Basler Electric VR63-4B User Manual

CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
INSTRUCTION MANUAL
FOR
VOLTAGE REGULATOR
Model: VR63-4B
Publication:
9 1668 00 996
© 1998, Basler Electric Co., Highland, IL 62249
First Printing August 1988 Revision: C January 1998 ECA: 16515
BASLER ELECTRIC, BOX 269, HIGHLAND, IL 62249 PHONE 618/654-2341 FAX 618/654-2351
WARNING
To prevent personal injury or equipment damage, only qualified technicians or operators should install, operate, or service this devi ce.
ELECTRICAL SPECIFICATIONS Dc Output Power:
Exciter Field Dc Resistance:
15 ohms minimum; 100 ohms m aximum.
Ac Power Input:
Operating range: 190 Vac to 240 Vac , +10%, Single phase, 50/60 Hz +5%, Burden 500 VA.
Voltage Adjust Range:
171-264 Vac.
Regulation Accuracy:
Better than ±1.0% no load to ful l l oad.
Response Time:
Less than 1.5 cycles for +10% change in sensing voltage.
EMI Suppression:
Internal electromagnetic interference filter (EMI filter).
Overexcitation Shutdown:
Output power is removed under the foll owi ng conditions: Exc i ter field voltage exceeds 100+5 Vdc for a time inversel y proportional to voltage magnitude, or inst ant aneously if the exciter field volt age exceeds 135+5 Vdc.
Voltage Build-up:
Internal provisions for aut omatic vol tage buil d­up from generator residual voltages as low as 10 Vac.
Power Dissipation:
8 Watts maximum.
PHYSICAL SPECIFICATIONS Operating Temperature:
-40° C (-40° F) to +60° C (+140° F).
Storage Temperature:
-65° C (-85° F) to +85° C (+185° F).
CSA Approved FUSES
It is recommended that fuses with high interruption capability be installed per the interconnection diagram to prot ect wiring from faults before the regulator. Refer to the Interconnection Diagram.
NOTE
Fuse must be installed per the interconnection diagrams t o avoid inter­rupting the field current.
MOUNTING
The regulator may be mounted in any position. Refer to the drilling diagrams.
Drilling Diagram
EXCITER FIELD P OWER CIRCUIT (wires F+ and F-).
Connect the regulator wire F+ to the brushl ess exciter field terminal F+, and wi re F- to terminal F-.
CAUTION
The dc resistance of the exciter field must be equal to or greater than 15 ohm s and less than 100 ohms.
POWER/SENSING INP UT CIRCUIT (wires 3 and 4)
Connect as shown by the Interconnection Diagram.
UNDERFREQUENCY CHARACTERIS T IC POINT
For 50 Hz systems, connect the Hz leads. For 60 Hz systems, disconnect the Hz leads. See curves the following figure.
Frequency Compensation Curves
OVEREXCITATION SHUT DOWN
This circuit removes the output power if the exciter field volt age exceeds 100 ±5 Vdc aft er a time delay. If the v oltage exceeds, 135 +5 Vdc, the output power is removed instantaneously.
After shutdown, reset the regulator by decreasing voltage below 6 Vac either by stopping the prime mover or interrupting the regulator input with a reset switch for 2 seconds or more.
VOLTAGE ADJUST
Screwdriver adjustable potentiometer adjusts generator output voltage. Adjustment CW increases voltage.
STABILITY ADJUST
Screwdriver adjustable (on non-label side) potentiometer adjusts the stability and response of the generator output voltage. Adjustment CW increases the stability.
NOTE: Excessive CCW rotation of this adjustment may result in osc illations (hunting) of the generator output voltage.
OPERATION
The following system operation procedures provide instructions f or adjusting t he VR63-4B Voltage Regulator.
CAUTION
Meggers and high potential test equipment must not be used. Incorrect use of such equipment could dam age the semiconductors contained in the regulator.
PRELIMINARY SE T -UP
To prevent damage to the regulat or, compl ete the following steps before proceeding with system start-up.
a. Verify that the voltage regulator
specification conform s with the generator system requirements.
b. Ensure that the regulator is correctly
connected to the generator. See
Interconnection Diagram. c. Install fuses per FUSES paragraph. d. Set the regulator voltage control fully
CCW and the Stability Potentiometer to
mid-range.
SYSTEM START-UP
a. Start the prime mover and bring up to
rated speed. Voltage should buildup. If a
minimum residual of 10V is not present,
perform field flashing. b. Slowly adjust volt age cont rol until voltage
reaches nominal value.
OPERATIONAL TEST
a. Connect the test setup as shown in
Operational Test. Do not apply power.
b. Adjust regulator voltage adjust to
maximum CCW. c. Apply 240V, 60 Hz power to regulator. RESULT: Light bulb flashes momentaril y. d. Slowly adjust the regulat or voltage adjsut
CW.
RESULT:
1) Before the full CW position i s reached, the light bulb reaches full brilliance to signify the regulating point.
2) At the regulating point, a small change in the voltage adjust should t urn the light bul b on or off.
FIELD FLASHING
When the regulator is operated with the generator for the first time, the polarity of residual magnetism may not correct or the magnitude not enough. If the generator does
not build-up after startup, shut down the prime mover and proceed with the followi ng steps:
a. With the prime mover at rest , apply a dc
source (not grounded) of not more than 12V, to terminals F+(positive) and F- (negative) in series with a limiting resistor of 3-5 ohms.
b. Allow approximately 3 seconds before
removing the dc source.
c. Start prime mover and measure voltage
at regulator leads 3 and 4. If volt age is greater than 10 volts, voltage build-up should be successful. Repeat field flashing procedure if less than 10 V residual is measured.
d. If repeating steps 1 and 2 does not result
in generator voltage build-up, replace the voltage regulator.
Interconnection Diagram, 208/240 V Nominal
Operational Test
Loading...