AQUASMARTTM 2-IN-1 SENSOR (Temperature & Presence of Water)
Installation Instructions
Do not use in steam applications. For use in hot water boilers or water
heaters only. Do not use outside of the intended use and specifi cations.
PARTS:
(1) 76002N1SXX 2-IN-1 Sensor
(1) 32704 Pipe Clamp for sensor ground
(1) 3214771 36” Green Ground Wire
Explosion,
Burn and Scald Hazards
Excessive water temperatures could cause explosion,
burns, scalding, pressure relief fl ooding and fi tting leaks.
The 2-in-1 Sensor shall only be installed by a trained
y
professional.
The sensor must be installed in the proper location for
y
correct low water cut-off (LWCO) operation in
accordance with the Boiler Manufacturer’s instructions.
The 2-in-1 sensor body is installed directly into the
y
boiler wall tapped hole in place of an immersion well.
Carefully follow the outlined procedures for temperature
y
sensor installation to ensure accurate water temperature
sensing and effective control operation.
Make sure the plumbing for domestic hot water has anti-
y
scald valve protection.
Follow all applicable safety codes, rules and guidelines
y
for installing an immersion well. Improper installation can
result in the Boiler overheating.
Part # Lead Length
76002N1S01 8-1/4” 1-1/2” 1-5/8”
76002N1S02 6-1/4” 3-1/2” 1-5/8”
76002N1S05 5.0” 4-3/4” 1-5/8”
76002N1S06 8-1/4” 1-1/2” 7/8”
Insulation Depth
(A)
Insertion Depth
(B)
Technical Specifi cations
Storage Temp. Range:
Operating Temp. Range:
Maximum Pressure:
Installation(screw-in)Torque Range:
-40°F to 250°F
32°F to 250°F
250 PSIG
185-200 in/lbs
Leak, Burn, and Scald
Hazards
Incompatible thread sealants could severely damage
the sensor threads.
Only use Tefl on®
y
DO NOT use any anaerobic fast-setting sealants such
y
as, but not limited to, Loctite®, Leak Lock®,
Permatex®, or Gasoila®.
Call RWB Technical Services at 1(800)645-2876 to
y
confi rm, if unsure.
Tape or Rectroseal® No. 5® (soft-set).
For proper operation, there must be
a secure electrical bond between
the green sensor wire from the sensor and the boiler
metal vessel in direct contact with the boiler water.
Failure to secure an electrical bond will result in the
AquaSmart locking out and displaying, “LOCKOUT
- LOW WATER”.
Installation Instructions on back.
INSTRUCTIONS:
Installing the 2-in-1 Sensor
This is very important for successful control operation.
Remove the existing immersion well. Clean the threads in the
1.
boiler port tapping. Follow all applicable safety codes, rules
and guidelines for removing/installing immersion wells.
Apply pipe sealant to the 2-in-1 sensor threads and install
2.
it securely into the port. BECKETT RECOMMENDS ONLY
TO USE TEFLON TAPE OR RECTROSEAL NO. 5 PIPE
SEALANT.
Tighten with 1-1/8” open end or box wrench. Pipe
3.
wrenches, pliers, and adjustable wrenches will damage/
round-off the hex.
Securely install the AquaSmart control to the sensor. Plug
4.
the 2-in-1 Sensor RJ connector (phone jack style) into the
receptacle (Item a, Figure 1) on the control.
Route the 36” green wire through the AquaSmart bottom
5.
rectangular slot (Item c, Figure 1). Securely install the
fork connector of the 36” ground wire and the ground
wire from the 2-in-1 sensor under the ground screw at the
bottom of the control (Item b, Figure 1).
Thoroughly clean the pipe surface and securely tighten
6.
the pipe clamp on the water inlet pipe to the boiler as close
to the boiler as possible.
Route the 36” green ground wire to the pipe clamp then
7.
cut to proper length, if necessary.
Strip the wire and insert the stripped end into hole on the
8.
pipe clamp (item d, Figure 3). Tighten retaining screw
against the wire making sure that you have good contact.
Complete control wiring and fi ll the appliance with
9.
water to the pressure required, according to appliance
manufacturer’s instructions. Make sure all air is purged
from the system and there are no leaks. Turn on power
to the appliance and observe one call for heat cycle with
shut off at set temperature.
Test the Low Water Cut-off (LWCO) Safety Function
WARNING! Avoid touching or shorting the live
terminals during this test.
Turn electric power ON to energize AquaSmart control.
Perform the following tests to verify the LWCO function.
For AquaSmart 7600A: Remove the green sensor
•
lead from the ground screw. The sensor should cause
the AquaSmart display to indicate, “LOCKOUT – LOW
WATER”. If it does not, replace the sensor.
For AquaSmart 7600B:
•
from the ground screw and remove both the B1 and B2 (24
Vac) leads from their terminals. The sensor should cause
the AquaSmart display to indicate, “LOCKOUT – LOW
WATER”. If it does not, replace the sensor.
Attach wires and tighten terminal screws securely when
•
testing is complete.
Remove the green sensor lead
Figure 1 - Sensor lead connection & ground screw connections
a
c
b
Figure 3 - Ground Clamp and Grounding Wire
d
Figure 2 - Sensor Water Detection Method
AquaSmart
Boiler Control
2-IN-1 SENSOR
Ground Screw
Ground Wire
Pipe Clamp
Water Inlet
The AquaSmart 2-in-1 Sensor uses the “conduction” method to
detect whether water is present in the boiler. This is done by using
the water in the boiler itself to “conduct” a signal and complete
an electrical circuit. It is necessary that the ground wire from the
sensor be bonded to the boiler wall (not the jacket - unless the
jacket is bonded to the boiler wall). When water is not present,
there is no “conduction” and the circuit is incomplete.
For the AquaSmart we recommend that a grounding pipe clamp be
mounted to the water inlet pipe, and that a ground wire be bonded
from the pipe clamp to the green terminal inside the AquaSmart
control. The 2-in-1 sensor green “ground wire” shall also be
bonded to the green terminal in the AquaSmart control.
Water Not Present
Incomplete
Circuit
Water Present
Complete
Circuit