If the information in these instructions is not followed exactly, a re or explosion may
result causing personal injury, death or property damage.
─ Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this
or any other appliance.
─ WHAT TO DO IF YOU SMELL GASy Do not try to light any appliancey Do not touch any electrical switch; do not use any phone in your building.y Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions.
y If you cannot reach your gas supplier, call the re department.y Installation and service must be performed by a qualied installer, service agency or the
gas supplier.
Contents
General Information ....................................................3
To the Owner: ................................................................................ 3
Replace the Blower Wheel ..........................................................25
Replacement Parts .................................................... 26
Limited Warranty Information .................................. 28
Before Calling Beckett . . .
Before contacting us about your burner, you must have a completely
lled out copy of the Contractor Start-Up Form (Located inside
of last page). This information is crucial for troubleshooting and
obtaining the correct replacement part.
2
Section: GENERAL INFORMATION
General Information
To the Owner:
This equipment must be installed, adjusted and started
by a qualied service agency that is licensed and
experienced with all applicable codes and ordinances
and responsible for the installation and commissioning of
the equipment.
Thank you for purchasing a Beckett CG4 burner for
use with your heating appliance. Please pay attention
to the Safety Warnings contained within this instruction
manual. Keep this manual for your records and provide it
to your qualied service agency for use in professionally
setting up and maintaining your burner.
Your CG4 burner will provide years of efcient operation if
it is professionally installed and maintained by a qualied
service technician. If at any time the burner does not
appear to be operating properly, immediately contact
your qualied service agency for consultation.
We recommend annual inspection/service of your
gas heating system by a qualied service agency.
Burn Hazard, Hot
Surface
Burner ange and air tube are hot
when burner is in operation. Do not
service this area during or immediately
after operation. Allow area to cool.
Owner’s Responsibility:
Explosion, Fire,
Asphyxiation Hazard
Failure to follow these instructions,
misuse, or incorrect adjustment of the
burner could lead to equipment
malfunction and result in
asphyxiation, explosion or re.
Contact a professional, qualied service agency for
the installation, adjustment and service of your gas
burning system. Thereafter, have your equipment
adjusted and inspected at least annually to ensure
reliable operation. This work requires technical
training, trade experience, licensing or certication
in some states and the proper use of special
combustion test instruments.
Please carefully read and comply with the following
instructions:
y See the front cover for ‘What to do if you smell gas’.
y Never store or use gasoline or other ammable
liquids or vapors near this burner or appliance.
y Never attempt to burn garbage or refuse in this
appliance.
y Never attempt to light the burner/appliance by
throwing burning material into the appliance.
y Never attempt to burn any fuel not specied and
approved for use in this burner.
y Never restrict the air inlet openings to the burner or
the combustion air ventilation openings in the room.
CG4 Burner Manual
Frozen Plumbing and
Water Damage Hazard
If the residence is unattended in severely cold
weather, burner primary control safety lockout,
heating system component failures, power
outages or other electrical system failures could
result in frozen plumbing and water damage in a
matter of hours. For protection, take preventive
actions such as having a security system installed
that operates during power outages, senses low
temperature and initiates an effective action.
Consult with your heating contractor or a home
security agency.
Contact a professional, qualied
service agency to replace any
component that has been exposed to water.
3
Section: GENERAL INFORMATION
Professional Installer’s Responsibility:
Professional Service
Required
Failure to follow these instructions
could lead to equipment malfunction
and result in asphyxiation, explosion
or re.
y Please read all instructions before proceeding.
Follow all instructions completely.
y This equipment must be installed, adjusted
and started by a qualied service agency that
is licensed and experienced with all applicable
codes and ordinances and responsible for the
installation and commissioning of the equipment.
y The installation must comply with all local codes
and ordinances having jurisdiction and the latest
edition of the National Fuel Gas Code ANSI
Z223.1 (NFPA 54) and CAN1-B149.1 in Canada.
Fire Hazard: Overheating
Should over-heating occur:
y Shut off the manual gas control to
the appliance.
y DO NOT shut off power to the
equipment, allow the blower and
pumps to continue running.
