Beckett CF3500A, CF800, CF2300A, CF375, CF2500A User Manual

COMMERCIAL PRODUCTS
C
OMMERCIAL
O
IL
B
URNERS
Models:
CF375
CF500
CF800
CF1000
CF1400
CF2500A
CF3500A
OEM Setup Guide
C O
Specifi cations for commercial and industrial oil-fi red heating appliances.
OMMERCIAL
IL
B
URNERS
Bryan Steam
DR
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
250 CF375 BCF3907 CF56KZ 1.79 1.50x60ES 1 10 1/2 N/A 140 51311 5.00"
350 CF375 BCF3907 C100KZ 2.50 2.00x60P 3 10 2 N/A 190 51311 5.00"
450 CF500 BCF809 CF100KK 3.21 2.50x45P 4 4 0 N/A 150 51311 5.00"
650 CF800 BCF403 CF100KH 4.64 4.00x60B (D) 3 7 0 N/A 140 51311 5.50"
850 CF800 BCF403 CF100KJ 6.07 5.00x45B (D) 2 8 8 N/A 150 51311 5.50"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
Page 1
Buderus
G215
Series Boiler
Head
Setting
Head
Setting
Blue -
Low Fire
Air or
Shutter
Blue -
Low Fire
Air or
Shutter
High
Boiler
Burner
3 AFG B2007 AFG50ML 1.10 0.90x45ES 0 8 1 N/A 170 51311 3.50"
4 AFG B2007 AFG50ML 1.40 1.10x45ES 2 8 2 N/A 175 51311 3.50"
5 CF375 BCF3907 CF56KY 1.75 1.35x45ES 2 5 1 N/A 170 51311 3.50"
6 CF375 BCF3907 CF56KZ 2.10 1.75x45ES 1 7 2 N/A 140 51311 3.50"
7 CF375 BCF3907 CF56KZ 2.50 2.00x45P 1 9 3 N/A 150 51311 3.50"
Chassis
Spec.
Air Tube
Combination
Buderus
Boiler
Burner
5 CF500 BCF809 CF80KK 3.00 2.50x45P 3 7 0 N/A 140 51311 4.75"
Chassis
Spec.
Air Tube
Combination
Fire Rate
High
Fire Rate
Nozzle
G315
Nozzle
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Red -
High Fire
Air or
Band
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
Low Fire
Pump
Press.
High Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Pressure
Firing Flange
Insertion
Insertion
6 CF800 BCF403 CF80KH 3.85 3.25x45P 1 7 0 N/A 140 51311 4.75"
7 CF800 BCF403 CF80KH 4.70 4.00x45P 2 10 0 N/A 140 51311 4.50"
8 CF1400 BCF205 CF66KD 5.50 3.25x45P 1 20 35 150 275 51312 4.50"
9 CF1400 BCF205 CF66KD 6.40 3.75x45P 3 25 40 150 275 51312 4.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Blue -
Low Fire
Head
Setting
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
High
Fire Rate
G515
Nozzle
Buderus
Boiler
10 CF2300A BCF304 CF102KG 11.60 6.50x45P 2 25 40 150 300 51312 6.00"
Burner
7 CF1400 BCF205 CF102KD 6.90 4.00x60P 5 20 30 150 300 51312 6.00"
8 CF1400 BCF205 CF102KD 8.40 5.00x60P 9 30 43 150 275 51312 6.00"
9 CF2300A BCF304 CF102KG 10.00 5.50x45P 0 20 33 150 300 51312 6.00"
Chassis
Spec.
