Downflow—6–8 ton 39
Downflow—10–18 ton 40
Downflow—20–28 ton 41
Upflow front-return—6–8 ton 42
Upflow front-return—10–18 ton 43
Upflow front-return—20–28 ton 44
Upflow rear-return—6–8 ton 45
Upflow rear-return—10–18 ton 46
iiAPC NetworkAIR AFX Series: Contents
Upflow rear-return—20–28 ton 47
Indoor rear-discharge centrifugal condenser—6–8 ton 48
Indoor rear-discharge centrifugal condenser—10–18 ton 49
Indoor rear-discharge centrifugal condenser—20–28 ton 50
Indoor top-discharge centrifugal condenser—6–8 ton 51
Indoor top-discharge centrifugal condenser—10–18 ton 52
Indoor top-discharge centrifugal condenser—20–28 ton 53
Key to the model number 55
Air-cooled condenser—physical data 56
Air-cooled condenser—electrical data 57
Single-fan air-cooled condenser—6 ton 58
Dual-fan air-cooled condenser—6–14 ton 59
Triple-fan air-cooled condenser—14–20 ton 60
Dual-fan air-cooled condenser—20–26 ton 61
Triple-fan air-cooled condenser—26–28 ton 62
IntroductionThe APC AFX series precision air-conditioning system provides compact,
quiet, efficient, and reliable system solutions in the expanding precision airconditioning market. The AFX series is offered in a wide variety of
capacities, configurations, and air patterns within an extremely compact
cabinet size.
Precision environmental control requirements now reach far beyond the
confines of the traditional data center or computer room to encompass a
larger suite of applications, referred to as technology rooms.
Typical technology room applications included:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• Archives
• LAN environments
A worldwide network of APC representatives is fully qualified to provide
engineering, sales, installation and service for our products.
Our commitment to quality is demonstrated by the APC industry-leading
two-year parts warranty.
CapacityAvailable are 6 through 28 nominal tons (20 kW–96 kW) in nine models and
3 cabinet designs.
Air patternDownflow units discharge air into the raised floor plenum eliminating the
need for air distributing ductwork. This enables the owner to locate the unit
where space is available or relocate the unit as the room changes or expands.
These units are suitable for areas with raised floors greater than 12" (305
mm) high. Air is drawn in through the top of the unit. Downflow units also
include a static regain duct which increases performance and efficiency while
reducing noise level.
Upflow units discharge air into either a plenum or ductwork. These units are
suitable for areas with raised floors less than 12" (300 mm) high. Air is drawn
in through the front on the standard design or optionally from the rear of the
unit.
ControlThe microprocessor controller provides advanced integrated system
operation and management ensuring simple, reliable and precise temperature
and humidity control.
APC NetworkAIR AFX Series: Overview3
ConfigurationAir-cooled. Unit used with an air-cooled condenser. Refrigerant lines must
be run between the indoor unit and the condenser. Air cooled units require
low maintenance and have low operating costs.
Configurations are:
• Air-cooled with remote outdoor condenser.
• Air-cooled with indoor floor mounted condenser.
Wat er-c ooled. Unit used with a cooling tower or other source of water. Field
refrigeration piping is eliminated by a factory sealed and tested system. Water
piping to and from the unit is required.
Glycol-cooled. Unit used with a drycooler. The need for field refrigeration
piping is eliminated by a factory sealed and tested system. The glycol piping
is sealed, eliminating costly water treatment often encountered with open
cooling towers.
Remote-condensing. Unit used with a remote air-cooled condensing unit
which includes the compressor(s). This allows key maintenance procedures
to be located outside the critical environment helping eliminate access by
maintenance personnel in high security areas.
Front accessThe AFX Series has full service front access for routine servicing of
components. Front access also narrows the footprint of the unit making it
possible for units to be placed side by side.
Humidity controlHumidity is managed through a self-contained steam canister humidifier for
maximum efficiency and ease of maintenance. Dehumidification control is
assured with a split evaporator coil which decreases the humidity level
without over-cooling the space, therefore reducing the need for electric
reheat.
