Benchmark Service Interval Record ................................................... 69
overview
These instructions are suitable for CLAS HE boilers :
Do not forget the Log Book!
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers
are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in
accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of
the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with
Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the
Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage
and promote the Scheme. Visit www.centralheating.co.uk for more information.
To The Installer
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder.
Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation
and the appliance service history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
ARISTON recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.
CUSTOMER CARE
ARISTON, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing
high quality products and a high quality after sales service.
Advice on installation or servicing can also be obtained by contacting the ARISTON Technical and Customer Service
Departments at High Wycombe.
TECHNICAL DEPARTMENT CUSTOMER SERVICE DEPARTMENT
Tel: 0333 240 7777 Tel: 0333 240 8777
Fax: 01494 459775 Fax: 01494 459775
GUARANTEE
The manufacturer’s guarantee is for 5 years from the date of purchase. The guarantee is invalidated if the appliance is not
installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To
assist us in providing you with an e cient after sales service, please register the guarantee online at www.ariston.co.uk
CAUTION
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person
only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person
in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations, reference
should also be made to the current ETCI rules for electrical installation.
All GAS SAFE registered installers carry a GAS SAFE ID card, and have a registration number. Both should be
recorded in your boiler Log Book. You can check your installer is GAS SAFE registered by calling GAS SAFE directly
on:- 0800 408 5500.
Improper installation may cause damage or injury to individuals, animals and personal property for which the
manufacturer will not be held liable. To ensure e cient and safe operation it is recommended that the boiler is serviced
annually by a competent person.
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent
person.
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland
3
overview
X
Advice for the installer
The installation and rst ignition of the boiler must be
performed by quali ed personnel in compliance with
current national regulations regarding installation, and
in conformity with any requirements established by
local authorities and public health organisations.
After the boiler has been installed, the installer must
ensure that the end user receives the declaration of
conformity and the operating manual, and should
provide all necessary information as to how the boiler
and the safety devices should be handled.
This appliance is designed to produce hot water for domestic use.
It should be connected to a heating system and a distribution
network for domestic hot water, both of which must be compatible
with its performance and power levels.
The use of the appliance for purposes other than those speci ed
is strictly forbidden. The manufacturer cannot be held responsible
for any damage caused by improper, incorrect and unreasonable
use of the appliance or by the failure to comply with the
instructions given in this manual.
Installation, maintenance and all other interventions must be
carried out in full conformity with the governing legal regulations
and the instructions provided by the manufacturer. Incorrect
installation can harm persons, animals and possessions; the
manufacturing company shall not be held responsible for any
damage caused as a result. The boiler is delivered in a carton. Once
you have removed all the packaging, make sure the appliance is
intact and that no parts are missing. If this is not the case, please
contact your supplier.
Keep all packaging material (clips, plastic bags, polystyrene foam, etc.)
out of reach of children as it may present a potential hazard.
In the event of a fault and/or malfunction, turn the appliance
o , turn o the gas cock and do not attempt to repair it yourself.
Contact a quali ed professional instead.
Before any maintenance or repair work is performed on the boiler,
make sure you have disconnected it from the electricity supply
by switching the external bipolar switch to the “OFF” position and
removing the fuse.
All repairs, which should only be performed using original spare
parts, should be carried out by a quali ed professional. Failure
to comply with the above instructions could compromise the
safety of the appliance and invalidate all liability on the part of
the manufacturer.
In the event of any maintenance or other structural work in
the immediate vicinity of the ducts or ue gas exhaust devices
and their accessories, switch the appliance o by switching the
external bipolar switch to the “OFF” position and shutting o
the gas control valve. When the work has been completed, ask a
quali ed technician to check the e ciency of the ducting and the
devices.
Turn the boiler o and turn the external switch “OFF” to clean the
exterior parts of the appliance.
Clean using a cloth dampened with soapy water. Do not use
aggressive detergents, insecticides or toxic products. If the
appliance is used in full compliance with current legislation, it
will operate in a safe, environmentally-friendly and cost-e cient
manner.
If using kits or optional extras, make sure they are authentic.
CE labelling
The CE mark guarantees that the appliance conforms to the following directives:
- 2009/142/CEE
relating to gas appliances
- 2004/108/CEE
relating to electromagnetic compatibility
- 92/42/CEE
relating to energy e ciency
- 2006/95/CEE
relating to electrical safety
Symbols used on the data plate
5
MIN
17
2
18
20
21
22
1
1
4
6
7
MA
Q
P
60/80°C
16
14
15
10
3
3
8
9
11
12
13
19
Legend :
1. Brand
2. Manufacturer
3. Boiler model - Serial number
4. Commercial reference
5. certi cation number
6. Destination country - gas category
7. Gas setting
8. Installation
type
9. Electrical data
10. Maximum domestic hot water pressure
11. Maximum heating pressure
12. Boiler type
13. NOx class / E ciency
14. Input rating nominal heating
15. Power ouput
heating
16. DHW speci c ow rate
17. Boiler output e ciency
18. Input rating nominal DHW
19. Gases which may be used
20. Minimum ambient temperature for use
21. Max. central heating temperature
22. Max. domestic hot water temperature
4
overview
Safety regulations
Key to symbols:
Failure to comply with this warning implies the risk of
personal injury, in some circumstances even fatal
Failure to comply with this warning implies the risk of
damage, in some circumstances even serious, to property,
plants or animals.
