LCD Display PID Temperature Controller
TX4S SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Please observe all safety considerations for safe and proper product operation to avoid hazards.
Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1.Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, fire, or economic loss.
2.The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock.
3.Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock.
4.Check the terminal numbers before connecting the power source.
Failure to follow this instruction may result in fire.
5.Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in electric shock or fire.
Caution
1. Do not use the unit outdoors.
Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock.
2.When connecting the power input and relay output cables, use AWG20 (0.05mm2) cables and make sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m.
Failure to follow this instruction may result in fire due to contact failure.
3.Use the unit within the rated specifications.
Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.
4. Do not use loads beyond the rated switching capacity of the relay contact.
Failure to follow this instruction may result in insulation failure, contact melt, contact failure, relay broken, or fire.
5.Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.
Failure to follow this instruction may result in electric shock or fire.
6.Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, vibration, or impact may be present.
Failure to follow this instruction may result in fire or explosion.
7.Keep dust and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
8.Check the polarity of the measurement input contact before wiring the temperature sensor.
Failure to follow this instruction may result in fire or explosion.
9.For installing the unit with reinforced insulation, use the power supply unit which basic level is ensured.
TX |
|
4 |
S |
|
|
1 |
4 |
R |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control output |
R |
Relay output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S |
SSR drive output |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
C |
Selectable current output or SSR drive output |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
100-240VAC 50/60Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
Alarm output 1 |
|
|
|
|
|
|
|
|
|
|
Option output |
2 |
Alarm output 1+Alarm output 2 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A |
Alarm output 1+Alarm output 2+Trans. output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B |
Alarm output 1+Alarm output 2+RS485 com. output |
|
|
|
|
|
|
Size |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
S |
DIN W48×H48mm |
|||
|
|
|
|
Digit |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Item |
|
|
|
|
|
|
|
|
4 |
9999(4 digit) |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TX |
LCD display standard PID temperature controller |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mount the unit on the panel. Push the bracket with tools to fix the unit as the figure.
The above specifications are subject to change and some models may be discontinued without notice.
Series |
|
|
TX4S |
Power supply |
100-240VAC 50/60Hz |
||
Allowable voltage range |
90 to 110% of rated voltage |
||
Power consumption |
Max. 8VA |
||
Display method |
11 segments (PV: white, SV: green), other display (yellow) with LCD method 1 |
||
Character |
|
PV(W×H) |
6.9×15.3mm |
size |
|
SV(W×H) |
4.1×9.2mm |
Input type |
|
RTD |
DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω) |
|
TC |
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) |
|
Display |
|
RTD |
●At room temperature (23 ±5 ): (PV ±0.3% or ±1 , select the higher one) ±1digit |
accuracy 2 |
TC |
●Out of room temperature: (PV ±0.5% or ±2 , select the higher one) ±1digit |
|
Control |
|
Relay |
250VAC 3A 1a |
|
SSR |
Max. 12VDC ± 2V 20mA |
|
output |
|
||
|
Current |
DC4-20mA or DC0-20mA (load resistance max. 500Ω) |
|
|
|
||
Option |
|
Alarm output |
AL1, AL2 Relay: 250VAC 3A 1a |
|
Trans. output |
DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.) |
|
output |
|
||
|
Com. output |
RS485 Communication output (Modbus RTU method) |
|
|
|
||
Control method |
ON/OFF control, P, PI, PD, PID control |
||
Hysteresis |
1 to 100 / (0.1 to 50.0 / ) variable |
||
Proportional band(P) |
0.1 to 999.9 / |
||
Integral time(I) |
0 to 9999 sec. |
||
Derivative time(D) |
0 to 9999 sec. |
||
Control period(T) |
0.5 to 120.0 sec. |
||
Manual reset |
0.0 to 100.0% |
||
Sampling period |
50ms |
||
Dielectric strength |
3,000VAC 50/60Hz for 1 min. (between all terminals and case) |
||
Vibration |
|
|
0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours |
Relay |
|
Mechanical |
OUT, AL1/2: Min. 5,000,000 operations |
life cycle |
|
Electrical |
OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load) |
Insulation |
resistance |
Min. 100MΩ (at 500VDC megger) |
|
Noise resistance |
Square shaped noise by noise simulator (pulse width 1 ) ±2kV R-phase, S-phase |
||
Memory retention |
Approx. 10 years (non-volatile semiconductor memory type) |
||
Environ- |
Ambient temp. |
-10 to 50 , storage: -20 to 60 |
|
ment |
Ambient humi. |
35 to 85%RH, storage: 35 to 85%RH |
|
Protection |
structure |
IP50 (front panel, IEC standards) |
|
Insulation type |
Double insulation (mark: : , dielectric strength between all terminals and case: 3kV) |
||
Approval |
|
|
|
Weight 3 |
|
|
Approx. 135.2g (approx. 85.2g) |
1: When using the unit at low temperature (below 0 ), display cycle is slow. Control output operates normally.