Air Tube
Combination
Insertion
11 CF2300A BCF304 CF102KG 13.00 7.50x45P 6 25 40 150 300 51312 6.00"
12 CF2300A BCF304 CF102KG 14.60 8.50x45P 8-1/2 30 70 150 300 51312 6.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 2
Buderus
G615
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
10 CF2500 BCF1801 CF102KP 18.50 5.00x45P (2) 2 23 25 300 300 51630 6.25"
11 CF2500 BCF1801 CF102KP 21.00 6.00x45P (2) 5 27 40 300 300 51630 6.25"
12 CF3500A BCF1301 CF114KM 23.50 6.50x45P (2) 4-1/2 20 35 300 300 51630 6.25"
13 CF3500A BCF1301 CF114KM 26.00 7.50x45P (2) 5 25 40 300 300 51630 6.25"
14 CF3500 BCF1301 CF114KR 28.50 8.50x60P (2) 6 30 60 300 300 51631 6.25"
Flange requires an additional adapter plate.
Burner
9 CF2300A BCF304 CF102KG 16.00 9.00x45P 5 30 60 150 300 51630 6.25"
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
Page 3
Burnham Corporation
E
Series Boiler
Head
Setting
Head
Setting
Blue -
Low Fire
Air or
Shutter
Blue -
Low Fire
Air or
Shutter
High
Boiler
E20 CF800 BCF403 CF80KJ 6.00 5.00x60SS 2 10 5 N/A 140 51628 5.50"
E20 CF1400 BCF205 CF66KE 6.00 3.50x60SS 1/2 20 40 125 300 51629 5.50"
E30 CF1400 BCF205 CF66KE 9.00 5.00x60SS 3 30 60 125 300 51629 5.50"
E40 CF2300A BCF304 CF66KG 12.00 7.00x60SS 1 30 40 125 300 51630 5.50"
E50 CF2300A BCF304 CF66KG 15.00 9.00x60SS 4 25 30 125 300 51630 5.50"
E60 CF2300A BCF304 CF66KG 18.00 11.00x60SS 6 35 90 125 300 51630 5.50"
Burner
Chassis
Spec.
Air Tube
Combination
Burnham Corporation
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
High
Fire Rate
FD
Nozzle
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Nozzle
Red -
High Fire
Air or
Band
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
Low Fire
Pump
Press.
High Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Pressure
Firing Flange
Insertion
Insertion
FD-9 CF500 BCF809 CF60KK 2.75 2.00x45P 2 4 0 N/A 150 51311 3.375"
FD-10 CF500 BCF809 CF60KK 3.00 2.50x45P 2 4 0 N/A 150 51311 3.375"
FD-12 CF800 BCF403 CF60KH 4.00 3.25x45P 1-1/2 5-1/2 0 N/A 150 51311 3.375"
FD-14 CF800 BCF403 CF60KH 4.50 3.75x45P 2 7 0 N/A 150 51311 3.375"
FD-15 CF800 BCF403 CF60KH 5.00 4.00x45P 2 8 0 N/A 150 51311 3.375"
FD-19 CF800 BCF403 CF60KH 6.00 4.50x60B 4 10 2 N/A 150 51628 3.375"
FD-24 CF1400 BCF205 CF66KD 7.50 4.50x45P 3 30 55 150 300 51629 3.375"
FD-30 CF1400 BCF205 CF66KE 9.50 5.50x45P 1-1/2 30 75 150 300 51629 3.375"
FD-38 CF2300A BCF304 CF66KG 12.00 7.00x45P 1 25 45 150 300 51313 3.375"
FD-45 CF2300A BCF304 CF66KG 13.80 8.00x45P 1-1/2 25 60 150 300 51313 3.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 4
Burnham Corporation
FDO
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