ComplianceThe AFX Series has received agency approvals by ETL and MEA #223-99-E.
Electrical systems comply with NEC and UL 1995 standards.
The microprocessor controller provides state of the art control for a wide
variety of environmental applications including the demanding requirements
of data centers, control rooms, clean rooms, switch rooms, MRI facilities,
CAT scan facilities and UPS Rooms. Operator Interface is provided by the
four-line, 80-character backlit LCD display. A user-friendly menu structure
along with clearly defined prompts allow the operator to easily move about
the program. Within the configuration menu the operator will find numerous
selections allowing the AFX to be tailored to meet specific requirements.
Sta tus. Complete status monitoring is provided within the status menu of the
microprocessor controller.
Available information includes:
• Current temperature• Cooling status
• Current humidity• Heating status
• Temperature setpoint• Humidification status
• Humidity setpoint• Dehumidification status
Alarms. Quick access to any alarm condition is facilitated through the menu
structure. The alarm key acts as a hot key, providing immediate access to the
alarm display menu. Presence of a new alarm will sound the audible alarm.
The red alarm LED on the display panel will remain illuminated until all
alarms have been cleared. The temperature and humidity alarm setpoints are
adjustable.
Alarm annunciations include:
• Loss of airflow• High temperature
• Clogged filter• Low temperature
• High head pressure• High humidity
• Low suction pressure• Low humidity
Setpoints. The microprocessor is provided with independent setpoints for:
• Heating• Humidification
• Cooling• Dehumidification
Automatic setpoint crossover protection will prevent the setting of the heat
setpoint above the cool setpoint and the humidify setpoint above the
dehumidify setpoint. Setpoint adjustment can be restricted to only operators
with knowledge of the security codes set within the security menu structure.
Configuration. Flexibility is offered through the use of the configuration
menu. Operating requirements are satisfied by changing the configuration
settings. New configurations are stored in EEPROM and protected from
unauthorized tampering by the four-digit security password, selected in the
security menu.
APC NetworkAIR AFX Series: Standard Features7
Configuration options include:
• Fahrenheit or celsius display• Alarm input polarity
• Compressor minimum on time• Alarm enable
• Compressor minimum off time• Temperature deadbands
• Power loss restart time delay• Humidity deadbands
• Redundant unit grouping• Small room delay
Common alarm contact. A common alarm relay is installed on every
microprocessor. In the event of an alarm condition, the relay will change
state. The user can select which alarms change the state of the relay. This
feature allows for remote enunciation of alarm status.
Run times. The major components within the unit (motor,humidifier, and
compressor) have independent run timers that monitor and store accumulated
run hours on the components. The run timers are provided with operator
adjustable run time alarms.
Security. Multiple security levels prevent unauthorized adjustment of
important system parameters. The user may select a four-digit password for
setpoint and configuration changes. Should the password be forgotten, APC
can provide temporary access.
Monitoring. With the addition of a network communications card the
microprocessor may interface with the locally installed APC remote
monitoring and control system. Gateways are available for interfacing with
building management systems. Please check with APC for compatibility with
your building management system.
Cool inhibit. Prevents the unit from over-cooling during the
dehumidification cycle. If the space temperature falls below a user adjustable
setpoint, cooling will become inhibited until the space temperature returns to
setpoint.
Cool override. A manual toggle switch will allow one compressor operation
in the event of a microprocessor failure. The cool override can be field wired
to a snap acting thermostat for cooling control.
Remote shutdown. Events external to the unit, such as activation of a fire
suppression system may require the unit to shut down remotely. Additionally
this feature may be tied into a BMS that would allow remote control of the
units on/off status.
Remote relay shutdown. Remote shutdown of the NetworkAIR system
can be done by a factory installed relay. The relay can be ordered with a 24,
120, or 240 volt coil. The relay must be powered by others to disable the
NetworkAIR system.
