Autonics TX4S Operating Manual

0 (0)
Autonics TX4S Operating Manual

LCD Display PID Temperature Controller

TX4S SERIES

I N S T R U C T I O N M A N U A L

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

Safety Considerations

Please observe all safety considerations for safe and proper product operation to avoid hazards.

Safety considerations are categorized as follows.

Warning Failure to follow these instructions may result in serious injury or death.

Caution Failure to follow these instructions may result in personal injury or product damage.

The symbols used on the product and instruction manual represent the following

symbol represents caution due to special circumstances in which hazards may occur.

Warning

1.Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)

Failure to follow this instruction may result in personal injury, fire, or economic loss.

2.The unit must be installed on a device panel before use.

Failure to follow this instruction may result in electric shock.

3.Do not connect, repair, or inspect the unit while connected to a power source.

Failure to follow this instruction may result in electric shock.

4.Check the terminal numbers before connecting the power source.

Failure to follow this instruction may result in fire.

5.Do not disassemble or modify the unit. Please contact us if necessary.

Failure to follow this instruction may result in electric shock or fire.

Caution

1. Do not use the unit outdoors.

Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock.

2.When connecting the power input and relay output cables, use AWG20 (0.05mm2) cables and make sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m.

Failure to follow this instruction may result in fire due to contact failure.

3.Use the unit within the rated specifications.

Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.

4. Do not use loads beyond the rated switching capacity of the relay contact.

Failure to follow this instruction may result in insulation failure, contact melt, contact failure, relay broken, or fire.

5.Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.

Failure to follow this instruction may result in electric shock or fire.

6.Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, vibration, or impact may be present.

Failure to follow this instruction may result in fire or explosion.

7.Keep dust and wire residue from flowing into the unit.

Failure to follow this instruction may result in fire or product damage.

8.Check the polarity of the measurement input contact before wiring the temperature sensor.

Failure to follow this instruction may result in fire or explosion.

9.For installing the unit with reinforced insulation, use the power supply unit which basic level is ensured.

Ordering Information

TX

 

4

S

 

 

1

4

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control output

R

Relay output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

SSR drive output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

C

Selectable current output or SSR drive output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

100-240VAC 50/60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Alarm output 1

 

 

 

 

 

 

 

 

 

 

Option output

2

Alarm output 1+Alarm output 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

Alarm output 1+Alarm output 2+Trans. output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Alarm output 1+Alarm output 2+RS485 com. output

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

DIN W48×H48mm

 

 

 

 

Digit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

 

 

 

4

9999(4 digit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TX

LCD display standard PID temperature controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation

Mount the unit on the panel. Push the bracket with tools to fix the unit as the figure.

The above specifications are subject to change and some models may be discontinued without notice.

Specifications

Series

 

 

TX4S

Power supply

100-240VAC 50/60Hz

Allowable voltage range

90 to 110% of rated voltage

Power consumption

Max. 8VA

Display method

11 segments (PV: white, SV: green), other display (yellow) with LCD method 1

Character

 

PV(W×H)

6.9×15.3mm

size

 

SV(W×H)

4.1×9.2mm

Input type

 

RTD

DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω)

 

TC

K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)

Display

 

RTD

●At room temperature (23 ±5 ): (PV ±0.3% or ±1 , select the higher one) ±1digit

accuracy 2

TC

●Out of room temperature: (PV ±0.5% or ±2 , select the higher one) ±1digit

Control

 

Relay

250VAC 3A 1a

 

SSR

Max. 12VDC ± 2V 20mA

output

 

 

Current

DC4-20mA or DC0-20mA (load resistance max. 500Ω)

 

 

Option

 

Alarm output

AL1, AL2 Relay: 250VAC 3A 1a

 

Trans. output

DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.)

output

 

 

Com. output

RS485 Communication output (Modbus RTU method)

 

 

Control method

ON/OFF control, P, PI, PD, PID control

Hysteresis

1 to 100 / (0.1 to 50.0 / ) variable

Proportional band(P)

0.1 to 999.9 /

Integral time(I)

0 to 9999 sec.

Derivative time(D)

0 to 9999 sec.

Control period(T)

0.5 to 120.0 sec.

