Basler Electric BE350 User Manual

Instructions
www.basler.com
+1 618.654.2341 (USA)
INTRODUCTION
The BE350 analog voltage controller regulates voltage on a 50 or 60 hertz brushless generator. Controller features include frequency compensation, solid-state buildup circuitry, and EMI filtering.
SPECIFICATIONS
Output Power
Maximum Continuous: 3.5 Adc at 73 Vdc (255 W) One-Minute Forcing: 5 Adc at 105 Vdc (525 W) with
240 Vac power input
Exciter Field DC Resistance
Minimum: 21 Ω
Input Power
Range: 190–240 Vac, ±10%, 1-phase Frequency: 50/60 Hz, ±10% Burden: 500 VA
Sensing Input
Common with ac power input: 190–240 Vac, single-phase, 50/60 Hz, ±10%
Fuse
Bussmann GDC-4A or equivalent Rating: 4 Aac, 250 Vac
Type: Glass tube, 5 x 20 mm, time
delayed
Voltage Adjustment Range
171 to 264 Vac
Regulation Accuracy
Better than ±1.0%, no-load to full-load
Response Time
Less than 1.5 cycles for ±5% change in sensing voltage
EMI Suppression
Internal electromagnetic interference (EMI) filtering
Voltage Buildup
Automatic voltage buildup occurs for residual generator voltages as low as 10 Vac.
Power Dissipation
8 W maximum
Temperature
Operating: –40 to 60°C (–40 to 140°F) Storage: –65 to 85°C (–85 to 185°F)
Vibration
2 to 27 Hz: 1.3 G 27 to 52 Hz: 0.914 mm, double-amplitude 52 to 1000 Hz: 5 G
Shock
Withstands up to 20 G in each of three mutually perpendicular axes.
info@basler.com
Model
Part Number
Weight
184 g (6.5 oz) net
Agency Certification
UL recognized and CSA certified
CONTROLS
BE350 controls consist of jumpers and screwdriver­adjusted potentiometers.
Potentiometer Controls
BE350 potentiometer controls are accessible through the controller front panel and are shown in Figure 1.
VOLT Control
This control raises and lowers the generator output voltage.
STAB Control
This control adjusts the stability by increasing and reducing the response time of the BE350.
U/F Control
This control adjusts the corner frequency point of the BE350 frequency compensation characteristic.
Jumpers
Two jumpers control BE350 operation: the Corner Frequency jumper and the Voltage Adjust Rheostat jumper. These jumpers are shown in Figure 2.
Corner Frequency Jumper
BE350 controllers are delivered with the Corner Frequency jumper set for 60 hertz operation. This gives a corner frequency of 55 hertz. For 50 hertz operation and a corner frequency of 45 hertz, the Corner Frequency jumper must be move to the 50 Hz terminal.
Voltage Adjust Rheostat Jumper
BE350 controllers are delivered with the Voltage Adjust Rheostat jumper connected across terminals 6 and 7. This enables adjustment of the generator output voltage through the controller’s internal Voltage Control potentiometer. Clockwise rotation of the Voltage Control potentiometer increases the generator voltage.
If remote adjustment of the generator output is desired, the Voltage Adjust Rheostat jumper must be replaced with a user-supplied rheostat. A 2000 ohm, ½ watt rheostat will provide adequate voltage adjustment for most applications. Figure 6 shows the proper remote rheostat connections.
INPUT POWER/SENSING INPUT
Power for the exciter field and BE350 is derived from the generator output. The acceptable power input range is 171 to 264 Vac. Connect the input power wiring to terminals 3 and 4 as shown in Figure 5.
EXCITER FIELD POWER CIRCUIT
Controller terminal F+ is connected to the brushless exciter field positive terminal and controller terminal F– is connected to the brushless exciter field negative terminal.
BE350
9166800143
Publication
9166800893
Revision
Date
-
Copyright
2010
Instructions
CAUTION
potential test equipment must
reading voltmeter for all voltage
The exciter field dc resistance must be no less than 21 ohms.
If the exciter field dc resistance is less than 21 ohms and the full-load field current does not exceed the maximum continuous current rating of the controller, a resistor of sufficient wattage must be added in series with the field to increase the total resistance to 21 ohms.
FREQUENCY COMPENSATION
The frequency compensation feature improves system load pickup performance by restraining voltage recovery until the frequency has also started to recover. Figure 3 illustrates the underfrequency characteristics of the BE350.
The corner frequency range is set for 50 hertz or 60 hertz by connecting the Corner Frequency jumper to the appropriate terminal. Refer to Controls, Jumpers for details about selecting the corner frequency range.
The corner frequency setting is adjusted by the Underfrequency control (potentiometer). Clockwise rotation of the Underfrequency control increases the corner frequency and counterclockwise rotation decreases the corner frequency. If user adjustment of the factory-set potentiometer is desired, follow the Preliminary Setup and System Startup procedures.
INSTALLATION
Mounting
The BE350 controller may be mounted on the generator in any convenient position. Figure 4 shows the mounting dimensions. Dimensions are shown in inches with millimeters in parenthesis.
The recommended mounting hardware is two #8 or M4 screws tightened to a torque of 9 inch-pounds (1 newton meter). Nylon-lined locking nuts are recommended when installing the controller with loose hardware.
Connections
BE350 controller terminals consist of quarter-inch, quick­connect tabs.
Figure 5 shows typical connections for the BE350 controller.
OPERATING PROCEDURES
The following procedures can be used when adjusting the BE350 controller. Symptoms caused by certain generator system problems or a faulty controller are included along with suggested remedies.
CAUTION
Meggers and high­not be used. Use of such equipment could damage the semiconductors contained in the controller.
Preliminary Setup
Complete the following steps before proceeding with system startup.
1. Verify that the BE350 specifications conform with the requirements of the generator system.
2. Ensure that the controller jumpers are positioned as follows.
a. If a remote voltage adjust rheostat will not be
used, ensure that the Voltage Adjust Rheostat jumper is connected across terminals 6 and 7.
b. If a 55 hertz corner frequency for a 60 hertz
system is desired, connect the Corner Frequency jumper to the 60 Hz terminal. If a 45 hertz corner frequency for a 50 hertz system is desired, connect the Corner Frequency jumper to the 50 Hz terminal.
3. Ensure that the connections between the generator system and the controller are correct.
4. Set the BE350 Voltage control fully counterclockwise and the remote voltage adjust rheostat (if used) to the center position.
5. Adjust the BE350 Stability control fully clockwise. This provides the most stability and the slowest response.
6. If user adjustment of the Underfrequency control is required, start with the potentiometer adjusted to the fully counterclockwise position. Then, slowly adjust the potentiometer clockwise to set.
System Startup
NOTE
Use an average­readings.
1. Perform the steps under Preliminary Setup.
2. Start the prime mover and bring it up to rated speed. Generator voltage should build up.
3. Slowly adjust the BE350 Voltage control (or remote voltage adjust rheostat) until the generator voltage reaches the nominal level.
If the voltage does not build up to the rated level, check the generator output for excessive load or a short-circuit.
4. Apply and remove the generator load to verify stability.
If the generator responds too slowly or hunts (oscillates), check the generator output for excessive load or a short-circuit. Adjust the controller’s Stability control with no load applied.
5. Check regulation under normal operating conditions. If the regulation is poor:
a. Verify that the prime mover is operating at rated
speed.
b. Verify that the voltmeter is connected to the same
point as the controller sensing.
c. Use an average-sensing voltmeter (not an rms-
sensing voltmeter).
Publication
9166800893
Revision
Date
-
Page
2 of 4
Loading...
+ 2 hidden pages