Specications
Table 1 – Burner Specications
Input Firing Rate 80,000 - 250,000 BTU/hr
Firing ModeOn-Off Only
Fuel
Required Input Gas Supply
Pressure
Input Voltage 120 Vac + 10% / -15%; 60 Hz
Input Current2.75 A (Run); 12.0 ALR
Gas Valve
Burner ControlBeckett 7590D Direct Ignition
Flame DetectionFlame Rectication
IgniterBeckett 7474001 Gas Igniter
Motor1/7 Hp; PSC
Combustion Air ProvingDifferential Pressure Switch
For altitudes higher than 2,000 feet, derate the burner capacity 4%
for each 1,000 feet above sea level.
Burner is not approved for use in 50 Hz applications.
Natural gas - 0.64 specic gravity
LP gas - 1.53 specic gravity
4.5” WC minimum
14” WC maximum
24 Vac Dual Seat with integral regulator
set to 3.5” WC for both natural gas and
LP
Up to 90° from upright with motor shaft
horizontal
-40°F to 150°F
Special Requirements:
When contacting Beckett for
service information — Please have the burner serial
number and contractor start-up form available when
calling or writing. You will nd the serial number on
the label located on the left rear of the burner. Refer
to Figure 2.
Concealed damage – If you
discover damage to the burner
or controls during unpacking, notify the carrier at
once and le the appropriate claim forms. Do not
install a burner or control that has been damaged.
If any of these instructions are not clear,
Call Beckett at 1-800-645-2876 for assistance.
For use only on approved
applications. See www.beckettcorp.com/cg4apps for the list of approved
applications.
ETL listed for use in the US or
Canada per ANSI Z21.17(a) / CSA
2.7(a) For use with natural gas or
propane.
4
1.13
Figure 1 – Burner Dimensions
8.3”
Section: GENERAL INFORMATION
15.8”
9.5”
8.0”
7.6”
13.1”
Figure 2 – Burner Nameplate
Your burner will have labels that are specic to its construction. This is for reference only.
General Model Information
Serial Number
R.W. Beckett Specication
Number and Revision
Approvals / Certications
Model “CG4”
Gas ConversionBurner
Brûleur de conversion
SERIAL NUMBER
140121-08157
CG4001 Rev.A 00
#########
Conforms to ANSI Std
Z21.17
Certified to CSA Std
En conformité avec la norme
Homologation en vertu de la
2.7
ANSI Z21.17
norme CSA 2.7
14.4”
10.3”
6.0”
80 TO 250 MBH, 24 to 73 kW
120V/60Hz, 3A run, 12A LR
For use with natural gas or
propane. A conversion kit
supplied by the manufacturer shall
be used to convert to the alternate
fuel.
Manifold pressure: 3.5” W.C.
Max press. to valve: 1/2 PSI
Min press. to valve: 4.5” W.C.
A utiliser avec du gas naturel ou
du propane. Se servir de la
trousse de conversion fournie
par le fabricant pour paser d’un
type decarburant à l’autre.
Pression d’admission: 870 Pa
Pression max.’ à la soupape:
3450 Pa
Pression min. à la soupape:
1120 Pa
Elyria, Ohio
Made in the U.S.A.
Rating Information
Fuel, Construction,
and Setting Data
CG4 Burner Manual
5
Section: INSPECT/PREPARE INSTALLATION SITE
Inspect/Prepare
Installation Site
Indoor Installation
Explosion, Fire,
Asphyxiation Hazard
Wet or dusty environments could lead
to blocked air passages, corrosion
damage to components, impaired
combustion performance and result in
asphyxiation, explosion or re.
y This burner is designed for clean, dry
installations.
y Electrical controls are not protected against rain
or sprayed liquids.
y Keep the installation clear of dust, dirt, corrosive
vapors, and moisture.
y Protective covers and frequent maintenance may
be required.
Fire, Smoke &
Asphyxiation Hazard
y Carefully inspect the chimney,
chimney liner & exhaust vent system.
y Make sure it is properly sized and in
good working condition.
y Follow the instructions supplied by
the appliance manufacturer.
y If a draft regulator is required, it must be a
double-acting type, agency recognized for use
with gas vent systems.
y The chimney installation and vent sizing
must strictly comply with all applicable codes,
authorities having jurisdiction and the latest
revision of the National Fuel Gas Code (ANSI
Z223.1, or NFPA54) or CAN/CGA B/49 Canada.
Remove any vent damper device.
y Regulation by these authorities take precedence
over the general instructions provided in this
installation manual.
Examine the installation site for conditions that could
adversely affect the health and safety of installation
personnel and the user of the appliance or proper
operation of the burner and appliance, and correct any
defects found.
