Aprilaire 8355 User Manual

Page 1
Important Safety Information Warning:
Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off position before installing, removing, cleaning, or servicing thermostat.
Read all of the information in this manual before installing or programming this thermostat.
This is a 24V AC low-voltage thermostat. Do not install on voltages higher than 30V AC.
All wiring must conform to local and national building and electrical codes and ordinances.
Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.
1
7 Day Programmable 2 Heat / 2 Cool Heat Pump
MODEL 8355
User’s Manual
Installation and Programming
ELECTRONIC THERMOSTATS
®
Page 2
Features
• Four pre-programmed setpoints for each day of the week.
• Fast and easy programming for setting all days of the week simultaneously.
• Energy efficient recovery.
• Residual cooling for added air-conditioning efficiency.
• Two “AA” ENERGIZER brand batteries retain program memory, even during power outages.
• Low battery indicator.
• Multi-colored LED indicators for system status.
• Zone compatible as master thermostat.
• Fahrenheit/Celsius display option.
• Programmable from 45°F (7°C) to 90°F (32°C).
• Accuracy within ±1 degree.
• Adjustable temperature differential: 1-3 degrees.
• Maintains summer and winter programming.
Replacing Existing Thermostat
1. Turn off power to heating and cooling system.
2. Remove cover of old thermostat to expose wires. Do not disconnect wires. (Fig. 1)
3. Label wires per Table 1.
TABLE 1
Old Label New Label Description
R, V-VR or VR-R R 24 VAC
Y, Y1 or M Y1 Stage 1 Cooling/Heating Circuit
O or R O Reversing Valve (Cooling Mode)
B B Reversing Valve (Heating Mode)
G or F G Fan Contactor Circuit
Y2 Y2 2nd Stage Cooling Circuit
W1 or W2 or W-U W2 2nd Stage Heating Circuit
L or X L System Monitor LED
E E Emergency Heating Circuit
C, X or B C 24 VAC, Transformer Common Side
NOTE: This thermostat requires a 24V AC common wire for proper operation.
4. After labeling wires, remove wires from terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to install thermostat.
2
Page 3
FIGURE 1
Installing the Model 8355 Thermostat
NOTE: For new installations, mount thermostat on inside wall, 4-5 feet
above the floor. Do not install behind a door, in a corner, near air vents, in direct sunlight, or near any heat or steam generating fixtures. Installation at these places will affect thermostat operation.
IMPORTANT: This thermostat is compatible with 100% lockout systems. To reset the system, turn thermostat to OFF position for at least 60 seconds.
1. Turn power off to the heating and cooling systems.
2. Place COOL-OFF-HEAT-EM in OFF position.
3. Place FAN: AUTO-ON switch into AUTO position.
4. Remove the cover using a coin or screwdriver.
FIGURE 2
5. Place thermostat against the wall at desired location. Make sure wires will feed through opening on base of thermostat.
6. Mark placement of mounting holes. See Fig. 3. Set base aside.
3
E
M
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
FAN: AUTO-ON
COOL-OFF-HEAT-EM
Page 4
FIGURE 3
7. Drill the marked holes using a 3/16" drill bit. NOTE: Enclosed plastic anchors do not require a drilled hole for drywall.
8. Tap plastic anchors into the holes.
9. Align base with plastic anchors and feed wires through opening. See Fig 4.
FIGURE 4
10. Secure base to wall with supplied screws.
11. Connect wires to terminal strip. Refer to wiring diagrams on other side of this sheet. Make sure wire connections are secure.
12. Install two "AA" ENERGIZER brand batteries or equivalent into battery compartment. Be sure to match positive (+) ends of batteries with positive (+) battery terminals in the battery compartment.
