Thank you for selecting this American Power Conversion Call-UPS II remote
control accessory. Whether you have the SmartSlot or external version, your
Call-UPS II has been designed for many years of reliable, maintenance-free
service in combination with your American Power Conversion Uninterruptible
Power Supply. American Power Conversion is dedicated to the development of
high-performance electrical power conversion and control products and we
hope that you will find this product a valuable, convenient addition to your
computing system.
Please read this manual! It provides installation and operating instructions
that will help you get the most from your Call-UPS II accessory.
Save this manual! It includes important instructions for the safe installation
of your Call-UPS II accessory. Further, it includes instructions for obtaining
factory service should the proper operation of the accessory come into
question.
Radio frequency interference
WARNING: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the users authority to operate
the equipment.
NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Shielded communications cables must be used with this unit
to ensure compliance with the Class A FCC limits.
This digital apparatus does not exceed the Class A limits for radio noise
emissions from digital apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.
Le présent appareil numérique német pas de bruits radioélectriques dépassant
les limites applicables aux appareils numériques de la Class A prescrites dans le
Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.
Triple Chassis 42
Symmetra Power Array 43
Daisy Chains 43
Smart-UPS ans Matrix-UPS 43
ii
1Introduction
1.1 Overview
American Power Conversion’s Call-UPS II is a remote UPS management
device that allows you to monitor and control your
It provides the following features:
APC UPS by modem.
•Remote
•Remote
UPS status display
UPS control (e.g., safe reboot during power
outage or when the server is down)
•Data and event logging
•Operator paging in case of trouble
Call-UPS II works with any
Symmetra
used with the
PowerNet
Callas a SmartSlot
TM
Power ArrayTM. It draws power from the UPS, and can be
APC Measure-UPSTM Environmental Monitor and the APC
TM
SNMP Adapter
UPS II comes in two versions: as an external device (AP9208) and
TM
card (AP9608). SmartSlot Call-UPS II mounts in all APC
APC Smart-UPS
TM
.
TM
, Matrix-UPS
TM
or
devices equipped with a SmartSlot. The external Call-UPS II connects to
the
UPS communications port.
1.2 Hardware Requirements
Call-UPS II requires an APC Smart-UPS, Matrix-UPS, Symmetra Power
Array or other
mote management, Callindustry standard
Call-
UPS II requires local DTE equipment — either a dumb terminal or a
computer running terminal emulation software (e.g., HyperTerminal). A
remote management site requires its own computer with modem and terminal emulation software. The communications rate for Callbe configured to 1200, 2400, 9600, and 19,200 baud. The default is
APC device equipped with a SmartSlot. For paging or re-
UPS II requires both a modem that understands
AT commands, and a telephone line. For configuration,
UPS II can
9600.
1
2Product Description
2.1 The Call-UPS II Panel
The SmartSlot Call-UPS II panel contains the management port and the
status indicator. See the figure below.
Management Port
Status
Smart SlotSmart Slot
AP9608 Call-UPS Remote Mgt Device
The external Call-UPS II rear panel contains the management port, status
indicator,
UPS monitoring port, and optional power jack. See the figure
below.
2.2 Management Port
The Call-UPS II management port is used for configuring Call-UPS II and
for remote management and paging by modem. For specifications, see
Sec. 6.1.
2.3 UPS Monitoring Port [External Version]
The UPS monitoring connector duplicates the signals from the UPS so
that the normal computer-tofor use with
APC software and interface kits only.
2
UPS connection is maintained. This port is
2.4 UPS Cable [External Version]
Use this cable to connect Call-UPS II to an APC Smart-UPS, Matrix-UPS,
Symmetra Power Array or other
APC smart device (Share-UPS or Triple
Chassis, for example).
2.5 Power Port [External Version]
The external version of Call-UPS II has a power port for an optional
power adapter. This adapter is not needed in most situations. Callnormally receives power from the UPS through the UPS connection cable,
giving Call-
UPS II protection from poor power conditions. After UPS
shutdown for low-battery condition, Call-UPS II will still draw power
from the
ity of the
UPS for a time determined by the size of the load and the capac-
UPS. However, Call-UPS II stops drawing power from the UPS
before the battery is completely drained.
To determine whether a power connector will be useful, refer to the two
paragraphs that follow. You can obtain a power adapter by contacting
APC technical support at one of the numbers given on the back cover of
this manual. The
APC part number for the power adapter is AP9505.
With Smart-UPS
The optional power adapter is required for some older Smart-UPS models
that do not supply power to CallSmart-
UPS supplies power to Call-UPS II, refer to the Smart-UPS user
UPS II. To determine whether your
manual. Plug the adapter into a wall receptacle if you want remote turnon and turn-off capability; otherwise, plug it into a Smart
(Smart-
UPS models 250, 370, and 400 cannot be turned on or off by
-UPS receptacle.
remote connection; for these models plug the adapter into a Smartreceptacle.)
