Beckett CG10 User Manual

COMMERCIAL PRODUCTS
Fire, Explosion and Asphyxiation Hazards
Failure to follow these instructions exactly could lead to fi re or explosion and result in death, severe personal injury or property damage.
Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
1.
What to do if you smell gas:
2.
- Do not try to light any appliance.
- Do not touch any electrical switch.
- Immediately call your gas supplier from a telephone outside the building.
- Follow the gas supplier’s instructions.
- Call the fi re department if you cannot contact your supplier. Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.
3.
Contents
General Information ....................................................3
Hazard Defi nitions: ........................................................................3
Owner’s Responsibility: ................................................................. 3
Professional Installer’s Responsibility: ..........................................4
Specifi cations ................................................................................ 4
Pre-installation Checklist ........................................... 5
Indoor Installation .......................................................................... 5
Combustion air supply ................................................................... 5
Clearances .................................................................................... 6
Fuel gas supply .............................................................................6
Flue vent system ...........................................................................6
Electrical supply ............................................................................ 6
Verify burner components .............................................................6
Verify fi ring input range ................................................................. 6
Verify burner air tube assembly ..................................................... 7
Mount the Burner ......................................................... 9
Connect Gas Piping ....................................................9
Gas Trains ...................................................................................10
Wire the Burner .......................................................... 12
Sequence of Operation ............................................. 13
Prepare the Burner for Start-up ............................... 13
Start-up checklist .........................................................................14
Start the Burner ........................................................ 16
Burner start procedure ...............................................................16
Verify input fi ring rate ..................................................................16
Check operation and safety controls ........................................... 20
Use test instruments to set combustion: .....................................21
Recommended combustion test sequence: ................................21
Maintenance and Service.......................................... 22
Annual maintenance ..................................................................22
Propane Restrictor Description ..................................................25
Installation ..................................................................................25
For the OPERATOR ....................................................................27
Replacement Parts .................................................... 28
Burner Confi gurations .............................................. 29
Limited Warranty Information .................................. 32
2
Section: General Information
General Information
Hazard Defi nitions:
Indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
Indicates a hazardous
situation, which, if not avoided, could result in death, or serious injury.
Used with the safety
alert symbol, indicates a hazardous situation, which, if not avoided, may result in minor or moderate injury.
Within the boundaries of the hazard warning, there will be information presented describing consequences if the warning is not headed and instructions on how to avoid the hazard.
Used to address practices not
related to personal injury.
To the Owner:
Thank you for purchasing a Beckett CG10 burner for use with your heating appliance. Please
pay attention to the Safety Warnings contained within this instruction manual. Keep this manual for your records and provide it to your qualifi ed service agency for use in professionally setting up and maintaining your burner.
Your CG10 burner will provide years of effi cient operation if it is professionally installed and maintained by a qualifi ed service technician. If at any time the burner does not appear to be operating properly, immediately contact your
qualifi ed service agency for consultation.
We recommend annual inspection/service of your gas heating system by a qualifi ed service agency.
Owner’s Responsibility:
Follow these instructions exactly.
Failure to follow these instructions, misuse, or incorrect adjustment of the burner could lead to equipment malfunction and result in asphyxiation, explosion or fi re.
Contact a professional, qualifi ed service agency for the installation, adjustment and service of your gas burning system. Thereafter, have your equipment adjusted and inspected at least annually to ensure reliable operation. This work requires technical training, trade experience, licensing or certifi cation in some states and the proper use of special combustion test instruments.
Please carefully read and comply with the following instructions:
CG10 Burner Manual
See the front cover for ‘What to do if you smell gas’.
y
Never store or use gasoline or other fl ammable
y
liquids or vapors near this burner or appliance.
Never attempt to burn garbage or refuse in this
y
appliance.
Never attempt to light the burner/appliance by
y
throwing burning material into the appliance.
Never attempt to burn any fuel not specifi ed and
y
approved for use in this burner.
Never restrict the air inlet openings to the burner or
y
the combustion air ventilation openings in the room.
3
Section: General Information
Professional Installer’s Responsibility:
Follow these instructions exactly.
Failure to follow these instructions could lead to equipment malfunction and result in asphyxiation, explosion or fi re.
Please read all instructions before proceeding.
y
Follow all instructions completely.
This equipment must be installed, adjusted and
y
started by a qualifi ed service agency that is licensed and experienced with all applicable codes and ordinances and responsible for the installation and commissioning of the equipment.
The installation must comply with all local codes and
y
ordinances having jurisdiction and the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA
54) and CAN1-B149.1 in Canada.
Concealed damage – If you
discover damage to the burner or controls during unpacking, notify the carrier at once and le the appropriate claim forms.