Overall cabinetThe frame is constructed of heavy gauge steel for maximum strength. Steel
access panels are insulated for quieter operation. The unit has been designed
for full service access from the front. The flush mounted panels are
removable using convenient quarter-turn fasteners. The access doors for the
electronic controller and electrical panel can be opened without interrupting
the operation of the unit.
8APC NetworkAIR AFX Series: Standard Features
Blower assemblyThe AFX series includes multiple, centrifugal blower assemblies that have
been engineered for quiet, reliable operation. Lower blower speeds reduce
noise and extend belt and bearing life to 200,000L
lubricated bearings, a single-belt variable pitch drive, and an adjustable
motor base all ensure dependable operation. In addition, the air return
patterns evenly distribute air across the cooling coil.
hours. Permanently
10
Electrical panelThe electrical panel contains the contactors, starters, overload protection
devices, and input power circuit breakers. Each wire (except jumpers) is
numbered every 3" (80 mm), or color coded to facilitate circuit tracing when
installing and servicing the unit. Each AC power circuit is individually
circuit-braker protected on all three phases. All compressor and motor
devices are thermally and short circuit protected. The electrical panel is
easily accessible from the front of the unit, and its modular construction
allows access to major components within the unit cabinet. An emergency
cool override switch can be manually activated to initiate cooling and a field
wired thermostat can be utilized to control cooling operation. All electrical
components are UL-listed and-recognized and all wiring conforms to NFPA
70 (NEC) and UL 1995 requirements.
HumidifierThe humidifier utilizes a pure steam generator specifically designed for hi-
tech area environmental control. The pure steam eliminates contaminating
mineral deposits, potentially deadly bacteria, white dust and excessive
humidity. The humidifier requires little or no scheduled maintenance.
Automatic flushing combined with an indicator that signals when the canister
is to be changed, ensure maintenance free operation.
Electric reheatA three-phase electrical resistance heater sized to offset the sensible cooling
capacity in the dehumidification mode is incorporated in each AFX series
unit. The reheat elements are low watt density sheathed components. The
reheat is three phase to provide even phase loading. Reheat elements are
electrically and thermally protected.
Refrigeration system
and compressor
The refrigeration system operates under an automatic microprocessor
controller for greater efficiency and accuracy. The heavy-duty compressors
are designed for year-round operation with a 15-year life expectancy. The
performance of the refrigeration system is enhanced by use of Scroll
Compressor Technology. Scroll compressors offer many advantages over
older technology semi-hermetic compressors. Vibration in the system is
greatly reduced by elimination of the reciprocating masses found in the semihermetic compressor. Risk of refrigeration leaks at compressor gaskets are
eliminated with the scroll compressors fully welded hermetic shell. The
design of the scroll is more tolerant to liquid flood back than the traditional
reciprocating compressor. Power consumption at full load is greatly reduced
with higher EER’s of the scroll. In addition reliability is enhanced due to the
fewer moving parts required using scroll technology. The end result is a
refrigeration system that offers the user optimized performance, efficiency
and reliability.
APC NetworkAIR AFX Series: Standard Features9
Each refrigeration system includes:
• Thermal expansion valve with equalizer
• High and low pressure switches
• Sight glass with moisture indicator
• Filter drier
• Liquid line solenoid valve
Cooling coilThe AFX utilizes dual distributors on one circuit of the refrigeration system.
During dehumidification the smaller distributor is turned off effectively
reducing the active circuits of the evaporator coil. During this mode of
operation the evaporating temperature is decreased, resulting in a lower coil
surface temperature. This reduction of the coil temperature decreases the
sensible heat ratio of the coil allowing a greater percentage of moisture
removal. Additionally the warmer air leaving the inactive circuits of the
evaporator coil blends with the near saturated air from the active circuits
raising the dry bulb temperature of the blended air well above saturation.
CondenserWater-and glycol-cooled systems employ a brazed plate condenser that uses
the latest heat transfer technology. Type 316L stainless plates are brazed
together in a vacuum furnace and comply with ASME pressure vessel code.