UPS II
UPS
With Matrix-UPS
You will need the optional power adapter for use with Matrix- UPS only
if you want remote turn-on capability. Matrixremotely by Calllose power. The
the
UPS Control menu of Call- UPS II ) without causing Call-UPS II to lose
UPS II, but, without the adapter, Call-UPS II will then
UPS will execute a Graceful Reboot command (item 5 on
UPS can be turned off
power. Plug the power adapter into a wall receptacle if you want remote
turn-on and turn-off capability. Otherwise, plug it into a Matrix-
UPS
receptacle.
3
2.6 Status Indicator
The status indicator shows the following conditions.
STATU S LEDIN DIC ATI ON
OffCall-UPS
On ContinuouslyCall-UPS II is on with no user logged in.
Single short flashesUser is logged in or logging in.
Double short flashesLockout is in progress.
Rapid flashesCall-UPS II failed its power on self-test.
II
is off.
4
3Installation and Setup
3.1 Handling
Call-UPS II is sensitive to electrostatic discharge. It is shipped in a con-
ductive bag to help dissipate damaging static charges. Leave the product
in the bag until ready to install. Handle CallDo not touch the printed circuit board or other components.
3.2 Receiving Inspection
Once the Call-UPS II has been removed from its shipping container,
inspect it for damage that may have occurred while in transit. Notify
the carrier and place of purchase immediately if any damage is found.
The packing materials are recyclable and should be disposed of properly.
Please complete and return the enclosed warranty card.
Call-
UPS II is shipped with a null modem cable ( APC part number 940-
0103).
3.3 Installation
Before installing Call-UPS II, install your UPS. Then refer to the appro-
priate section that follows.
UPS II by the end plate only.
SmartSlot
If you are using a SmartSlot Call-UPS II with other SmartSlot devices,
refer to the appendix, “Multiple SmartSlot Installation” on pages 42 –43 .
While it is not possible to install the Calldamage the unit in the attempt to do so. Note the proper orientation of the
Call-
UPS II shown in the figure that follows. The sides of the printed cir-
cuit board align with the locating slots in the sides of the SmartSlot. In a
UPS, the SmartSlot may be oriented horizontally or vertically.
Use the following procedure to install the Call-
1 Shut down the protected loads and turn off the UPS.
2 Use a #2 Phillips head screwdriver to remove the two screws re-
taining the cover. Keep the screws handy for step 4 below. Retain
the cover for future use.
3 Orient the Call-
Slide the Callthe Call-
UPS II to fit in the SmartSlot as shown below.
UPS II all the way into the SmartSlot. The panel of
UPS II should be flush with the front face of the slot.
UPS II upside down, you can
UPS II:
5
4 Secure the Call5 Turn on the
UPS II with the screws removed in step 2.
UPS and the protected equipment.
External Version
It is not necessary to turn off the the UPS or its load before connecting or
disconnecting the external Callcause the
UPS to beep, or, if the UPS is powered off, to power on. This is
UPS II. When connected, Call-UPS II may
normal.
Use only
of Call-
APC-supplied cables to connect the external version
UPS II to the UPS. Do not connect to any Call-UPS II port
except as specified in these instructions. Connections using a
cable or any other manufacturer may cause damage to or
improper operation of Call-
UPS II, the UPS, or the computer.
If a device such as a server or workstation is currently using the communi-
cations port on the back of the UPS, disconnect it now according to the
UPS connection instructions. Connect that device securely to the UPS
Monitoring Port on Call-UPS II. See Sec. 2.5 to determine if the optional
power adapter is required.
3.4 Confirm Operation
Observe the status indicator on Call-UPS II. After a moment it should
be on continuously. If the indicator flashes rapidly, Callits power-on self-test. See Chapter 5.
6
UPS II has failed
3.5 Configure Call-UPS II
Call-UPS II requires on-site configuration before remote operation. You
will be able to change any of the settings later by the remote connection.
Follow these steps to configure Call-
•Communication parameters
•Password protection
•Time and date
•Paging (optional)
•Dial-back security (optional)
•Event logging (optional)
Initial Logging On
Connect DTE equipment (a dumb terminal or a computer running terminal emulation software) to the Management Port of Callsupplied null modem cable. It may be necessary to use an adapter (not
supplied) to connect the
DTE equipment to the null modem cable.
UPS II for:
UPS II using the
Set the communication parameters of the DTE equipment to
second, 8 data bits, no parity, and 1 stop bit (
With Call-
UPS II running (Status Indicator on steady), press CTRL+P
9600, 8, N, 1).
9600 bits per
(press and hold the CTRL key while pressing the P key). At the prompt:
Enter Password>
Type in APC and press ENTER.
Note:“
APC” is the factory default password for Call-UPS II. If the
default has been changed through previous configuration,
enter the changed password. Callcase sensitive. Enter
Call-UPS II by American Power Conversion Corp
(c) Copyright 1994,95,97 All Rights Reserved
Site ID: 12345678
Location: Physical Location of This UPS
Press Any Key To Continue...