High altitude installations – Accepted industry practice requires no derate of burner capacity up to 2000 feet above sea level. For altitudes higher than 2000 feet, derate the burner capacity 2% for each 1000 feet above the 2000 feet.
Specifi cations
Table 1 – Burner Specifi cations
Input fi ring range 300 to 1200 MBh
Fuel Natural gas - 0.6 specifi c gravity typical
Gas train Standard: UL listed/CSD-1 Confi guration
Options: IRI and FM
Manifold pressure 1.0 to 4.6 inches W.C. typical
Firing mode On/Off or On/Off with Low Fire Start
Flame safeguard RM7895A Standard (Options available)
Flame detection Standard: Flame rod rectifi cation
Optional: Ultraviolet scanner
Air proving switch Standard
Gas pressure switches
Ignition Direct spark main fl ame
Motor Standard: 1/3 HP; 3450 RPM; 120
Weight 55 lbs.
Dimensions Refer to Figure 5.
service information — Please record the burner serial number (and have available when calling or writing). You will fi nd the serial number on the silver label located on the left rear of the burner. Refer to Figure 1.
Standard high and low
volt/60 hz, single phase Optional motor: 50 or 60 hz (see notice for 50 hz), 240 volt single phase
Special Requirements:
When contacting Beckett for
50 Hz motors – The burner ratings, air settings and other adjustments are based on 60 hz motors at 3450 rpm. Derate fi ring capacity 20% when using 50 hz motors. Consult factory for specifi c application data.
Agency Approvals
Underwriters Laboritories Certifi ed by C-UL Accepted by N.Y.C.M.E.A. Other approvals may be available and must be specifi ed at time of order.
4
Figure 1. Burner Nameplate
General Model Information
Serial Number,
Including Date Code
Section: Pre-installation Checklist
R.W. Beckett Construction and Setting Data
Rating Information
Approval Agency
Symbols
Primary Group
and Fuel
Pre-installation Checklist
Combustion air supply
Adequate Combustion and Ventilation Air Supply
Required
Failure to provide adequate air supply could seriously affect the burner performance and result in damage to the equipment and emission of poisonous carbon monoxide gas.
The burner cannot properly burn the fuel if it is not
y
supplied with a reliable combustion air source.
Follow the guidelines in the latest edition of National
y
Fuel Gas Code ANSI Z223.1 (NFPA 54) and CAN1-B149.1 regarding providing adequate air for combustion and ventilation.
For appliance/burner units in confi ned spaces, the
y
room must have an air opening near the top of the room, plus one near the fl oor, each with a free area at least one square inch per 1000 Btu/hr input for all fuel-burning equipment in the room.
R.W. Beckett Specifi cation Number and Revision
Boiler Manufacturer and Model, When Applicable
Additional Codes
Indoor Installation
Protect against Dust and Moisture
Wet or dusty environments could lead to blocked air passages, corrosion damage to components, impaired combustion performance and result in asphyxiation, explosion or fi re.
This burner is designed for clean, dry installations.
y
Electrical controls are not protected against rain or
y
sprayed liquids.
Keep the installation clear of dust, dirt, corrosive
y
vapors, and moisture.
Protective covers and more frequent maintenance
y
may be required.
If there is risk of the space being under negative pressure, or of exhaust fans or other devices depleting available air for combustion and ventilation, the appliance/burner should be installed in an isolated room provided with outside combustion air.
CG10 Burner Manual
5
Section: Pre-installation Checklist
Test For Gas Pipe Leaks
Leaking gas could result in asphyxiation, explosion, or fi re hazard.
The gas supply piping must be absolutely leak-free.
y
Pressure test the gas piping with air that is at least
y
three times greater than the gas pressure being used.
Verify that there are no leaks before proceeding.
y
Clearances
With the burner installed in the appliance, there must be adequate space in front of and on the sides of the burner to allow access and operation. Verify that the clearance dimensions comply with local codes and with the appliance manufacturer’s recommendations.
Flange mounting arrangement (Includes high­temperature gasket and /or fi ber rope for pressure ring).
Verify fi ring input range
Refer to appliance manufacturer’s instructions (if available) for the fi ring input range. Otherwise the maximum recommended fi ring range for the burner depends on the length and width of the fi ring chamber and the distance from the burner center to the chamber oor. Verify that the chamber dimensions are at least as large as the minimum values given in Figure 2. If the appliance dimensions are smaller, reduce the fi ring rate accordingly.
Dimensions shown are for cast
iron sectional boilers with uptakes between sections. For minimum dimensions of other furnace types consult R.W. Beckett Corporation.
Fuel gas supply
Verify that the gas supply piping complies with all applicable local codes and the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54).
