2.3CX2550-0179 - Technical data ..................................................................................................... 10
2.4CX2550-0279 - Technical data ..................................................................................................... 11
3 Mounting and wiring ...............................................................................................................................12
3.1Unpacking, installation and transport............................................................................................ 12
8.2Support and Service ..................................................................................................................... 30
CX2550-0179 / CX2550-02793Version: 1.0
Page 4
Table of contents
CX2550-0179 / CX2550-02794Version: 1.0
Page 5
Foreword
1Foreword
1.1Notes on the documentation
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning the components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered
trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents:
EP1590927, EP1789857, DE102004044764, DE102007017835
with corresponding applications or registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and
patents:
EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany
Please note the following safety instructions and explanations!
Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of symbols
In this documentation the following symbols are used with an accompanying safety instruction or note. The
safety instructions must be read carefully and followed without fail!
DANGER
WARNING
CAUTION
Attention
Note
Serious risk of injury!
Failure to follow the safety instructions associated with this symbol directly endangers the
life and health of persons.
Risk of injury!
Failure to follow the safety instructions associated with this symbol endangers the life and
health of persons.
Personal injuries!
Failure to follow the safety instructions associated with this symbol can lead to injuries to
persons.
Damage to the environment or devices
Failure to follow the instructions associated with this symbol can lead to damage to the environment or equipment.
Tip or pointer
This symbol indicates information that contributes to better understanding.
CX2550-0179 / CX2550-02796Version: 1.0
Page 7
1.3Documentation issue state
VersionChanges
1.0first Version
Foreword
CX2550-0179 / CX2550-02797Version: 1.0
Page 8
Product overview
2Product overview
2.1Intended use
The CX20x0 device series is a modular control system designed for DIN rail installation. The system is
scalable, so that the required modules can be assembled and installed in the control cabinet or terminal box
as required.
Only switch the PC off after closing the software
Before the Embedded PC is switched off, the software currently running on it should be stopped properly in
order to avoid data loss on the hard disk. Please read the section on “Switching off”.
Switch off all system components and uncouple the Industrial PC from the system if the PC is not used for
control purposes, e.g. during a function test. To disconnect first pull the first terminal behind the power
supply unit (optional), then pull the connectors of the fieldbus connections.
System components that have been switched off must be secured against being switched on again.
The Embedded PC’s power supply unit must be supplied with 24VDC.
Damage to the environment or devices
Do not exchange any parts when under power! The exchange of controller parts when live
Attention
can lead to short-circuits or overvoltages. These can damage the controller itself and connected peripherals (terminals, monitors, input devices, etc.).
When components are being fitted or removed, the supply voltage must be switched off.
Software knowledge
System malfunctions
Mandatory software knowledge! Every user must be familiar with any of the functions of the
Attention
software installed on the PC that he can reach.
CX2550-0179 / CX2550-02798Version: 1.0
Page 9
2.2System overview
Product overview
CX2550-0x79 system module USB extension
The CX2550-0x79 systems modules are attachments for the CX2000 Embedded PC series. They transmit
USB signals via a CAT 5e cable over distances of up to max. 50 m. The CX2550-0179 system module
transmits USB signals according to the USB 1.1 standard (full speed, max. 12 Mbit/s) while the
CX2550-0279 system module transmits USB signals according to the USB 2.0 standard (high speed, max.
480 Mbit/s). Both modules can be attached at the right-hand side of a CX20x0-CPU and are placed between
the power supply unit and the CPU. The internal connection is made via a USB port of the CX20x0-CPU; this
way, no PCI Express resources are required or used. No additional drivers are required for operation since
signal transformation and forwarding of the USB signals take place at the electrical level and are completely
transparent for the operating system.
The CX2550-0179 and CX2550-0279 modules enable the direct connection of Beckhoff Control Panels with
USB Extended interface. The CX2550-0179 system module is suitable for the connection of the Beckhoff
CP69xx and CP79xx Control Panel series with USB Extended 1.1 connection. The CX2550-0279 system
module is suitable for the connection of the Beckhoff CP29xx and CP39xx Control Panel series with USB
Extended 2.0 connection.