○The area around the appliance should be
unobstructed and dry.
○Wiring must be in good condition and meet code
requirements.
○If the burner is replacing an existing oil burner, old
piping and the tank must be secured or removed to
prevent leakage or unintended deliveries of oil.
○Local jurisdictions may require removal of oil tanks.
See NFPA-30 ammable and combustible liquids
code for approved procedures.
Inspect Chimney and Vent System
1. Any accumulation of soot or debris in chimney
offsets must be removed
2. Any obstructions such as a protruding joint or a
piece of broken tile wedged in the chimney must be
removed.
3. No other appliance connection should be made to
the same ue pipe.
4. The ue pipe should have an upward pitch toward
the chimney of at least 1/4” per foot of length. It
should t tightly and should not project into the
chimney, see Figure 3.
Figure 3 – Vent Pipe with Draft Regulator
Barometric Draft Control
Flue Pipe Ell
Heating Unit
1/4” per Foot
Minimum
6
Section: INSPECT/PREPARE INSTALLATION SITE
5. Any leakage between tiles, around clean-out doors,
or around the vent pipe should be sealed.
6. A Draft regulator is required, it shall be a double-
acting type, agency recognized for use with gas
vent systems.
7. The design and sizing of the appliance’s vent
system shall comply with the requirements of NFPA
54 Chapters 12 and 13.
8. A chimney ue shall extend at least 3 feet above
the highest point at which the chimney comes in
contact with the roof, and not less than 2 feet above
the highest roof surface or structure within 10 feet
horizontally of the chimney. Refer to Figure 4.
Some local codes and gas
utilities require the installation of
a thermal Safety switch on the double-acting draft
control, or draft hood. This is a very good practice
and provides the following protection:
The thermal safety switch senses ue gas spillage
caused by blocked ue exhaust, prolonged down-draft,
or insufcient draft. The safety is wired in series with the
burner control circuit and shuts the burner off, when the
spillage of hot ue gases is detected.
Insulated stainless steel chimney liners
The new designs of furnaces and boilers in conjunction
with ame retention gas burners are more efcient.
One result of increased efciency is lower ue gas
temperatures. As ue gases rise in the chimney, they
cool and condense when they reach the dew point.
The condensation mixes with sulphur in the ue gases
creating sulfuric acid. The acid attacks the chimney
mortar, brick and clay liners causing corrosion,
deterioration and blockage of the chimney. Eventually
the blockage could prevent exhausting the ue gases.
Instead, the ue gases vent out the barometric damper
into the living space.
Therefore it is strongly recommended that an approved
insulated stainless steel chimney liner be installed. The
installing contractor is solely responsible for installation
of the proper vent system.
○For those installations not requiring a chimney, such
as through-the-wall vented appliances, follow the
instructions given by the appliance and power venter
(if used) manufacturers.
Figure 4 – Chimney Design - Above the Roof
Minimum Clearence: 2 FT.
NOTE: Correct chimney design is shown by dotted lines. Incorrect chimney design, as shown by the solid
lines, may result in down-drafts.
CG4 Burner Manual
7
Section: INSPECT/PREPARE INSTALLATION SITE
Combustion Air Supply
Some local codes and
gas utilities require the
installation of a CO detector, this is
strongly recommended in all
applications.
Carbon Monoxide
Hazard
Do not block combustion air inlet. Failure to
provide adequate air supply could seriously affect
the burner performance and result in damage to
the equipment and emission of poisonous carbon
monoxide gas.
Buildings with Adequate Air Inltration
In many cases, a burner operating in an unconned
space of a conventional frame, brick or stone building
will receive adequate air supply from leakage in the
building itself. But if the burner is located in a conned
space such as a furnace or boiler room, that space
must have one permanent opening toward the top of the
space and one near the bottom of the space.
One method to accomplish this is through a permanent
opening(s) in an exterior wall. The opening, or openings,
must have a total free area of not less than one sq. in.
per 5,000 BTU per hour. All appliances must be taken
into consideration. Refer to NFPA 54 & 58.
Another method is to supply outside air directly to the
burner through round, smooth duct work (See Figure
5). Some manufacturers offer accessories which allow
outside combustion air duct work to be coupled to the
burner. These kits must meet the engineered system
requirements of NFPA54. For safety reasons it is
important that you comply strictly with their installation
instructions.