Insure that the supply gas pipe size is capable of providing at least the minimum pressure required to the burner gas train inlet at the burner’s full capacity rating. Refer to Table 1.
Flue vent system
The fl ue gas vent system must be in good condition and must comply with National Fuel Gas Code ANSI Z223.1 (NFPA 54) and all other applicable codes having jurisdiction for vent construction, capacity, and sizing.
Electrical supply
Check the nameplate on the burner to verify that the power connections available are correct for the burner. Refer to Figure 1. All power must be supplied through fused disconnect switches and comply with the latest edition of National Electric Code NFPA 70 (Canada CSA C22.1) and all other local or applicable codes.
Figure 2. Minimum Combustion Chamber Dimensions
Minimum Combustion
Chamber Dimensions (inches)
Input Firing Rate in MBH
300-400 18 12 12 6
400-600 22 14 14 7
600-900 26 16 16 8
Length
‘L’
Width
‘W’
Height
‘H’
Burner Head Centerline to
oor ‘A’
Verify burner components
Burner model can be checked from burner carton or
rating label on burner.
6
900-1200 30 18 18 9
Section: Pre-installation Checklist
Verify burner air tube assembly
The information in this section may be disregarded if the burner supplied by the appliance manufacturer is a matched component. Maximum fi ring capacity depends on the furnace
pressure. Use the charts shown in Figure 3 and Figure 4, to verify the correct burner con guration for
the input rate. Refer to Figure 5 to verify the air tube assembly
length and mounting insertion dimensions.
The volume of the furnace
also infl uences the combustion process. R. W. Beckett Corp. recommends at least 1 cubic foot of furnace volume for each 150,000 BTU/Hr of ring rate.
Figure 3. Maximum Capacity (at 3% O
1400 1300 1200 1100 1000
900 800 700 600
Maximum Capacity, MBH
500 400
0 0.2 0.4 0.6 0.8 1
) vs Furnace Pressure - Step Spud Confi guration
2
Flames are shaped by their
furnaces and by its fl ue locations. Increased height and width can decrease the length requirement. When shaping is too severe fl ames impinge on the walls. Impingement causes CO and carbon deposits and may damage the wall. Maintaining these minimum dimensions should prevent impingement, but smaller furnaces may be acceptable depending upon the results of applications testing. We recommend factory testing of all new burner/furnace combinations by the furnace manufacturer and/or R. W. Beckett Corp.
CG10.6S CG10.5S CG10.4S CG10.3S CG10.2S CG10.1S
Furnace Pressure, In. W.C.
Figure 4. Maximum Capacity (at 3% O2) vs Furnace Pressure - Swirler Head Confi guration
800
700
600
500
400
Maximum Capacity, MBH
300
0 0.2 0.4 0.6 0.8 1
Furnace Pressure, In. WC
CG10 Burner Manual
CG10.3 CG10.2 CG10.1
7
Section: Pre-installation Checklist
Figure 5. Burner Dimensions
Burner Model Airtube Dim. A Dim. B O.D.
10.1 - 10.3, 10.1S - 10.3S 51927 25.0” 11.7” 4.43”
10.4 - 10.6 51928 26.0” 12.7” 4.86”
10.4S - 10.6S 51961 25.7” 12.5” 4.61”
8
Mount the Burner
Mount the burner to the appliance. The burner specifi ed for packaged equipment will have a fl ange welded for the required insertion. Follow the appliance manufacturer’s instructions for mounting.
In the absence of instructions, or for retrofi ts, make sure that the air tube insertion dimension, measured along the side of the air tube from the welded fl ange to the end of burner air tube, is correct.
Protect the Air Tube from Overheating
Section: Mount the Burner & Connect Gas Piping
Figure 6. Custom Mounting Plate
C
B
A
Overheating could cause damage to the air tube and other combustion components leading to equipment malfunction and impaired combustion performance.
The end of the air tube must not extend into the
y
combustion chamber unprotected unless it has been factory-tested and specifi ed by the appliance manufacturer.
The end of the air tube should be set back ¼”
y
from fl ush with the refractory inside wall to prevent damage from overheating.
y
Refer to the instructions outlined in this section for methods of additional protection.
If this dimension cannot be achieved, protect the end of the air tube by installing a suitable ceramic refractory material such as a refractory mill board capable of withstanding at least 2300°F. The entry hole diameter in the appliance should be 1” larger than the air tube to facilitate ease of installation and provide adequate protection.
Referring to Figure 6, if the front plate opening (C) in the boiler is larger than the burner fl ange bolt circle, then a custom mounting plate (A) of at least 1/4” thickness must be used with a suitable high-temperature refractory material anchored on the fi re-side. A suitable high- temperature gasket (B) must be used for an effective seal.