Install the appliance on a solid wall which is not subject
to vibration.
Noisiness during operation.
When drilling holes in the wall for installation
purposes, take care not to damage any electrical
wiring or existing piping.
Electrocution caused by contact with live wires. Explosions,
res or asphyxiation caused by gas leaking from damaged
piping. Damage to existing installations. Flooding caused
by water leaking from damaged piping.
Perform all electrical connections using wires which
have a suitable section.
Fire caused by overheating due to electrical current
passing through undersized cables.
Protect all connection pipes and wires in order to
prevent them from being damaged.
Electrocution caused by contact with live wires. Explosions,
res or asphyxiation caused by gas leaking from damaged
piping. Flooding caused by water leaking from damaged
piping.
Make sure the installation site and any systems to
which the appliance must be connected comply with
the applicable norms in force.
Electrocution caused by contact with live wires which
have been installed incorrectly. Damage to the appliance
caused by improper operating conditions.
Use suitable manual tools and equipment (make sure
in particular that the tool is not worn out and that its
handle is xed properly); use them correctly and make
sure they do not fall from a height. Replace them once
you have nished using them.
Personal injury from the falling splinters or fragments,
inhalation of dust, shocks, cuts, pricks and abrasions.
Damage to the appliance or surrounding objects caused
by falling splinters, knocks and incisions.
Use electrical equipment suitable for its intended use
(in particular, make sure that the power supply cable
and plug are intact and that the parts featuring rotary
or reciprocating motions are fastened correctly); use
this equipment correctly; do not obstruct passageways
with the power supply cable, make sure no equipment
could fall from a height. Disconnect it and replace it
safely after use.
Personal injury caused by falling splinters or fragments,
inhalation of dust, knocks, cuts, puncture wounds,
abrasions, noise and vibration. Damage to the appliance
or surrounding objects caused by falling splinters, knocks
and incisions.
Make sure any portable ladders are positioned
securely, that they are suitably strong and that the
steps are intact and not slippery and do not wobble
when someone climbs them. Ensure someone provides
supervision at all times.
Personal injury caused by falling from a height or cuts
(stepladders shutting accidentally).
Make sure any rolling ladders are positioned securely,
that they are suitably strong, that the steps are intact
and not slippery and that the ladders are tted with
handrails on either side of the ladder and parapets on
the landing.
Personal injury caused by falling from a height.
During all work carried out at a certain height (generally
with a di erence in height of more than two metres),
make sure that parapets are used to surround the work
area or that individual harnesses are used to prevent
falls. The space where any accidental fall may occur
should be free from dangerous obstacles, and any
impact upon falling should be cushioned by semi-rigid
or deformable surfaces.
Personal injury caused by falling from a height.
Make sure the workplace has suitable hygiene and
sanitary conditions in terms of lighting, ventilation
and solidity of the structures.
Personal injury caused by knocks, stumbling etc.
Protect the appliance and all areas in the vicinity of the
work place using suitable material.
Damage to the appliance or surrounding objects caused
by falling splinters, knocks and incisions.
Handle the appliance with suitable protection and
with care.
Damage to the appliance or surrounding objects from
shocks, knocks, incisions and squashing.
During all work procedures, wear individual protective
clothing and equipment.
Personal injury caused by electrocution, falling splinters
or fragments, inhalation of dust, shocks, cuts, puncture
wounds, abrasions, noise and vibration.
Place all debris and equipment in such a way as to
make movement easy and safe, avoiding the formation
of any piles which could yield or collapse.
Damage to the appliance or surrounding objects from
shocks, knocks, incisions and squashing.
All operations inside the appliance must be performed
with the necessary caution in order to avoid abrupt
contact with sharp parts.
Personal injury caused by cuts, puncture wounds and
abrasions.
Reset all the safety and control functions a ected
by any work performed on the appliance and make
sure they operate correctly before restarting the
appliance.
Explosions, res or asphyxiation caused by gas leaks or an
incorrect ue gas exhaust. Damage or shutdown of the
appliance caused by out-of-control operation.
Before handling, empty all components that may contain
hot water, carrying out any bleeding if necessary.
Personal injury caused by burns.
Descale the components, in accordance with the
instructions provided on the safety data sheet of the
product used, airing the room, wearing protective
clothing, avoid mixing di erent products, and protect
the appliance and surrounding objects.
Personal injury caused by acidic substances coming into
contact with skin or eyes; inhaling or swallowing harmful
chemical agents. Damage to the appliance or surrounding
objects due to corrosion caused by acidic substances.
If you detect a smell of burning or smoke, keep clear of
the appliance, disconnect it from the electricity supply,
open all windows and contact the technician.
Personal injury caused by burns, smoke inhalation,
asphyxiation.
5
product description
Control panel
1
2
3
4
5
6
Legend :
1. Display
2. Domestic Hot Water temperature adjustment button +/-
(only for Clas HE EVO models)
ODE button
3. M
(Operation mode selection (summer/winter)
4. Pressure gauge
5. Auto Function and/or Comfort Function
enable/disable button
(Comfort function only for Clas HE EVO models)
6. ESC button - reserved for technical assistance
7. “encoder” programming knob
- reserved for technical assistance
8. OK button - reserved for technical assistance
9. ON/OFF button
10.
