Beckett CG4 User Manual

Operation On/Off Rate: 80 to 250 MBH
Fire or Explosion Hazard
Can cause severe injury, death or property damage
If the information in these instructions is not followed exactly, a re or explosion may
result causing personal injury, death or property damage.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this
or any other appliance.
instructions.
y If you cannot reach your gas supplier, call the re department. y Installation and service must be performed by a qualied installer, service agency or the
gas supplier.
Contents
General Information ....................................................3
To the Owner: ................................................................................ 3
Owner’s Responsibility: ................................................................. 3
Professional Installer’s Responsibility: .......................................... 4
Specications ................................................................................ 4
Inspect/Prepare Installation Site ............................... 6
Indoor Installation .......................................................................... 6
Inspect Chimney and Vent System ...............................................6
Combustion Air Supply .................................................................. 8
Buildings with Adequate Air Inltration .......................................... 8
Buildings with Less Than Adequate Air Inltration ........................ 8
Clearances to Burner and Appliance .............................................8
Fuel Gas Supply ............................................................................ 9
Electrical Supply ............................................................................ 9
Verify Burner Components ............................................................9
Verify Burner Selection ..................................................................9
Prepare the Appliance ................................................11
Assemble the Burner ................................................ 12
Gather the Necessary Parts ........................................................12
Prepare the Chassis ....................................................................12
Prepare and Install the Air Tube ..................................................12
Assemble the Gas Valve and Manifold .......................................12
Install the Valve and Manifold to the Burner ................................13
Propane Applications ..................................................................13
Mount the Burner ...................................................... 16
Connect Gas Piping .................................................. 16
Wire the Burner .......................................................... 17
Sequence of Operation ............................................. 18
Prepare the Burner for Start-up ............................... 19
Start-up Checklist ........................................................................19
Start the Burner ........................................................ 19
Burner Start Procedure ..............................................................19
Verify the Firing Rate ...................................................................20
Check Operation and Safety Controls .........................................21
Use Test Instruments to Set Combustion ....................................22
Recommended Combustion Adjustment Procedure ...................22
Maintenance and Service.......................................... 23
Annual Maintenance ..................................................................23
Replace the Blower Wheel ..........................................................25
Replacement Parts .................................................... 26
Limited Warranty Information .................................. 28
Before Calling Beckett . . .
Before contacting us about your burner, you must have a completely lled out copy of the Contractor Start-Up Form (Located inside of last page). This information is crucial for troubleshooting and obtaining the correct replacement part.
2
Section: GENERAL INFORMATION
General Information
To the Owner:
This equipment must be installed, adjusted and started
by a qualied service agency that is licensed and
experienced with all applicable codes and ordinances and responsible for the installation and commissioning of the equipment.
Thank you for purchasing a Beckett CG4 burner for use with your heating appliance. Please pay attention to the Safety Warnings contained within this instruction manual. Keep this manual for your records and provide it
to your qualied service agency for use in professionally
setting up and maintaining your burner.
Your CG4 burner will provide years of efcient operation if it is professionally installed and maintained by a qualied
service technician. If at any time the burner does not appear to be operating properly, immediately contact
your qualied service agency for consultation.
We recommend annual inspection/service of your gas heating system by a qualied service agency.
Burn Hazard, Hot Surface
Burner ange and air tube are hot
when burner is in operation. Do not service this area during or immediately
after operation. Allow area to cool.
Owner’s Responsibility:
Explosion, Fire, Asphyxiation Hazard
Failure to follow these instructions, misuse, or incorrect adjustment of the burner could lead to equipment malfunction and result in
asphyxiation, explosion or re.
Contact a professional, qualied service agency for
the installation, adjustment and service of your gas burning system. Thereafter, have your equipment adjusted and inspected at least annually to ensure reliable operation. This work requires technical
training, trade experience, licensing or certication
in some states and the proper use of special combustion test instruments.
Please carefully read and comply with the following instructions:
y See the front cover for ‘What to do if you smell gas’.
y Never store or use gasoline or other ammable
liquids or vapors near this burner or appliance.
y Never attempt to burn garbage or refuse in this
appliance.
y Never attempt to light the burner/appliance by
throwing burning material into the appliance.
y Never attempt to burn any fuel not specied and
approved for use in this burner.
y Never restrict the air inlet openings to the burner or
the combustion air ventilation openings in the room.
CG4 Burner Manual
Frozen Plumbing and Water Damage Hazard
If the residence is unattended in severely cold weather, burner primary control safety lockout, heating system component failures, power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours. For protection, take preventive actions such as having a security system installed that operates during power outages, senses low temperature and initiates an effective action. Consult with your heating contractor or a home security agency.
