Beckhoff CX1010-0020, CX1010-0010, CX1010-0011, CX1010-0012, CX1010-0021 Hardware Documentation

...
Hardware documentation for CX1010 Embedded PC
CX1010-0xxx
CX1010-Nxxx
version: 1.4 date: 2008.10.26
Table of contents
Table of contents
1. Foreword
Notes on the documentation 3 Safety instructions 4 Documentation issue status 6
2. Product overview 7
Product overview 7 System overview 8 Basic modules 11
Technical data 11 Configurations 12 Connections 13 Battery compartment 15 Compact Flash slot 16 Compact Flash card 17 Memory overview 18 PC 104 Bus 20
System interfaces 22
Technical data 22 Connectors CX1010-N010 25 Connectors CX1010-N020 27 Connectors CX1010-N030/40 28 Connectors CX1010-N031/41 29 Connectors CX1010-N060 33
Power supply units 35
Overview power supply units 35 Technical data CX1100-0001 36 Technical data CX1100-0002 37 Technical data CX1100-0012 38 Technical data CX1100-0003 39 Technical data CX1100-0013 40 Technical data CX1100-0004 41 Technical data CX1100-0014 42 Connectors CX1100-0001 43 Connectors CX1100-00x2 44 Connectors CX1100-00x3 45 Connectors CX1100-00x4 46 LCD Display 47
3. Transport 48
Unpacking, installation and transport 48
Embedded-PC 1
Table of contents
4. Assembly and connecting 49
Mechanical assembly 49
Dimensions 49 Mechanical assembly of basic module 57 Mechanical assembly of fieldbus connectors 60
Inbetriebnahme 62
Start-up procedure 62
BIOS Setup 63
Standard CMOS Features 65
IDE Primary Master 67 IDE Primary Slave 69
Advanced BIOS Features 71 Advanced Chipset Features 74 Integrated Peripherals 76 Power Management Setup 78
IRQ Wakeup Events 79
PnP / PCI Configuration 81
IRQ Resources 82 DMA Resources 83 Memory Resources 84
PC Health Status 85
5. Error handling and diagnostics 86
CPU basic module 86
LED CPU basic module 86
Power supply units 87
LED CX1100-0001 87 LED CX1100-0002 88 LED CX1100-0012 90 LED CX1100-0003 92 LED CX1100-0013 95 LED CX1100-0004 98 LED CX1100-0014 99
Faults 100
6. Removal and disposal 101
Removal and disposal 101
7. Appendix 104
Accessories 104 Certifications 105 Support and service 106
2 Embedded-PC
Foreword
1. Foreword
Notes on the Documentation
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the following notes and explanations are followed when installing and commissioning these components.
Liability Conditions
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. None of the statements of this manual represents a guarantee (Garantie) in the meaning of § 443 BGB of the German Civil Code or a statement about the contractually expected fitness for a particular purpose in the meaning of § 434 par. 1 sentence 1 BGB. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
© This documentation is copyrighted. Any reproduction or third party use of this publication, whether in whole or in part, without the written permission of Beckhoff Automation GmbH, is forbidden.
Embedded-PC 3
Foreword
Safety Instructions
Safety Rules
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
State at Delivery
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH.
Personnel Qualification
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards.
Description of safety symbols
The following safety symbols are used in this operating manual. They are intended to alert the reader to the associated safety instructions
Danger
This symbol is intended to highlight risks for the life or health of personnel.
Warning
This symbol is intended to highlight risks for equipment, materials or the environment.
Note
This symbol indicates information that contributes to better understanding.
Operator's obligation to exercise diligence
The operator must ensure that
· the product is only used for its intended purpose.
· the product is only operated in sound condition and in working order.
· the instruction manual is in good condition and complete, and always available for reference at the location where the products are used.
· the product is operated only by suitably qualified and authorized personnel.
· the personnel is instructed regularly about relevant occupational safety and environmental protection aspects, and is familiar with the operating manual and in particular the safety notes contained herein.
