Basler Electric BE3-59V User Manual

www.basler.com
+1 618.654.2341 (USA)
info@basler.com
INTRODUCTION
SPECIFICATIONS
Inputs
All units obtain operating power from the voltage sensing input.
Nominal Voltage ................ 120 Vac
Overload Withstand ........... 1.25 times nominal continuously
2 times nominal for 3 s
Frequency ......................... 50/60 Hz
Burden ............................... <2.5 VA per phase on single
units
Setpoints
Overvoltage Range ........... Adjustable 0 to 110 Vac
Repeatability ..................... Better than 0.5% of full span
Reset ................................. Adjustable 1 to 15% of nominal
Operating Time ................. 200 ms typical
Outputs
Relay Type ........................ D.P.D.T.
AC Rating .......................... 250 V, 5 A, non-resistive,
1200 VA
DC Rating .......................... 125 V, 1 A, resistive, 120 W
Mechanical Life ................. 5 million operations
Temperature
Operating Temperature ..... 0°C (32°F) to 60°C (140°F)
Storage Temperature ........ –40°C (–40°F) to 70°C (158°F)
Temperature Coefficient .... 0.03% per °C (300 ppm/ °C)
Humidity
Relative Humidity .............. 95% non-condensing
Physical
Mounting ........................... DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)
Case .................................. Complies with IEC 529, DIN
40050, BS 5490
Case Material .................... Complies with UL 94VO
Weight ............................... 14 oz (400 g)
Size ................................... 2.17” wide (55 mm)
Model
BE3-59V
AGENCY COMPLIANCE
The BE3-59V complies with the following:
cULus Listed to UL 508 and CSA C22.2 No. 14
CE compliant
GOST-R certified per the relevant standards of
Gosstandart of Russia
OPERATION
BE3-59V ac voltage relays have two user-adjustable controls labeled SET and RESET. The SET control adjusts the relay trip point. When the monitored voltage exceeds the SET control setting (adjustable from 0 to 110 Vac) the output relay operates. The RESET control adjusts the difference between the trip voltage and the reset vo ltage. Reset occurs when voltage decreases below the RESET setting (adjustable from 1 to 15% of the nominal voltage). The RESET setting is set as the percentage below the trip voltage where the relay will reset.
Setting Example: a BE3-59V relay with a nominal input rating of 120 Vac has the following settings:
SET - 80 Vac
RESET - 5%
A trip occurs when the sensing voltage rises above 80 Vac. Reset occurs when the voltage decreases below 74 Vac (80 Vac – 6 Vac or 5% of the nominal voltage).
INSTALLATION
BE3 ac voltage relays are designed for mounting on standard DIN rails that comply to DIN-EN 50022. Mounting involves hooking the top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout containing the release clip is then pushed over the opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. BE3 relays should be installed in a dry, vibration-free location where the ambient temperature does not exceed the operating temperature range. Connections to the relay should be made using wire that meets applicable codes and is properly sized for the application. Figure 1 shows the connection terminals for the BE3-59V relay.
CALIBRATION
The calibration marks on the faceplate have a maximum error of 10% and are provided only as guides. Proper calibration requires using an accurate voltmeter in parallel with the input signal. Use the following procedure to calibrate your relay.
Overvoltage
1. Adjust the SET and RESET controls fully clock wise
(CW).
2. Apply the desired trip voltage to the relay.
3. Slowly (allow for the 200 ms operating time) adjust the
SET control CCW until the relay t rips.
4. Reduce the applied voltage to the desired reset level.
5. Slowly adjust the RESET control CCW until the relay
resets.
Publication
9319300990
Revision
C
Instructions
Date
04/14
Copyright
2014
MAINTENANCE
BE3 relays are solid-state devices that require no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland, IL, USA for return authorization.
FIGURES
ORDERING INFORMATION
Figure 2 shows the BE3 style number identification chart.
Figure 1. BE3-59V Connection Terminals (3-Phase/3-Wire)
Figure 2. BE3-59V Style Number Identification Chart
Publication
9319300990
Revision
C
Instructions
Date
04/14
Page
2 of 2
Loading...