7
Note the top line, which displays the model number of the
currently connected . Site
ID and Location are user configuration items.
UPS that is
The display shows the factory defaults.
Press any key to bring up the Main menu:
---------------------- MAIN MENU ------------------------
Date: Dec-16 '97 Time: 08:39:36
1- UPS Status
2- UPS Control
3- UPS Characteristics
4- Data/Event Logging
5- Call-UPS Settings
6- Paging Setup
7- Measure-UPS Info
?- Help
<ENTER> Display Menu
<ESC> End Session
>
Customize Settings
From the Main menu, you can go to the various menus by pressing the
number associated with each of them. Press 5, then
the Call-
UPS Settings menu. Set the date, time, password, location, and
baud rate from this menu. The baud rate should be set at
ENTER to bring up
9600. The other
menu items can be left alone for now. Note that any changes you make
are displayed when you return to the menu.
Then press
the Paging Setup menu, where you can change the Site
its default setting. If you will be using the paging capability of Call-
ESC to return to the Main menu. Type 6 and press ENTER for
ID number from
UPS
II, use this menu to enable and set up paging.
If you plan to use Calland press
ENTER for the Data/Event Logging menu. Proceed from there
UPS II for logging, go to the Main menu, type 4
to set up logging.
To change any of the changeable setting of the UPS and Call-UPS II, use
the other menus listed in the Main menu. For a full description of the entire menu scheme, see Section 4.
8
Any changes to Callof the session. Changes are made when Call-
UPS II communication settings are held until the end
UPS II issues modem com-
mands at that time.
Connect to Modem
Call-UPS II requires a modem for remote UPS control and paging. If a
modem is used with Callit. Plugging the modem into the protected power output of the
UPS II, some thought must be given to powering
UPS will
keep the modem operating in bad power conditions, but remote turn-on
of the
UPS will not be possible since, when the UPS is off, the modem
is off. By plugging the modem into a wall socket, remote turn-on of the
UPS will work, but the modem will have to get by with unprotected
power. Also, it is possible in this situation to miss pages, since the
modem would be off in a power outage that Call-
UPS II tries to report by
paging.
A better option is to use a modem designed for portable computers that
draws power from the computer. Callproviding protected power whether the
a modem that draws power from Call-
UPS II will power such a modem,
UPS is on or off. Be careful to use
UPS II, not a battery.
The configuration is complete. Disconnect the management device from
Call-UPS II. Connect the Call-UPS II according to the appropriate system
connection diagram on the following page.
Note: Use a standard modem cable to make this connection. Do not
use the null modem cable supplied with Call-
UPS II.
9
SmartSlot Configuration
External Configuration
10
4Operation
4-1 Logging On to Call-UPS II
For on-site logging on to Call-UPS II, see Section 3.5.
For remote logging on to Call-
the
UPS. After establishing communication, press CTRL+P. Call-UPS II
UPS II, connect via modem to the site of
prompts you for the password. Type in your password. (If you have not
changed the password, the default password is
APC.) The Opening
screen is diplayed. After pressing any key, the Main menu appears.
All Call-UPS II functions are available from the Main menu. To gain
access to one of the listed functions, type the associated number and
press
ENTER. To redraw the screen, press ENTER by itself.
Tip: Extensive online help is available throughout the menu
system. It is available whenever a “?” appears on a menu.
The “>” is the Call-
UPS II menu prompt. Call-UPS II uses the double
prompt “>>” to request a settable value. Some of these values can be
viewed by selecting them on the menu, pressing
through a list of possible settings and then pressing
SPACEBAR to cycle
ENTER to change the
setting to the current one listed.
Any time Call-UPS II responds to a command with the prompt “Are You
Sure?” Call-
UPS II requires confirmation of the command. Type YES in
uppercase letters at the prompt to confirm the command. Any other entry
aborts the command.
To return to the Main menu from another menu, press
ESC. Press ESC
from the Main menu screen to end the Call-UPS II session and hang up
the modem.
The paragraphs which follow give a description of the menus available in
the Main menu.
Note: Menu item 7 on the Main menu, Measure-
only if Call-
UPS II is used with a Measure-UPS environment
UPS Info, appears
monitor.
4.2 UPS Status [and Diagnostics]
The name and content of the first item on the Main menu varies according to the UPS being used. With a Smartitem is “
UPS Status.” When used with the Symmetra Power Array, the
UPS or a Matrix-UPS, the first
11
first item is “UPS Status and Diagnostics.” Refer to the appropriate
sections and accompanying tables that follow.
With Smart-UPS and Matrix-UPS
Type 1, then ENTER at the Main menu to display the status of the connected UPS.
Note: This example is from a Matrix-
UPS 3000. Other models may
not show this exact information.
------------------ MATRIX 3000 STATUS ------------------Utility Line: 241.2 VAC Battery Info
UPS Output: 235.6 VAC ------------------