INSTRUCTION MANUAL
FOR
VOLTAGE REGULATOR
Model: VR63-4/UL
Publication:
© 1998, Basler Electric Co., Highland, IL 62249
Revision: J September 1998
ECO: 143
9 1668 00 994
First Printing March 1984
BASLER ELECTRIC, BOX 269, HIGHLAND, IL 62249 PHONE 618/654-2341 FAX 618/654-2351
INTRODUCTION
The VR63-4/UL Voltage Regulators are
designed for use on 50/60 Hz brushless
generators. The regulator includes frequency
compensation, overexcitation shutdown, a
solid-state build-up circuit, and EMI filtering.
WARNING
To prevent personal injury or equipment
damage, only qualified technicians or
operators should install, operate, or
service this device.
ELECTRICAL SPECIFICATIONS
Dc Output Power:
4 Adc at 63 Vdc (252W) maximum continuous,
7 Adc at 100 Vdc (700W) forcing one minute
(at 240 Vac input).
Exciter Field Dc Resistance:
15 ohms minimum; 100 ohms maximum.
Ac Power Input:
Operating range: 190 Vac to 240 Vac, +
10%
Single phase, 50/60 Hz, Burden 500 VA.
Sensing Input:
190-240 Vac, Single phase, 50/60 Hz +
10%,
common with AC Power Input.
Voltage Adjust Range:
171-264 Vac.
Regulation Accuracy:
Better than ±1.0% no load to full load.
Response Time:
Less than 1.5 cycles for +
10% change in
sensing voltage.
EMI Suppression:
Internal electromagnetic interference filter
(EMI filter).
Overexcitation Shutdown:
Output power is removed under the following
conditions: Exciter field voltage exceeds
100+
5 Vdc for a time inversely proportional to
voltage magnitude, or instantaneously if the
exciter field voltage exceeds 135+
5 Vdc.
Voltage Build-up:
Internal provisions for automatic voltage buildup from generator residual voltages as low as
10 Vac.
Power Dissipation:
8 Watts maximum.
PHYSICAL SPECIFICATIONS
Operating Temperature:
-40 C (-40 F) to +60 C (+140 F).
Storage Temperature:
-65 C (-85 F) to +85 C (+185 F).
Vibration:
Withstands 1.3 Gs at 2 to 27 Hz; 0.036"
double amplitude at 27 to 52 Hz; and 5 Gs at
52 to 1000 Hz.
Shock:
Withstands up to 20 Gs in each of three
mutually perpendicular axes.
Weight:
14 oz. (0.40 kg) Net.
CSA Approved/UL Recognized
FUSES
It is recommended that fuses with high
interruption capability be installed per the interconnection diagram to protect wiring from
faults before the regulator. Refer to the
Interconnection Drawings.
NOTE
Fuse must be installed per the
interconnection diagrams to avoid interrupting the field current.
MOUNTING
The regulator may be mounted in any position.
Refer to the drilling diagrams.
Drilling Diagram
EXCITER FIELD POWER CIRCUIT (wires F+
and F-).
Connect the regulator wire F+ to the brushless
exciter field terminal F+, and wire F- to
terminal F-.
CAUTION
The dc resistance of the exciter field must
be equal to or greater than 15 ohms and
less than 100 ohms.
POWER/SENSING INPUT CIRCUIT (wires 3
and 4)
Connect as shown by the Interconnection
Diagrams.
Power for the exciter field and regulator
circuitry is derived from the generator output or
auxiliary winding. The operable power input
range is 171 to 264 Vac and is connected to
Terminals 3 and 4.
FREQUENCY COMPENSATION
The frequency compensation characteristic is
to improve system load pickup performance by
restraining voltage recovery until frequency
has also started to recover.
For 50 Hz system, the regulator is preset at
the factory for a 45 Hz “corner frequency”.
For 60 Hz systems, a 55 Hz “corner
frequency”. is achieved by cutting the external
Hz jumper wires on the generator. Be sure to
insulate the the two wires so that they are not
exposed.
Frequency Compensation Curves
OVEREXCITATION SHUTDOWN
If the exciter field voltage exceeds 100 ±5 Vdc,
the regulator automatically removes the field
current after a time delay. The time delay is
inversely proportional to the magnitude of the
detected overvoltage condition up to the 135
Vdc point. Beyond 140 Vdc, the field voltage
is removed within 0.2 seconds.
After shutdown, reset the regulator by
decreasing voltage below 6 Vac either by
stopping the prime mover or interrupting the
regulator input with a reset switch for 2
seconds or more.
Typical Time Delay Characteristic Curves
VOLTAGE ADJUST RHEOSTAT
Screwdriver adjustable potentiometer adjusts
generator output voltage. Adjustment CW
increases voltage.
When using remote voltage adjust rheostat
(VAR), the VAR wire on the regulator should
be cut and the rheostat connected to both
ends. A 1 kohm and 1/2 watt resistance is
adequate for most applications. See
Interconnection Diagrams.
OPERATION
The following system operation procedures
provide instructions for adjusting the VR634/UL Voltage Regulator.
CAUTION
Meggers and high potential test
equipment must not be used. Incorrect
use of such equipment could damage the
semiconductors contained in the
regulator.
PRELIMINARY SET-UP
To prevent damage to the regulator, complete
the following steps before proceeding with
system start-up.
a. Verify that the voltage regulator
specification conforms with the generator
system requirements.
b. Ensure that the regulator is correctly
connected to the generator. See
Interconnection Diagram.
c. Install fuses per FUSES paragraph.
d. Set the regulator VAR fully CCW and the
remoteVAR (if used) to centered.
SYSTEM START-UP
a. Start the prime mover and bring up to
rated speed. Voltage should buildup. If a
minimum residual of 6 Vac is not present,
perform field flashing.
b. Slowly adjust VAR CW until voltage
reaches nominal value. If used, adjust
remote voltage adjust to set generator
output to exact value desired.
OPERATIONAL TEST
a. Connect the test setup as shown in
Operational Test. Do not apply power.
Ensure that light bulbs are rated for 120
V and less than 100 W.
b. Adjust regulator VAR and/or remote VAR
to maximum CCW.
c. Apply 240V, 60 Hz power to regulator.
d. Slowly adjust the regulator VAR control
CW.
RESULT:
1) Before minimum brilliance is reached, the
light bulb should attain maximum brilliance to
signify the regulating point.
2) At the regulating point, a small change in
the VAR should turn the light bulb on or off.
FIELD FLASHING
When the regulator is operated with the
generator for the first time, the polarity of
residual magnetism may not correct or the
magnitude not enough. If the generator does
not build-up after startup, shut down the prime
mover and proceed with the following steps:
a. With the prime mover at rest, apply a dc
source (not grounded) of not more than
12V, to terminals F+(positive) and F-
(negative) in series with a limiting resistor
of 3-5 ohms.
b. Allow approximately 3 seconds before
removing the dc source.
c. Start prime mover and measure voltage
at regulator leads 3 and 4. If voltage is
greater than 6 volts, voltage build-up
should be successful. Repeat field
flashing procedure if less than 6 V
residual is measured.
d. If repeating steps 1 and 2 does not result
in generator voltage build-up, replace the
voltage regulator.
Operational Test
Interconnection Diagram, 208-240 V Nominal