Pressure rating is 450 psi (3100 kPa).
Air filterThe filtration of conditioned air is extremely vital to maintaining the clean,
particle-free environment required by electrical equipment. The AFX Series
uses 30% efficient (ASHRAE 52.1–92), 4" (102 mm) deep filters, with full
depth filter pleats. In addition to high filtration properties, these filters
produce a lower pressure drop than standard filters so less energy is required
during normal operation. Filters are easily replaced from the top on
downflow units and from the front on upflow units.
Water-regulating
valves
The water-and glycol-cooled systems maintain proper performance by
sensing refrigerant discharge pressure and regulating the amount of water or
glycol supplied to the condenser. Two-way and three-way valves are
available. The standard valve pressure rating is 150 psi (1030 kPa).
Airflow sensorThe air proving switch is continuously monitored by the microprocessor.
Upon detection of a loss of air flow the microprocessor will deactivate:
cooling, heating, humidification and dehumidification. After the air flow has
been restored for a predetermined period of time the microprocessor will
reactivate the functions as needed.
Clogged filter alarmAn adjustable air pressure differently switch senses the pressure drop across
the filters. Upon sensing an excessive pressure drop, the switch activates the
alarm circuit of the microprocessor and displays a clogged filter message
simultaneously with an audible signal.
10APC NetworkAIR AFX Series: Standard Features
Emergency drain
pan
Systems are provided with two drain pans. The primary stainless steel
condensate drain pan lies directly under the cooling coil. A secondary
emergency drain pan provides additional protection by catching any water
before it reaches the subfloor and becomes a problem. An optional factory
supplied water detector in the emergency drain pan functions as your early
warning system in the event of any water problems. A threaded flange is
factory supplied for secondary drain connections. A secondary drain pan is
not provided on bottom return or precool units.
APC NetworkAIR AFX Series: Standard Features11
Optional Features
The following optional features are available on the AFX Series unless
otherwise noted. Certain combinations of options may not be available.
Emergency/
environmental
External
components
Smoke detector(s). The factory installed smoke detector(s) is designed to
sense smoke concentration in the return air stream. Upon detecting smoke
concentration an audible and visual alarm on the microprocessor will be
activated and the unit will immediately shut-down.
Firestat. A Firestat is available for installation in the air stream. If the return
air temperature reaches 125° F (52° C), the air conditioner will be turned off
and both an audible and visual alarm will be activated on the microprocessor.
Water detector(s). The solid-state water detector(s) activates an audible
and visual alarm on the microprocessor when moisture is detected. The water
detector is provided with 15' (5 m) of wire. Multiple detectors can be used in
the optional secondary drain pan in the sub floor.
Essential/non-essential lockout. When facilities have limited backup
power capacity, this lockout prevents the operation of electrical loads that are
not essential for continued site operation.
Floorstand. The heavy gauge floorstand raises the unit above the subfloor to
match the height of the raised floor. Heights are available from 6" to 36" (12"
to 36" for downflow units) in 3" increments and are adjustable +/- 1.5".
Adjustment is provided by threaded pedestals. Vibration absorbing pads are
included. The floorstand, pedestal and pads ship loose. Floorstands are
available for seismic applications.
Air deflector. An air deflector ships loose and attaches to the floorstand for
changing air direction from vertical to horizontal.
Plenum. The discharge plenum mounts on top of the upflow unit to direct
and distribute conditioned air. Manually adjustable, double deflecting grilles
are provided on 3 or 4 sides.Plenum shall be painted to match the color of the
unit.
Duct flange. A 1" (25 mm) duct flange is installed on a unit to provide
convenient connection to external ductwork. The duct flange can be installed
at the air outlet on upflow units, or at the air inlet on downflow units.