CX2550-0179 / CX2550-02799Version: 1.0
Page 10
Product overview
2.3CX2550-0179 - Technical data
The system module CX2550-0179 transmits USB signals according to USB 1.1 standard (full speed, max. 12
Mbit/s).
Technical dataCX2550-0179
Interfaces1 x USB Extended 1.1
Type of connectionRJ 45socket
Propertiestransmission of USB1.1 up to max. 50 m via CAT-5e cable
Diagnostics LED1 x power, 1 x speed, 1 x +15V, 1 x suspend
Power supplyvia system bus (via power supply module CX2100-0xxx)
Dimensions (W x H x D)24 mm x 99 mm x 54.5 mm
Weightapprox. 189 g
Operating/Storage temperature-25° C ... +60° C / -40° C ... +85° C
Relative humidity95% no condensation
Vibration/shock resistantconforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protection classIP 20
Further Information: www.beckhoff.de/CX2000
CX2550-0179 / CX2550-027910Version: 1.0
Page 11
2.4CX2550-0279 - Technical data
Product overview
The system module CX2550-0279 transmits USB signals according to USB 2.0 standard (full speed, max.
480 Mbit/s).
Technical dataCX2550-0279
Interfaces1 x USB Extended 2.0
Type of connectionRJ 45socket
Propertiestransmission of USB2.0 up to max. 50 m via CAT-5e cable
Diagnostics LED1 x power, 1 x host, 1 x activity, 1 x link
Power supplyvia system bus (via power supply module CX2100-0xxx)
Dimensions (W x H x D)24 mm x 99 mm x 54.5 mm
Weightapprox. 189 g
Operating/Storage temperature-25° C ... +60° C / -40° C ... +85° C
Relative humidity95% no condensation
Vibration/shock resistantconforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protection classIP 20
Further Information: www.beckhoff.de/CX2000
CX2550-0179 / CX2550-027911Version: 1.0
Page 12
Mounting and wiring
3Mounting and wiring
3.1Unpacking, installation and transport
The specified storage conditions must be adhered to (see "Technical data").
Dimensions and weight of the individual modules:
Dimensions (W x H x D): 24 mm x 100 mm x 55 mm
Weight: approx. 195 g (system interface)
Unpacking
Proceed as follows to unpack the unit:
1. Remove packaging.
2. Do not discard the original packaging. Keep it for transporting the device in the future.
3. Check the delivery for completeness by comparing it with your order.
4. Please keep the associated paperwork. It contains important information for handling the unit.
5. Check the contents for visible shipping damage.
6. If you notice any shipping damage or inconsistencies between the contents and your order, you
should notify Beckhoff Service.
Danger of damage to the device!
During transport in cold conditions, or if the device is subjected to extreme temperature dif-
Attention
Installation
The devices are designed for installation in control cabinets.
Shipping and relocation
Despite the robust design of the unit, the components are sensitive to strong vibrations and impacts. During
transport, your computer should therefore be protected from excessive mechanical stress. Therefore, please
use the original packaging.
ferences, condensation on and inside the device must be avoided. Prior to operation, the
device must be allowed to slowly adjust to room temperature. Should condensation occur,
a delay time of approximately 12 hours must be allowed before the unit is switched on.
CX2550-0179 / CX2550-027912Version: 1.0
Page 13
Mounting and wiring
3.2Dimensions
The following drawings show the dimensions of the CX2550-0x79 interface. Both variants CX2550-0179
(USB1.1) and CX2550-0279 (USB 2.0) have the same dimensions
Dimensions
CX2550-0179 / CX2550-027913Version: 1.0
Page 14
Mounting and wiring
3.3Attaching the system interface to the CX20x0 system
The USB extension is positioned directly between the CPU and the power supply unit.
When the module is connected to the CPU it engages audibly.
Further modules can be connected to the system in the same way. Please note that some modules are
connected on the left-hand side of the CPU. Once all modules are connected, the system can be placed on
the DIN rail as a block. For details please refer to the section on DIN rail mounting.
Maximum number of extension modules
Up to two extension modules can be attached on the right-hand side of the system.
