
www.basler.com
+1 618.654.2341 (USA)
INTRODUCTION
The BE300PM static voltage regulator regulates voltage on
a 50- or 60-Hz generator with a brushless exciter and a
permanent magnet generator (PMG) excitation system.
ELECTRICAL SPECIFICATIONS
Output Power
Maximum Continuous: 3 Adc at 63 Vdc (190 W)
One-Minute Forcing: 5 Adc at 100 Vdc (500 W) with
240 Vac power input
Exciter Field DC Resistance
Minimum: 15 Ω
Input Power
Range: 171 to 264 Vac, single-phase
Frequency: 250 to 300 Hz, ±10%
Burden: 500 VA
Sensing Input
Range: 171 to 264 Vac, single-phase
Frequency: 50 to 75 Hz
Fuse
Bussmann GDC-4A or equivalent
Rating: 4 Aac, 250 Vac
Type: Glass tube, 5 x 20 mm, time delay
Voltage Adjustment Range
171 to 264 Vac
Regulation Accuracy
Better than ±1.0%, no-load to full-load
EMI Suppression
Internal electromagnetic interference (EMI) filtering
Voltage Buildup
Automatic voltage buildup occurs for residual generator
voltages as low as 10 Vac.
Power Dissipation
8 W maximum
PHYSICAL SPECIFICATIONS
Temperature
Operating: –40 to 60°C (–40 to 140°F)
Storage: –40 to 85°C (–40 to 185°F)
Vibration
20 to 60 Hz with 0.035” displacement
1,000,000 cycles @ 30 Hz in all planes
Shock
Withstands 15 G in each of three perpendicular planes.
Moisture and Humidity
Tested per MIL-STD-705B, Method 711-1C
Salt Fog
Tested per ASTM B117-73
Weight
184 g (6.5 oz) net
Part Number
Terminal Type
¼ inch male quick connect with insulating barrier
Agency Certification
Standard CSA-C22.2 No. 0 and 14
File LR 23131
OVEREXCITATION PROTECTION
If the exciter field voltage exceeds 85 to 90 Vdc, the
BE300PM automatically removes field power after a time
delay. This delay is inversely proportional to the field
voltage.
When field power is removed due to overexcitation, the
BE300PM will not reset or return to operation until the
generator output is interrupted.
CONTROLS
BE300PM controls consist of jumpers and screwdriver
adjusted potentiometers.
Potentiometer Controls
BE300PM potentiometer controls are accessible through
the controller front panel and are shown in Figure 1.
VOLT Control
This control raises and lowers the generator output voltage.
STAB Control
This control adjusts the stability by increasing and
decreasing the response time of the BE300PM.
U/F Control
This control adjusts the corner frequency point of the
BE300PM frequency compensation characteristic.
Optional Remote Voltage Adjust Rheostat
If remote adjustment of the generator output is desired, the
Voltage Adjust Rheostat jumper must be replaced with a
user-supplied rheostat. A 2,000 ohm, ½ watt rheostat will
provide ±10% voltage adjustment. For ±5% voltage
adjustment, use a 1,000 ohm, ½ watt rheostat. Figure 2
shows the proper remote rheostat connections. Refer to
Operating Procedures for instructions on setting up the
remote rheostat.
Jumpers
Two jumpers control BE300PM operation: the Corner
Frequency jumper and the Voltage Adjust Rheostat jumper.
These jumpers are shown in Figure 3.
Corner Frequency Jumper
BE300PM controllers are delivered with the nominal corner
frequency preset to 58 hertz in the 60 hertz mode. For 50
hertz operation, and a nominal corner frequency of 48
hertz, the Corner Frequency jumper must be moved to the
50 Hz terminal.
Voltage Adjust Rheostat Jumper
BE300PM controllers are delivered with the Voltage Adjust
Rheostat jumper connected across terminals 6 and 7. This
enables adjustment of the generator output voltage through
Publication
9166800894
For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at www.basler.com/terms.
Revision
B
Instructions
Date
01/13
Copyright
2013

the controller’s internal Voltage Control potentiometer.
Clockwise rotation of the Voltage Control potentiometer
increases the generator voltage.