APC NetworkAIR AFX Series: Optional Features13
Control/monitoringCustom alarm dry contact closures. Each unit can be equipped with any
or all of the listed dry contact closures. Upon activation of the associated
alarm, a discreet Normally Open or Normally Closed contact is available for
remote monitoring of that discreet alarm.
• High Temperature Alarm
• Low Temperature Alarm
• High Humidity Alarm
• Low Humidity Alarm
• Compressor High Pressure Alarm
• Fan Status Alarm
• Change Filter Alarm
• Fire Alarm (with addition of optional firestat)
• Smoke Detector Alarm (with addition of optional smoke detector)
• Humidifier Change Canister Alarm
• Water Underfloor Alarm (with addition of water detector)
• Additional Common Alarm
Redundant group control. Allows up to six NetworkAIR units the ability
to communicate with each other to automatically switch upon alarm
condition, or timed rotation. Can also allow standby units the ability to assist
the running system.
Remote display panel. The microprocessor controller allows facility or
building-maintenance personnel to evaluate and control the unit from up to
50 ft. away from the unit, without having to enter the secured space.
Remote sensor(s). Environmental sensors can be strategically placed, up to
50 ft. from the unit to better meet the site’s cooling needs. The sensor must be
positioned to permit air movement across the sensors.
Monitoring system. A PC-based monitoring application which provides
single terminal monitoring and control for up to 120 units. The Windowsbased operated program (except Windows NT) has status screens for
individual unit conditions, mode of operation and alarms. The system
graphically presents temperature and relative humidity over time.
Temperature, relative humidity, alarm history, and other readings are stored
for future use.
Environmental monitoring unit. A stand-alone unit which performs
continuous temperature and humidity sensing through two available probes
(one included) and contact monitoring. The unit is controlled by available
web, control console, or SNMP interface with network connection. In the
event of an environmental anomaly, notification is sent to the customer via email or SNMP. The unit is 18.25" × 9" × 2.75" (464 mm × 229 mm × 70 mm)
and sits in or on top of a rack. The probes extend up to 12' (3.66 m) from the
unit.
14APC NetworkAIR AFX Series: Optional Features
ReheatHot water or steam reheat. An on/off solenoid valve for steam reheat, or a
modulating valve for hot water reheat maintains the dry bulb temperature
when the system is in dehumidification and heat mode. Completely factory
pre-piped, the system includes a copper tube, aluminum-fin reheat coil,
solenoid valve, float, and thermostatic and steam trap for steam reheat only.
Hot gas reheat. The copper tube, aluminum fin hot gas reheat coil
maintains the leaving dry bulb temperature when the system is in the
dehumidification mode. The coil is controlled by the microprocessor through
a factory-piped-and-wired three-way heat reclaim regulator and check valve
(water/glycol only).
System ComponentsPremium efficiency motor(s). High efficiency motors conserve energy
over periods of continuous fan operation.
High efficiency filter(s). Pleated final filters with an efficiency of 40% and
60% (ASHRAE 52.2), 4" (102 mm) deep, allow the removal of a greater
percentage of airborne particulate contaminates.
Prefilter(s). Intended to capture large airborne particulate contaminates,
thereby extending the life of the high-efficiency filter. Prefilters are 1" (25
mm) deep and easily disposable.
Condensate pump. The factory installed and wired condensate pump will
pump 36 gal/h (0.06 L/s) at 15 ft. (4.6 m) head.
High pressure water regulating valve(s). Water and glycol systems may
utilize an optional regulating valve, which operates with a maximum pressure
of 350 psi (2400 kPa), to automatically control condensing temperature.
Flared filter-drier connection. Flared threaded connections can be
provided on either side of the filter drier to expedite replacement.
Hot gas bypass. An auxiliary side-port hot gas bypass circuit. The
activation of the hot gas bypass circuit will maintain the evaporator coil
temperature during low load conditions. This optional feature will offer
longer compressor run times and minimize compressor cycling and
temperature fluctuations.
Pressure gauges. Suction and discharge pressure gauges may be provided
for the convenience of service personnel.
