Basler Electric ICRM-7 User Manual

www.basler.com
info@basler.com
Model
ICRM-7, ICRM-15
9387900103, 9387900 104
Model
P/N
Compatible Products
ICRM-7
9387900103
DECS-100
DECS-200, DECS-250
Caution
+1 618.654.2341 (USA)

INTRODUCTION

The Inrush Current Reduction Module (ICRM) prevents damage to a protected voltage regulator during power-up by limiting inrush current to a safe level. Without inrush protection, the inrush current is limited only by the level of the power source impedance. The lower the impedance, the greater the risk of damaging the regulator from excessive inrush current. Devices with a pulse-width modulated (PWM) power stage are especially vulnerable to high inrush current due to a large amount of capacitance inherent to the design. However, voltage regulators that use SCR-type power stages do not require the protection of an ICRM since these regulators do not have a large amount of capacitance in the power stage.
When a voltage regulator with a PWM power stage is energized, the ICRM limits the inrush current by adding a high level of resistance in series with the voltage regulator power input. Once the inrush current subsid es, the series resistance diminishes quickly to allow nominal, steady-state current flow.

APPLICATION

Applications where a voltage regulator is powered by a permanent magnet generator (PMG), auxiliary winding, or generator output (shunt fed), usually do not require the protection of an ICRM. These sources usually have a higher source impedance which inherently minimizes inrush current. Also, these sources are typically connected directly to the voltage regulator with no interposing relays, contactors, or switches. If this is the case, then no inrush occurs since the source voltage ramps up to its rated value.
However, if rated or near rated voltage is applied to the voltage regulator, then some amount of inrush current is expected and an ICRM should be considered. Typically, voltage regulators in these applications receive power from a station service bus that is switched by a relay or contactor. Applications where a PWM type voltage regulator is powered by a low-impedance source need an ICRM to minimize the amount of inrush current.
To summarize, if the voltage that powers the voltage regulator ramps up to nominal as the generator comes up to rated speed, then an ICRM is not needed. If this is not the case, an ICRM should be used. If you are unsure whether your application requires an ICRM, contact Basler Electric Technical Support Services for assistance.

ICRM Versions

Two versions of the ICRM are available. Each version is uniquely suited to protect a specific family of Basler Electric products. Table 1 lists each ICRM model, its part number, and the compatible products.
Publication
9387900990
Revision
C
Instructions
Table 1. ICRM Cross-Reference
ICRM-15 9387900104
If operating power is removed from an energized ICRM, a minimum interval of five minutes should elapse before operating power is restored. This cool-down interval allows the ICRM to regain its ability to limit inrush current.
AVC63-12, AVC125-10,

SPECIFICATIONS

The following electrical and physical specifications, type tests, and certifications apply to the ICRM.

Electrical Specifications

Input Voltage: 90 to 277 Vac, 90 to 300 Vdc Input Frequency: dc, 50 to 420 Hz Input Current ICRM-7: 9 Aac ICRM-15: 18 Aac Power Dissipation: 25 W

Physical Specifications

Temperature Operating: –25 to 70°C (–13 to 158°F) Storage: –40 to 70°C (–40 to 158°F) Dimensions: Refer to Figure 1 Weight: 227 g (8 oz)

Type Tests

Dielectric

Withstands 2,000 Vac for one minute in accordance with IEC 60255-5

Shock

Withstands 15 G in three perpendicular planes in accordance with IEC 60255-21-1

Vibration

Tested in accordance with IEC 60255-21-2. Withstands 2 G in each of three mutually perpendicular axes, swept over the range of 10 to 500 Hz for a total of six sweeps, 15 minutes each sweep.

Humidity

Qualified to IEC 68-1, IEC 68-2-28

Certifications

UL Recognition

cURus recognition per UL Standard 508 and CSA Standard C22.2 No. 14
Date
03/15
Copyright
2015
For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at www.basler.com/terms.

CE Qualification

Caution
ICRM Output Terminals
A-OUT
B-OUT
C-OUT
AVC63-12, AVC125-10
26
28
30
DECS-100
3 4 5
DECS-200
C2
C3
C4
DECS-250
87
88
89
This product meets or exceeds the standards required for distribution in the Eur ope an co m m unity.

EAC Mark (Eurasian Conformity)

TP TC 004/2011
TP TC 020/2011

INSTALLATION

The ICRM may be installed in any environment where the conditions do not exceed the capabilitie s liste d in the Specifications section.

Mounting

For maximum cooling, the ICRM should be mounted on a vertical surface and oriented so that the ventilation holes are located at the top and bottom of the unit.
Case may become hot during operation.
Figure 1 shows the ICRM mounting dimensions. Mounting dimensions are identical for both ICRM models. Dimensions are shown in inches with millimeters in parenthesis.

Connections

Figure 2 illustrates typical connections for an application using single-phase operating power. The ICRM is not phase sensitive. Figure 3 illustrates typical connections for an application using three-phase operating power.
Table 2 lists the terminal connections for each voltage regulator that is compatible with the ICRM.
Table 2. ICRM Terminals Cross-Reference
Wiring requirements are subject to the specifications of the voltage regulator. Refer to the appropriate device instruction manual for wire sizing, fuse recommendations, and terminal designations.

TROUBLESHOOTING

The ICRM contains no serviceable component s. Replacement of the ICRM is recommended in the event of a failure.
If the protected device is not receiving operating power, check the following:
Verify that the ICRM connections between the power
source and voltage regulator are correct.
Confirm that the voltage supplied by the power source
is sufficient to energize the voltage regulator.
If operating power is applied to the input terminals of the ICRM but voltage is not present at the output terminals, remove operating power, disconnect all ICRM wiring, and perform the following procedure:
1. Connect a suitable ohmmeter across the A-IN and
A-OUT terminals. The resistance measured across the IN and OUT terminals should be approximately 2 Ω for the ICRM-7 and 0.5 for the ICRM-15. If an open circuit or short circuit is detected, the ICRM should be replaced.
2. Repeat step 1 for the B-IN and B-OUT pair of terminals
and the C-IN and C-OUT pair of terminals.
Voltage Regulator
Publication
9387900990
Revision
C
Instructions
Date
03/15
Page
2 of 4