4 Embedded-PC
Foreword
National regulations depending on the machine type
Depending on the type of machine and plant in which the product is used, national regulations governing the controllers of such machines will apply, and must be observed by the operator. These regulations cover, amongst other things, the intervals between inspections of the controller. The operator must initiate such inspections in good time.
Operator requirements
Read the operating instructions
All users of the product must have read the operating instructions for the system they work with.
System know-how
All users must be familiar with all accessible functions of the product.
Embedded-PC 5
Foreword
Documentation Issue Status
Version Changes
1.4 annotations to network ports changed
1.3 BIOS changes added
1.2 system interfaces CX1200-xxxx removed
1.1 system interfaces CX1010-N070 and CX1010-N080 renamed
1.0 version at start of series production
0.0.1 preliminarily version
6 Embedded-PC
Product overview
2. Product overview
Appropriate Use
The CX1010 device series is a modular control system designed for top-hat rail installation. The system is scalable, so that the required modules can be assembled and installed in the control cabinet or terminal box as required.
Only switch the PC off after closing the software
Before the Embedded PC is switched off, the software currently running on it should be stopped properly in order to avoid data loss on the hard disk. Please read the section on “Switching off”.
Switch off all system components and uncouple the Industrial PC from the system if the PC is not used for control purposes, e.g. during a function test. Disconnect the device by pulling the first terminal after the power supply unit (CX1100-002 and CX1100-002) (optional) and the fieldbus connectors. System components that have been switched off must be secured against being switched on again.
The power supply unit of the Embedded PC requires a 24 V DC supply.
Danger
Do not exchange any parts when under power!
When components are being fitted or removed, the supply voltage must be switched off.
Software knowledge
Warning
Mandatory software knowledge!
Every user must be familiar with any of the functions of the software installed on the PC that he can reach.
Embedded-PC 7
Product overview
System overview
The system
With the CX series of Embedded PCs Beckhoff has combined PC technology and modular I/O level to form a top-hat rail unit in the control cabinet. The CX1020 extends the CX product family by a version with higher CPU performance. The CX1020 enables direct connection of Bus Terminals and EtherCAT terminals.
While the CX1000 features an 266 MHz AMD Geode processor, the CX1010 is equipped with a 500 MHz AMD® Geode LX 800Intel(r) CPU. It is an energy-saving device that operates with ultra-low core voltage and features low thermal power dissipation of only 8 W TDP (thermal design power). As a result, no fan is required despite the compact design of the CX1010 Embedded PC. Since Compact Flash is used as boot and memory medium, no rotating media are required in the controller. This is an important aspect for increasing the MTBF (Mean Time Between Failures) of the overall system.
The case and assembly concept of the CX1010 is similar to that of its smaller brother, the CX1000: It also consists of several components that can be assembled by the user. The simplest configuration consists of a CPU module and a multi-functional power supply unit. The PC104 bus is used for the connection between these and all other CX components, although in the CX1020 this was extended with EtherCAT signals. The basic CPU module is equipped with one RJ-45 socket.
Like the CX1000, the CX1020 can be expanded with optional system interfaces. A DVI-I (=DVI-D + VGA) output, two USB-2.0 interfaces, up to four RS232 interfaces and audio are available. The four RS232 interfaces feature opto­decoupling and can optionally be implemented as RS422/RS.
The same reusability also applies to the multi-functional power supplied units (CX1100-000x) of the CX1020: one without I/O terminal connection, one with K-Bus connection, one with K-Bus and IP-Link connection for IP-67­protected Fieldbus Box modules, and a power supply unit with direct connection facility for Beckhoff EtherCAT Terminals.
EtherCAT as a fast I/O system
The CX1010 Embedded PC was developed for optimum interaction with EtherCAT. The Ethernet interface of the CPU module is not primarily intended for EtherCAT operation. The EtherCAT connection is established via the EK1110 (EtherCAT) extension terminal. The power supply CX1100-0004 establishes the possibility to connect E-Bus Terminal to the CPU Module.