TIME CLOCK (CLAS HE Evo System models optional)
11. RESET button
12. Heating temperature adjustument button +/-
12
1
24
2
23
3
22
4
12
5
6
7
9
8
9
10
21
20
I
19
18
17
16
6
15
11
14
12
13
11
10
9
8
7
Digits indicating:
Hot water operation set
- boiler status and temperature
Hot water operation active
Hot Water Comfort activated
Boiler o with antifreeze function active
Antifreeze function activated
AUTO function activated
(Temperature regulation activated)
Clip-in solar connected (optional)
indication (°C)
- error code signals (Err)
- menu settings
Technical assistance request
Flame detected with indication of
power used or indication of operation
shutdown
Heating operation set
AUTO
Note: A radio frequency (RF) Programmable Room
Heating operation active
Thermostat is available from Ariston stockists.
The Receiver unit can be tted in the time clock
position (10)
6
Overall view
product description
CLAS HE EVO
1
2
3
4
5
6
7
8
9
10
12
CLAS HE EVO SYSTEM
24
23
22
21
20
19
16
14
1
2
3
4
5
6
7
9
10
12
24
23
22
21
20
19
15
14
1. Flue connector
2. Manual air vent
3. Main heat exchanger
4. Detection electrode
5. C.H. Return temperature probe
6. C.H. Flow temperature probe
7. Silencer
8. Secondary heat exchanger
9. Gas valve
10. Trap
12. C.H. Pressure relief valve
14. C.H. Circuit lter
16. Circulation pump with air release valve
17. D.H.W. Flow switch
18. Diverter valve
19. Low Water Pressure Switch
20. Modulating fan
21. Ignition electrodes
22. Ignitor
23. Thermal fuse
24. Combustion analysis test point
7
product description
Overall Dimensions
200
120 120
CLAS HE EVOCLAS HE EVO SYSTEM
200
180
25 770
F
200
120120
F
150
65 65 67 67
28
315 mod. 24
1326567
385 mod. 30/38
200
28
A. Central Heating Flow
B. Domestic Hot Water Outlet
C. Gas Inlet
D. Domestic Cold Water Inlet
E. Central Heating Return
F. Safety Relief Valve
Minimum clearances
In order to allow easy access to the boiler for maintenance
operations, The boiler must be installed in accordance with the
clearances stated below.
0 0 3
5
55
450
0 0 3
8
product description
Technical Data
Model: CLAS HE EVO243038
CE Certi cation (pin)0085CL0440
GENERAL NOTE
Boiler type
Max/min nominal calori c ow rate (Pci) QnKW22.0/5.528.0/6.531.0/7.5
Max/min nominal calori c ow rate (Pcs) QnKW24.4/6.131.1/7.234.4/8.3
Domestic hot water max/min nominal calori c ow rate (Pci) QnKW26.0/5.530.0/6.538.0/7.5
Domestic hot water max/min nominal calori c ow rate (Pcs) QnKW28.9/6.133.3/7.242.2/8.3
Max/min power output (80°C-60°C) PnKW21.5/5.427.3/6.330.2/7.3
Max/min power output (50°C-30°C) PnKW23.3/5.729.7/6.833.0/7.9
Domestic hot water max/min power output PnKW26.0/5.529.3/6.338.0/7.5
Combustion e ciency (of ue gas)%97.897.897.9
Nominal calori c ow rate e ciency (60/80°C) Hi/Hs%97.5/87.897.6/87.897.6/87.9
Nominal calori c ow rate e ciency (30/50°C) Hi/Hs%105.8/95.3106.0/95.5106.4/95.8
E ciency at 30% at 30°C Hi/Hs%107.7/97.0107.7/97.0107.7/97.0
POWER SPECIFICATIONS
E ciency at 30% at 47°C Hi/Hs%97.7/88.097.6/87.997.6/87.9
Minimum calori c ow rate e ciency (60/80°C) Hi/Hs%97.6/87.997.5/87.897.5/87.8
E ciency rating (dir. 92/42/EEC)stars
Sedbuk classclassA/90A/90A/90.1
Loss when stopped (∆T = 50°C)%
Loss of burner gas when operating%2.22.22.2
Available air pressurePa100100100
NoX classclass555
Flue gas temperature (G20) (80°C-60°C)°C646464
CO2 content (G20) (80°C-60°C)%9.09.09.0
CO content (0%O2) (80°C-60°C)ppm11910198
EMISSIONS
O2 content (G20) (80°C-60°C)%4.54.54.5
Maximum ue gas ow (G20) (80°C-60°C)Kg/h42.849.462.6
Excess air (80°C-60°C)%272727
Expansion chamber in ation pressurebar111
Maximum heating pressure bar2,52,52,5
Expansion chamber capacityL6.56.56.5
Min/max heating temperature (high temperature range)°C35 / 8235 / 8235 / 82
HEATING CIRCUIT
Min/max heating temperature (low temperature range)°C20 / 4520 / 4520 / 45
Domestic hot water max/min temperature°C36 / 6036 / 6036 / 60
Speci c ow rate of domestic hot water (∆T=30°C) l/mn12.214.118.4
Quantity of hot water ∆T=25°Cl/mn14.516.821.3
Quantity of hot water ∆T=35°Cl/mn10.412.015.2
Hot water comfort rating (EN13203)stars*********
Hot water minimum ow ratel/mn<2<2<2
DOMESTIC HOT WATER CIRCUIT
Domestic hot water max/min pressurebar7 / 0.37 / 0.37 / 0.3
Power supply frequency/voltageV/Hz230/50230/50230/50
Total electrical power absorbedW110113116
Minimum ambient temperature for use°C+5+5+5
ELECTRICAL
Protection level for the electrical appliancePIX5DX5DX5D
Weightkg323536
C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)
C83(X)-C93(X)-B23-B23P-B33
************
9
product description
Model: CLAS HE EVO SYSTEM182430
CE Certi cation (pin)0085CL0440
GENERAL NOTE
Boiler type
Max/min nominal calori c ow rate (Pci) QnkW18.0/4.522.0/5.528.5/6.5
