These registers exist once for each channel.
KL304x, KL305x 33Version: 4.0
Access from the user program
Address Name Default value R/W Storage medium
R0 [}35]
R1 to R5 reserved 0x0000 R
R6 [}35]
R7 [}35]
R8 [}35]
R9 [}35]
R10 [}35]
R11 [}35]
R12 [}35]
R13 [}35]
R14 reserved 0x0000 R
R15 [}36]
R16 [}36]
R17 [}36]
R18 [}36]
R19 [}36]
R20 [}36]
R21 [}36]
R22 [}36]
R23 [}36]
R24 to R30 reserved 0x0000 R/W SEEROM
R31 [}36]
R32 [}37]
R33 [}37]
R34 [}37]
R35 [}37]
R36 [}38]
R37 to R63 reserved 0x0000 R/W SEEROM
Raw ADC value variable R RAM
Diagnostic register variable R RAM
Command register - not used 0x0000 R
Terminal type e.g.3042 R ROM
Software version number 0x???? R ROM
Multiplex shift register 0x0218/0130 R ROM
Signal channels 0x0218 R ROM
Minimum data length 0x0098 R ROM
Data structure 0x0000 R ROM
Alignment register variable R/W RAM
Hardware version number 0x???? R/W SEEROM
Hardware compensation: Offset specific R/W SEEROM
Hardware compensation: Gain specific R/W SEEROM
Manufacturer scaling: Offset 0x0000 R/W SEEROM
Manufacturer scaling: Gain 0x2002 R/W SEEROM
Overrange limit 0x0FFF R/W SEEROM
Under range limit 0x0000 R/W SEEROM
ADC hardware preset 0x0000 R/W SEEROM
Code word register variable R/W RAM
Feature register 0x01106 R/W SEEROM
User scaling: Offset 0x0000 R/W SEEROM
User scaling: Gain 0x0100 R/W SEEROM
Limit value 1 0x0000 R/W SEEROM
Limit value 2 0x0000 R/W SEEROM
KL304x, KL305x34 Version: 4.0
Access from the user program