APC NetworkAIR AFX Series: Optional Features15
Performance Specifications
Net cooling capacity—air/remote condensing
80° F DB, 67° F WBTotal (BTUH)78,100 111,000 132,800 147,200 158,000 226,900 267,300 296,800 329,600
CAPACITY IN BTU/H6T8T10T12T14T18T20T26T28T
(26.7° C DB, 19.4° C WB)(kW)(22.9)(32.5)(38.9)(43.1)(46.3)(66.4)(78.3)(86.9)(96.5)
50% RHSensible (BTUH)72,50089,000 125,200 134,200 151,700 184,600 239,800 258,100 283,300
(kW)(21.2)(26.1)(36.7)(39.3)(44.4)(54.1)(70.2)(75.6)(83.0)
75° F DB, 62.5° F WBTotal (BTUH)72,800 103,100 123,300 136,300 148,900 210,300 248,700 279,200305,000
(23.9° C DB, 16.9° C WB)(kW)(21.3)(30.2)(36.1)(39.9)(43.6)(61.6)(72.8)(81.8)(89.3)
50% RHSensible (BTUH)70,90088,000 122,400 131,800 148,900 181,600 237,300 256,300 277,900
(kW)(20.8)(25.8)(35.8)(38.6)(43.6)(53.2)(69.5)(75.0)(81.4)
75° F DB, 61° F WBTotal (BTUH)73,100 101,700 124,500 137,000 149,000 205,500 251,500 281,100308,200
(23.9° C DB, 16.1° C WB)(kW)(21.4)(29.8)(36.5)(40.1)(43.6)(60.2)(73.6)(82.3)(90.2)
45% RHSensible (BTUH)73,10095,000 124,500 137,000 149,000 195,600 251,500 281,100 308,200
(kW)(21.4)(27.8)(36.5)(40.1)(43.6)(57.3)(73.6)(82.3)(90.2)
72° F DB, 60° F WBTotal (BTUH)69,70098,800 119,400 130,300 143,000 201,500 238,800 269,400 292,700
(22.2° C DB, 15.5° C WB)(kW)(20.4)(28.9)(35.0)(38.2)(41.9)(59.0)(69.9)(78.9)(85.7)
50% RHSensible (BTUH)68,70086,000 119,400 127,800 143,000 177,700 231,200 251,400 272,700
(kW)(20.1)(25.2)(35.0)(37.4)(41.9)(52.0)(67.7)(73.6)(79.8)
72° F DB, 58.6° F WBTotal (BTUH)70,20097,600 119,500 131,700 143,000 197,500 242,200 271,900296,500
(22.2° C DB, 14.8° C WB)(kW)(20.6)(28.6)(35.0)(38.6)(41.9)(57.8)(70.9)(79.6)(86.8)
45% RHSensible (BTUH)70,20092,500 119,500 131,700 143,000 191,100 242,200 271,900 296,500
(kW)(20.6)(27.1)(35.0)(38.6)(41.9)(56.0)(70.9)(79.6)(86.8)
70° F DB, 58.5° F WBTotal (BTUH)67,60096,000 116,100 126,800 139,100 196,000 232,400 262,600284,300
(21.1° C DB, 14.8° C WB)(kW)(19.8)(28.1)(34.0)(37.1)(40.7)(57.4)(68.0)(76.9)(83.2)
50% RHSensible (BTUH)66,90084,400 116,100 125,300 139,100 174,400 226,300 246,800 266,200
FLA= Full Load Amperes MOP=Maximum Overcurrent Protection WSA=Wire Size Amperes
*Values are calculated based on 3– phase power
APC NetworkAIR AFX Series: Electrical Data27
Steam/hot water/or no-reheat—18 –28 ton
HUMIDIFIERElectricStea m or None
VO LTAG E208230460575208230460575
18TFLA Air 85.782.541.132.969.367.733.726.9
Water79.376.137.930.362.961.330.524.3
Glycol89.986.744.134.573.571.936.728.5
Remote Condensing34.030.815.412.417.616.08.06.4
WSAAir113.7110.156.244.393.291.646.936.8
Water113.7110.156.244.393.291.646.936.8