Figure 5 – Outdoor Air Ducted to Burner
Each opening must have a free area of not less than one
sq. in. per 1,000 BTU per hour of the highest input rating
listed for the appliance (refer to NFPA 54 & 58).
Remember to take the total input of all air-using
appliances into consideration when guring the
openings. The openings must connect with the inside of
the building, which should have adequate inltration from
the outside.
As an example:
If a gas burner was ring at 175,000 BTU/Hr and a water
heater was ring at 70,000 BTU/Hr, in an enclosed room
in a building each opening in the enclosure should be
245 sq. in. (245,000/1,000 x 1 sq. in. = 245 sq. in.) A
245 sq. in. opening would typically be 10” x 25” or 16” x
16”.
Buildings with Less Than Adequate Air
Inltration
If the burner is located in a tightly constructed building
where there is inadequate outside air inltration, outside
combustion air must be supplied by some other means.
Clearances to Burner and Appliance
○Provide space around burner and appliance for easy
service and maintenance.
○Check minimum clearances against those shown
by the appliance manufacturer and by applicable
building codes.
○The recommended clearance around the burner
itself is 12” minimum for service access.
8
Section: INSPECT/PREPARE INSTALLATION SITE
Fuel Gas Supply
Explosion, Fire,
Asphyxiation Hazard
Leaking gas could result in asphyxiation,
explosion, or re hazard.
Prior to burner installation all gas supply piping must be
inspected, tested and purged in accordance with the
requirements of the National Fuel Gas Code ANSI Z
223.1 (NFPA 54).
The burner valve must not be exposed to pressure
exceeding 1/2 PSI under any circumstances.
Insure that the supply gas pipe size is capable of
providing at least 4.5” W.C. pressure to the burner gas
train inlet at the burner’s full capacity rating. Refer to
Tables 2 and 3.
Table 2
Gas Supply Pressure Requirements (Natural or Propane)
Maximum14” WC (1/2 PSI)
Minimum4.5” WC
Explosion, Fire, and Gas
Leak Hazard
A Drip Leg is required in Gas Supply
Piping. Foreign matter could lodge in gas
valve cutoff seals, resulting in gas leak-
through, explosion or re.
Insure that a full-size drip leg or dirt pocket has been
installed in the piping directly ahead of the main shutoff
valve to capture foreign matter.
Electrical Supply
Check the nameplate on the burner to verify that the
power connections available are correct for the burner.
Refer to Figure 2 on Page 5. All power must be
supplied through a disconnect switch fused at 20A
maximum and comply with the latest edition of National
Electric Code NFPA 70 (Canada CSA C22.1) and all
other local or applicable codes.
Verify Burner Components
Your CG4 burner is shipped in two boxes. Verify that
you received all the necessary components.
Table 3 – Gas supply piping capacity, CFH
Schedule 40 metallic pipe with 0.50 psi or less inlet pressure
and 0.30” W.C. pressure drop
Maximum capacity in cubic feet of gas per hour (CFH). Natural
gas with 0.60 specic gravity.
Pipe
Length
(ft.)
1013227852010501600
20921903507301100
3073152285590890
4063130245500760
5056115215440670
6050105195400610
704696180370560
804390170350530
904084160320490
1003879150305460
1103472130275410
1203164120250380
1502859110225350
1/2”3/4”1”1-1/4”1-1/2”
Pipe size (inches) IPS
The larger box contains:
○The burner chassis○The literature package, which includes the burner
manual
○The gas valve○A small parts bag, containing a reducing tee, a pipe
plug, a union and a bafe (P/N 5880)
The smaller box contains:
○The air tube○The burner head and its (2) mounting screws○A blank air band (only packaged with tubes using the
F3G head)
○A box containing the manifold assembly, the natural
gas orices, an O-ring, a packet of O-ring lubricant
and 10 mounting screws.
Verify Burner Selection
If the burner is supplied as an original equipment part
of a boiler or furnace appliance the information in this
section may be disregarded. Instead, use the appliance
manufacturer’s specications.
If the gas supply pressure is not correct, it must be
corrected before starting the CG4 installation. Contact
your gas utility or qualied contractor.
CG4 Burner Manual
Verify that the proper burner chassis and air tube
assembly have been selected.
○Determine the appliance’s design ring rate from the
appliance rating plate. The appliance rating plate will
probably have an input rating and an output rating.
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.