5.4 Register description

The registers can be read or written via the register communication. They are used for the parameterization of the terminal.
R0 to R7: Registers in the internal RAM of the terminal
The process variables can be used in addition to the actual process image. Their function is specific to the terminal.
R0 ADC raw value (X_R) This register contains the raw ADC value with gain and offset error
R1 to R5: Reserved
R6: Diagnostic register
◦ High byte: reserved
◦ Low byte: Status byte
R7: Command register High-Byte_Write = function parameter Low-Byte_Write = function number High-Byte_Read = function result Low-Byte_Read = function number
R8 to R15: Registers in the internal ROM of the terminal
The type and system parameters are hard programmed by the manufacturer, and the user can read them but cannot change them.
R8: Terminal type The terminal type in register R8 is needed to identify the terminal.
R9: Software version (X.y) The software version can be read as a string of ASCII characters.
R10: Data length R10 contains the number of multiplexed shift registers and their length in bits. The Bus Coupler sees this structure.
R11: Signal channels Related to R10, this contains the number of channels that are logically present. Thus for example a shift register that is physically present can perfectly well consist of several signal channels.
R12: Minimum data length The particular byte contains the minimum data length for a channel that is to be transferred. If the MSB is set, the control and status byte is not necessarily required for the terminal function and is not transferred to the control, if the Bus Coupler is configured accordingly.
R13: Data type register
Data type register Meaning
0x00 Terminal with no valid data type
0x01 Byte array
0x02 Structure 1 byte n bytes
0x03 Word array
0x04 Structure 1 byte n words
0x05 Double word array
0x06 Structure 1 byte n double words
0x07 Structure 1 byte 1 double word
0x08 Structure 1 byte 1 double word
0x11 Byte array with variable logical channel length
0x12 Structure 1 byte n bytes with variable logical channel length (e.g. 60xx)
0x13 Word array with variable logical channel length
0x14 Structure 1 byte n words with variable logical channel length
0x15 Double word array with variable logical channel length
0x16 Structure 1 byte n double words with variable logical channel length
KL304x, KL305x 35Version: 4.0
Access from the user program
R14: reserved
R15: Alignment bits (RAM) The alignment bits are used to place the analog terminal in the Bus Coupler on a byte boundary.
R16 to R30: Manufacturer parameter area (SEEROM)
The manufacturer parameters are specific for each type of terminal. They are programmed by the manufacturer, but can also be modified by the controller. The manufacturer parameters are stored in a serial EEPROM in the terminal, and are retained in the event of voltage drop-out.
These registers can only be altered after a code word has been set in R31 [}36].
R17: Hardware compensation - offset (B_a) 16bit signed integer
This register is used for offset compensation of the terminal (Eq. 1.1 [}12]). Register value approx. 0xFFXX
R18: Hardware compensation - gain (A_a) 16bit signed integer*2-
12
This register is used for gain compensation of the terminal (Eq. 1.1 [}12]). 1 corresponds to register value 01000 Register value approx. 0x11XX
R19: Manufacturer scaling - offset (B_h) 16bits signed integer [0x0000]
This register contains the offset of the manufacturer straight-line equation (equation 1.3 [}12]). The straight-line equation is activated via register R32 [}37].
R20: Manufacturer scaling - gain (A_h) 16bit signed integer*2
-10
[0x2002]
This register contains the scale factor of the manufacturer's equation of the straight line (Eq. 1.3 [}12]). The straight-line equation is activated via register R32 [}37].
1 corresponds to register value 0x0400.
R21: Over range limit (OVRL) 16bits signed integer in Y_a (Eq. 1.0 [}12]) [0x0FFF]
This limit value limits the maximum measuring range of the input terminal. If it is exceeded, the associated status bit is set, and the maximum value is displayed.
R22: Under range limit (UNRL) 16bit signed integer in Y_a (Eq. 1.0 [}12]) [0x0000]
If the actual value falls below this limit, the associated status bit is set, and the minimum value is displayed.
R23: ADC hardware preset [0x0000] Initialization of the ADC offset register.
R31 to R47: User parameter area (SEEROM)
The user parameters are specific for each type of terminal. They can be modified by the programmer. The user parameters are stored in a serial EEPROM in the terminal, and are retained in the event of voltage drop-out. The user area is write-protected by a code word.
• R31: Code word register in RAM
The code word 0x1235 must be entered here so that parameters in the user area can be
Note
R32: Feature register [0x1106] This register specifies the operation modes of the terminal. Thus, forinstance, a user-specific scaling can be activated for the analog I/Os.
modified. If any other value is entered into this register, the write-protection is active. When write protection is not active, the code word is returned when the register is read. If the write protection is active, the register contains a zero value.
KL304x, KL305x36 Version: 4.0
Feature bit no. Description of the operation mode Bit 0 1
Bit 1 1
User scaling (R33, R34 [}37]) active [0]
Manufacturer scaling (R19, R20 [}36]) active [1]
Bit 2 1 Watchdog timer active [1]
In the delivery state, the watchdog timer is switched on.
Bit 3 1 Sign / amount representation [0]
Sign / amount representation is active instead of two's-complement representation. (-1=0x8001).
Bit 4 1 Siemens output format [0]
This bit is used for inserting status information on the lowest 3 bits (see below).
Bits 5 to 7 - Reserved, don't change Bit 8 1 Over range Protection [1]
If values exceed or fall below the limits of the registers OVRL (R21 [}36]) and UNRL (R22 [}36]), the status bits are set and the measuring range is
restricted accordingly.
Bit 9 1 Limit value 1 active [0]
The process data are compared with limit value 1 (R35 [}37]), and appropriate status bits are set.
Bit 10 1 Limit value 2 active [0]
The process data are compared with limit value 2 (R36 [}38]), and appropriate status bits are set.
Bit 11 1 Filter1 active [0]
For filter properties, see R37 [}38]
Bits 12 to 15 - Reserved, don't change
Access from the user program
If the Siemens output format is selected, the lowest threebits are used for status evaluation. The process data is represented in bits 15 to 3, with bit15 representing the sign bit. Scaling of the measured value
according to the Siemens standard has to be done via user scaling (R33, R34 [}37]).
KL3041, KL3042 and KL3044
Measured value Bits 15 to 3 Bit 2
X
Bit1 Error
Bit 0 Overflow
Measured value > 20mA 0 0 1 Measured value <20mA Process data 0 0 0
KL3051, KL3052 and KL3054
Measured value Bits 15 to 3 Bit 2
X
Bit1 Error
Bit 0 Overflow
Measured value > 20mA 0 0 1 4mA < measured value
Process data 0 0 0
<20mA Measured value < 4mA Process data 0 1 1
R33: User scaling - offset (B_w) 16bit signed integer
This register contains the offset of the user straight-line equation (Eq. 1.4 [}12]). The straight-line equation is activated via register R32 [}37].
R34: User scaling - gain (Aw_) 16bit signed integer*2
-8
This register contains the scale factor of the user straight-line equation (Eq. 1.4 [}12]). The straight-line equation is activated via register R32 [}37].
R35: Limit value 1 (Y_2) If the process data are outside this threshold, the appropriate bits are set in the status byte.
KL304x, KL305x 37Version: 4.0
Access from the user program
R36: Limit value 2 (Y_2) If the process data are outside this threshold, the appropriate bits are set in the status byte.
R37: Filter constant [0x0000]
If the internal filter is activated via R32.11 [}37], you can choose between the following filter constants in R37 (not possible with KL3044 and KL3054). In the standard setting, the corresponding conversion time is 2.5ms:
Applies to all terminals from firmware version 3x.
This documentation applies to all terminals from firmware version 3x. The version informa-
Note
R37 Explanation
0x0000 2nd order FIR filter default value 0x0100 1st order IIR filter, cut-off frequency f
approx.1kHz
0x0200 1st order IIR filter, cut-off frequency fg approx.
100Hz
0x0300 1st order IIR filter, cut-off frequency fg approx.
50Hz
0x0400 1st order IIR filter, cut-off frequency fg approx.
20Hz
0x0500 1st order IIR filter, cut-off frequency fg approx.
10Hz
0x0600 1st order IIR filter, cut-off frequency fg approx.
5Hz
0x0700 1st order IIR filter, cut-off frequency fg approx.
1Hz
0x1000 50Hz FIR filter
Averaging over 16 values and first notch 25Hz
0x2000 60Hz FIR filter
Averaging over 16 values and first notch 20Hz
Other
No filter active
values
tion can be found on the right-hand side of the terminal in the serial number: xxxx3xxx.
Example: 52983A2A => the firmware version is 3A.
g
The implemented IIR filters do not have any notch behavior, i.e.,they do not explicitly suppress any frequency.
In contrast to the IIR filters, FIR filter have notch behavior. The timer settings of the notch filter are made via channel 0 of the terminal. This means that the 50Hz filter on channel 0 and the 60Hz filter on channel 1 cannot be active simultaneously.
KL304x, KL305x38 Version: 4.0
Access from the user program