Max/min nominal calori c ow rate (Pcs) QnkW20.0/5.024.4/6.131.1/7.2
Max/min power output (80°C-60°C) PnkW17.6/4.421.5/5.427.3/6.3
Max/min power output (50°C-30°C) PnkW19.1/4.723.3/5.729.7/6.8
Combustion e ciency (of ue gas)%98.097.897.8
Nominal calori c ow rate e ciency (60/80°C) Hi/Hs%97.6/87.997.5/87.897.6/87.8
Nominal calori c ow rate e ciency (30/50°C) Hi/Hs%106,1/95.5105.8/95.3106.0/95.5
E ciency at 30% at 30°C Hi/Hs%107.7/97.0107.7/97.0107.7/97.0
E ciency at 30% at 47°C Hi/Hs%97.7/88.097.7/88.097.6/87.9
POWER SPECIFICATIONS
Minimum calori c ow rate e ciency (60/80°C) Hi/Hs%97.6/87.997.6/87.997.5/87.8
E ciency rating (dir. 92/42/EEC)stars************
Sedbuk Band / RatingBand / %A/90.1A/90.0A/90.0
Loss when stopped (∆T = 50°C)%
Loss of burner gas when operating%2.02.22.2
Available air pressurePa100100100
NoX class (5 = less than 70mg/kWhclass555
Flue gas temperature (G20) (80°C-60°C)°C616464
CO2 content (G20) (80°C-60°C)%9.09.09.0
CO content (0%O2) (80°C-60°C)ppm93119101
EMISSIONS
O2 content (G20) (80°C-60°C)%4.54.54.5
Maximum ue gas ow (G20) (80°C-60°C)Kg/h29.736.346.1
Excess air (80°C-60°C)%272727
Expansion chamber in ation pressurebar111
Maximum heating pressure bar2,52,52,5
Expansion chamber capacityL6.56.56.5
Min/max heating temperature (high temperature range)°C35 / 8235 / 8235 / 82
HEATING CIRCUIT
Min/max heating temperature (low temperature range)°C20 / 4520 / 4520 / 45
C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)
C83(X)-C93(X)-B23-B23P-B33
DOMESTIC HOT WATER CIRCUIT ELECTRICAL
Power supply frequency/voltageV/Hz230/50230/50230/50
Total electrical power absorbedW106113116
Minimum ambient temperature for use°C+5+5+5
Protection level for the electrical appliancePIX5DX5DX5D
Weightkg323235
10
installation
Reference Standards
In the United Kingdom, the installation and initial start-up of the
boiler must be by a Gas Safe registered installer in accordance
with the installation standards currently in e ect, as well as with
any and all local health and safety standards i.e. Gas Safe.
In the Republic of Ireland the installation and initial start-up of
the appliance must be carried out by a Competent Person in
accordance with the current edition of I.S.813 “Domestic Gas
Installations” and the current Building Regulations, reference
should also be made to the current ETCI rules for electrical
installation.
The installation of this appliance must be in accordance with
the relevant requirements of the Local Building Regulations, the
current I.E.E. Wiring Regulations, the by-laws of the local authority,
in Scotland, in accordance with the Building Standards (Scotland)
Regulation and Health and Safety document No. 635, “Electricity
at Work Regulations 1989” and in the Republic of Ireland with the
current edition of I.S. 813 and the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are nonhazardous and no special precautions are required when servicing.
Codes of Practive
Installation should also comply with the following British
Standards Code of Practice:
Flue
Detailed information on ue assembly can be found in the
“Connecting the Flue” section.
The boiler must be installed so that the ue terminal is exposed
to the free passage of external air at all times and must not be
installed in a place likely to cause nuisance. It must not be allowed
to discharge into another room or space such as an outhouse or
closed lean-to.
Condensing boilers have a tendency to form a plume of water
vapour from the ue terminal due to the low temperature of
the ue gasses. The terminal should therefore be located with
due regard for the damage or discolouration that may occur to
building within the vicinity and consideration must also be given
to adjacent boundaries, openable windows should also be taken
into consideration when siting the ue.
The minimum acceptable clearances are shown below:
BS 7593: Treatment of water in domestic hot water
central heating systems
BS 5546: Installation of hot water supplies for
domestic purposes
BS 5440-1: Flues
BS 5440-2: Air supply
BS 5449: Forced circulation hot water systems
BS 6798: Installation of gas red hot water boilers
of rated input not exceeding 70kW
BS 6891: Installation of low pressure gas pipes up to
28mm
BS 7671: IEE Wiring Regulations
BS 4814: Speci cation for expansion vessels
BS 5482: Installation of L.P.G.
and in the Republic of Ireland in accordancce with the following
codes of practice:
I.S. 813 Domestic Gas Installations
Avoid installing the boiler where the air inlet can be polluted
by chemical products such as chlorine (swimming pool area), or
ammonia (hair dresser), or alkalin products (launderette).