8 Embedded-PC
Product overview
Interestingly, EtherCAT offers several options for connecting conventional fieldbus systems to the CX1010: either as a CX1500 module directly at the CPU or as an EtherCAT device in terminal form. The PROFIBUS master is available either as a CX1500-M310 or as a EL6731 EtherCAT terminal. Both types offer the same performance characteristics - e.g. both support PROFIBUS DP-V2. In practice, this means that the PROFIBUS master can be positioned exactly where it is required within a machine. It no longer has to be implemented as a plug-in card in the IPC or a master controller in the control cabinet.
PLC, Motion Control, interpolation and visualisation
As a top-hat rail IPC and in conjunction with the TwinCAT software from Beckhoff, the CX1010 offers the same functionality as large Industrial PCs. In terms of PLC, up to four virtual IEC 61131 CPUs can be programmed with up to four tasks each, with a minimum cycle time of 50 µs. All IEC 61131-3 languages can be used.
Moreover, all TwinCAT functionalities are available for Motion Control applications: In theory, up to 256 axes can be controlled. In addition to simple point-to-point movements, more complex multi-axis functions such as "electronic gearbox", "cam plates" and "flying saw" can be implemented. In contrast to the CX1000, due to its higher CPU performance the CX1010 can now also execute interpolating 3D path movements and DIN66025 programs.
In addition to real-time execution of control tasks, the TwinCAT real-time kernel ensures that enough time remains for the user interface (HMI), to communicate with the real-time components via software interfaces such as ADS or OPC.
For the CX1010 the same basic principle applies: it is a programming tool for all controllers. The complete programming of PLC, Motion Control and visualization is transferable to all PC controls from Beckhoff, which is reassuring in cases where it becomes apparent during a project that more processing power is required after all. In this case a system with higher performance can be used.
Basic CPU module
Further system interfaces or fieldbus connections can be added to the basic CPU module. The CPU module requires a CX1100 type power supply module.
All CX1500 fieldbus modules and all CX1100 power supply units from the CX1000 series can be used in combination with the CX1010.
The CX1100-0004 power supply unit offers a direct interface between the CX1010 and the EtherCAT Terminals. The combination of CX1010, EtherCAT and TwinCAT enables cycle and response times of less than 1 millisecond.
The CPU module is available in several variants. These relate to:
- System interface configuration: as an option, a DVI and two USB Interfaces can be added to the combination of the Ethernet RJ 45 port that is always present.
- Operating system: There is a choice between "Microsoft Windows CE.NET" or "Microsoft Windows XP Embedded".
- Pre-installed TwinCAT software: CX1010 can be pre-installed without a TwinCAT system, with TwinCAT CE PLC, TwinCAT CE NC PTP or TwinCAT CE NCI, or with the associated full version of the individual TwinCAT levels for PLC and Motion Control.
System interfaces
Further system interfaces for serial communication (2x RS 232 or RS422, RS485), 2 x USB 2.0 interfaces, video output (DVI +) , CF card reader/writer or audio signals can be ordered separately.
Fieldbus interfaces
All CX1500 fieldbus modules and all CX1100 power supply units from the CX1000 series can be used in combination with the CX1010.
The fieldbus interfaces are currently available as master and slave versions for the following fieldbuses:
Beckhoff Lightbus, Profibus DP, CANopen, DeviceNet or SERCOS interface (only master)
The master fieldbus connections enable a CX1020 system to use Beckhoff fieldbus components (such as Bus Coupler, Bus Terminal Controller or Drive Technology) as local control components for complex systems.
Slave fieldbus connections enable the CX1020 system to be used as a subordinate distributed control system for complex or modular systems.
Note:
Documentation describing the fieldbus connections is available separately.
Embedded-PC 9
Product overview
The software
In combination with the TwinCAT automation software, the CX1010 Industrial PC becomes a powerful IEC 61131-3 PLC with up to four user tasks. Additionally, Motion Control tasks can also be executed. Depending on the required cycle time, several servo axes can be controlled. Even special functions such as flying saw, electronic gearbox and cam plate can be realized.