13. Replace cover onto thermostat by snapping into place.
14. Turn on power to system. Test thermostat as described in the following section.
4
PROGPROG
MANMAN
Y2
Y1Y1
E G
W2
FAN AUTO ONFAN AUTO ON
COOL OFF HEAT EMCOOL OFF HEAT EM
CHANGECHANGE
SETSET PROG/MANPROG/MAN
AMAM PMPM
MORN DAY EVE NITE EER
O B
C L RC L R
MOUNTING HOLES
PROGPROG
MANMAN
Y2
Y1Y1
E G
W2
FAN AUTO ONFAN AUTO ON
COOL OFF HEAT EMCOOL OFF HEAT EM
CHANGECHANGE
SETSET PROG/MANPROG/MAN
AMAM PMPM
MORN DAY EVE NITE EERMORN DAY EVE NITE EER
O B
C L RC L R
OPENING
Page 5
Programming Guide
Set Time of Day, Day of Week, Temperature Differential, Residual Cooling
1. Press SET & PROG/MAN. Release simultaneously.
Press or to change Time of Day.
2. Press 3. Press
To Change Day of Week
4. Press 5. Press
To change 1st Stage
Temperature Differential
NOTE: The Temperature Differential is Factory preset at 1°. This means that whenever the room temperature changes by one full degree from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential.
6. Press 7. Press
To change 2nd Stage
Temperature Differential
NOTE: The Second Stage Temperature Differential is Factory preset at 2°.
8. Press 9. Press
To change
Residual Cooling
NOTE: The residual cool feature will keep the system fan on for an additional 30, 60 or 90 seconds after the compressor cycles off in cool mode. The residual cool feature can only be set in the cool mode.
5
>
>
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
SET PROG/MAN
SET P
1=MO 2=TU 3=WE 4=TH 5=FR 6=SA 7=SU
SET P
P
P
>
>
>
>
>
>
SET
>
>
SET
>
>
Page 6
Changing Fahrenheit (F) to Celsius (C)
Press and Hold SET Press
Release both simultaneously.
Energy Efficient Recovery
The energy efficient recovery feature looks ahead up to 2 hours prior to the end of the setback (or set-up) period to begin monitoring performance and calculating when to turn on your system. It also determines whether the aux­iliary heat or cool stages should be activated prior to setpoint time to meet your chosen setpoint temperature. The thermostat will indicate “EER” in the display when this program feature is active. The energy efficient recovery feature will lockout the auxiliary stages until 20 minutes prior to upcoming setpoint time to utilize the most energy efficient first stage. The auxiliary stages of heating and cooling will be available during this lock-out period to maintain the setpoint temperature should the system not be able to keep up with the heating or cooling demand.
Simple Programming Mode
1. Place COOL-OFF-HEAT-EM in COOL or HEAT position.
2. Press & Hold SET. Press the button. Release simultaneously.
3. The MORN indicator should be blinking. Program the Time-of-Day and the temperature as outlined in the Setting Daily Program section.
NOTE: Use this function to set all 7 days of the week with the same program.
6
SET P
SET P
>
>
COOL-OFF-HEAT-EM
>
PROG
>
>
SET PROG/MAN COOL-OFF-HEAT-EM
MAN
AUX CHECK EMER
FAN: AUTO - ON
Page 7
Setting Daily Programming
1. Place COOL-OFF-HEAT-EM in COOL position.
2. Press SET button. The display will show a number from 1 to 7. This number represents the day of the week to be programmed. If programming individual days, press either or button to adjust the day of the week to program (1=Mon., 2=Tues., etc.).
3. Press SET. Press or to change MORN time.
4. Press SET.
5. Press or to change MORN temperature.
6. Repeat Steps 2-5 for DAY, EVE, and NITE.
7. Press SET to finish this day.
8. Repeat steps 2–7 above to program any other day of the week.
9. Shift COOL-OFF-HEAT-EM to HEAT position.
10. Repeat steps 2-7 to program HEAT (winter) settings.
Begin Programmed Operation
1. Place FAN: AUTO-ON into AUTO.
2. Place COOL-OFF-HEAT-EM into COOL or HEAT, depending upon the season.
7
>
>
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
COOL-OFF-HEAT-EM
SET PR
>
>
>
>
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
SET PR
>
>
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
FAN: AUTO-ON
SUMMER
WINTER
COOL-OFF-HEAT-EM
COOL-OFF-HEAT-EM
COOL-OFF-HEAT-EM
>
>
Page 8
3. Press PROG/MAN button until indicator is in PROG position.
Temporary Program Override
To temporarily increase or decrease temperature
Press or
The thermostat will automatically return to the program at the next scheduled setting change or after four hours.