2: At room temperature(23 ±5 )
TC R(PR), S(PR), below 200 : (PV ±0.5% or ±3 , select the higher one) ±1 digit , over 200 : (PV ±0.5% or ±2 , select the higher one) ±1 digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2 , select the higher one) ±1 digit Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5 , select the higher one) ±1 digit TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3 , select the higher one) ±1 digit
3: The weight includes packaging. The weight in parentheses is for unit only.Environment resistance is rated at no freezing or condensation.
|
Unit Description |
1. |
Measured value (PV) component: |
|
|
|
RUN mode: Displays current measured value (PV). |
|
|
|
SETTING mode: Displays parameters. |
|
1 |
2. |
Setting value (SV) display component: |
|
|
|
RUN mode: Displays setting value(SV). |
|
|
|
SETTING mode: Displays setting value of parameter. |
4 |
|
3. |
Temperature unit( / ) indicator: |
3 |
|
Displays the set temperature unit as temperature unit [UNIT] of |
|
5 |
|
parameter 2 group. |
|
2 |
|
||
6 |
4. Control output (OUT1) indicator: Turns ON while control output is ON. |
||
|
9 |
|
Turns ON when MV is over 3.0% at cycle/phase control of SSR drive |
|
|
output method. |
|
|
5. Alarm output (AL1, AL2) indicator: |
|
|
Turns ON when the corresponding alarm output turns ON. |
7 |
8 |
6. Auto-tuning indicator: |
Flashes during auto-tuning every 1 sec. |
||
|
7. |
key: Enters parameter group, returns to RUN mode, moves parameters, |
10and saves the setting value.
8.Setting value adjutment key: Enters SV setting mode and move digits.
9.Digital input key: Press the + keys for 3 sec. to execute the digital input key functions which is set at digital input key[DI-K]of parameter 2 group (RUN/STOP, clear alarm output, auto-tuning).
10.PC loader port: It is for serial communication to set parameter and monitoring by DAQMaster installed in PC. Use this for connection EXT-US (converter cable, sold separately) + SCM-US (USB to Serial converter, sold separately).