Note
3.4Installation on the mounting rail
Snapping onto the mounting rail
The CX20x0 can simply be snapped onto the mounting rail. The bar clips are inserted on the top side and
underside Then simply position the block on the mounting rail and push it slightly until it engages on the
right-hand side. This is indicated by a distinct click. The bars are then engaged again. The engagement of
the individual bars is indicated by a distinct click.
CX2550-0179 / CX2550-027914Version: 1.0
Page 15
Attention
Mounting and wiring
Avoid damage!
Do not force the module or apply excessive pressure!
Installation position
Comply with the permitted installation position and minimum distances!
The maximum ambient temperature for CPU modules mounted on a DIN rail is 60°C. The
Attention
Correct installation position
The high performance and the compact design of the CX20x0 systems may result in increased heat
generation. The heat is dissipated via a passive ventilation system. This system requires the unit to be
mounted correctly. Ventilation openings are located at the top and bottom of the housing. The system
therefore has to be installed horizontally. This ensures optimum air flow.
orientation in which the device is fitted must be selected in such a way that cooling air can
flow vertically through the ventilation holes. The images below show the permitted and two
incorrect installation positions. Mounting must provide a clearance of 30 mm both above
and below a CX20x0 device combination to ensure adequate ventilation of the base CPU
module and the power supply unit.
CX2550-0179 / CX2550-027915Version: 1.0
Page 16
Mounting and wiring
Incorrect installation positions
The CX20x0 system must not be operated vertically on the DIN rail. A vertical position would lead to
insufficient CPU ventilation, since the ventilation openings are located on the top and bottom of the housing.
Installation of the system on its side would also lead to inadequate ventilation.
CX2550-0179 / CX2550-027916Version: 1.0
Page 17
Mounting and wiring
3.5Mounting the module lock
Mounting the lock
The CX20x0 controller system is fully modular, i.e. all system interfaces of the system are field-configurable.
As a rule the latching of the modules to each other is sufficiently strong. However, it is possible for the
controller and its modules to be exposed to vibrations, shocks or impacts. The modules can be securely
connected to one another with the aid of bar clips.
The bar clips are inserted on the top side and underside.
If all system interfaces are locked, then the entire assembly can be snapped onto the support rail.
Dismounting the lock
In order to dismantle the assembly it must first be removed from the support rail. Afterwards the bar clips can
be removed with the aid of a screwdriver:
CX2550-0179 / CX2550-027917Version: 1.0
Page 18
Mounting and wiring
Once the bar clips have been raised they can be pulled out. Subsequently, the system interfaces can be
separated again.
CX2550-0179 / CX2550-027918Version: 1.0
Page 19
3.6USB connection
RJ 45 interface for CX2550-0179 (USB1.1) (X179):
EtherCAT cable, category CAT5e.
Table1: Assignment of RJ 45 interface:
PINSignalDescription
115 V15 V +
2GNDGround
3TXUSB TX
4RXUSB RX
5RXUSB RX
6TXUSB TX
715 V15 V +
8GNDGround
Mounting and wiring
the LEDs of the RJ 45 sockets are redundantly implemented on the lower dagnostic LEDs [}25].
RJ 45 interface for CX2550-0279 (USB2.0) (X279):
EtherCAT cable, category CAT5e.
Table2: Assignment of RJ 45 interface:
PINSignal
1MX0+
2MX0-
3MX1+
4MX1-
5MX2+
6MX2-
7MX3+
8MX3-
the LEDs of the RJ 45 sockets are redundantly implemented on the lower dagnostic LEDs [}25].
CX2550-0179 / CX2550-027919Version: 1.0
Page 20
Commissioning / Configuration
4Commissioning / Configuration
4.1EtherCAT cable redundancy
EtherCAT cable redundancy can be realised in the CX20x0 systems through the two independent Ethernet
ports. Minimum requirements:
can be downloaded. The required licence key can be ordered from our sales division. The required couplers
are ordered together with the other hardware. These components can then be used to configure the
controller. The upper figure shows a minimum configuration example for cable redundancy. Once the
hardware has been wired and commissioned, the supplement must be installed on the device, for example
via a USB stick or the IT network. During the installation the system asks for the licence key. The cable
redundancy can be set up in the System Manager. The first step involves reading the terminal configuration.