Attach the plate and gasket to the boiler and tighten
the mounting nuts or bolts securely. Verify that the air tube is ¼” back from fl ush (see
Figure 2), and there is nothing blocking the fl ame zone that could cause fl ame impingement.
Key:
A Burner mouning fl ange
B Gasket
C Appliance mounting plate
Connect Gas Piping
All gas piping installation must
comply with the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54) and other applicable local codes.
The gas supply system must be sized to deliver at least the minimum required pressure to the gas train inlet. Contact your local gas utility for verifi cation of gas pressures, allowable pressure drops, and any local piping code requirements. Refer to Figure 7 for an illustration of a gas piping layout and refer to Table 1 for pipe sizing.
Do Not Use Tefl on Tape on Gas Piping
Damage to gas valve cutoff seals and valve bodies could cause gas leaks and result in asphyxiation, explosion or fi re.
Pieces of tape can be cut loose during installation
y
and lodge in gas valves causing cutoff seal problems.
Te fl on tape ‘lubricates’ pipe threads, allowing iron
y
pipes to penetrate too deeply into aluminum valve bodies causing distortion and leakage.
Use only pipe sealant compounds that are resistant
y
to the gas being used.
CG10 Burner Manual
9
Section: Connect Gas Piping
Figure 7. Typical Gas Piping Layout
ABBREV.
ITEM DESCRIPTION
HGPS
HIGH GAS PRESSURE SWITCH
LGPS
LOW GAS PRESSURE SWITCH
MSC
MAIN SHUTOFF COCK
MLTC
MAIN LEAK TEST COCK
PG
PRESSURE GAUGE
S
STRAINER
SSOV1
SAFETY SHUTOFF VALVE #1
TC
TEST COCK
U
UNION
2PRV
TWO POSITION REGULATING VALVE
REGULATOR
GAS UTILITY PIPING
PG
METER
LGPS
U
DRIP LEG
FACILITY PIPING
S
(IF USED)
MSC
U
TC
SSOV1
2PRV
GAS TRAIN BURNER
TC
MLTC
U
HGPS
BURNER
TC
Table 1. Gas supply piping capacity
Schedule 40 metallic pipe with 0.50 psi or less inlet pressure and 0.30” W.C. pressure drop
Maximum capacity in cubic feet of gas per hour (CFH). Natural gas with 0.60 specifi c gravity. Pipe size (inches) IPS
Pipe Length (ft.) 0.75” 1.0” 1.25” 1.5” 2.0” 2.5” 3.0” 4.0”
10 278 520 1050 1600 3050 4800 8500 17500
20 190 350 730 1100 2100 3300 5900 12000
30 152 285 590 800 1650 2700 4700 9700
40 130 245 500 760 1450 2300 4100 8300
50 115 215 440 670 1270 2000 3600 7400
60 105 195 400 610 1150 1850 3250 6800
70 96 180 370 560 1050 1700 3000 6200
80 90 170 350 530 990 1600 2800 5800
90 84 160 320 490 930 1500 2600 5400
100 79 150 305 460 870 1400 2500 5100
125 72 130 275 410 780 1250 2200 4500
150 64 120 250 380 710 1130 2000 4100
175 59 110 225 350 650 1050 1850 3800
200 55 100 210 320 610 980 1700 3500
Install a Drip Leg in Gas Supply Piping
Foreign matter could lodge in gas valve cutoff seals, resulting in gas leak-through, explosion or fi re.
Install a full-size drip leg or dirt pocket in the piping directly ahead of the main shutoff valve to capture foreign matter.
Gas Trains
Gas Leaks and Exposion Hazards
Provide Over-pressure Protection
CSD-1 requires that if gas pressure entering the building exceeds the rating of any gas train component an overpressure protection device must be installed.
10
Standard – An Underwriters Laboratories (UL) listed gas train is standard for the CG10 gas burner. This confi guration also meets CSD-1 requirements. See Figure 8 for typical component layout.
Propane (LP) – When the correct propane restrictor is added to a burner’s gas pipe assembly it changes the burner’s gas pressure drop so that the propane pressure drop is equal to the natural gas pressure drop of the same BTU fi ring rate. That is why the Manifold to Furnace Pressure Drop curves of Figures 12 and 13 are correct for both propane and natural gas. That is also why a gas train adjusted for the burner’s natural gas requirements will be correctly adjusted for its propane requirements. R. W. Beckett provides the same pressure regulating safety shutoff valve in the gas train (usually a Honeywell V4944B) for both natural gas and propane. The valve is marked for natural gas due to its primary usage in a pressure range normally used
Loading...
+ 22 hidden pages