OUT |
|
|
|
|
|
|
|
|
|
|
|
Shaded terminals is standard model. |
|||||
SSR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12VDC±2V20mAMax. |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Current |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AL1 OUT: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
DC0/4-20mA |
|
|
|
1 |
|
|
|
|
|
|
13 |
|
|
7 |
|
||
Load500ΩMax. |
|
|
|
|
|
|
|
|
|
250VAC 3A 1a |
|||||||
Relay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RESISTIVE LOAD |
|
250VAC3A1a |
|
|
|
2 |
|
|
|
|
|
|
14 |
|
|
8 |
|
AL2 OUT: |
|
RESISTIVELOAD |
|
|
|
|
|
|
|
|
|
|
|
|
250VAC 3A 1a |
||||
|
+ |
|
+ |
|
3 |
|
+ |
|
RS485(A+) |
15 |
|
|
9 |
|
RESISTIVE LOAD |
||
|
- |
mA- |
|
|
mA- |
|
|
|
|
|
|
|
|
A |
|||
4 |
|
|
|
|
|
|
16 |
|
|
10 |
|
|
|||||
|
|
RS485(B-) |
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
Communication |
17 |
11 |
B |
+ |
|
Output |
|
||||
SOURCE |
6 |
TransferOutput |
18 |
12 |
B' |
- |
DC4-20mA |
||||||
100-240VAC |
|
|
|
|
RTD |
TC |
|
|
|
|
SENSOR |
||
50/60Hz 8VA |
|
|
|
|
||
|
|
|
|
|
|
Input type |
|
Decimal point |
Display |
Input range( ) |
Input range( ) |
|
|
K(CA) |
1 |
KCaH |
-50 to 1200 |
-58 to 2192 |
|
|
0.1 |
KCaL |
-50.0 to 999.9 |
-58.0 to 999.9 |
||
|
|
|||||
|
J(IC) |
1 |
JIcH |
-30 to 800 |
-22 to 1472 |
|
|
0.1 |
JIcL |
-30.0 to 800.0 |
-22.0 to 999.9 |
||
|
|
|||||
Thermocouple |
L(IC) |
1 |
LIcH |
-40 to 800 |
-40 to 1472 |
|
0.1 |
LIcL |
-40.0 to 800.0 |
-40.0 to 999.9 |
|||
|
|
|||||
|
T(CC) |
1 |
TCcH |
-50 to 400 |
-58 to 752 |
|
|
0.1 |
TCcL |
-50.0 to 400.0 |
-58.0 to 752.0 |
||
|
|
|||||
|
R(PR) |
1 |
RPR |
0 to 1700 |
32 to 3092 |
|
|
S(PR) |
1 |
SPR |
0 to 1700 |
32 to 3092 |
|
|
DPt 100Ω |
1 |
DPtH |
-100 to 400 |
-148 to 752 |
|
RTD |
0.1 |
DPtL |
-100.0 to 400.0 |
-148.0 to 752.0 |
||
CU50Ω |
1 |
CUsH |
-50 to 200 |
-58 to 392 |
||
|
||||||
|
0.1 |
CUsL |
`-50.0 to 200.0 |
-58.0 to 392.0 |
||
|
|
Parameter Groups |
|
|
|
|
● Parameter 2 group |
1: |
: Press any key among |
, |
, . |
||||||||
|
|
|
|
2: Press the |
key once after changing the setting value, to save the setting |
||||||||||||
|
|
|
|
RUN mode |
|
|
|
|
RUN mode |
1 |
value and move to the next parameter |
||||||
|
|
|
|
|
|
|
|
|
|
4sec. |
Hold the |
key for 3 sec. to save the setting value and return to RUN mode |
|||||
Press any key among |
|
|
|
|
3 sec. |
|
after changing the setting value. |
|
|||||||||
2 sec. |
|
|
4 sec. |
|
PAR2 |
|
|
Dotted parameters may not appear by model type or other parameter |
|||||||||
|
, |
, |
, |
once. |
|
|
|
|
settings. |
|
|
|
|
||||
|
|
|
|
|
|
|
|
Setting range: Refer to ' Input Type And Range'. |
|||||||||
SV setting |
|
|
Parameter 1 group[PAR1] |
Parameter 2 group[PAR2] |
Input sensor |
IN-T |
|
KCaH |
|
When changing the setting value, SV, [IN-B, H-SV/L-SV, |
|||||||
|
|
|
|
|
|
|
|
3 sec. |
|
|
AL1, AL2, LBaB, AHYS] parameters of parameter 2 group are |
||||||
|
|
|
|
|
3 sec. |
|
|
|
|
|
|
2 |
reset. |
|
|
||
Order of parameter setup Parameter 2 group |
Parameter 1 group |
SV setting |
|
|
|
|
|
|
|
When changing the setting value, SV, [IN-B, H-SV/ |
|||||||