Then select "Advanced Settings" under the "EtherCAT" tab in the EtherCAT device properties. The second
adapter can be set under the "Redundancy" menu. Use the "Search" button to open the selection menu.
Select "Local Area Connection 2 (Intel(R).....)" for the lower network connection (X001). Click "OK" to
complete the configuration.
CX2550-0179 / CX2550-027920Version: 1.0
Page 21
Commissioning / Configuration
The supplement only supports CABLE REDUNDANCY
This supplement only supports cable redundancy. This means that fail safety exists only for
Note
Cases of failure
The two possible failures are described in the example below.
the cable sections. That means the connections between the couplers. Failures of individual terminals are not covered.Further details can be found in the Beckhoff Information System under EtherCAT cable redundancy.
In this example the supply line for coupler EK1100 is faulty. The EK1100 terminals continue to run despite
the cable failure. The System Manager indicates the failure as follows:
CX2550-0179 / CX2550-027921Version: 1.0
Page 22
Commissioning / Configuration
The interruption is indicated by "LNK_MIS B" and "LNK_MIS A".
The next example shows a failure of the "return line":
In this case the second cable is faulty. The terminals at the coupler continue to run without malfunction. The
System Manager indicates the behaviour as follows:
CX2550-0179 / CX2550-027922Version: 1.0
Page 23
Commissioning / Configuration
The interruption is indicated by "LNK_MIS C" at coupler EK1100.
The EtherCAT ring is expandable. The number of devices in the ring is controlled by licenses: up to 250, up
to 1000, more than 1000. A master is only able to bridge one failure. In the event of two failures the ring
components will continue to run up to the breaking points.
4.2Switching on and off
Switching on
The power supply for the basic CPU module comes from the power supply unit. The basic CPU module
starts automatically when the power supply unit is connected to the mains.
Switching on for the first time
When you switch on the PC for the first time, the pre-installed operating system (optional) will be started.
Switching off
The Embedded PC switches off when the power supply unit is switched off. The control software typically
running on Embedded PCs should be shut down or stopped correctly. A user who may not close software
may also not switch the Embedded PC off, since data can be lost from the hard disk by switching off while
software is running.
Once the software has been stopped, the operating system can be shut down. Only then should the power
supply be interrupted.
CX2550-0179 / CX2550-027923Version: 1.0
Page 24
CX2550-0179 - Architecture description
5CX2550-0179 - Architecture description
Within the USB extension the length of USB data transmission can be increased from 5 meters up to 58
meters. This is a USB 1.1 connection. Due to the USB signal runtime, it is not possible to connect more than
one USB hub in the chain.
The following image shows the possible configuration with the maximal allowed distances:
The USB hub has to be connected after the extension. The maximal distance is 58 meters: 50 Meter cable
from CX2550-0179 to the extension box CU8850, 3 meters from the extension box to the USB hub and 5
meters from the USB hub to the USB device.
Via the USB extension a Beckhoff Touch Panel can be connected. Thus a panel of type CP69xx/79xx can be
operated up to 50 meters from the CX system without additional devices.
CX2550-0179 / CX2550-027924Version: 1.0
Page 25
Error handling and diagnostics
6Error handling and diagnostics
6.1LEDs Diagon the USB extension
LEDs diagnosis for CX2550-0179
The following table shows the states for the LEDs of the CX2550-0179 (USB 1.1):
DisplayLEDMeaning
PWRPower supply The Power LED lights if the device is
connected to a live power supply unit (green).
SPDSpeed
The LED lights green if an USB device with full speed
( 1,5 MBit/s) is connected.
The LED lights yellow if an USB device low low speed ( 12
MBit/s) is connected.
The LED doesn`t light if the no device is connected.
15 VThe LED lights (green) if 15 V is supplied to USB
extension.
SUSSuspend
The LED doesn´t light if the USB extension is operational.
The LED lights (red),if the USB extension is in suspend
mode resp. no device connected.
LEDs diagnosis for CX2550-0279
The following table shows the states for the LEDs of the CX2550-0279 (USB 2.0):
DisplayLEDMeaning
PWRPower supply The Power LED lights if the device is
connected to a live power supply unit (green).
HSTHost
The LED lights green if an USB host device is detected.
The LED doesn`t light if the no device is connected.
