Control Replacement Cross-Reference Guide
Features & Benefi ts
Beckett HeatManagerTM dynamic temperature reset
Q
Energy saving through circulator-off delay
Q
Priority override for domestic hot water
Q
Freeze resistance
Q
2N1 self checking sensor w/ Low Water Cut-off
Q
Cycle history diagnostic information
Q
Backlit LCD screen with programming touch pad
Q
Reduce inventory through universal design
Q
Backlit LCD screen with programming touch pad
Q
Built-in power disconnect switch (optional)
Q
Oil and gas offerings available
Q
Cold-Start compatible
Q
Table 1 - Direct Replacements
Model 7600 Boiler Control
PARTS & ACCESSORIES
2N1 Sensor
Honeywell
L8124A (All) L8124C (All)
L7124A (All)
L7124C (All)
L7148A (All)
L7224A (All)
L8148A (All)
L8124E 1016 L8148E 1265
L8124M (All)
L8151A
Hydrolevel
3100 7600B
3150 7600A
Carlin
90524A 7600A
White Rodgers
11C15-11
11C30-3 11B54-4
8B48A-217
11C61-12
8F48A-351 8B43A-601 7600B
R.W. Beckett Corporation
Mail: P.O. Box 1289, Elyria, OH 44036 ● Phone: 800-OIL-BURN (800-645-2876) ● FAX: (440)327-1064
R.W. Beckett Canada Ltd.
Unit 3 - 430 Laird Road, Guelph, Ontario, Canada N1G 3X7 ● Phone: 800-665-6972 ● FAX: (519)763-5656
www.beckettcorp.com
L7224C (All)
L7224U (All)
L7248A (All)
L7248C (All)
Beckett Replacement Notes
7600A 7600 outputs are not rated for 240 VAC.
7600A
7600A
7600B
7600A
7600A
Beckett Replacement Notes
Beckett Replacement Notes
Beckett Replacement Notes
7600A
The 7600 has no Honeywell EnviraCOMTM Communications port. The diagnostic LED
lights are replaced by the 7600’s display.
7600 outputs are not rated for 240 VAC. B1 terminal on 7600 utilizes a 1/4” quick
connect. Set low limit on 7600 to OFF.
7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z,
respectively.
For replacement with the 7600: Turn low limit off so the circulator is controlled directly by
the thermostat and ZC is constantly powered.
7600 outputs are not rated for 240 VAC. Remote mount sensor cable needed (Part No.
52120)
Not a suitable replacement if Low Water Cutoff (LWCO) functionality is used.
Make sure 7600 outputs do not exceed 7.4A. Available operating limit and differential
ranges are not equivalent.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
Available operating limit and differential ranges may not be equivalent.
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
More on
Back
Table 2 - Functional Replacement (Advanced Wiring Needed)
Note: Available operating limit and/or differential ranges may not be equivalent. Compare settings to the AquaSmart ranges before replacing.
Honeywell
L4006A (All)
L4006G 1022
L4006H 1004
L4008A (All)
L4080B,D
L4006E (All)
L4008E (All)
L4080F,G
L6006A (All)
L6006C 1018
L6008A 1192
L6008A 1242
L8124B 1039
L8148J 1009
L7148F (All)
L8148E (All)
L4081A,B
L6081A,C
Beckett Replacement Notes
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation.
Set low limit on 7600 to OFF.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.
Requires the addition of a manual-reset high limit.
Make sure 7600 outputs do not exceed 7.4A @ 120VAC.
7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
7600A or 7600B
(Based on System
Voltage Requirements)
7600B
7600A or 7600B
(Based on System
Voltage Requirements)
Set low limit on 7600 to OFF.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation.
Set low limit on 7600 to OFF.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit. 7600 outputs are not rated for 240 VAC.
Must confi rm that 7600 VA rating is adequate to meet VA requirements of system.
Make sure 7600 B1 output does not exceed 1.25A @ 24VAC (30 VA).
7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z, respectively.
If damper is used, consult damper manufacturer’s wiring instructions for using damper without damper plug.
Remove switching relay, if used, from the system when replacing the L4081 or L6081
Make sure 7600 outputs do not exceed 7.4A@120VAC. 7600 outputs are not rated for 240 VAC.
Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Carlin
90200A
90000 (All)
90200E
90200EL
90300B
90200D
White Rodgers
11B06-1
11D18-1
11B18-101
11B30-104
11B02-1
1145-33
11B06-46
11B95-31
11B18-153
11D82-1
11D31-1
1131-102
1127-2
11A79-2
1127-9
11B27-9
Beckett Replacement Notes
Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.
7600A or 7600B
(Based on System
Voltage Requirements)
Beckett Replacement Notes
7600A or 7600B
(Based on System
Voltage Requirements)
Requires the addition of a manual-reset high limit. Make sure 7600 outputs do not exceed 7.4A.
Set low limit on 7600 to OFF.
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. Make sure 7600
outputs do not exceed 7.4A. Set low limit on 7600 to OFF.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an
additional wire (L2) for operation.
Set low limit on 7600 to OFF.
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. 7600 outputs are not
rated for 240 VAC.
7600 will require an additional wire (L2) for operation.
Set low limit on 7600 to OFF.
Requires the addition of a manual-reset high limit.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an
additional wire (L2) for operation.
Set low limit on 7600 to OFF.
Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
8J48A-209
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.
Form No. 61749 R01, Printed in the USA 11/09