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
It may be necessary to protect the terminal with a guard, if this is
the case it will be necessary to purchase a stainless steel terminal
guard. Reference should be made to the Building Regulations for
guidance.
Ventilation
The room in which the boiler is installed does not require speci c
ventilation. If the boiler is installed in a cupboard or compartment
ventilation is not required for cooling purposes.
11
installation
Gas Supply
The gas installation and tightness testing must be in accordance
with the requirements of BS6891. Ensure that the pipe size is
adequate for demand including other gas appliances on the same
supply.
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must
be in accordance with current I.E.E. regulations. It must also be
possible to be able to completely isolate the appliance electrically.
Connection should be via a 3 amp double pole fused isolating
switch with contact separation of at least 3mm on both poles.
Alternatively, a fused 3 amp, 3 pin plug and unswitched socket
may be used, provided it is not used in a room containing a bath
or shower, it. It should only supply the appliance.
Water Supply
The boiler is suitable for sealed systems only. The maximum
working pressure for the appliance is 6 bar. All ttings and
pipework for the appliance should be of the same standard. If
there is a possibility of the incoming mains pressure exceeding
6 bar, particularly at night, then a suitable pressure limiting valve
must be tted.
The boiler is designed to provide hot water on demand to
multiple outlets within the property. If there is a requirement for
greater demands, for example if the boiler has several bathrooms
and cloakrooms, a vented or unvented hot water storage system
may be used.
Showers
Any shower valves used with the appliance should be of a
thermostatic or pressure balanced type. Refer to the shower
manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The boiler is equipped with a stainless steel heat exchanger.
Any treatment of water by additives in the system for frost
protection or for corrosion inhibition has to be absolutely suitable
for all metals used in the circuit.
The use of a corrosion inhibitor in the sysem such as Fernox
MB-1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is
recommended to prevent corrosion (sludge) damaging the boiler
and system;
If anti-freeze substances are to be used in the system, check
carefully that they are compatible with the metals used in the
circuit.
ARISTON suggests the use of suitable anti-freeze products such as
Fernox ALPHI 11, which will prevent rust and incrustation taking
place.
Periodically check the pH balance of the water/anti-freeze mixture
of the boiler circuit and replace it when the amount measured is
out of the range stipulated by the manufacturer (7 < pH < 8).
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under- oor systems, the use of plastic pipes without protection
against penetration of oxygen through the walls can cause
corrosion of the systems metal parts (metal piping, boiler etc),
through the formation of oxides and bacterial agents.
To prevent this problem it is necessary to use pipes with an “oxygen
proof barrier”, in accordance with standards DIN 4726/4729. If
pipes of this kind are not used, keep the system separate by
installing heat exchangers of those with a speci c system
water treatment.
IMPORTANT
Failure to carry out the water treatment procedure will
invalidate the appliance guarantee.
The detailed recommendations for water treatment are given in
BS 7593:1992 (Treatment of water in domestic hot water central
heating systems); the following notes are given for general
guidance.
If the boiler is installed on an existing system, any unsuitable
additives must be removed.
Under no circumstances should the boiler be red before the
system has been thoroughly ushed; the ushing procedure must
be in line with BS 7593:1992.
We highly recommend the use of a ushing detergent appropriate
for the metals used in the circuit. These include cleansers
produced by Fernox BetzDearbon, whose function is to disolve
any foreign matter that may be in the system.
In hard water areas or where large quantities of water are in the
system the treatment of water to prevent premature scaling of the
main exchanger is necessary.
The formation of scale heat compromises the e ciency of the
thermic exchanger because small areas of scale cause a high
increase of the temperature of the metallic walls and therefore
add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it
is necessary to treat the water with an appropriate corrosion
inhibitor.
System Controls
The boiler is electrically controlled and is suitable for most modern
electronic time and temperature controls. The addition of such
external controls can be bene cial to the e cient operation of the
system. The boiler connections for external controls are 12V DC
and so only controls of 12V DC that have voltage free contacts
should be used. (page 25).
ARISTON supply a range of wired and wireless system controls.
Contact your supplier for more details.
Location
The boiler can be installed on any suitable internal wall (suitable
sound proo ng may be required when installing onto a stud
partition wall). Provision must be made to allow for the correct
routing of the ue and siting of the terminal to allow the safe
and e cient removal of the ue products. A compartment or
cupboard may be used provided that it has been built or modi ed
for this purpose. It is not necessary to provide permanent
ventilation for cooling purposes. Detailed recommendations are
given in BS 5440 Part 2. If it is proposed that it is to be installed in a
timber framed building then reference should be made to British
Gas Document DM2, IGE/UP/7 or advice sought from CORGI.
Where a room sealed appliance is installed in a room
containing a bath or shower, the appliance and any electrical
switch or appliance control, utilising mains electricity should
be situated speci cally in accordance with current IEE Wiring
Regulations.