Contact a professional, qualied
service agency to replace any
component that has been exposed to water.
3
Section: GENERAL INFORMATION
Professional Installer’s Responsibility:
Professional Service Required
Failure to follow these instructions could lead to equipment malfunction and result in asphyxiation, explosion
or re.
y Please read all instructions before proceeding.
Follow all instructions completely.
y This equipment must be installed, adjusted
and started by a qualied service agency that
is licensed and experienced with all applicable codes and ordinances and responsible for the installation and commissioning of the equipment.
y The installation must comply with all local codes
and ordinances having jurisdiction and the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54) and CAN1-B149.1 in Canada.
Fire Hazard: Overheating
Should over-heating occur:
y Shut off the manual gas control to
the appliance.
y DO NOT shut off power to the
equipment, allow the blower and pumps to continue running.
Specications
Table 1 – Burner Specications
Input Firing Rate 80,000 - 250,000 BTU/hr
Firing Mode On-Off Only
Fuel
Required Input Gas Supply Pressure
Input Voltage 120 Vac + 10% / -15%; 60 Hz
Input Current 2.75 A (Run); 12.0 ALR
Gas Valve
Burner Control Beckett 7590D Direct Ignition
Flame Detection Flame Rectication
Igniter Beckett 7474001 Gas Igniter
Motor 1/7 Hp; PSC
Combustion Air Proving Differential Pressure Switch
Weight 55 lbs.
Mounting Orientation
Dimensions 10.3” x 13.1” x 15.8”
Acceptable Ambient Temperature Range
Acceptable Ambient Humidity 5% - 95% RH non-condensing
For altitudes higher than 2,000 feet, derate the burner capacity 4%
for each 1,000 feet above sea level.
Burner is not approved for use in 50 Hz applications.
Natural gas - 0.64 specic gravity LP gas - 1.53 specic gravity
4.5” WC minimum 14” WC maximum
24 Vac Dual Seat with integral regulator set to 3.5” WC for both natural gas and LP
Up to 90° from upright with motor shaft horizontal
-40°F to 150°F
Special Requirements:
When contacting Beckett for service information — Please have the burner serial number and contractor start-up form available when
calling or writing. You will nd the serial number on
the label located on the left rear of the burner. Refer to Figure 2.
Concealed damage – If you
discover damage to the burner or controls during unpacking, notify the carrier at
once and le the appropriate claim forms. Do not
install a burner or control that has been damaged.
If any of these instructions are not clear,
Call Beckett at 1-800-645-2876 for assistance.
For use only on approved
applications. See www. beckettcorp.com/cg4apps for the list of approved applications.
ETL listed for use in the US or Canada per ANSI Z21.17(a) / CSA
2.7(a) For use with natural gas or propane.
4
1.13
Figure 1 – Burner Dimensions
8.3”
Section: GENERAL INFORMATION
15.8”
9.5”
8.0”
7.6”
13.1”
Figure 2 – Burner Nameplate
Your burner will have labels that are specic to its construction. This is for reference only.
General Model Information
Serial Number
R.W. Beckett Specication
Number and Revision
Approvals / Certications
Model “CG4”
Gas ConversionBurner
Brûleur de conversion
SERIAL NUMBER
140121-08157
CG4001 Rev.A 00
#########
Conforms to ANSI Std
Z21.17
Certified to CSA Std
En conformité avec la norme
Homologation en vertu de la
2.7
ANSI Z21.17
norme CSA 2.7
14.4”
10.3”
6.0”
80 TO 250 MBH, 24 to 73 kW
120V/60Hz, 3A run, 12A LR
For use with natural gas or propane. A conversion kit supplied by the manufacturer shall be used to convert to the alternate fuel. Manifold pressure: 3.5” W.C. Max press. to valve: 1/2 PSI Min press. to valve: 4.5” W.C.
A utiliser avec du gas naturel ou du propane. Se servir de la trousse de conversion fournie par le fabricant pour paser d’un type decarburant à l’autre. Pression d’admission: 870 Pa Pression max.’ à la soupape: 3450 Pa Pression min. à la soupape: 1120 Pa
Elyria, Ohio
Made in the U.S.A.
Rating Information
Fuel, Construction,
and Setting Data
CG4 Burner Manual
5
Section: INSPECT/PREPARE INSTALLATION SITE
Inspect/Prepare
Installation Site
Indoor Installation
Explosion, Fire, Asphyxiation Hazard
Wet or dusty environments could lead to blocked air passages, corrosion damage to components, impaired combustion performance and result in
asphyxiation, explosion or re.
y This burner is designed for clean, dry
installations.
y Electrical controls are not protected against rain
or sprayed liquids.
y Keep the installation clear of dust, dirt, corrosive
vapors, and moisture.
y Protective covers and frequent maintenance may
be required.
