Basler Electric BE3-59T-V User Manual

www.basler.com
+1 618.654.2341 (USA)
info@basler.com
INTRODUCTION
SPECIFICATIONS
Inputs
All units obtain operating power from the voltage sensing input. Nominal Voltage: 100 to 120 Vac Overload Withstand: 1.25 times nominal continuously.
2 times nominal for 3 s. Frequency: 50, 60, or 400 Hz Burden: <2.5 VA per phase on single units
Setpoints
Overvoltage Range: Adjustable 110 to 150 Vac Repeatability: Better than 0.5% of full span Time Delay: Adjustable 0 to 10 seconds Operating Time: 200 ms typical Differential: Fixed 1% of nominal
Outputs
Relay Type: D.P.D.T. AC Rating: 250 V, 5 A, non-resistive,
1200 VA DC Rating: 125 V, 1 A, resistive, 120 W Mechanical Life: 5 million operations
Temperature
Operating Temperature: 0°C (32°F) to 60°C (140°F) Storage Temperature: –40°C (–40°F) to 70°C (158°F) Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity: 95% non-condensing
Physical
Mounting: DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)
Case: Complies with IEC 529, DIN 40050,
BS 5490 Case Material: Complies with UL 94VO Weight: 14 oz (400 g) Size: 2.17” wide (55 mm)
AGENCY COMPLIANCE
cULus listed to UL 508 and CSA C22.2 No. 14 CE compliant GOST-R certified per the relevant standards of Gosstandart of
Russia
Model
BE3-59T-V
OPERATION
BE3-59T-V ac voltage relays have two user-adjustable controls labeled SET and DELAY. The SET control adjusts the relay trip point. The DELAY control adjusts the length of time required to operate the output relay after the trip point is exceeded. When the monitored voltage exceeds the SET control setting (adjustable from 110 to 150 Vac), the time delay (established by the DELAY control and adjustable from 0 to 10 seconds) begins timing down. If the overvoltage condition persists for the duration of the time delay, the output relay operates.
Setting Example: a BE3-59T-V relay with a nominal input rating of 130 Vac has the following settings:
SET - 130 Vac
DELAY - 4 seconds
A trip occurs when the sensing voltage rises above 130 Vac and 4 seconds elapses. Reset occurs when the voltage decreases below 1% of nominal below setpoint.
INSTALLATION
BE3 ac voltage relays are designed for mounting on standard DIN rails that comply to DIN-EN 50022. Mounting involves hooking the top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout containing the release clip is then pushed over the opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. BE3 relays should be installed in a dry, vibration-free location where the ambient temperature does not exceed the operating temperature range. Connections to the relay should be made using wire that meets applicable codes and is properly sized for the application. Figures 1, 2, and 3 show the connection terminals for the BE3-59T-V relay.
CALIBRATION
The calibration marks on the faceplate have a maximum error of 10% and are provided only as guides. Proper calibration requires using an accurate voltmeter in parallel with the input signal. Use the following procedure to calibrate your relay.
Overvoltage
1. Adjust the SET control fully clockwise (CW) and the DELAY
control fully counterclockwise (CCW).
2. Apply the desired trip voltage to the relay.
3. Slowly (allow for the 200 ms operating time) adjust the SET
control CCW until the relay trips.
4. Reduce the trip voltage from the relay and set the DELAY
control to the desired time delay.
5. Apply the trip voltage to the relay and measure the time to trip.
6. Adjust the DELAY and repeat Steps 4 and 5 until you have the
desired time delay.
MAINTENANCE
BE3 relays are solid-state devices that require no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland, IL, USA for return authorization.
ORDERING INFORMATION
Figure 4 shows the BE3 style number identification chart.
Publication
9319600990
Revision
C
Instructions
Date
04/14
Copyright
2014
FIGURES
L N
P0066-11
A B C
P0066-10
A B C
P0066-12
N
BE3-59T-V
A N 1
1) Single Phase
3) Three Phase Three Wire
4) Three Phase Four Wire
Sensing Input
Type
MODEL NO.
P0066-13
A) 100 - 120 Vac
Nominal Input Type
1
1) 50/60 Hz
2) 400 Hz
Frequency
N) Not required
External Power
1) Energize to trip (59T)
Output Type
1
Voltages are line-to-line.
Figure 1. BE3-59T-V Connection Terminals (Single Phase)
Figure 3. BE3-59T-V Connection Terminals (3-Phase/4-Wire)
Figure 2. BE3-59T-V Connection Terminals (3-Phase/3-Wire)
Figure 4. BE3-59T-V Style Number Identification Chart
Publication
9319600990
Revision
C
Instructions
Date
04/14
Page
2 of 2
Loading...