Manual Operation
Manual operation allows continuous override of the program settings.
1. Press PROG/MAN until indicator is in MAN position.
2. Press or to adjust temperature settings.
Reset
To reset the thermostat to factory pre-programmed conditions, press the reset button located directly to the right of the display.
8
>
>
PROG
MAN
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
>
>
PROG
MAN
PROG
MAN
SET PROG/MAN COOL-OFF-HEAT-EM
AUX CHECK EMER
FAN: AUTO - ON
>
>
>
>
AM PM
MORN DAY EVE NITE EER
>
>
NOTE: While in the Cool or Heat mode, once the thermostat turns the system off, a built-in delay keeps the compressor from turning on for about 5 minutes. This protects the compressor. No additional time delay relay (delay on break) is necessary.
RESET BUTTON
CHANGE
SET PROG/MAN
PROG
MAN
C L R
Y 2
Y 1
E G
W 2
O B
COOL OFF HEAT EM
FAN AUTO ON
Page 9
To Test Thermostat
WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS
VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: Do not switch system to cool if the temperature is below 50°F (10°C). This can damage the air conditioning system and cause personal injury.
1. Place the COOL-OFF-HEAT-EM switch into the COOL position
2. Press the button until the temperature setting is at least 3 degrees below the room temperature. The air conditioning system should turn on within a few seconds.
NOTE: While in the Cool or Heat mode once the thermostat turns the system off, a built-in delay keeps the compressor from turning on for about 5 minutes. This protects the compressor. No additional time delay relay (delay on break) is necessary.
3. Put the COOL-OFF-HEAT-EM switch into the OFF position. The air conditioning system should turn off. The fan may continue to run for a short period of time.
4. Put the COOL-OFF-HEAT-EM switch into the HEAT position.
5. Press the button until the temperature setting is at least 3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending upon the fan delay built into the furnace.
6. Put the COOL-OFF-HEAT-EM switch into the OFF position. The heating system should turn off. Once again, the fan may have a delay.
7. Put the FAN: AUTO-ON switch to the ON position. The blower fan should turn on.
8. Put the FAN: AUTO-ON switch to the AUTO position. The blower fan should turn off.
LED Indicators
The LED indicators are used to indicate system activity. The AUX indicator illuminates during a call for second stage heating. The auxiliary stages are used to maintain comfort during extremes in weather conditions. If the AUX LED is illuminated too frequently during periods of moderate temper­ature, check the differential settings (page 5).
The CHECK indicator is used to monitor system status. If the CHECK indicator is illuminated, call your local HVAC service provider.
The EMER indicator is illuminated only when the system switch is moved to the EM, emergency heat position. The EM position is only used when the primary stage of heat is not functioning or requires service.
9
COOL-OFF-HEAT-EM
COOL-OFF-HEAT-EM
COOL-OFF-HEAT-EM
COOL-OFF-HEAT-EM
FAN: AUTO - ON
FAN: AUTO-ON
>
>
Page 10
Troubleshooting
SYMPTOM REMEDY
10
Thermostat does not turn on system.
Check Wiring (see INSTALLATION).
Check fuse. Replace with 3 amp fuse if fuse has opened. Five minute compressor short cycle protection may be in effect. Press RESET to override. NOTE: This will
erase programming.
Thermostat turns on and off too frequently.
Increase Temperature Differential (see PROGRAMMING).
Display is blank, flashing or constant "LO BAT."
Replace batteries.
Time shown on display is not the current time of day.
Change time of day setting (see PROGRAMMING).
Thermostat does not follow program.
Thermostat in MANUAL mode (see PROGRAMMING).
Thermostat may not have been programmed in HEAT or COOL position. Verify program.