5.5 Control and status byte

The control and status byte is transmitted from the controller to the terminal. It can be used
• in register mode [}40] (REG = 1
• in process data exchange [}39] (REG = 0
) or
bin
).
bin

5.5.1 Process data exchange

Control byte in process data exchange (REG=0)
A gain and offset calibration of the terminal can be carried out with the control byte. The code word must be entered in R31 [}36] so that the terminal calibration can be carried out. The gain and offset of the terminal
can then be calibrated. The parameter will only be saved permanently once the code word is reset!
Bit Description Bit 7 0 Bit 6 1 Bit 5 reserved Bit 4 1 Bit 3 1 Bit 2 0
Bit 1 1 Bit 0 1
bin
: Terminal compensation function is enabled
bin
: Gain calibration
bin
: Offset calibration
bin
: slower cycle = 1000ms
bin
1
: fast cycle = 50ms
bin
: up
bin
: down
bin
Status byte in process data exchange (REG=0)
The status byte is transferred from the terminal to the controller. The status byte contains various status bits for the analog input channel:
Bit Description Bit 7 0 Bit 6 1
bin
: Error (general error bit)
bin
Bit 5 Bit 4
0
bin
0
bin
1
bin
1
bin
0 1 0 1
Limit value 2 not enabled
bin
Process data < limit value 2
bin
Process data > limit value 2
bin
Process data = limit value 2
bin
Bit 3 Bit 2
Bit 1 1 Bit 0 1
0
bin
0
bin
1
bin
1
bin
bin
bin
0
bin
1
bin
0
bin
1
bin
: Overrange : Underrange
Limit value 1 not enabled Process data < limit value 1 Process data > limit value 1 Process data = limit value 1
KL304x, KL305x 39Version: 4.0
Access from the user program