FDO-7 CF500 BCF809 CF60KK 2.25 2.00x45P 1 3-1/2 0 N/A 140 51311 4.375"
FDO-9 CF500 BCF809 CF60KK 2.75 2.25x45P 2 4 0 N/A 140 51311 4.375"
FDO-10 CF500 BCF809 CF60KK 3.00 2.75x45P 2 4 0 N/A 140 51311 4.375"
FDO-12 CF800 BCF403 CF60KH 4.00 3.50x45P 2 6 0 N/A 140 51311 4.375"
FDO-14 CF800 BCF403 CF60KH 4.50 4.00x45P 2 7 0 N/A 140 51311 4.375"
FDO-15 CF800 BCF403 CF60KH 5.00 4.50x45P 2 8 0 N/A 140 51311 4.375"
FDO-19 CF800 BCF403 CF60KJ 6.00 5.00x45P 3 10 3 N/A 140 51628 4.375"
FDO-24 CF1400 BCF205 CF66KD 7.50 4.50x45P 3 30 55 150 300 51629 4.375"
FDO-30 CF1400 BCF205 CF66KE 9.00 5.50x45P 1-1/2 45 75 150 300 51629 4.375"
FDO-38 CF2300A BCF304 CF66KG 12.00 7.00x45P 1 25 45 150 300 51313 4.375"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
FDO-45 CF2300A BCF304 CF66KG 13.80 8.00x45P 1-1/2 25 60 150 300 51313 4.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 5
Burnham Corporation
MPC
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
MPC-4 CF500 BCF809 CF66KK 3.55 02.75x70B D 3 10 2 N/A 150 0 4.25"
MPC-5 CF800 BCF403 CF60KH 5.50 04.50x70B D 3 8.5 0 N/A 150 0 4.25"
MPC- 6 CF1400 BCF205 CF66KD 7.10 04.25x60B D 4 43 48 150 250 0 4.25"
MPC-7 CF1400 BCB8302 CF66KE 7.80 05.00x45B D 6 45 51 150 300 0 4.25'
MPC-8 CF2300A BCF304 CF66KG 10.20 06.00x45B D 1 37 47 150 300 0 4.25"
MPC-9 CF2500A BCF304 CF66KG 11.20 07.00x45B D 7 39 47 150 300 0 4.25"
MPC-10 CF2300A BCF304 CG66KG 13.40 08.00x45B D 9 43 54 150 280 0 4.25"
MPC-11 CF2500A BCF3001 CF66KP 15.00 04.50x45P H 0 22 35 275 275 0 4.25"
MPC-12 CF2500A BCF3001 CF66KP 16.60 05.00x45P H 2 23 41 300 300 0 4.25"
MPC-13 CF2500A BCF3001 CF66KP 18.20 05.50x45P H 5 24 38 300 300 0 4.25"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
MPC-14 CF2500A BCF3001 CF66KP 19.20 06.00x45P D 6 26 43 275 275 0 4.25"
MPC-15 CF2500 BCF1801 CF66KP 21.50 06.50x45P H 9 25 40 275 275 0 4.25"
MPC-16 CF3500A BCF1301 CF144KR 23.00 07.00x45P H 7 29 42 275 275 0 5.125"
MPC-17 CF3500A BCF1301 CF114KR 24.50 07.50x45P H 8 30 51 275 300 0 5.125"
MPC-18 CF3500A BCF1301 CF114KR 26.00 07.00x45P H 7 29 42 275 275 0 5.125"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 6
Burnham Corporation
PF-5
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
504 CF800 BCF403 CF60KH 5.45 4.50x45P 2-1/2 5 10 N/A 140 51628 3.00"
505 CF1400 BCF205 CF66KD 6.80 3.50x45P 3 25 50 150 300 51629 3.375"
506 CF1400 BCF205 CF66KD 8.30 4.50x45P 4 30 60 150 300 51629 3.375"
507 CF1400 BCF205 CF66KD 9.80 5.50x45P 5 35 70 150 300 51629 3.375"
508 CF2300A BCF304 CF66KG 11.20 6.00x45P 2 20 70 150 300 51630 3.375"
509 CF2300A BCF304 CF66KG 12.60 7.00x45P 2-1/2 20 85 150 300 51630 3.375"
510 CF2300A BCF304 CF66KG 14.00 8.00x45P 3 25 95 150 300 51630 3.375"