Check AM/PM indicators at time of day and programmed time changes (see PROGRAMMING).
Verify program and day of week is correct (see PROGRAMMING).
Thermostat does not advance day of week.
To view or change day of week use method on page 5.
If problems with thermostats cannot be solved, call:
Technical Support: 608-257-8801
Monday-Friday 7:45 am-5:00 pm CST
Page 11
11
Wiring Diagrams
The following is just a sample of the most common types of HVAC systems. Refer to your system’s installation manual for wiring information.
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO CARRIER
SPLIT SYSTEM CONDENSORS AND HEAT PUMP SYSTEMS
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
O
BG EW2LC
Y1
24 VAC, RETURN
R
COMPRESSOR CONTACTOR
Y
REVERSING VALVE [COOLING MODE]
O
FAN CONTACTOR CIRCUIT
G
EMERGENCY HEATING CIRCUIT
E
2ND. STAGE HEATING CIRCUIT
W2
SYSTEM MONITOR LED
L
24 VAC, COMMON
C
CARRIER LOW VOLTAGE TERMINAL BOARD
W3
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO
ROBERT SHAW 3000 SERIES HEAT PUMP SYSTEMS
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
24 VAC, RETURN
R
COMPRESSOR CONTACTOR
Y
REVERSING VALVE [HEATING MODE]
B
FAN CONTACTOR CIRCUIT
G
EMERGENCY HEATING CIRCUIT
E
2ND. STAGE HEATING CIRCUIT
W2
SYSTEM MONITOR LED
L
24 VAC, COMMON
X
COLEMAN LOW VOLTAGE TERMINAL BOARD
O
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
O
BG EW2LC
Y1
Y2
Page 12
12
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
Y
O
G
W1
W2
X
C
COMFORTMAKER LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO COMFORTMAKER
CYC SERIES HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
Field
Installed
Jumper
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
2ND. STAGE HEATING CIRCUIT
OUTDOOR THERMOSTAT [CAPPED]
DEFROST SENSOR [CAPPED]
24 VAC, COMMON
NOTE 1: E AND W2 TERMINALS
JUMPERED AT THERMOSTAT
NOTE 2: W2 TERMINAL ON
COMFORTMAKER PCB CAPPED
NOTE 3: X TERMINAL ON
COMFORTMAKER PCB CAPPED
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
Y
O
G
W1
W2
C
HEIL-QUAKER LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO HEIL-QUAKER
867.814 SERIES AND PH50 SERIES HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
2ND. STAGE HEATING CIRCUIT [SEQUENCER 1]
3RD. STAGE HEATING CIRCUIT [SEQUENCER 2]
24 VAC, COMMON
NOTE 1: E AND W2 TERMINALS
JUMPERED AT THERMOSTAT
NOTE 2: W2 TERMINAL ON
HEIL-QUAKER PCB CAPPED
Field
Installed
Jumper
Page 13
13
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO PAYNE
RELIANT AND ENDURA MODEL HEAT PUMP SYSTEMS
NOTE 1: W3 TERMINAL ON
PAYNE PCB CAPPED
24 VAC, RETURN
R
COMPRESSOR CONTACTOR
Y
REVERSING VALVE [COOLING MODE]
O
INAL BOARD
VOLTAGE TERM
PAYNE LOW
FAN CONTACTOR CIRCUIT
G
EMERGENCY HEATING CIRCUIT
E
2ND. STAGE HEATING CIRCUIT
W2
SYSTEM MONITOR LED
L
24 VAC, COMMON
C
3RD. STAGE HEATING CIRCUIT [CAPPED]
W3
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO RHEEM/RUUD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
O
BG EW2LC
Y1
HEAT PUMP SYSTEMS
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
O
BG EW2LC
Y1
24 VAC, RETURN
R
COMPRESSOR CONTACTOR
Y
INAL BOARD
VOLTAGE TERM
/RUUDLOW
RHEEM
REVERSING VALVE [HEATING MODE]
B
FAN CONTACTOR CIRCUIT
G
EMERGENCY HEATING CIRCUIT
E
2ND. STAGE HEATING CIRCUIT
W2
SYSTEM MONITOR LED
L
24 VAC, COMMON
X
B
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
Y2
Y2
Page 14
14
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
Y
O
G
X2
W-U
B