5.5.2 Register communication

Register access via process data exchange
Bit 7=1: Register mode If bit 7 of the control byte is set, the first two bytes of the user data are not used for process data exchange but written into the register set of the terminal or read from it.
Bit 6=0: read, bit 6=1: write Bit 6 of the control bytes is used to specify whether a register should be read or written.
Bit 6=0: A register is read without changing it. The value can be found in the input process
image.
Bit 6=1: The user data are written into a register. The process is complete once the status
byte in the input process image has returned an acknowledgment (see example).
Bit 0 to 5: Address The address of the register to be addressed is entered in bits 0 to 5 of the control byte.
Control byte in register mode (REG=1)
MSB
REG=1 W/R A5 A4 A3 A2 A1 A0
REG = 0 REG = 1
W/R = 0 W/R = 1
: Process data exchange
bin
: Access to register structure
bin
: Read register
bin
: Write register
bin
A5..A0 = register address Addresses A5...A0 can be used to address a total of 64 registers.
Fig.20: Register mode control byte
The control or status byte occupies the lowest address of a logical channel. The corresponding register values are located in the following 2 data bytes. (The BK2000 is an exception: here, an unused data byte is inserted after the control or status byte, and the register value is therefore placed on a word boundary).
KL304x, KL305x40 Version: 4.0
Access from the user program
Example 1: Reading of register 8 in the BK2000 with a KL3042 and the end terminal:
If the following bytes are transferred from the control to the terminal,
Byte Byte 3 Byte 2 Byte 1 Byte 0 Name DataOUT 1 DataOUT 0 Not used Control byte Value 0xXX 0xXX 0xXX 0x88
The terminal returns the following type identifier (0x0BE2 corresponds to unsigned integer 3042).
Byte Byte 3 Byte 2 Byte 1 Byte 0 Name DataIN 1 DataIN 0 Not used Status byte Value 0x0B 0xE2 0x00 0x88
Example 2: Writing of register 31 in the BK2000 with an intelligent terminal and the end terminal:
If the following bytes (code word [}36]) are transferred from the control to the terminal,
Byte Byte 3 Byte 2 Byte 1 Byte 0 Name DataOUT 1 DataOUT 0 Not used Control byte Value 0x12 0x35 0xXX 0xDF
the code word [}36] is set, and the terminal returns the register address with bit7 for register access as acknowledgment.
Byte Byte 3 Byte 2 Byte 1 Byte 0 Name DataIN 1 DataIN 0 Not used Status byte Value 0x00 0x00 0x00 0x9F

5.6 Examples of Register Communication

The numbering of the bytes in the examples corresponds to the display without word alignment.

5.6.1 Example 1: reading the firmware version from Register 9

Output Data
Byte 0: Control byte Byte 1: DataOUT1, high byte Byte 2: DataOUT1, low byte
0x89 (1000 1001
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 not set means: reading the register.
• Bits 0.5 to 0.0 specify the register number 9 with 00 1001
• The output data word (byte 1 and byte 2) has no meaning during read access. To change a register, write the required value into the output word.
) 0xXX 0xXX
bin
.
bin
Input Data (answer of the bus terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0x89 0x33 0x41
Explanation:
KL304x, KL305x 41Version: 4.0
Access from the user program
• The terminal returns the value of the control byte as a receipt in the status byte.
• The terminal returns the firmware version 0x3341 in the input data word (byte 1 and byte 2). This is to be interpreted as an ASCII code:
◦ ASCII code 0x33 represents the digit 3
◦ ASCII code 0x41 represents the letter A
The firmware version is thus 3A.