For unusual locations, special procedures may be necessary. BS
6798:2000 gives detailed guidance on this aspect.
12
installation
Codensate Discharge
The condensate discharge hose from the boiler must have
a continuous fall of 2.5o and must be inserted by at least
50mm into a suitable acid resistant pipe - e.g. plastic waste or
over ow pipe. The condensate discharge pipe must have a
minimum diameter of 22mm, must have a continuous fall and
preferably be installed and terminated to prevent freezing.
The discharge pipe must be terminated in a suitable position:
i) Connecting into an internal soil stack (at least 450mm above
the invert of the stack). A trap giving a water seal of at least
75mm must be incorporated into the pipe run, there also
must be an air beak upstream of the trap.
ii) Connecting into the waste system of the building such as
a washing maching or sink trap. The connection must be
upstream of the washing machine/sink. If the connection is
downstream of the waste trap then an additional trap giving
a minimum water seal of 75mm and an air break must be
incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level
iv) Into a soakaway
Note: If any condensate pipework is to be installed externally
then it should be kept to a minimum and be insulated with a
waterproof insulation and have a continuous fall. The total length
of external pipe used should not exceed 3 metres.
2. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste) and condensate siphon.
Tundish
trap
3. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste - proprietary tting).
Tundish
Some examples of the type of condensate terminations can be
found below.
1. Internal termination of condensate drainage pipe to internal
stack.
Tundish
trap
4. External termination of condensate drainage pipe via
condensate siphon
External pipe length
Tundish
max. 3 metres
(must be insulated)
Condensate Discharge
Push t the exible condensate pipe into the outlet spigot on the
appliance. Cut to length and locate outlet into a tundish
13
installation
Installing the Boiler
Please check that you are familiar with the installation requirement
before commencing work (pages 11 - 15).
The installation accessories described in the following list are
included in the boiler packaging:
- Hanging bracket
- A paper template (showing the dimensions of the boiler with
5 mm side clearances)
- Connection valves (compression)
- Screws and washers
- Filling loop
- Installation, Servicing and User manual
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct positioning
of kitchen cabinets etc.
The paper template has to be xed to the wall and used to locate
the position of the hanging bracket and the centre for the ue
hole.
Drill and plug the wall and secure the hanging bracket using the
screws provided ensure the hanging bracket is level. Remove the
boiler from its packaging and remove the front casing panel.
Place the boiler on the hanging bracket.
- Remove the boiler casing as described on page 15
- Remove the caps and connect the valves to the boiler using
the washers provided
- 5 x bre washers for the CH ow and return, cold water inlet, gas
and hot water outlet connections
Safety Valve Discharge
The pressure relief valve pipe is made of copper. It should
terminate below the boiler safely outside the premises. Care
should be taken that it does not terminate over an entrance or
window or where a discharge of heated water could endanger
occupants or passers by.
Warning !
Do not apply heat to the copper safety valve outlet pipe
whilst it is connected to the 3 bar safety relief valve.
Fill the central heating and DHW system and bleed air from the
system as described in the Commissioning instructions (page 31).
The system should be carefully checked for leaks, as frequent
re lling could cause premature system corrosion or unnecessary
scaling of the heat exchanger. The pipe from the trap should be
connected to a drain as described in the relevant regulations.
Note: Connections viewed from behind boiler
Note.
Connections viewed from
behind boiler.
CLAS HE EVO SYSTEM
Note: Connections viewed from behind boiler
Pay special attention not to bend the condensate silicone drain
pipe is such a way as to interrupt the ow. Please only use drain
pipe material compatible with condensate products (refer to BS
6798:2000).
The condensate ow can reach 2 litres/hour because of the acidity
of the condensate products (Ph close to 2), take care before
operation.
See page 13 for condensate discharge options.
14
A
A
- remove the 2 screws A from the transport bar
- dispose of the transport bar and reassemble
the xing screws.
installation
Gas connection
Make sure, using the labels on the packaging and the data plate
on the appliance itself, that the boiler is in the correct country
and that the gas category for which the boiler was designed
corresponds to one of the categories available in the country
where it will be used.
The gas supply piping must be created and measured out in
compliance with speci c legal requirements and in accordance
with the maximum power of the boiler.
Check that the supplied gas corresponds to the type of gas for
which the boiler was designed (see the data plate located on the
appliance itself).
It is also important to check that the pressure of the gas (methane
or LPG) you will be using to feed the boiler is suitable, because if it
is insu cient the power may be reduced, causing inconvenience
for the user.
Water connection
The illustration below shows the connections for the water and
gas attachments of the boiler. See valves con guration on page
14.
Check that the maximum water mains pressure does not exceed 6
bar; if it does, a pressure reducing valve must be installed.
For the measuring of the pipes and of the heating bodies in the
heating system, the residual head value should be calculated as a
function of the requested ow rate, in accordance with the values
shown in the circulation pump graph.
Instructions for opening the casing and performing an
internal inspection
Before performing any work on the boiler, rst disconnect it from
the electrical power supply using the external bipolar switch
removing the fuse and shutting o the gas valve.
To access the inside of the boiler, the following is necessary:
1. Remove the casing by unhooking it from the control panel (a)
2. Loosen the two screws on the front casing (b), pull it forwards
and unhook it from the upper pins (c)
3. Lower the control panel (d)
4. Unhook the two clips on the combustion chamber panel and
lift o (e).