WEATHERTRON LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION
TO WEATHERTRON HEAT PUMPS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
2ND. STAGE HEATING CIRCUIT
24 VAC, COMMON
NOTE 1: E AND W2 TERMINALS
JUMPERED AT THERMOSTAT
NOTE 2: X2 TERMINAL CAPPED AT
WEATHERTRON PCB
NOTE 3: T TERMINAL CAPPED AT
WEATHERTRON PCB
T
Field
Installed
Jumper
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
Y
O
G
B
YORK LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO YORK
-E1CS, -E1FB, -E1FH HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
2ND. STAGE HEATING CIRCUIT
SYSTEM MONITOR LED
24 VAC, COMMON
NOTE 1: E AND W2 TERMINALS
JUMPERED AT THERMOSTAT
W
X
Field
Installed
Jumper
Page 15
15
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R
Y
O
G
E
W1
L
C
T
LENNOX LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO LENNOX
CB19 HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
EMERGENCY HEATING CIRCUIT
2ND. STAGE HEATING CIRCUIT
SYSTEM MONITOR LED
24 VAC, COMMON
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
V-VR
M
R
F
E
Y
X
LENNOX LOW
VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO LENNOX
HP19 AND HP20 HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
EMERGENCY HEATING CIRCUIT
2ND. STAGE HEATING CIRCUIT
24 VAC, COMMON
Page 16
Limited Warranty
Your Research Products Corporation Aprilaire®Thermostat unit is expressly warranted for two (2) years from date of installa­tion to be free from defects in materials and workmanship. Research Products Corporation’s exclusive obligation under this war­ranty shall be to supply, without charge, a replacement for any thermostat which is found to be defective within a two (2) year period and which is returned, together with the date of installation, no later than thirty (30) days after said two (2) year period by you to either your original supplier or to Research Products Corporation, Madison, Wisconsin 53701.
THIS WARRANTY SHALL NOT OBLIGATE RESEARCH PRODUCTS CORPORATION FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE THERMOSTAT ITSELF.
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURA­TION TO THE AFORESAID TWO YEAR PERIOD. RESEARCH PRODUCTS CORPORATION’S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WAR­RANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS THERMOSTAT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CON­TRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or con­sequential damages, so the above exclusion or limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R-VR
Y1
O
F
E
W1
X
LENNOX LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO LENNOX
HP21 WITH CB21 PCB HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [COOLING MODE]
FAN CONTACTOR CIRCUIT
EMERGENCY HEATING CIRCUIT
2ND. STAGE HEATING CIRCUIT
24 VAC, COMMON
L
Y2
R
Y1
O
BG EW2LC
Y2
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT
R-VR
M
R
F
E
Y
X
LENNOX LOW VOLTAGE TERMINAL BOARD
APRILAIRE MODEL 8355 HEAT PUMP THERMOSTAT CONVERSION TO LENNOX
HP22 WITH CB19 PCB HEAT PUMP SYSTEMS
THE LOW VOLTAGE TERMINAL DESIGNATIONS AND THEIR DESCRIPTION AND/OR
FUNCTION ARE USED ON ALL SPLIT SYSTEM CONDENSORS AND HEAT PUMPS
24 VAC, RETURN
COMPRESSOR CONTACTOR
REVERSING VALVE [HEATING MODE]
FAN CONTACTOR CIRCUIT
EMERGENCY HEATING CIRCUIT
2ND. STAGE HEATING CIRCUIT
SYSTEM MONITOR LED
24 VAC, COMMON
2ND. STAGE COOLING CIRCUIT
L
Y2
P.O. BOX 1467 • MADISON, WI 53701-1467
Products For Better Indoor Air Quality
B2202518 REV.12/00