INPUT POWER
Power for the exciter field and BE300PM is derived from
the permanent magnet generator (PMG) output. The
acceptable power input range is 171 to 264 Vac. Connect
the PMG input power wiring to terminals 3 and E3/4.
Typical connections are shown in Figure 2.
SENSING INPUT
BE300PM sensing is derived from the generator output.
The acceptable input range is 171 to 264 Vac. Connect the
generator sensing wiring to terminals E1 and E3/4. Typical
connections are shown in Figure 2.
EXCITER FIELD POWER CIRCUIT
Controller terminal F+ is connected to the brushless exciter
field positive terminal and controller terminal F– is
connected to the brushless exciter field negative terminal.
The exciter field dc resistance must be no less than
15 ohms.
If the exciter field dc resistance is less than 15 ohms and
the full-load field current does not exceed the maximum
continuous current rating of the controller, a resistor of
sufficient wattage must be added in series with the field to
increase the total resistance to ≥ 15 ohms.
STABILITY ADJUST
The stability adjust potentiometer allows for tuning of the
regulator to optimize generator voltage settling time.
Achieving the desired voltage stability on larger machines
may not be possible with adjustment of the Stability Adjust
potentiometer alone. If this occurs, cutting both stability
circuit-selection jumpers (see Figure 4) will allow
adjustment to the desired stability.
FREQUENCY COMPENSATION
The frequency compensation feature improves system load
pickup performance by restraining voltage recovery until
the frequency has also started to recover. Figure 5
illustrates the underfrequency characteristics of the
BE300PM.
The corner frequency range is set for 50 hertz or 60 hertz
by connecting the Corner Frequency jumper to the
appropriate terminal. The adjustable range is 54 to 61 hertz
in 60 Hz operation and 45 to 51 hertz in 50 Hz operation.
Refer to Controls, Jumpers for details on selecting the
corner frequency range.
The corner frequency setting is adjusted by the
Underfrequency control (potentiometer). Clockwise rotation
of the Underfrequency control increases the corner
frequency and counterclockwise rotation decreases the
corner frequency. If user adjustment of the factory-set
Underfrequency potentiometer is desired, follow the
Preliminary Setup and System Startup procedures.
INSTALLATION
Mounting
The BE300PM controller may be mounted on the generator
in any convenient position. Figure 6 shows the mounting
dimensions. Dimensions are shown in inches with
millimeters in parenthesis.
The recommended mounting hardware is two #8 or M4
screws tightened to a torque of 9 inch-pounds (1 newton
meter). Nylon-lined locking nuts are recommended when
installing the controller with loose hardware.
Connections
BE300PM controller terminals consist of quarter-inch,
quick-connect tabs.
Figure 2 shows typical connections for the BE300PM
controller.
OPERATING PROCEDURES
The following procedures can be used when adjusting the
BE300PM controller. Symptoms caused by certain
generator system problems or a faulty controller are
included along with suggested remedies.
Meggers and high-potential test equipment must not be
used. Use of such equipment may damage the
semiconductors contained in the controller.
Preliminary Setup
Complete the following steps before proceeding with
system startup.
1. Verify that the BE300PM specifications conform to the
requirements of the generator system.
2. Ensure that the controller jumpers are positioned as
follows:
a. If a remote voltage adjust rheostat will not be
used, ensure that the Voltage Adjust Rheostat
jumper is connected across terminals 6 and 7.
b. If a 54 to 61 hertz corner frequency is desired,
connect the Corner Frequency jumper to the 60
Hz terminal. If a 45 to 51 hertz corner frequency is
desired, connect the Corner Frequency jumper to
the 50 Hz terminal. The corner frequency is finetuned in the System Startup procedure.
3. Ensure that the connections between the generator
system and the controller are correct.
4. Set the BE300PM Voltage control fully
counterclockwise and the remote voltage adjust
rheostat (if used) to the center position.
5. Adjust the BE300PM stability control fully clockwise.
This provides the most stability and the slowest
response.
6. If user adjustment of the Underfrequency control is
required, start with the potentiometer adjusted to the
fully counterclockwise position. Then, slowly adjust the
potentiometer clockwise to set.
Publication
9166800894
For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at www.basler.com/terms.
Revision
B
Instructions
Date
01/13
Page
2 of 4