The CX1010 system is programmed in the same way as other bus controllers:
Remote programming via Ethernet
This option is used if the basic unit is equipped with “Windows CE.NET”. In this case, the system is programmed via a laptop or a desktop PC, which is connected to the CX1020 via Ethernet (network or crossover cable). The programs are developed on the laptop with a standard TwinCAT software licence and then loaded into the target device.
Visualization
The Beckhoff OPC server is available for interfacing with SCADA packets, if the two operating system variants “Windows CE.NET” or “Windows XP Embedded” are used. In other words, the CX1010 also offers straightforward visualization and simultaneous control in real-time on a single system.
10 Embedded-PC
Product overview
Basic modules
Dimensions:
The basic configuration of the CX1010 includes a 64 MB Compact Flash card. One Ethernet RJ 45 interface is also part of the basic configuration. All other CX family components can be connected via the PC104 interface that is available on both sides. The passive cooling module is included in the scope of supply. For power supply one of the system power supply modules (CX1100-000x) is needed)
Technical data CX1010-xxxx
Processor Processor AMD Geode® LX 800, 500 MHz clock frequency
Internal Flash Memory 64 MByte Compact Flash card
Internal Memory 256 MByte DDR-RAM
Interfaces 1 x RJ45 (Ethernet)
Diagnose LED 1 x Power, 1 x LAN Link/Activty, 1 x TC, 1 x Flash-Access
Expansion slot 1 x Compact Flash type I+ II insert with eject mechanism
Clock internal battery-backed clock for time and date
Operating system Microsoft Windows CE.NET or Microsoft Windows XP Embedded
Control software TwinCAT PLC Runtime , TwinCAT NC PTP Runtime or TwinCAT NCI
Runtime
System bus 16 Bit ISA (PC104 Standard)
Power supply via system bus (through power supply module CX1100-000x)
Dimensions (W x H x D) 58 mm x 120 mm x 91 mm
Max. power loss 8 W (including CX1010-N0xx system interfaces)
Wight app. 355 g
Operating/storage temperature
Relative humidity 95% no condensation
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27/29
EMC resistance burst / ESD conforms to EN 61000-6-2/EN 61000-6-4
protection class IP 20
0° C ... +50° C / -25° C ... +85° C
Embedded-PC 11
Product overview
Configurations
The Basic CPU-Module can be ordered with different hardware and software variations. As operating systems there are "Windows CE.NET" and "Windows XP Embedded" available. The TwinCAT automation software transforms a CX1020 system into powerful PLC and Motion Control system that can be operated with or without visualisation.
The order identifier of the basic CPU module is derived as follows:
Following CX1020 configurations are available:
Modul
CX1010­0000
CX1010­0010
CX1010­0011
CX1010­0012
CX1010­0100
CX1010­0110
CX1010­0111
CX1010­0112
CX1010­0020
DVI / USB
no operating system
Windows CE
Windows XPE
without TwinCAT
TwinCAT PLC Runtime
TwinCAT NC PTP Runtime
- X - - X - -
- - X - X - -
- - X - - X -
- - X - - - X
X X - - X - -
X - X - X - -
X - X - - X -
X - X - - - X
- - - X X - -
CX1010­0021
CX1010­0022
CX1010­0120
CX1010­0121
CX1010­0122
X1010 Systems with Windows XP Embedded require a Compact Flash card with a capacity of al least 1 GB.
Note:
For detailed information about the software images see the CX10x0 Software Documentation.
- - - X - X -
- - - X - - X
X - - X X - -
X - - X - X -
X - - X - - X
12 Embedded-PC
Product overview
Connections
The basic CPU module is available with different hardware and software options. It is supplied from the power supply unit, so that only the connections are described here.
Basic CPU module with 2 Ethernet RJ 45 interfaces:
RJ 45 interface (socket):
Assignment of the RJ45 interface: PIN Signal Description
1 TD + Transmit +
2 TD - Transmit -
3 RD + Receive +
4
5
6 RD - Receive -
7
8
TD & RD are exchanged at the hubs or between two PCs.
Schematic structure of the network components:
Connected not used
Connected not used
The CX1010 features two MAC blocks. The first one (MAC1) operates the left network interfaces for the standard IP network. This port is also used for PLC programming.