511 CF2300A BCF304 CF66KG 15.50 8.50x45P 4 25 100 150 300 51630 3.375"
512 CF2300A BCF304 CF66KG 17.00 9.50x45P 4 30 105 150 300 51630 3.375"
513 CF2500A BCF1801 CF66KP 18.40 5.00x60P (2) 3 23 35 300 300 51630 3.375"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
514 CF2500A BCF1801 CF66KP 19.50 5.50x60P (2) 4 25 40 300 300 51630 3.375"
515 CF2500 BCF1801 CF66KP 21.00 6.00x60P (2) 4-1/2 25 50 300 300 51630 3.375"
516 CF2500 BCF1801 CF66KP 22.50 6.50x60P (2) 5 25 50 300 300 51630 3.375"
517 CF3500A BCF1301 CF80KM 24.00 7.00x60PLP (2) 2 30 80 300 300 51630 4.25"
518 CF3500A BCF1301 CF80KM 25.50 7.50x60PLP (2) 3 32 95 280 280 51630 4.25"
519 CF3500A BCF1301 CF80KM 27.00 7.50x60PLP (2) 3-1/2 35 105 300 300 51630 4.25"
520 CF3500A BCF1301 CF114KR 28.50 8.00x60P (2) 4 37 95 300 300 51631 5.00"
521 CF3500A BCF1301 CF114KR 29.90 8.50x60P (2) 4 40 103 300 300 51631 5.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 7
Burnham Corporation
V11
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
V1104 CF1400 BCF205 CF66KD 5.80 3.50x45P 0 25 50 150 300 51629 4.12"
V1105 CF1400 BCF205 CF66KE 7.40 4.50x45P 0 30 50 150 300 51629 4.12"
V1106 CF1400 BCF205 CF66KE 9.20 5.50x45P 2 30 60 150 300 51629 4.12"
V1107 CF2300A BCF304 CF66KG 11.00 6.50x45P 2 30 60 150 300 51630 4.00"
V1108 CF2300A BCF304 CF66KG 13.00 7.50x45P 4 35 60 150 300 51630 4.12"
V1109 CF2300A BCF304 CF66KG 14.80 8.50x45P 4 35 75 150 300 51630 4.12"
V1110 CF2300A BCF304 CF66KS 16.60 9.50x45P 4 30 55 150 300 51630 4.12"
V1111 CF2300A BCF304 CF66KS 18.40 10.50x45P 6 40 60 150 300 51630 4.12"
V1112 CF2500A BCF1801 CF66KP 20.00 5.50x45P (2) 4 20 45 300 300 51630 4.12"
V1113 CF2500A BCF1801 CF66KP 21.50 6.00x45P (2) 5 22 55 300 300 51630 4.12"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
V1114 CF3500 BCF1301 CF80KM 23.50 6.50x45P (2) 2 25 80 300 300 51630 4.12"
V1115 CF3500A BCF1301 CF80KM 25.50 7.00x45P (2) 3 30 90 300 300 51630 4.12"
V1116 CF3500A BCF1301 CF114KR 27.00 7.50x45P (2) 6 32 85 300 300 51631 5.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 8
Burnham Corporation
V9
Series Boiler
Head
Setting
Blue -
Low Fire
Air or
Shutter
High
Boiler
V-903 CF500 BCF809 CF80KK 2.75 2.25x60P 2 10 5-1/2 N/A 140 51628 4.00"
V-904 CF500 BCF809 CF80KK 3.50 3.00x45P 3-1/2 10 5-1/2 N/A 140 51628 4.00"
V-905 CF800 BCF403 CF80KH 4.60 4.00x60P 4 10 5 N/A 140 51628 4.00"
V-906 CF800 BCF403 CF80KJ 5.80 5.00x60P 3 10 6 N/A 140 51628 4.00"
V-907 CF1400 BCF205 CF66KD 6.90 4.00x45P 3 35 60 125 300 51629 4.00"
V-908 CF1400 BCF205 CF66KE 8.00 4.50x45P 3 25 50 125 300 51629 4.00"
V-909 CF1400 BCF205 CF66KE 9.10 5.00x45P 3 30 55 125 300 51629 4.00"