●All parameters are related one another. Set the parameters as above order. |
|
Temp. unit |
UNIT |
|
?C |
|
?F |
L-SV, AL1, AL2, LBaB, AHYS] parameters of |
|||||||||
|
|
|
|
|
|
|
parameter 2 group are reset. |
||||||||||
If there is no key input for 30 sec. while setting SV or the parameters, the new settings are ignored, and |
Input |
|
|
|
|
|
|
|
|
||||||||
the unit will return to RUN mode with previous settings. |
|
|
|
IN-B |
|
0 Setting range: -999 to 999 / (-199.9 to 999.9 / ) |
|||||||||||
|
|
key within 1 sec. to |
correction |
|
|||||||||||||
When returning to RUN mode by holding the |
key for over 3 sec., press the |
|
|
|
|
|
|
|
|
|
|||||||
re-enter the first parameter of previous parameter group. |
|
|
|
Input digital |
MAvF |
|
)1 Setting range: 0.1 to 120.0 sec. |
||||||||||
Hold the |
+ |
+ |
keys for 5 sec. in RUN mode, to enter re-set parameter menu. Select 'YES' and all |
|
|||||||||||||
filter |
|
|
|
|
|
|
|
|
|||||||||
parameters are reset as factory default. |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
● SV setting |
|
|
|
|
|
|
|
SV low-limit |
|
|
|
Setting range: Within temperature range of each sensor[L-SV≤(H-SV-1digit)] |
|||||
To change set temperature from 210 to 250 |
|
|
|
value |
L-SV |
|
-50 When changing the setting value, and SV L-SV, SV is reset as L-SV. |
||||||||||
RUN mode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
SV high-limit |
H-SV |
|
1200 |
Setting range: Within temperature range of each sensor [H-SV≥(L-SV+1digit)] |
||||
|
|
|
|
|
|
|
|
|
value |
|
When changing the setting value, and SV H-SV, SV is reset as H-SV. |
|
|
|
|
|
|
|
|
|
|
|
Control |
|
|
|
|
|
Press any key among |
|
, |
, |
, |
once. |
Completes SV |
output mode O-FT |
HEAT |
COOL |
|
||||
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SV setting mode |
|
|
|
|
|
|
|
|
setting |
Control |
|
|
|
When changing the setting value, [ErMV] is reset as )0, |
|
|
|
|
|
|
|
|
|
|
|
C-MD |
PID |
ONOF [DI-K] is reset as OFF. |
||
|
|
|
|
|
|
|
|
|
|
|
method |
||||
|
Change SV |
|
|
|
|
|
|
Control |
|
|
|
Appears only in selectable current output or SSR drive |
|||
|
by |
, |
, |
key |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
output |
OUT |
CURR |
SSR |
||||||
|
|
|
|
|
|
|
|
|
|
|
selection |
|
|
|
output model(TX4S4C). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Check SV |
|
|
|
|
|
|
|
|
|
SSR drive |
|
|
|
PHAS Appears only in SSR drive output model |
|
|
|
|
|
|
|
|
|
|
output |
SSrM |
STND |
CYCL |
|||
● Parameter 1 group |
1: : Press any key among |
, |
, . |
method |
|
|
|
(TX4S4S). |
|||||||
Current |
|
|
|
|
|||||||||||
|
|
2: Press the |
|
key once after changing the setting value, to save the setting |
output |
oMA |
4-20 |
0-20 Appears only when control output[OUT] is set as CURR. |
|||||||
|
RUN mode |
|
|
value and move to the next parameter |
|||||||||||
|
|
|
range |
|
|
|
|
||||||||
|
2sec. |
Hold the |
|
key for 3 sec. to save the setting value and return to RUN mode |
|
|
|
|
|||||||
|
|
|
|
|
Setting range: 0.5 to 120.0 sec. |
||||||||||
3 sec. |
|
|
after changing the setting value. |
|
Control |
|
|
||||||||
PAR1 |
|
|