The second block (MAC2) operates the extended PC104 bus. The second physical network connection can be utilized via additional system interfaces. This requires either a CX1100-0004 power supply unit or a CX1020-N060 system interface. A connection to the E-bus for EtherCAT terminals is realized via the power supply unit. The CX1010-N060 interface establishes the Ethernet connection, thereby making a further network interface available.
Embedded-PC 13
Product overview
Operating system perspective:
The operating system only sees the connections for the network interface. The internal connection via the PC104 bus extension is shown as the second interface. If no expansion module is connected, the line is reported as not connected. When the CX1100-0004 power supply unit is connected Windows XPe reports "restricted or no connection" This behavior is normal, since Windows itself does not use this interface, and therefore no IP address is allocated. If the CX1020-N060 extension is connected, the connection behaves like a 'normal' network port.
Note
The network ports are only for communication with standard network. Do not connect to
telecommunication circuits.
Basic CPU module with DVI/USB interface:
In addition to the Ethernet port, this basic module also features DVI/USB interfaces. The pin assignment of the basic CPU module with two USB and a DVI-I interface is explained under the associated CX1010-N 010 system interface.
Applicable to all basic CPU modules:
LED
The green power LED (PWR) is on if the basic CPU module is connected correctly to a live power supply unit.
Compact Flash slot
Further information can be found under Compact Flash slot.
PC 104 Bus
The PC 104 bus is a standardized bus with 104 ISA signals for compact embedded systems.
14 Embedded-PC
Product overview
Battery compartment
The battery compartment is located on the left-hand side of the CPU module, between the two Ethernet ports.
It can be opened with the aid of a screwdriver (proceed carefully in order to avoid damage).
The battery is a CR2032 type from Panasonic
with the following specification:
Battery type Electrical properties (at 20° C)
CR2032 3.0 V 225 mAh 0.20 mA 20.0 mm 3.20 mm 3.1 g
Danger
nominal
voltage
nominal
capacity
Standard
charge
continuous
load
Diameter Height Weight
Dimensions
Replace Battery Part. No. CR2032 manufactured by Sanyo or Panasonic Only. Use of Another Battery May Present A Risk Of Fire Or Explosion. WARNING, Battery may explode if mistreated. Do Not Recharge, Disassemble or Dispose of in fire.
Note
The battery must be changed every 5 years.
Spare batteries can be ordered from Beckhoff Service.
Embedded-PC 15
Product overview
Compact Flash slot
A Compact Flash slot is provided at the front of module. This enables an additional Compact Flash memory medium (format I or II) to be operated. The change - in case of the Basic CPU module CF slot - is only allowed while the system is powered down - otherwise the system could crash. In case of using the CF-slot extension (CXxxxx-A001) the CF card can be removed after signing out the media from the system. The card can be removed for maintenance or to extend the system storage capacity. The Compact Flash cards (CF cards) are available as accessories with different storage capacities.
As example the following pictures show the handling of the CF cards with a CX1000 system. Activating the eject mechanism below the slot with a screwdriver causes the card to be ejected by approx. 4 mm (FIGURE 1), so that it can be pulled out (FIGURE 2). If the card is pushed in (FIGURE 3), the eject mechanism will re-engage. The card is positioned correctly, if it is located approx. 1 mm lower than the front of the housing.
FIG1: Ejecting the CF card
FIG2: Removing the CF card
FIG3: Inserting the CF card
Warning
The Compact Flash slot is a memory interface, not an I/O type CF slot.
16 Embedded-PC
Product overview
Compact-Flash card
The Compact Flash card (CF card) is a non-volatile memory medium.
Data to be retained in the event of a power failure should be saved on the CF card. The CF card operates similar to a hard disk.
Warning
It is recommended only use CF cards supplied by Beckhoff Automation GmbH.
The CF cards are made for industrial use. They possess a higher number of read / write cycles and an enhance temperature range (up to + 85°C).
A proper operation of the CX-System can only be guaranteed with the use of CF cards from
Beckhoff Automation GmbH!