Fire, Smoke & Asphyxiation Hazard
y Carefully inspect the chimney,
chimney liner & exhaust vent system.
y Make sure it is properly sized and in
good working condition.
y Follow the instructions supplied by
the appliance manufacturer.
y If a draft regulator is required, it must be a
double-acting type, agency recognized for use with gas vent systems.
y The chimney installation and vent sizing
must strictly comply with all applicable codes, authorities having jurisdiction and the latest revision of the National Fuel Gas Code (ANSI Z223.1, or NFPA54) or CAN/CGA B/49 Canada. Remove any vent damper device.
y Regulation by these authorities take precedence
over the general instructions provided in this installation manual.
Examine the installation site for conditions that could adversely affect the health and safety of installation personnel and the user of the appliance or proper operation of the burner and appliance, and correct any defects found.
The area around the appliance should be
unobstructed and dry.
Wiring must be in good condition and meet code
requirements.
If the burner is replacing an existing oil burner, old
piping and the tank must be secured or removed to prevent leakage or unintended deliveries of oil.
Local jurisdictions may require removal of oil tanks.
See NFPA-30 ammable and combustible liquids
code for approved procedures.
Inspect Chimney and Vent System
1. Any accumulation of soot or debris in chimney
offsets must be removed
2. Any obstructions such as a protruding joint or a
piece of broken tile wedged in the chimney must be removed.
3. No other appliance connection should be made to
the same ue pipe.
4. The ue pipe should have an upward pitch toward
the chimney of at least 1/4” per foot of length. It
should t tightly and should not project into the
chimney, see Figure 3.
Figure 3 – Vent Pipe with Draft Regulator
Barometric Draft Control
Flue Pipe Ell
Heating Unit
1/4” per Foot
Minimum
6
Section: INSPECT/PREPARE INSTALLATION SITE
5. Any leakage between tiles, around clean-out doors, or around the vent pipe should be sealed.
6. A Draft regulator is required, it shall be a double- acting type, agency recognized for use with gas vent systems.
7. The design and sizing of the appliance’s vent system shall comply with the requirements of NFPA 54 Chapters 12 and 13.
8. A chimney ue shall extend at least 3 feet above the highest point at which the chimney comes in contact with the roof, and not less than 2 feet above the highest roof surface or structure within 10 feet horizontally of the chimney. Refer to Figure 4.
Some local codes and gas
utilities require the installation of a thermal Safety switch on the double-acting draft control, or draft hood. This is a very good practice and provides the following protection:
The thermal safety switch senses ue gas spillage caused by blocked ue exhaust, prolonged down-draft, or insufcient draft. The safety is wired in series with the
burner control circuit and shuts the burner off, when the
spillage of hot ue gases is detected.
Insulated stainless steel chimney liners
The new designs of furnaces and boilers in conjunction
with ame retention gas burners are more efcient. One result of increased efciency is lower ue gas temperatures. As ue gases rise in the chimney, they
cool and condense when they reach the dew point.
The condensation mixes with sulphur in the ue gases
creating sulfuric acid. The acid attacks the chimney mortar, brick and clay liners causing corrosion, deterioration and blockage of the chimney. Eventually
the blockage could prevent exhausting the ue gases. Instead, the ue gases vent out the barometric damper
into the living space.
Therefore it is strongly recommended that an approved insulated stainless steel chimney liner be installed. The installing contractor is solely responsible for installation of the proper vent system.
For those installations not requiring a chimney, such
as through-the-wall vented appliances, follow the instructions given by the appliance and power venter (if used) manufacturers.
Figure 4 – Chimney Design - Above the Roof
Minimum Clearence: 2 FT.
NOTE: Correct chimney design is shown by dotted lines. Incorrect chimney design, as shown by the solid lines, may result in down-drafts.
CG4 Burner Manual
7
Section: INSPECT/PREPARE INSTALLATION SITE
Combustion Air Supply
Some local codes and
gas utilities require the installation of a CO detector, this is
strongly recommended in all applications.
Carbon Monoxide
Hazard
Do not block combustion air inlet. Failure to provide adequate air supply could seriously affect the burner performance and result in damage to the equipment and emission of poisonous carbon monoxide gas.
Buildings with Adequate Air Inltration
In many cases, a burner operating in an unconned
space of a conventional frame, brick or stone building will receive adequate air supply from leakage in the
building itself. But if the burner is located in a conned
space such as a furnace or boiler room, that space must have one permanent opening toward the top of the space and one near the bottom of the space.