Manual reset

0.0 to 100.0%

Sampling period

50ms

Dielectric strength

3,000VAC 50/60Hz for 1 min. (between all terminals and case)

Vibration

 

 

0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours

Relay

 

Mechanical

OUT, AL1/2: Min. 5,000,000 operations

life cycle

 

Electrical

OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load)

Insulation

resistance

Min. 100MΩ (at 500VDC megger)

Noise resistance

Square shaped noise by noise simulator (pulse width 1 ) ±2kV R-phase, S-phase

Memory retention

Approx. 10 years (non-volatile semiconductor memory type)

Environ-

Ambient temp.

-10 to 50 , storage: -20 to 60

ment

Ambient humi.

35 to 85%RH, storage: 35 to 85%RH

Protection

structure

IP50 (front panel, IEC standards)

Insulation type

Double insulation (mark: : , dielectric strength between all terminals and case: 3kV)

Approval

 

 

 

Weight 3

 

 

Approx. 135.2g (approx. 85.2g)

1: When using the unit at low temperature (below 0 ), display cycle is slow. Control output operates normally.

2: At room temperature(23 ±5 )

TC R(PR), S(PR), below 200 : (PV ±0.5% or ±3 , select the higher one) ±1 digit , over 200 : (PV ±0.5% or ±2 , select the higher one) ±1 digit

TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2 , select the higher one) ±1 digit Out of room temperature range

TC R(PR), S(PR): (PV ±1.0% or ±5 , select the higher one) ±1 digit TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3 , select the higher one) ±1 digit

3: The weight includes packaging. The weight in parentheses is for unit only.Environment resistance is rated at no freezing or condensation.

 

Unit Description

1.

Measured value (PV) component:

 

 

 

RUN mode: Displays current measured value (PV).

 

 

 

SETTING mode: Displays parameters.

 

1

2.

Setting value (SV) display component:

 

 

 

RUN mode: Displays setting value(SV).

 

 

 

SETTING mode: Displays setting value of parameter.

4

 

3.

Temperature unit( / ) indicator:

3

 

Displays the set temperature unit as temperature unit [UNIT] of

5

 

parameter 2 group.

2

 

6

4. Control output (OUT1) indicator: Turns ON while control output is ON.

 

9

 

Turns ON when MV is over 3.0% at cycle/phase control of SSR drive

 

 

output method.

 

 

5. Alarm output (AL1, AL2) indicator:

 

 

Turns ON when the corresponding alarm output turns ON.

7

8

6. Auto-tuning indicator:

Flashes during auto-tuning every 1 sec.

 

7.

key: Enters parameter group, returns to RUN mode, moves parameters,

10and saves the setting value.

8.Setting value adjutment key: Enters SV setting mode and move digits.

9.Digital input key: Press the + keys for 3 sec. to execute the digital input key functions which is set at digital input key[DI-K]of parameter 2 group (RUN/STOP, clear alarm output, auto-tuning).

10.PC loader port: It is for serial communication to set parameter and monitoring by DAQMaster installed in PC. Use this for connection EXT-US (converter cable, sold separately) + SCM-US (USB to Serial converter, sold separately).

Connection

OUT

 

 

 

 

 

 

 

 

 

 

 

Shaded terminals is standard model.

SSR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12VDC±2V20mAMax.

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL1 OUT:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC0/4-20mA

 

 

 

1

 

 

 

 

 

 

13

 

 

7

 

Load500ΩMax.

 

 

 

 

 

 

 

 

 

250VAC 3A 1a

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESISTIVE LOAD

250VAC3A1a

 

 

 

2

 

 

 

 

 

 

14

 

 

8

 

AL2 OUT:

RESISTIVELOAD

 

 

 

 

 

 

 

 

 

 

 

 

250VAC 3A 1a

 

+

 

+

 

3

 

+

 

RS485(A+)

15

 

 

9

 

RESISTIVE LOAD

 

-

mA-

 

 

mA-

 

 

 

 

 

 

 

 

A

4

 

 

 

 

 

 

16

 

 

10

 

 

 

 

RS485(B-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Communication

17

11

B

+

 

Output

 

SOURCE

6

TransferOutput

18

12

B'

-

DC4-20mA

100-240VAC

 

 

 

 

RTD

TC

 