(a)
(b)
(c)
CLAS HE EVO
(d)
E
D
F
A
I
F
A
I
C
B
H
CLAS HE EVO SYSTEM
E
D
C
H
(e)
A. Central heating Flow
B. Domestic Hot Water Outlet
C. Gas Inlet
D. Domestic Cold Water Inlet
E. Central Heating Return
F. Safety Valve Discharge
H. Drain Valve
I. Drain condensate
15
installation
To calculate the size of the heating installation, refer to the
"Available pressure" graph below.
Graph representing the available circulation pump pressure
o
T20
C
CLAS HE EVO
5
4,5
4
3,5
3
2,5
[mCE]
2
1,5
1
0,5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
[l\h]
CLAS HE EVO SYSTEM
6
5
4
3
[mCE]
2
1
0
0 100 200 300 400 500 600 700 800 900 1000
38
30
24
30
18/24
Under oor heating
For appliances with under oor heating, it is possible but not
necessary to t a safety thermostat onto the under oor heating
outlet. For the electrical connection of the thermostat see the
section on “Electrical connections - page 25”.
If the outlet temperature is too high, the boiler will stop both
domestic hot water and the heating production and the error
code 1 16 “ oor thermostat contact open” will appear on the
display. The boiler will restart when the thermostat is closed
during automatic resetting.
If the thermostat cannot be installed, the under oor heating
equipment must be protected by a thermostatic valve, or by a bypass to prevent the oor from reaching too high a temperature.
Before the equipment is used, for the rst time the trap
must be lled with water. To do this, add approximately
1/4 litre of water via the ue outlet before tting the ue
system, or unscrew the cap on the trap positioned underneath the boiler, ll it with water and re t it
Warning! Insu cient water in the trap can temporarily
cause the ue gas to be expelled into the surrounding
ambient air
I
16
Water circuit diagram
A
B
C
E
installation
1
3
4
5
6
7
8
10
11
12
A
B
C
D D E
22
21
20
19
18
17
16
15
14
13
1
3
4
5
6
8
10
11
12
A C E
22
21
20
19
18
17
14
1. Manual air vent
3. Burner
4. Detection electrode
5. C.H. ow temperature probe
6. C.H. return temperature probe
7. Secondary heat exchanger
8. C.H. pressure relief valve
10. By-pass
11. Drain valve
12. Condensate trap
13. Filling loop
14. C.H. circuit lter
15. D.H.W. Flow switch
16. diver ter valve
17. water pressure sensor
18. circulation Pump
19. expansion vessel
20. modulating Fan
21. ignition elec trodes
22. thermal fuse
17
installation
Connecting the Flue
Flue System
The provision for satisfactory ue termination must be made as
described in BS 5440-1.
The appliance must be installed so that the ue terminal is exposed to outdoor air.
The terminal must not discharge into another room or space such
as an outhouse or lean-to.
It is important that the position of the terminal allows a free passage of air across it at all times.
The terminal should be located with due regard for the damage
or discolouration that might occur on buildings in the vicinity, it
must also be located in a place not likely to cause nuisance.
In cold or humid weather water vapour may condense on leaving
the ue terminal.
The e ect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground
or above a at roof to which people have access, then a suitable
stainless steel terminal guard must be tted.
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are speci ed in Fig. 1.
Fig. 1
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
18
Minimum Length = 500mm
150mm
180mm
118mm
Fig. 2
installation
Warning
The exhaust gas ducts must not be in contact with or close
to in ammable material and must not pass through building
structures or walls made of in ammable material.
When replacing an old appliance, the ue system must be
changed.
Installation without extension
118
Installation with extension
slope
* pente
Important
Ensure that the ue is not blocked.
Ensure that the ue is supported and assembled in accordance
with these instructions.
Once the boiler has been positioned on the wall, t the rubber
ue seal into the internal ue turret (see diagram opposite),
Insert the elbow into the socket and rotate to the required
position. note: It is possible to rotate the elbow 360° on its vertical
axis.
Using the ue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal ue kit (3318073) supplied is suitable for
an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face
of the ue elbow (X - Fig 2), this gure must now be subtracted
from 753mm, you now have the total amount to be cut from the
plain end of the ue.
150 mm
* Min slope: 1˚
1˚= 17.5mm per metre
Fig. 3
Note: A Plume management kit is available for 60/100
horizontal termination. Instructions for installation are
supplied with the Plume management kit.
Draw a circle around the outer ue and cut the ue to the required
length taking care not to cut the inner ue, next cut the inner
ue ensuring that the length between the inner and outer ue is
maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the
ue).
Once cut to the required length, ensure that the ue is free from
burrs and reassemble the ue. If tting the ue from inside of
the building attach the outer wall seal to the ue terminal and
push the ue through the hole, once the wall seal has passed
through the hole, pull the ue back until the seal is ush with the
wall. Alternatively, the ue can be installed from outside of the
building, the outer seal being tted last.
Should the ue require extending, the ue connections are push
t, however, one ue bracket should be used to secure each metre
of ue.
Note: See table for maximum and minimum ue runs.