One method to accomplish this is through a permanent opening(s) in an exterior wall. The opening, or openings, must have a total free area of not less than one sq. in. per 5,000 BTU per hour. All appliances must be taken into consideration. Refer to NFPA 54 & 58.
Another method is to supply outside air directly to the burner through round, smooth duct work (See Figure
5). Some manufacturers offer accessories which allow outside combustion air duct work to be coupled to the burner. These kits must meet the engineered system requirements of NFPA54. For safety reasons it is important that you comply strictly with their installation instructions.
Figure 5 – Outdoor Air Ducted to Burner
Each opening must have a free area of not less than one sq. in. per 1,000 BTU per hour of the highest input rating listed for the appliance (refer to NFPA 54 & 58).
Remember to take the total input of all air-using
appliances into consideration when guring the
openings. The openings must connect with the inside of
the building, which should have adequate inltration from
the outside.
As an example:
If a gas burner was ring at 175,000 BTU/Hr and a water heater was ring at 70,000 BTU/Hr, in an enclosed room
in a building each opening in the enclosure should be 245 sq. in. (245,000/1,000 x 1 sq. in. = 245 sq. in.) A 245 sq. in. opening would typically be 10” x 25” or 16” x 16”.
Buildings with Less Than Adequate Air Inltration
If the burner is located in a tightly constructed building
where there is inadequate outside air inltration, outside
combustion air must be supplied by some other means.
Clearances to Burner and Appliance
Provide space around burner and appliance for easy
service and maintenance.
Check minimum clearances against those shown
by the appliance manufacturer and by applicable building codes.
The recommended clearance around the burner
itself is 12” minimum for service access.
8
Section: INSPECT/PREPARE INSTALLATION SITE
Fuel Gas Supply
Explosion, Fire, Asphyxiation Hazard
Leaking gas could result in asphyxiation,
explosion, or re hazard.
Prior to burner installation all gas supply piping must be inspected, tested and purged in accordance with the requirements of the National Fuel Gas Code ANSI Z
223.1 (NFPA 54). The burner valve must not be exposed to pressure exceeding 1/2 PSI under any circumstances.
Insure that the supply gas pipe size is capable of providing at least 4.5” W.C. pressure to the burner gas train inlet at the burner’s full capacity rating. Refer to
Tables 2 and 3.
Table 2
Gas Supply Pressure Requirements (Natural or Propane)
Maximum 14” WC (1/2 PSI)
Minimum 4.5” WC
Explosion, Fire, and Gas Leak Hazard
A Drip Leg is required in Gas Supply Piping. Foreign matter could lodge in gas valve cutoff seals, resulting in gas leak-
through, explosion or re.
Insure that a full-size drip leg or dirt pocket has been installed in the piping directly ahead of the main shutoff valve to capture foreign matter.
Electrical Supply
Check the nameplate on the burner to verify that the power connections available are correct for the burner. Refer to Figure 2 on Page 5. All power must be supplied through a disconnect switch fused at 20A maximum and comply with the latest edition of National Electric Code NFPA 70 (Canada CSA C22.1) and all other local or applicable codes.
Verify Burner Components
Your CG4 burner is shipped in two boxes. Verify that you received all the necessary components.
Table 3 – Gas supply piping capacity, CFH
Schedule 40 metallic pipe with 0.50 psi or less inlet pressure and 0.30” W.C. pressure drop
Maximum capacity in cubic feet of gas per hour (CFH). Natural
gas with 0.60 specic gravity.
Pipe
Length
(ft.)
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 890
40 63 130 245 500 760
50 56 115 215 440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
110 34 72 130 275 410
120 31 64 120 250 380
150 28 59 110 225 350
1/2” 3/4” 1” 1-1/4” 1-1/2”
Pipe size (inches) IPS
The larger box contains:
The burner chassis The literature package, which includes the burner
manual The gas valve A small parts bag, containing a reducing tee, a pipe
plug, a union and a bafe (P/N 5880)
The smaller box contains:
The air tube The burner head and its (2) mounting screws A blank air band (only packaged with tubes using the
F3G head) A box containing the manifold assembly, the natural
gas orices, an O-ring, a packet of O-ring lubricant
and 10 mounting screws.
Verify Burner Selection
If the burner is supplied as an original equipment part of a boiler or furnace appliance the information in this section may be disregarded. Instead, use the appliance
manufacturer’s specications.
If the gas supply pressure is not correct, it must be corrected before starting the CG4 installation. Contact
your gas utility or qualied contractor.
CG4 Burner Manual
Verify that the proper burner chassis and air tube assembly have been selected.
Determine the appliance’s design ring rate from the
appliance rating plate. The appliance rating plate will
probably have an input rating and an output rating.
9
Loading...
+ 19 hidden pages