 

 

 

SENSOR

50/60Hz 8VA

 

 

 

 

 

 

 

 

 

 

Input Type And Range

Input type

 

Decimal point

Display

Input range( )

Input range( )

 

K(CA)

1

KCaH

-50 to 1200

-58 to 2192

 

0.1

KCaL

-50.0 to 999.9

-58.0 to 999.9

 

 

 

J(IC)

1

JIcH

-30 to 800

-22 to 1472

 

0.1

JIcL

-30.0 to 800.0

-22.0 to 999.9

 

 

Thermocouple

L(IC)

1

LIcH

-40 to 800

-40 to 1472

0.1

LIcL

-40.0 to 800.0

-40.0 to 999.9

 

 

 

T(CC)

1

TCcH

-50 to 400

-58 to 752

 

0.1

TCcL

-50.0 to 400.0

-58.0 to 752.0

 

 

 

R(PR)

1

RPR

0 to 1700

32 to 3092

 

S(PR)

1

SPR

0 to 1700

32 to 3092

 

DPt 100Ω

1

DPtH

-100 to 400

-148 to 752

RTD

0.1

DPtL

-100.0 to 400.0

-148.0 to 752.0

CU50Ω

1

CUsH

-50 to 200

-58 to 392

 

 

0.1

CUsL

`-50.0 to 200.0

-58.0 to 392.0

 

 

Parameter Groups

 

 

 

 

● Parameter 2 group

1:

: Press any key among

,

, .

 

 

 

 

2: Press the

key once after changing the setting value, to save the setting

 

 

 

 

RUN mode

 

 

 

 

RUN mode

1

value and move to the next parameter

 

 

 

 

 

 

 

 

 

 

4sec.

Hold the

key for 3 sec. to save the setting value and return to RUN mode

Press any key among

 

 

 

 

3 sec.

 

after changing the setting value.

 

2 sec.

 

 

4 sec.

 

PAR2

 

 

Dotted parameters may not appear by model type or other parameter

 

,

,

,

once.

 

 

 

 

settings.

 

 

 

 

 

 

 

 

 

 

 

 

Setting range: Refer to ' Input Type And Range'.

SV setting

 

 

Parameter 1 group[PAR1]

Parameter 2 group[PAR2]

Input sensor

IN-T

 

KCaH

 

When changing the setting value, SV, [IN-B, H-SV/L-SV,

 

 

 

 

 

 

 

 

3 sec.

 

 

AL1, AL2, LBaB, AHYS] parameters of parameter 2 group are

 

 

 

 

 

3 sec.

 

 

 

 

 

 

2

reset.

 

 

Order of parameter setup Parameter 2 group

Parameter 1 group

SV setting

 

 

 

 

 

 

 

When changing the setting value, SV, [IN-B, H-SV/

●All parameters are related one another. Set the parameters as above order.

 

Temp. unit

UNIT

 

?C

 

?F

L-SV, AL1, AL2, LBaB, AHYS] parameters of

 

 

 

 

 

 

 

parameter 2 group are reset.

If there is no key input for 30 sec. while setting SV or the parameters, the new settings are ignored, and

Input

 

 

 

 

 

 

 

 

the unit will return to RUN mode with previous settings.

 

 

 

IN-B

 

0 Setting range: -999 to 999 / (-199.9 to 999.9 / )

 

 

key within 1 sec. to

correction

 

When returning to RUN mode by holding the

key for over 3 sec., press the

 

 

 

 

 

 

 

 

 

re-enter the first parameter of previous parameter group.

 

 

 

Input digital

MAvF

 

)1 Setting range: 0.1 to 120.0 sec.

Hold the

+

+

keys for 5 sec. in RUN mode, to enter re-set parameter menu. Select 'YES' and all

 

filter

 

 

 

 

 

 

 

 

parameters are reset as factory default.

 

 

 

 

 

 

 

 

 

 

 

 

 

● SV setting

 

 

 

 

 

 

 

SV low-limit

 

 

 

Setting range: Within temperature range of each sensor[L-SV≤(H-SV-1digit)]

To change set temperature from 210 to 250

 

 

 

value

L-SV

 

-50 When changing the setting value, and SV L-SV, SV is reset as L-SV.

