Overview
The APC by Schneider Electric Rack Automatic Transfer Switch (ATS) provides reliable, redundant
power to single-corded equipment loads, such as servers. The Rack ATS has two input power cords
supplying power to the connected loads. If the primary source becomes unavailable or out of the
selected range, the Rack ATS will seamlessly source power from the secondary source without
interrupting critical loads.
The Rack ATS has built-in network connectivity, which allows for remote management via Web,
Telnet, SNMP, SSH or StruxureWare Data Center Expert
®
interfaces.
ATS sc h ematic
present in all models
Extra fuses present in
Front
-OK
-OK
-Warni ng
-Overload
-Warni ng
-Overload
x
x
Reset
Reset
Rear
Networ k
Networ k
Serial
Serial
Load
pdu0765a
Inlets: The two (2) C20 inlets support the connection of two power cords (not provided) to link the
ATS to two separate power sources (A, B). The switch draws power from the preferred source and
automatically switches to the secondary source when necessary.
Outlets: The outlets connect the ATS to equipment in the rack or enclosure, providing a redundant
source of power to the connected equipment. The switch has eight (8) C13 outlets and one (1) C19
outlet.
Specifications
Electrical
Nominal input voltage 230 Vac
Acceptable input voltage ±10% of nominal
Input frequency 50/60 Hz
Input connectors Two (2) C20 inlets
Output connectors
Maximum output current (outlet)
Maximum output/input current 16 A
Overload protection
Internal
External (recommended)
Transfer time
Short circuit current rating 10 kA
Eight (8) C13 outlets
One (1) C19 outlet
10 A–C13
16 A–C19
10 A–gang
Not provided with unit
16 A facility provided
10 ms maximum (high sensitivity, 50–60 Hz)
12 ms maximum (low sensitivity, 50–60 Hz)
Physical
Dimensions (H x W x D) 43.7 x 431.8 x 236.2 mm (1.72 x 17.00 x 9.30 in)
Shipping dimensions (H x W x D) 114.3 x 600.2 x 355.6 mm (4.50 x 23.63 x 14.00 in)
Weight 3.74 kg (8.25 lb)
Shipping weight 5.51 kg (12.15 lb)
Environmental
Maximum elevation (above MSL)
Operating
Storage
Temperature
Operating
Storage
Humidity
Operating
Storage
Compliance
EMC EMC Directive 2014/30/EU
Safety
Approved for IT Power Systems Yes
0 to 3000 m (0 to 10,000 ft)
0 to 15 000 m (0 to 50,000 ft)
–5 to 45°C (23 to 113°F)
–25 to 65°C (–13 to 149°F)
5 to 95%, non-condensing
5 to 95%, non-condensing
UL - EU / CE UL/EN/IEC 60950-1
LVD 2014/35/EU