V-910 CF1400 BCF205 CF66KE 10.20 5.50x45P 5-3/4 40 75 125 300 51629 4.00"
V-911 CF2300A BCF304 CF66KG 11.40 6.50x45P 1-1/2 38 45 125 300 51630 4.00"
V-912 CF2300A BCF304 CF66KG 12.60 7.00x45P 4 40 50 125 300 51630 4.00"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
Nozzle
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Blue -
Low Fire
Head
Setting
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Insertion
High
Fire Rate
V9A
Nozzle
Burnham Corporation
Boiler
V-903A CF500 BCF809 CF60KK 3.10 2.50x45P 2 10 3 N/A 150 51628 4.12"
V-904A CF800 BCF403 CF80KH 4.20 3.50x45P 1 8 0 N/A 150 51628 4.12"
V-905A CF800 BCF403 CF80KH 5.60 4.50x45P 2 10 6 N/A 150 51628 4.12"
V-906A CF1400 BCF205 CF66KD 7.00 4.00x60P 3 28 40 150 300 51629 4.12"
V-907A CF1400 BCF205 CF66KD 8.30 5.00x45P 4 30 65 150 275 51629 4.12"
V-908A CF1400 BCF205 CF66KEE 9.60 5.50x45P 1 35 85 150 300 51629 4.12"
V-909A CF2300A BCF304 CF66KG 11.60 7.00x45P 0 20 40 150 275 51630 4.12"
V-910A CF2300A BCF304 CF66KG 13.20 8.00x45P 1 20 60 150 275 51630 4.12"
Burner
Chassis
Spec.
Air Tube
Combination
V-911A CF2500A BCF1801 CF66KP 14.80 4.50x45P (2) 0 17 30 275 275 51630 4.12"
V-912A CF2500A BCF1801 CF66KP 16.40 5.00x45P (2) 0 20 40 275 275 51630 4.12"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 9
Columbia Boiler
CT
Series Boiler
Head
Setting
Head
Setting
Blue -
Low Fire
Air or
Shutter
Blue -
Low Fire
Air or
Shutter
High
Boiler
CT-20 CF800 BCF403 CF100KJ 6.00 5.00x60P 3 7 0 N/A 150 51628 4.75"
CT-25 CF1000 BCF101 CF66KD 7.50 4.50x60P 3 5 N/A N/A 275 51629 4.75"
CT-25 CF1400 BCF205 CF66KD 9.00 5.50x60P 3 30 50 150 300 51629 4.75"
CT-35 CF2300A BCF304 CF66KG 10.50 6.00x45P 3 30 50 150 300 51630 4.75"
CT-50 CF2300A BCF304 CF66KG 15.00 9.00x60P 3 30 50 150 300 51630 4.75"
Burner
Chassis
Spec.
Air Tube
Combination
Columbia Boiler
Boiler
CWH-780 CF800 BCF403 CF100KJ 6.00 5.00x60P 3 7 0 N/A 150 51628 4.75"
Burner
Chassis
Spec.
Air Tube
Combination
Fire Rate
High
Fire Rate
Nozzle
CWH
Nozzle
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Red -
High Fire
Air or
Band
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
Low Fire
Pump
Press.
High Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing Flange
Pressure
Firing Flange
Insertion
Insertion
CWH-1200 CF1000 BCF101 CF66KD 9.00 5.50x60P 3 5 N/A N/A 275 51629 4.75"
CWH-1200 CF1400 BCF205 CF66KD 9.00 5.50x60P 3 30 50 150 300 51629 4.75"
CWH-1510 CF2300A BCF304 CF66KG 12.00 7.00x45SS 3 30 50 150 300 51630 4.75"
CWH-1810 CF2300A BCF304 CF66KG 14.00 8.00x60P 3 30 50 150 300 51630 4.75"
CWH-2460 CF2300A BCF304 CF66KG 18.00 10.00x60P 3 30 50 150 300 51630 4.75"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 10