RUN mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV high-limit

H-SV

 

1200

Setting range: Within temperature range of each sensor [H-SV≥(L-SV+1digit)]

 

 

 

 

 

 

 

 

 

value

 

When changing the setting value, and SV H-SV, SV is reset as H-SV.

 

 

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

Press any key among

 

,

,

,

once.

Completes SV

output mode O-FT

HEAT

COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV setting mode

 

 

 

 

 

 

 

 

setting

Control

 

 

 

When changing the setting value, [ErMV] is reset as )0,

 

 

 

 

 

 

 

 

 

 

 

C-MD

PID

ONOF [DI-K] is reset as OFF.

 

 

 

 

 

 

 

 

 

 

 

method

 

Change SV

 

 

 

 

 

 

Control

 

 

 

Appears only in selectable current output or SSR drive

 

by

,

,

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output

OUT

CURR

SSR

 

 

 

 

 

 

 

 

 

 

 

selection

 

 

 

output model(TX4S4C).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check SV

 

 

 

 

 

 

 

 

 

SSR drive

 

 

 

PHAS Appears only in SSR drive output model

 

 

 

 

 

 

 

 

 

output

SSrM

STND

CYCL

● Parameter 1 group

1: : Press any key among

,

, .

method

 

 

 

(TX4S4S).

Current

 

 

 

 

 

 

2: Press the

 

key once after changing the setting value, to save the setting

output

oMA

4-20

0-20 Appears only when control output[OUT] is set as CURR.

 

RUN mode

 

 

value and move to the next parameter

 

 

 

range

 

 

 

 

 

2sec.

Hold the

 

key for 3 sec. to save the setting value and return to RUN mode

 

 

 

 

 

 

 

 

 

Setting range: 0.5 to 120.0 sec.

3 sec.

 

 

after changing the setting value.

 

Control

 

 

PAR1

 

 

Dotted parameters may not appear by model type or other parameter

T

2)0

Appears only when control method[C-MD] is PID.

 

 

cycle

 

 

 

 

 

 

 

settings.

 

 

 

 

 

 

 

 

 

Does not appear when SSR drive output is set as CYCL, or PHAS.

 

 

AL1 temperature

 

1

 

 

 

 

 

 

 

 

 

AL1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL1

 

 

 

 

1250

 

Setting range: Deviation alarm(-[F.S] to [F.S]),

operation

AL-1

 

 

 

 

 

AM!A

 

 

 

LBaA

 

 

 

 

AM!A

 

 

 

AM!B

 

When changing the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Absolute value alarm(temperature range)

 

 

 

 

 

 

 

 

 

Alarm operation

 

 

Alarm option

setting value,

 

 

 

 

 

 

 

 

 

 

 

 

2 Does not appear when AL1/AL2 alarm operation[AL-1, AL-2]

 

 

 

 

 

 

 

 

 

 

 

[AL1, AL2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL2 temperature

 

 

 

 

 

 

 

of parameter 2 group is set as AM)_/SBa /LBa .

 

 

 

 

 

 

 

Press the key to switch 'Alarm operation'

 

 

parameter of

 

 

 

 

AL2

 

 

 

 

1250

 

Only alarm output 2 models have [AL2].

 

 

 

 

 

 

 

 

 

'Alarm option' setting.

 

 

 

 

 

 

 

 

parameter 1 group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL2

 

 

 

 

 

 

 

 

 

Set method is same as AL1 alarm

 

 

is reset.

 

 

 

Auto-tuning

 

 

 

 

 

 

 

When setting as ON, the unit starts auto-tuning.After

operation

AL-2

 

 

 

 

 

AM@A

 

operation[AL-1].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appears only in alarm output 2 models.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT

 

 

 

 

 

OFF

 

 

 

ON

 

completing, OFF is automatically set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During auto-tuning, the auto-tuning indicator

Alarm

 

 

 

 

 

 

 

 

 

Setting range: 1 to 100 / (0.1 to 100.0 / )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flashes (every 1 sec.).

output

AHYS

 

 

 

 

 

1

Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] is set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Proportional band

 

 

 

Setting range: 0.1 to 999.9 /

 

hysteresis

 

 

 

 

 

 

 

 

 

 

as AM)_/SBa

/LBa .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

1)0

 

 

LBA

 

 

 

 

 

 

 

 

 

Setting range: 0 to 9999 sec.(automatically set during auto-tuning)

 

 

Integral time

 

 

 

 

 

 

 

 

 

monitoring

LBaT

 

 

 

 

 

0

 

 

 

 

 

Setting range: 0 to 9999 sec.