Embedded-PC 17
Product overview
Adapter RAM Hardware address overview
available memory addresses CX1020: D0000-DFFFF (hex)
Base Address (hex)
D0000 D0FFF 1000 R/W CX1100-0002/3 Dual Ported RAM
D1000 D100F 10 R/W CX1100 Auxiliary Control Block( LCD
D1010 D101F 10 R/W CX1100-0900 UPS Control Block
D2000 D3FFF 2000 R/W CX1100 Non Volatile RAM
D4000 D5FFF 2000 R/W CX1500-M310 Profibus Master
D6000 D7FFF 2000 R/W CX1500-M510 CANopen Master
D8000 D9FFF 2000 R/W CX1500-M520 DeviceNet Master
DA000 DBFFF 2000 R/W CX1500-M200 Lightbus Master
DC000 DDFFF 2000 R/W CX1500-M750 Sercos Master
For some fieldbus connections (all Slave modules) the base addresses are mapped in the memory region upper DFFFF(hex). So this modules must be ordered with other base addresses. The same situation takes place if more than two or more master modules of same type are used (for more see note below). The order numbers for the modules are:
End Address (hex) Size(Bytes)(hex)
Access Type Description
Display, misc. registers)
DPRAM
DPRAM
DPRAM
DPRAM
DPRAM
order number alternative ISA-address
Master connection
CX1500-Mxxx-0001 D4000
CX1500-Mxxx-0002 D6000
CX1500-Mxxx-0003 D8000
CX1500-Mxxx-0004 DA000
CX1500-Mxxx-0005 DC000
Slave connection
CX1500-Bxxx-0001 D4000
CX1500-Bxxx-0002 D6000
CX1500-Bxxx-0003 D8000
CX1500-Bxxx-0004 DA000
CX1500-Bxxx-0005 DC000
Replace xxx with the following number for the requested fieldbus system:
200 for Lightbus
310 for Profibus
510 for CAN-open
520 for DeviceNet
750 for Sercos (only Master connection available)
18 Embedded-PC
Product overview
Note
Two connection modules (master or slave) can be used simultaneously. If more than two connections are needed call Beckhoff Automation GmbH for further information.
Embedded-PC 19
Product overview
PC/104 Bus
The PC 104 bus is a standardized bus with 104 ISA signals for compact embedded systems.
For the functionality of the CX1020 modules eight further signals have been added ( here marked with color). Pin assignment of 16 Bit PC 104 Bus:
Pin Number
1 IOCHCHK* GND GND GND
2 SD7 RESETDRV SBHE* MEMCS16*
3 SD6 +5V LA23 IOCS16*
4 SD5 IRQ9 LA22 IRQ10
5 SD4 -5V LA21 IRQ11
Row A
Row B Row C4 Row D4
6 SD3 DRQ2 LA20 IRQ12
7 SD2 -12V LA19 IRQ13
8 SD1 ENDXFR* LA18 IRQ14
9 SD0 +12V LA17 DACK0*
10 IOCHRDY (KEY)² MEMR* DRQ0
11 AEN SMEMW* MEMW* DACK5*
12 SA19 SMEMR* SD8 DRQ5
13 SA18 IOW* SD9 DACK6*
14 SA17 IOR* SD10 DRQ6
15 SA16 DACK3* SD11 DACK7*
16 SA15 DRQ3 SD12 DRQ7
17 SA14 DACK1* SD13 +5V
18 SA13 DRQ1 SD14 MASTER*
19 SA12 REFRESH* SD15 GND
20 SA11 SYSCLK (KEY)² GND
21 SA10 IRQ7 -- --
22 SA9 IRQ6 -- --
23 SA8 IRQ5 -- --
24 SA7 IRQ4 -- --
25 SA6 IRQ3 -- --
26 SA5 DACK2* -- --
27 SA4 TC -- --
28 SA3 BALE -- --
29 SA2 +5V -- --
30 SA1 OSC -- --
31 SA0 GND -- --
32 GND GND -- --
Remarks:
20 Embedded-PC
Product overview
1. B10 and C19 are key locations.
2. Signal timing and function are as specified in ISA specification.
3. Signal source/sink current differ from ISA values.
4. in the specification the pins are counted from 0 to 19
Assignment on the 8 additional pins
Pin number (yellow fields)
Row C
Row D
1 LAN TX- LAN TX+
2 LAN RX- LAN RX+
3 USB D- USB D+
4 SMBDAT SMBCLK
Note:
Further information to PC104 Bus can be found in the datasheet or under http://www.pc104.org.