ACTActivity
The LED blinks (orange) if there is USB communication
via the USB-E extension.
The LED doesn`t light if there is no communication.
LNKLink
The LED doesn´t light if the USB extension is not
operational.
The LED lights (green) if the USB extension is connected
and running0.
CX2550-0179 / CX2550-027925Version: 1.0
Page 26
Error handling and diagnostics
6.2Faults
Please also refer to the Safety instructions section.
Possible faults and their correction
FaultCauseMeasures
no function after the Embedded PC
has been switched on
Embedded PC does not boot fullyHard disk damaged (e.g. due to
Computer boots, software starts,
but control does not operate
correctly
CF card access errorFaulty CFast card, faulty CFast slot Use a different CFast card to check
Embedded PC only works partially
or temporarily
no power supply for the Embedded
PC
other causes
switching off while software is
running), incorrect setup, other
causes
Cause of the fault is either in the
software or in parts of the plant
outside the Embedded PC
Defective components in the
Embedded PC
1.Check the fuse
2. Measure voltage at connection,
check plug wiring, call Beckhoff
support
Check setup Call Beckhoff Support
Call the manufacturer of the
machine or the software.
the CFast slot Call Beckhoff
Support
Call Beckhoff support
Please make a note of the following information before contacting Beckhoff service or support:
1. Precise device ID: CXxxxx-xxxx
2. Serial number
3. Hardware version
4. Any interfaces (N030, N031, B110, ...)
5. TwinCAT version used
6. Any components / software used
The quickest response will come from support / service in your country. Therefore please contact your
regional contact. For details please refer to our website at www.beckhoff.de or ask your distribution partner.
CX2550-0179 / CX2550-027926Version: 1.0
Page 27
Decommissioning
7Decommissioning
7.1Disassembly and disposal
The disassembly of a CX20x0 hardware configuration with system interfaces takes place in 3 steps
1. Switching off and disconnecting the power supply
Before a CX20x0 system can be dismantled, the system should be switched off, and the power supply
should be disconnected.
2. Removing from the DIN rail
Before the individual modules are disconnected, the whole CX20x0 hardware block should be removed from
the DIN rail. Proceed as follows:
2.1. Release and remove the first Terminal next to the power supply unit on the DIN rail.
First remove any wiring from power supply unit and then from the first terminal on the DIN rail next to the
power supply unit. If the wiring is to be reused for another system, it is advisable to make a note of the
connections. Then pull the orange terminal release (see arrow) to release the terminal and pull it out.
2.2. Releasing the CX20x0 systems
In order to release the CX20x0 block, the DIN rail fastening above and below the device must be released.
To do this, press the hooks outwards using a screwdriver. An audible click indicates that the device is
released.
CX2550-0179 / CX2550-027927Version: 1.0
Page 28
Decommissioning
After pulling on the terminal release of the power supply unit (see arrow) the block can be carefully removed
from the DIN rail.
Disposal
The device must be fully dismantled in order to dispose of it.
Electronic parts must be disposed of in accordance with national electronics scrap regulations.
3. Disconnecting the system interface
Disconnecting the system modules from the basic module
If the modules are locked, i.e. attached with tie clips, the clips must be released. To this end lift the tie clips
with a screwdriver and pull them out. Subsequently, the system interfaces can be separated again.
Do not use force to open the device!
Opening the module housing by force would destroy it. The devices may only be opened by
Attention
Beckhoff service personnel.
CX2550-0179 / CX2550-027928Version: 1.0
Page 29
Appendix
8Appendix
8.1Certifications
All products of the Embedded PC family are CE, UL and GOST-R certified. Since the product family is
continuously developed further, we are unable to provide a full listing here. The current list of certified
products can be found at www.beckhoff.com.
FCC Approvals for the United States of America
FCC: Federal Communications Commission Radio Frequency Interference Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
FCC Approval for Canada
FCC: Canadian Notice
This equipment does not exceed the Class A limits for radiated emissions as described in the Radio
Interference Regulations of the Canadian Department of Communications.
CX2550-0179 / CX2550-027929Version: 1.0
Page 30
Appendix
8.2Support and Service
Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.
Beckhoff's branch offices and representatives
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components