Dotted parameters may not appear by model type or other parameter |
T |
2)0 |
Appears only when control method[C-MD] is PID. |
|||||||||
|
|
cycle |
|||||||||||||
|
|
|
|
||||||||||||
|
|
|
settings. |
|
|
|
|
|
|
|
|
|
Does not appear when SSR drive output is set as CYCL, or PHAS. |
|
|
AL1 temperature |
|
1 |
|
|
|
|
|
|
|
|
|
AL1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
AL1 |
|
|
|
|
1250 |
|
Setting range: Deviation alarm(-[F.S] to [F.S]), |
operation |
AL-1 |
|
|
|
|
|
AM!A |
|
|
|
LBaA |
|
|
|
|
AM!A |
|
|
|
AM!B |
|
When changing the |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Absolute value alarm(temperature range) |
|
|
|
|
|
|
|
|
|
Alarm operation |
|
|
Alarm option |
setting value, |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
2 Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] |
|
|
|
|
|
|
|
|
|
|
|
[AL1, AL2] |
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
|
|
AL2 temperature |
|
|
|
|
|
|
|
of parameter 2 group is set as AM)_/SBa /LBa . |
|
|
|
|
|
|
|
Press the key to switch 'Alarm operation' |
|
|
parameter of |
|||||||||||||||||||||||
|
|
|
|
AL2 |
|
|
|
|
1250 |
|
Only alarm output 2 models have [AL2]. |
|
|
|
|
|
|
|
|
|
'Alarm option' setting. |
|
|
|
|
|
|
|
|
parameter 1 group |
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AL2 |
|
|
|
|
|
|
|
|
|
Set method is same as AL1 alarm |
|
|
is reset. |
|||||||||||
|
|
|
Auto-tuning |
|
|
|
|
|
|
|
When setting as ON, the unit starts auto-tuning.After |
operation |
AL-2 |
|
|
|
|
|
AM@A |
|
operation[AL-1]. |
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appears only in alarm output 2 models. |
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
AT |
|
|
|
|
|
OFF |
|
|
|
ON |
|
completing, OFF is automatically set. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
During auto-tuning, the auto-tuning indicator |
Alarm |
|
|
|
|
|
|
|
|
|
Setting range: 1 to 100 / (0.1 to 100.0 / ) |
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
flashes (every 1 sec.). |
output |
AHYS |
|
|
|
|
|
1 |
Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] is set |
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
Proportional band |
|
|
|
Setting range: 0.1 to 999.9 / |
|
hysteresis |
|
|
|
|
|
|
|
|
|
|
as AM)_/SBa |
/LBa . |
|
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
|
|
|
|
|
P |
|
|
|
|
1)0 |
|
|
LBA |
|
|
|
|
|
|
|
|
|
Setting range: 0 to 9999 sec.(automatically set during auto-tuning) |
|||||||||||||||||||||
|
|
Integral time |
|
|
|
|
|
|
|
|
|
monitoring |
LBaT |
|
|
|
|
|
0 |
|||||||||||||||||||||||||
|
|
|
|
|
Setting range: 0 to 9999 sec. |
|
time |
|
|
|
|
|
|
|
|
|
Appears only when alarm operation[AL-1, AL-2] is set as LBa . |
|||||||||||||||||||||||||||
|
|
|
|
|
I |
|
|
|
|
|
0 |
|
Integral operation will be OFF |
Only appears when control |
|
|
|
|
|
|
|
|
|
Setting range: 0 to 999 / (0.0 to 999.9 / ) |
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
when the setting value is '0. |
method [C-MD] of parameter |
LBA |
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(automatically set during auto-tuning) |
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 group is set as PID. |