Embedded-PC 21
Product overview
System interfaces
Technical Data
Dimensions:
22 Embedded-PC
Product overview
Like for the CX1000, a number of optional interface modules are available for the basic CX1010 CPU module that can be installed ex works. The following interfaces are available:
CX1010-N010 DVI / USB Module
CX1010-N020 Audio interfaces
CX1010-N030/40 serial interface for RS323
CX1010-N031/41 serial interface for RS422 / RS485
CX1010-N060 Ethernet-interface
The CX1010-N010 option can be connected to Beckhoff Control Panels or standard monitors with DVI or VGA input via the DVI or USB interfaces.Devices such as printer, scanner, mouse, keyboard, mass storage, CR-RW etc. can be connected via the USB 2.0 interfaces. Multimedia capability is realized via the CX1010-N020 audio interface. The modules CX1010-N030 and CX1010-N040 offer a total of four serial RS232 interfaces with a maximum transfer speed of 115 kbaud. These four interfaces can be implemented in pairs as RS422/RS485, in which casethey are identified as CX1010-N031 and CX1010-N041 respectively.The system interfaces cannot be retrofitted or expanded in the field. They are supplied ex factory in the specified configuration and cannot be separated from the CPU module. The system interfaces run through the internal PC104 bus, so that further CX components can be connected. The power supply of the system interface modules is ensured via the internal PC104 bus.
Embedded-PC 23
Product overview
CX1010-N030
Technical data CX1010-N010 CX1010-N020
Interfaces 1 x DVI +
2 x USB 2.0 max. 100 mA
Line IN, MIC IN, Line OUT
CX1010-N040
1 x COM1+2, RS232 1 x COM3+4, RS232
per port
Connection type DVI-I 29-pin
socket +
3,5 mm socket for jack plug
2 x D-Sub plug 9-pin 2 x D-Sub plug 9-pin
2 USB Ports type A
Properties DVI-I interface
also carries out VGA signals (DVI­A)
built-in PC-Beeper Line OUT output, max. 200 mW, suitable for earphones
max. baud rate 115 kbaud, can not be used simultaneously with N031/N041
Power supply via system bus (Through CX1100-000x power supply module)
Dimensions 19 mm x 100 mm x 51 mm
Operating
0 °C ... +55 °C
temperature
Storage
-25 °C ... +85 °C
temperature
Relative humidity 95% no condensations
CX1010-N031 CX1010-N041
1 x COM1+2, RS422/RS485 1 x COM3+4,RS422/RS485
max. baud rate 115 kbaud, can not be used simultaneously with N030/N040
Vibration/Shock
conforms to EN 60068-2-6 / EN 60068-2-27/29
resistance
EMC resistance
conforms to EN 61000-6-2/EN 61000-6-4
burst / ESD
Protection class IP 20
weight app. 80 g
Technical data CX1010-N060
Interfaces 1 x Ethernet 10/100 Mbit
Connection type 1 x RJ45
Properties network connection for enhanced PC104 Bus
Power supply via system bus (through CX1100-000x power supply module)
Dimensions 19 mm x 100 mm x 51 mm
Operating
0 °C ... +55 °C
temperature
Storage
-25 °C ... +85 °C
temperature
Relative
95% no condensations
humidity
Vibration/Shock
conforms to EN 60068-2-6 / EN 60068-2-27/29
resistance
EMC resistance
conforms to EN 61000-6-2/EN 61000-6-4
burst / ESD
Protection class IP 20
weight app. 80 g
24 Embedded-PC
Product overview
CX1010-N010 connections
This module features a DVI-I and two USB interfaces.