19
installation
Clamp
Screws
Seal
Fitting the 5” Flue (Ø 80 / 125 Horizontal/vertical)
Total length
of Vertical Kit
1240 mm
* This length will vary
according to the type
of ashing installed
Fig. 5
5" Adaptor
Part no: 3318095
180mm
Useable length
of Vertical ue
575 mm*
Fig. 4
Once the boiler has been positioned on the wall, it is necessary to
insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical
ue runs into the boiler ue socket (not supplied with ue kit Part No 3318095).
Push the adaptor onto the boilers ue connection, grease the seals
then add extensions or elbows as required, secure the adaptor,
using the clamp and screws provided.
To t extensions or elbows it is rst necessary to ensure that the
lip seal is tted correctly into the inner ue, once veri ed, it is
simply necessary to push them together, no clamps are necessary
to secure the ue components.
Before proceeding to t the ue, ensure that the maximum ue
length has not been exceeded (See the tables) and that all elbows
and bends have been taken into consideration, for each additional
90° elbow 1 metre must be subtracted from the total ue length,
and for each 45° 0.5 metres must be subtracted from the total ue
length (the height of the vertical adaptor and a 45° bend can be
seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical ue kit.
20
Fig. 6
Fig. 7
installation
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)
Total length
of Vertical Kit
1355 mm
Vert Adaptor
(supplied with ue kit)
Vertical Starter
Part No: 3318079
* This length will vary
according to the type
of ashing installed
180mm
Useable length
of Vertical ue
690 mm*
Note: See table for maximum and minimum ue runs.
The vertical ue kit is supplied with a specially designed weather
proof terminal tted, it can be used either with a at roof or a
pitched roof.
The Vertical ue kits useable lengths with the pitched roof
ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the maximum ue
length has not been exceeded (See the tables) and that all elbows
and bends have been taken into consideration, for each additional
90° elbow 1 metre must be subtracted from the total ue length,
and for each 45° 0.5 metres must be subtracted from the total ue
length (the height of the vertical adaptor and a 45° bend can be
seen in Fig. 8).
Mark the position of the ue hole in the ceiling and/or roof (see
Fig. 7 for distance from wall to the centre of the ue).
Cut a 130mm diameter hole through the ceiling and/or roof and
t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
Fig. 7
To connect the vertical ue kit directly to the boiler, place the
vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust
manifold and secure with the clamp, t the vertical adaptor onto
the vertical starter kit (note: there is no need to use a clamp to
secure this as it is a push t connection), the vertical ue kit must
then be inserted through the roof ashing, this will ensure that
the correct clearance above the roof is provided as the terminal
is a xed height.
Should extensions be required, they are available in 1 metre
(Part No. 3318077), 500mm (Part No. 3318078) and they must be
connected directly to the vertical starter kit before connecting the
adaptor to allow the vertical ue kit to be tted. In the event that
extension pieces need to be shortened, they must only be cut at
the male end and it must be ensured that the inner and outer ue
remain ush.
When utilising the vertical ue system, action must be taken to
ensure that the ue is supported adequately to prevent the weight
being transferred to the appliance ue connection by using 1 ue
bracket per extension.
When the ue passes through a ceiling or wooden oor, there
must be an air gap of 25mm between any part of the ue
system and any combustible material. The use of a ceiling plate
will facilitate this. Also when the ue passes from one room to
another a re stop must be tted to prevent the passage of smoke
or re, irrespective of the structural material through which the
ue passes.
Fig. 8
21
installation
Fitting the Twin Pipe (Ø80 / 80)
When siting the twin ue pipe, the air intake and exhaust terminals
must terminate on the same wall, the centres of the terminals
must be a minimum of 280 mm apart and the air intake must
not be sited above the exhaust terminal (refer to Fig. 10). The air
intake pipe can be run horizontally, however, the terminal and the
nal 1 metre of ue must be installed either horizontally or with a
slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be
constructed of insulated pipe to prevent condense forming on
the outside of the tube.
Ensure the exhaust tube has a minimum fall back to the boiler of
1˚ / metre (1˚ = 17.5mm/metre)
The maximum permissible ue length for twin ue is dependent
on the type of run used (see table on page 24).
For further information relating to ue runs not illustrated, please
contact the Technical Department on 0870 241 8180.
Note: See table for maximum and minimum ue runs.
Where it is not possible to terminate the ue within the distance
permitted for coaxial ues, the twin ue pipe can be used by tting
a special adaptor to the ue connector and using the aperture for
the air intake located on top of the combustion chamber.
Always ensure that the ue is adequately supported, using one
ue bracket per extension and avoiding low points. (ARISTON
supply suitable clamps as Part No. 705778).
To utilise the air intake it is necessary to:
1) Take the air intake cover o the top of the appliance
2) Assemble the ange on the header supplied with the boiler
3) Insert the header on the tube or the elbow up until the lower
stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten
it with screws.
The twin ue pipes can be tted with or without additional elbows
and need no clamps, simply ensure that the lip seal is inserted in
the female end of the ue pipe and push the extension piece fully
into the previous section of ue pipe or elbow, check that the lip
seal is not dislodged when assembling the ue (greasing the seal
will aid assembly).
Twin pipe can also be converted back to Coaxial ue to enable
vertical termination with a coaxial kit by using the pipe bridge
(Twin - Coaxial Adaptor - Part No. 3318089). When running the
twin ue pipe vertically.
It is not possible to terminate concentrically horizontally.
Termination is only possible with separate air and exhaust
terminals.
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.