
INTRODUCTION
BE3 dc millivolt sensing relays provide voltage monitoring
and protection for any application where dc voltage levels
are critical. A common application is overcurrent protection
for dc charging systems. Millivolt input signals from shunts,
sensors, or transducers can provide the input signals.
Undervoltage, overvoltag e, and combi ned ov er/un der v olt age
units are available. A time delay control provides an
adjustment of 0 to 10 seconds (operating time is typically
200 ms). This time delay may be used to prevent false
tripping when there are slight variations in the input signal.
BE3 dc millivolt sensing relays operate when the adjustable
trip point is reached. On overvoltage units, the output relay
energizes when the input signal exceeds the trip point. On
undervoltage units, the output relay de-energizes when the
input signal falls below the trip point. A red LED indicates
the state of the relay. A green LED indicates the condition of
the power supply.
SPECIFICATIONS
Operating Power
All units require external operating power.
Nominal Voltage: 120 Vac, 240 Vac, 380 Vac, 480
Frequency: 45 to 65 Hz
Impedance: 100 Ω max
Overload: 10 times nominal continuously
Burden
Vac: 2 VA
Vdc: <3 W
Sensing Input
Nominal Voltage: 50 mVdc, 100 mVdc, and 10 to
Impedance: 50 kΩ
Setpoint
Undervoltage Range: Adjustable 0 to 80% (±3%) of
Overvoltage Range: Adjustable 40 to 120% (±3%) of
Time Delay: Adjustable 0 to 10 s
Repeatability: Greater than 0.5% of full span
Differential: Fixed at 5% of nominal
Operating Time: 200 ms typical
Output
Relay Type: D.P.D.T.
AC Rating: 250 V, 5 A, non-resistive,
DC Rating: 125 V, 1 A, resistive, 120 W
Mechanical Life: 5 million operations
Publication
9320800990
+1 618.654.2341 (USA)
Vac, or 24 Vdc
99 mVdc (specify nominal range)
nominal
nominal
1200 VA
Revision
C
Instructions
Model
BE3-74SH, BE3-74SL,
and BE3-74SD
Temperature
Operating Temperature: 0°C (32°F) to 60°C (140°F)
Functional Temperature: –25°C (–13°F) to 70°C (158°F)
Storage Temperature: –40°C (–40°F) to 70°C (158°F)
Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity: 95% non-condensing
Physical
Mounting: DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)
Case: Complies with IEC 529, DIN
40050, BS 5490
Case Material: Complies with UL 94VO
Weight
Single Unit: 0.88 lb (0.4 kg)
Combined Unit: 1.32 lb (0.6 kg)
Size
Single Unit: 2.17” wide (55 mm)
Combined Unit: 3.93” wide (100 mm)
Agency
cULus listed to UL 508 and CSA C22.2 No. 14
CE compliant
GOST-R certified per the relevant standards of Gosstandart
of Russia
OPERATION
BE3-74SH and BE3-74SL dc millivolt sensing relays have
two user-adjustable controls marked SET and DELAY. The
BE3-74SD has four controls: UNDER SET, UNDER DELAY,
OVER SET, and OVER DELAY. The SET control adjusts
the relay trip point. An overvoltage trip causes the relay
output to energize when the voltage rises above the SET
threshold. The overvoltage SET level is adjustable from 40
to 120% (±3%) of nominal input (V
causes the relay output to de-energize when the voltage
decreases below the SET threshold. The undervoltage SET
level is adjustable from 0 to 80% (±3%) of nominal input.
The time delay is the amount of time that elapses after the
trip point is reached and when the output relay operates.
Setting Example
A BE3-74SH relay with a nominal input rating of 100 mVdc
has the following settings:
• SET - 80%
• DELAY - 4 s
A trip occurs when the sensing voltage rises above 80 mVdc
and 4 seconds elapse. Reset occurs when the voltage
decreases below 75 mVdc (5% of nominal below the
setpoint).
). An undervoltage trip
nom
Date
03/14
Copyright
2014

INSTALLATION
BE3 dc millivolt sensing relays are designed for mounting on
standard DIN rails that comply to DIN-EN 50022. Mounting
involves hooking the top edge of the cutout on the base of
the case over one edge of the DIN rail. The opposite side of
the cutout containing the release clip is then pushed over
the opposite side of the DIN rail. To remove or reposition the
relay, lever the release clip and move the relay as required.
BE3 relays should be installed in a dry, vibration-free
location where the ambient temperature does not exceed
the operating temperature range. Connections to the relay
should be made using wire that meets applicable codes and
is properly sized for the application. Figure 1 shows the
input connections for the BE3-74SH, BE3-74SL, and BE374SD relays.
CALIBRATION
The calibration marks on the faceplate have a maximum
error of 10% and are provided only as guides. Proper
calibration requires using an accurate millivolt meter in
parallel with the input signal. Use the following procedure to
calibrate your relay.
Overvoltage
1. Adjust the SET control fully clockwise and the delay
control fully counterclockwise.
2. Apply the desired trip voltage to the relay.
3. Slowly (allow for the 200 ms operating time) adjust the
SET control counterclockwise until the relay trips .
4. Remove the applied voltage (do not change the voltage
level) and set the DELAY control to the desired time
delay.
FIGURES
5. Apply the trip voltage to the relay and measure the time
to trip.
6. Adjust the DELAY and repeat Steps 4 and 5 until you
have the desired time delay.
Undervoltage
1. Adjust the SET and DELAY controls fully
counterclockwise.
2. Decrease the applied sensing voltage from the nominal
value until the desired tripping voltage is reac hed.
3. Slowly (allow for the 200 ms operating time) adjust the
SET control clockwise until the relay trips.
4. Set the DELAY control to the desired time delay and
apply nominal voltage to the relay.
5. Step down the applied voltage from nominal to a level
just below the trip level set in Step 3 and measure the
time delay.
6. Adjust the DELAY and repeat Steps 4 and 5 until the
desired time delay is achieved.
MAINTENANCE
BE3 relays are solid-state devices that require no
maintenance. In the event that your relay requires repair,
contact Basler Electric, Highland, IL, USA for return
authorization.
ORDERING INFORMATION
Figure 2 shows the BE3 relay style chart.
Publication
9320800990
Figure 1. BE3-74SH, BE3-74SL, and BE-74SD Input Connections
Figure 2. BE3-74SH, BE3-74SL, and BE3-74SD Style Number Identification Chart
Revision
C
Instructions
Date
03/14
Page
2 of 2