DVI-I interface
The DVI-I interface transfers analog and digital data and is suitable for connection to analog graphics cards with 15 pin D-Sub connector and digital graphics cards with DVI-D output. The resolution at the screen or the Beckhoff Control Panel depends on the distance (maximum 5 m).
The DVI interface uses VGA signals, so that the connection of CRT VGA monitors to the CX1000 system using a DVI to VGA adapter is also possible. This adapter is available as an accessory.
DVI-I socket:
Pin Assignment Pin Assignment Pin Assignment
1 TMDS Data 2- 9 TMDS Data 1- 17 TMDS Data 0-
2 TMDS Data 2+ 10 TMDS Data 1+ 18 TMDS Data 0+
3 TMDS Data 2/4 Shield 11 TMDS Data 1/3 Shield 19 TMDS Data 0/5 Shield
4 not connected 12 not connected 20 not connected
5 not connected 13 not connected 21 not connected
6 DDC Clock 14 + 5V Power 22 TMDS Clock Shield
7 DDC Data 15 Ground ( +5V, Analog H/V Sync) 23 TMDS Clock +
8 Analog Vertical Sync 16 Hot Plug Detect 24 TMDA Clock -
Embedded-PC 25
Product overview
Assignment cross
Pin Assignment
C1 Analog Red Video Out
C2 Analog Green Video Out
C3 Analog Blue Video Out
C4 Analog Horizontal Sync
Resolution at the monitor:
Resolution in Pixel Distance of the interface from the monitor
1600 x 1200 5 m
1280 x 1024 5 m
1024 x 768 5 m
800 x 600 5 m
640 x 480 5 m
USB interface:
The USB socket is a type A socket. The USB interface complies to USB 2.0 specification
Pin Assignment Typical Assignment
1 VBUS Red
2 D- White
3 D+ Green
4 GND Black
Shell Shield Drain Wire
26 Embedded-PC
Product overview
CX1020-N020 connections
This system interface provides the audio interface for the CX1020 system. Two inputs, "LINE IN" and "MIC IN", are available. The "LINE OUT" connection is used as output for audio signals. It can also be used for connecting headphones with a maximum output of 200 mW. It also features a PC beeper. The audio interfaces are accessed via the operating system. "Windows XPe" offers an option for switching the audio module to surround mode.
The 3.5 mm sockets are designed for jack plugs.
Standard / stereo mode:
The audio module operates in stereo mode as standard, using stereo outputs/inputs and a single-channel input for the microphone. The inputs should be connected as indicated. The pin assignments are described below.
Line In / Line Out stereo jack plugs:
Pin assignment Line In /Line Out: Signal Assignment
L left channel
R right channel
Ground ground
The left channel is transferred via the tip of the jack plug, the right channel via the first ring. The remainder of the sleeve is used for signal ground.
Mic In mono jack plug:
The only existing channel is transferred via the tip, the remainder of the sleeve is used for signal ground.
Embedded-PC 27
Product overview
CX1010-N030/40 connections
The CX1010-N030 system interface features two RS232 interfaces, COM1 and COM2 (9 pin Sub-D plug connector). If there is need for more than two serial interfaces two further RS232 interfaces, COM3 and COM4 (9 pin Sub-D plug connector) can be added to the system via the system interface CX1010-N40. The maximum baud rate on all channels is 115 kBit. The pin assignment for all interfaces is equal and described below. The interface parameter can be set in the operating system or in the PLC program.
RS232 COM interface (connector):
Pin assignment COM interface: PIN Signal Type Description
1 DCD Signal in Data Carrier Detected
2 RxD Signal in Receive Data
3 TxD Signal out Transmit Data
4 DTR Signal out Data Terminal Ready
5 GND Ground Ground
6 DSR Signal in Dataset Ready
7 RTS Signal out Request to Send
8 CTS Signal in Clear to Send
9 RI Signal in Ring Indicator
Note
The system interface CX1010-N30 can only be used instead and not simultaneously with
system interface CX1010-N031.
The system interface CX1010-N40 can only be used instead and not simultaneously with
system interface CX1010-N041.
28 Embedded-PC