detection |
LBaB |
|
|
|
|
|
2 |
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Appears only when alarm operation [AL-1, AL-2] is set as LBa |
||||||||||||||||||||
|
|
Derivative time |
|
|
|
|
|
|
Setting range: 0 to 9999 sec. |
|
band |
|
|
|
|
|
|
|
|
|
|
and [LBaT] is not set as 0. |
|
|
|
|||||||||||||||||||
|
|
|
|
|
D |
|
|
|
|
0 |
|
Derivative operation will be OFF |
|
Trans. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
when the setting value is '0. |
|
output low- |
FS-L |
|
|
|
|
|
-50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
limit value |
|
|
|
|
|
|
|
|
|
|
|
Setting range: Refer to ' Input Type And Range'. |
||||||||||||
|
|
Manual reset |
|
|
|
|
|
|
Setting range: 0.0 to 100.0% |
|
Trans. |
|
|
|
|
|
|
|
|
|
|
|
Appears only in transmission output model(TX4S-A4 ). |
|||||||||||||||||||||
|
|
|
|
REST |
|
|
|
|
5)0 |
|
Only appears in P, PD control. |
|
output high- |
FS-H |
|
|
|
|
|
1200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
limit value |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hysteresis |
|
|
|
|
|
|
Setting range: 1 to 100 / (0.1 to 50.0 / ) |
Comm. |
|
|
|
|
|
|
|
|
|
Setting range: 1 to 127 |
|
|
|
||||||||||||||||||||
|
|
|
|
HYS |
|
|
|
|
2 |
|
Only appears when control method [C-MD] of parameter 2 group is |
address |
ADRS |
|
|
|
|
|
1 |
|
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
set as ONOF. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Dimensions |
|
|
|
(unit:mm) |
|
|
|
|
|
48 |
5 |
45 |
Panel cut-out dimensions |
|
|
Min. 65 |
|||
|
|
|
|
|
|
|
|
|
45+0.6 |
|
|
|
|
0 |
|
|
44.8 |
Min. 65 |
45+0.60 |
Comm. |
|
|
|
|
|
|
|
|
|
Setting range: 24, 48, 96, 192, 384 bps |
|
||||||||
BPS |
|
|
|
|
|
96 |
|
||||||||||||
speed |
|
|
|
|
|
|
|
|
|
Multiply 100 to read the setting value. |
|
||||||||
|
|
|
|
|
|
|
|
|
|
||||||||||
Comm. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
parity-bit |
PRTY |
|
|
|
NONE |
|
|
|
EVEN |
|
|
|
ODD |
|
Appears in RS485 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
communication output |
Comm. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
model(TX4S-B4 ). |
stop-bit |
STP |
|
|
|
2 |
|
|
|
1 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Comm. |
|
|
|
|
|
|
|
|
|
Setting range: 5 to 99ms |
|
||||||||
response |
RSwT |
|
|
|
20 |
|
waiting time
Bracket |
|
31 |
Terminal cover(sold separately) |
48.6 |
|
●RSA-COVER(48×48mm) |
|
5 |
20 |
48.4 |
|
45 |
|
||
|
|
|
44.9 |
36 |
16 |
41.5 |
|
|
15 |
|
55 |
|
21 |
|
|
|
18 |
22 |
|
|
9.8 |
|
|
|
22.5 |
|
56 |
|
|
|
Comm.write |
COMW |
Digital |
DI-K |
input key |
|
Control |
|
output MV for |
ErMV |
input break |
|
EnA DIsA
STOP |
AlRE |
AT |
OFF |
AT does not appear when control method [C-MD] is set as ONOF.
Setting range: 0.0 to 100.0%
)0 Only )0(OFF)/10)0(ON) appear when control method [C-MD] is set as ONOF.
When control method [C-MD] is changing PID↔ONOF and the setting value is below 10)0, it is reset as )0.
Lock |
LOC |
OFF |
LOC1 |
LOC2 |
LOC3 |
Setting range: OFF Unlock
LOC1 Parameter 2 group lock
LOC2 Parameter 1,2 group lock
LOC3 Parameter 1,2 group, SV setting lock