Beckett CG10 User Manual

BECKETT
CG10
COMMERCIAL GAS BURNER
Overall Dimensions
11.7
6.0
4.4
4.6
25.5
6.8
8.2
Specifi cations
Input fi ring range 300 to 1200 MBh
Fuel Natural gas - 0.6 speci c gravity typical
Gas train Standard: UL listed/CSD-1 Con guration
Firing mode On/Off or On/Off with Low Fire Start
Flame safeguard RM7895A Standard (Options available)
Flame detection Standard: Flame rod recti cation
Air proving switch Standard
Gas pressure
switches
Ignition Direct spark main ame
Motor Standard: 1/3 HP; 3450 RPM; 120 volt/60 hz,
Weight 55 lbs.
Options: IRI and FM
Optional: Ultraviolet scanner
Standard high and low
single phase Optional motor: 50 or 60 hz (see notice for 50 hz), 240 volt single phase
8.1
9.9-11.0
Gas Gun Assembly
Features
S - Standard O - Optional N/A - Not Available
On/Off with Low Fire Start S
Propane Restrictor O
Linkageless Low/High/Low or Low/High/Off N/A
Modulation with Pressure/Temperature Modulating Controller N/A
Right or Left Side Gas Train Connection S
Air Pressure Switch S
Low Gas Pressure Switch S
High Gas Pressure Switch S
Main Shutoff Cock, Leak Test Cock, Test Connections, and Test Cocks S
Direct Spark Ignition of Main Flame S
Flame Safeguard with Flame Rod O
Flame Safeguard with UV Sensor S
Customized Electrical Cabinet O
UL/CUL - CSD1 - Swiss Re S
FM O
IRI (old standard) O
Power On - Fuel On, Indicator Light O
Gas Train Assembly (Typical Gas Train, other confi gurations are available)
LGPS
MSC
www.beckettcorp.com R.W. Beckett Corporation ● Elyria, Ohio
U SSOV1 2PRSSOV MLTC U TP
TC TC HGPS
Typical Wiring (Honeywell RM7897A - for reference only)
Combustion Chamber Dimensions
Minimum Combustion
Chamber Dimensions (inches)
Input Firing Rate in
MBH
300-400 18 12 12 6
400-600 22 14 14 7
600-900 26 16 16 8
900-1200 30 18 18 9
‘L’ (Length)
‘W’ (Width)
‘H’ (Height)
Burner Head Centerline
to fl oor ‘A’
Loading...