 

time

 

 

 

 

 

 

 

 

 

Appears only when alarm operation[AL-1, AL-2] is set as LBa .

 

 

 

 

 

I

 

 

 

 

 

0

 

Integral operation will be OFF

Only appears when control

 

 

 

 

 

 

 

 

 

Setting range: 0 to 999 / (0.0 to 999.9 / )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the setting value is '0.

method [C-MD] of parameter

LBA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(automatically set during auto-tuning)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 group is set as PID.

detection

LBaB

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appears only when alarm operation [AL-1, AL-2] is set as LBa

 

 

Derivative time

 

 

 

 

 

 

Setting range: 0 to 9999 sec.

 

band

 

 

 

 

 

 

 

 

 

 

and [LBaT] is not set as 0.

 

 

 

 

 

 

 

 

D

 

 

 

 

0

 

Derivative operation will be OFF

 

Trans.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the setting value is '0.

 

output low-

FS-L

 

 

 

 

 

-50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limit value

 

 

 

 

 

 

 

 

 

 

 

Setting range: Refer to ' Input Type And Range'.

 

 

Manual reset

 

 

 

 

 

 

Setting range: 0.0 to 100.0%

 

Trans.

 

 

 

 

 

 

 

 

 

 

 

Appears only in transmission output model(TX4S-A4 ).

 

 

 

 

REST

 

 

 

 

5)0

 

Only appears in P, PD control.

 

output high-

FS-H

 

 

 

 

 

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limit value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hysteresis

 

 

 

 

 

 

Setting range: 1 to 100 / (0.1 to 50.0 / )

Comm.

 

 

 

 

 

 

 

 

 

Setting range: 1 to 127

 

 

 

 

 

 

 

HYS

 

 

 

 

2

 

Only appears when control method [C-MD] of parameter 2 group is

address

ADRS

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set as ONOF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions

 

 

 

(unit:mm)

 

 

 

 

48

5

45

Panel cut-out dimensions

 

Min. 65

 

 

 

 

 

 

 

 

45+0.6

 

 

 

 

0

 

 

44.8

Min. 65

45+0.60

Comm.

 

 

 

 

 

 

 

 

 

Setting range: 24, 48, 96, 192, 384 bps

 

BPS

 

 

 

 

 

96

 

speed

 

 

 

 

 

 

 

 

 

Multiply 100 to read the setting value.

 

 

 

 

 

 

 

 

 

 

 

Comm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parity-bit

PRTY

 

 

 

NONE

 

 

 

EVEN

 

 

 

ODD

 

Appears in RS485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication output

Comm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model(TX4S-B4 ).

stop-bit

STP

 

 

 

2

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comm.

 

 

 

 

 

 

 

 

 

Setting range: 5 to 99ms

 

response

RSwT

 

 

 

20

 

waiting time

Bracket

 

31

Terminal cover(sold separately)

48.6

 

●RSA-COVER(48×48mm)

5

20

48.4

45

 

 

 

 

44.9

36

16

41.5

 

 

15

 

55

 

21

 

 

 

18

22

 

 

9.8

 

 

 

22.5

 

56

 

 

 

Comm.write

COMW

Digital

DI-K

input key

Control

 

output MV for

ErMV

input break

 

EnA DIsA

STOP

AlRE

AT

OFF

AT does not appear when control method [C-MD] is set as ONOF.

Setting range: 0.0 to 100.0%

)0 Only )0(OFF)/10)0(ON) appear when control method [C-MD] is set as ONOF.

When control method [C-MD] is changing PID↔ONOF and the setting value is below 10)0, it is reset as )0.

Lock

LOC

OFF

LOC1

LOC2

LOC3

Setting range: OFF Unlock

LOC1 Parameter 2 group lock

LOC2 Parameter 1,2 group lock

LOC3 Parameter 1,2 group, SV setting lock