5.6.2 Example 2: Writing to an user register

Code word
In normal mode all user registers are read-only with the exception of Register 31. In order
Note
I. Write the code word (0x1235) into Register 31.
Output Data
to deactivate this write protection you must write the code word (0x1235) into Register 31. If a value other than 0x1235 is written into Register 31, write protection is reactivated. Please note that changes to a register only become effective after restarting the terminal (power­off/power-on).
Byte 0: Control byte Byte 1: DataOUT1, high byte Byte 2: DataOUT1, low byte
0xDF (1101 1111
) 0x12 0x35
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 set means: writing to the register.
• Bits 0.5 to 0.0 specify the register number 31 with 01 1111
.
bin
• The output data word (byte 1 and byte 2) contains the code word (0x1235) for deactivating write protection.
Input Data (answer of the bus terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0x9F (1001 1111
) 0xXX 0xXX
bin
Explanation:
• The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
• The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!
II. Read Register 31 (check the set code word)
Output Data
Byte 0: Control byte Byte 1: DataOUT1, high byte Byte 2: DataOUT1, low byte
0x9F (1001 1111
) 0xXX 0xXX
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 not set means: reading the register.
• Bits 0.5 to 0.0 specify the register number 31 with 01 1111
.
bin
• The output data word (byte 1 and byte 2) has no meaning during read access.
KL304x, KL305x42 Version: 4.0
Access from the user program
Input Data (answer of the bus terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0x9F (1001 1111
) 0x12 0x35
bin
Explanation:
• The terminal returns the value of the control byte as a receipt in the status byte.
• The terminal returns the current value of the code word register in the input data word (byte 1 and byte
2).
III. Write to Register 32 (change contents of the feature register)
Output data
Byte 0: Control byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0xE0 (1110 0000
) 0x00 0x02
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 set means: writing to the register.
• Bits 0.5 to 0.0 indicate register number 32 with 10 0000
.
bin
• The output data word (byte 1 and byte 2) contains the new value for the feature register.
Observe the register description!
The value of 0x0002 given here is just an example!
CAUTION
Input data (response from the Bus Terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0xA0 (1010 0000
Explanation:
• The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
• The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!
IV. Read Register 32 (check changed feature register)
Output Data
Byte 0: Control byte Byte 1: DataOUT1, high byte Byte 2: DataOUT1, low byte
0xA0 (1010 0000
The bits of the feature register change the properties of the terminal and have a different meaning, depending on the type of terminal. Refer to the description of the feature register of your terminal (chapter Register description) regarding the meaning of the individual bits before changing the values.
) 0xXX 0xXX
bin
) 0xXX 0xXX
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 not set means: reading the register.
• Bits 0.5 to 0.0 indicate register number 32 with 10 0000
.
bin
• The output data word (byte 1 and byte 2) has no meaning during read access.
KL304x, KL305x 43Version: 4.0
Access from the user program
Input Data (answer of the bus terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0xA0 (1010 0000
) 0x00 0x02
bin
Explanation:
• The terminal returns the value of the control byte as a receipt in the status byte.
• The terminal returns the current value of the feature register in the input data word (byte 1 and byte 2).
V. Write Register 31 (reset code word)
Output Data
Byte 0: Control byte Byte 1: DataOUT1, high byte Byte 2: DataOUT1, low byte
0xDF (1101 1111
) 0x00 0x00
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 set means: writing to the register.
• Bits 0.5 to 0.0 specify the register number 31 with 01 1111
.
bin
• The output data word (byte 1 and byte 2) contains 0x0000 for reactivating write protection.
Input Data (answer of the bus terminal)
Byte 0: Status byte Byte 1: DataIN1, high byte Byte 2: DataIN1, low byte
0x9F (1001 1111
) 0xXX 0xXX
bin
Explanation:
• The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
• The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!
KL304x, KL305x44 Version: 4.0
Appendix

6 Appendix

6.1 Support and Service

Beckhoff and their partners around the world offer comprehensive support and service, making available fast and competent assistance with all questions related to Beckhoff products and system solutions.
Beckhoff's branch offices and representatives
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages:
http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Beckhoff Headquarters
Beckhoff Automation GmbH & Co. KG
Huelshorstweg 20 33415 Verl Germany
Phone: +49(0)5246/963-0 Fax: +49(0)5246/963-198 e-mail: info@beckhoff.com
Beckhoff Support
Support offers you comprehensive technical assistance, helping you not only with the application of individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components
Hotline: +49(0)5246/963-157 Fax: +49(0)5246/963-9157 e-mail: support@beckhoff.com
Beckhoff Service
The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline: +49(0)5246/963-460 Fax: +49(0)5246/963-479 e-mail: service@beckhoff.com
KL304x, KL305x 45Version: 4.0

List of illustrations

List of illustrations
Fig. 1 KL3041, KL3051 .......................................................................................................................... 8
Fig. 2 KL3042, KL3052 .......................................................................................................................... 9
Fig. 3 KL3044, KL3054 .......................................................................................................................... 10
Fig. 4 KL304x, KL305x - Data flow ........................................................................................................ 12
Fig. 5 Spring contacts of the Beckhoff I/O components......................................................................... 13
Fig. 6 Attaching on mounting rail ........................................................................................................... 14
Fig. 7 Disassembling of terminal............................................................................................................ 15
Fig. 8 Power contact on left side............................................................................................................ 16
Fig. 9 Standard wiring............................................................................................................................ 18
Fig. 10 Pluggable wiring .......................................................................................................................... 18
Fig. 11 High Density Terminals................................................................................................................ 18
Fig. 12 Connecting a cable on a terminal point ....................................................................................... 19
Fig. 13 KL3041, KL3051 - Connection and LEDs .................................................................................... 21
Fig. 14 KL3042, KL3052 - Connection and LEDs .................................................................................... 22
Fig. 15 KL3044, KL3054 - Connection and LEDs .................................................................................... 23
Fig. 16 KS2000 configuration software .................................................................................................... 27
Fig. 17 Mapping in the Lightbus coupler - example for KL3042 and KL3052 .......................................... 29
Fig. 18 Mapping in the Profibus coupler - example for KL3042 and KL3052 .......................................... 29
Fig. 19 Mapping in the Interbus coupler - example for KL3042 and KL3052........................................... 30
Fig. 20 Register mode control byte .......................................................................................................... 40
KL304x, KL305x46 Version: 4.0