Glycol113.7110.156.244.393.291.646.936.8
Remote Condensing42.538.519.315.522.020.010.08.0
MOPAir125.0125.070.050.0125.0125.060.050.0
Water125.0125.070.050.0125.0125.060.050.0
Glycol125.0125.070.050.0125.0125.060.050.0
Remote Condensing45.040.020.015.025.025.015.015.0
20TFLA Air 104.8 100.449.939.985.883.441.433.0
Water96.892.445.936.777.875.437.429.8
Glycol110.0105.652.541.991.088.644.035.0
Remote Condensing45.441.020.516.526.424.012.09.6
WSAAir144.7139.865.849.3120.9118.555.240.7
Water144.7139.865.849.3120.9118.555.240.7
Glycol144.7139.865.849.3120.9118.555.240.7
Remote Condensing56.851.325.620.633.030.015.012.0
MOPAir175.0175.080.080.0150.0150.070.050.0
Water175.0175.080.080.0150.0150.070.050.0
Glycol175.0175.080.080.0150.0150.070.050.0
Remote Condensing50.050.025.020.035.030.015.015.0
26TFLA Air 118.9 107.453.642.899.990.445.135.9
Water110.599.849.839.891.582.841.332.9
Glycol122.4110.655.244.1103.493.646.737.2
Remote Condensing45.441.020.516.526.424.012.09.6
WSAAir156.1151.266.753.8132.4130.056.145.2
Water156.1151.266.753.8132.4130.056.145.2
Glycol156.1151.266.753.8132.4130.056.145.2
Remote Condensing56.851.325.620.633.033.015.012.0
MOPAir175.0175.080.080.0175.0175.070.060.0
Water175.0175.080.080.0175.0175.070.060.0
Glycol175.0175.0100.080.0175.0175.090.070.0
Remote Condensing50.050.025.020.035.030.015.015.0
28TFLA Air 115.2 104.152.041.796.287.143.534.8
Water107.797.348.639.088.780.340.132.1
Glycol117.9106.553.242.798.989.544.735.8
Remote Condensing45.441.020.516.526.424.012.09.6
WSAAir156.1151.278.963.0132.4130.068.354.4
Water156.1151.278.963.0132.4130.068.354.4
Glycol156.1151.278.963.0132.4130.068.354.4
Remote Condensing56.851.325.620.633.030.015.012.0
MOPAir175.0175.0100.0100.0175.0175.090.070.0
Water175.0175.0100.0100.0175.0175.090.070.0
Glycol175.0175.0100.0100.0175.0175.090.070.0
Remote Condensing50.050.025.020.035.030.015.015.0
FLA= Full Load Amperes MOP=Maximum Overcurrent Protection WSA=Wire Size Amperes
*Values are calculated based on 3– phase power
28APC NetworkAIR AFX Series: Electrical Data
Indoor centrifugal condenser units
VO LT A GE208230460575
6TFLA8.68.44.23.6
WSA/MCA10.810.55.34.5
MOP15.015.015.015.0
8TFLA8.68.44.23.6
WSA/MCA10.810.55.34.5
MOP15.015.015.015.0
10TFLA17.216.88.47.2
WSA/MCA19.418.99.58.1
MOP25.025.015.015.0
12TFLA17.216.88.47.2
WSA/MCA19.418.99.58.1
MOP25.025.015.015.0
14TFLA17.216.88.47.2
WSA/MCA19.418.99.58.1
MOP25.025.015.015.0
18TFLA17.216.88.47.2
WSA/MCA19.418.99.58.1
MOP25.025.015.015.0
20TFLA25.825.212.610.8
WSA/MCA28.027.313.611.7
MOP35.035.015.015.0
26TFLA25.825.212.610.8
WSA/MCA28.027.313.611.7
MOP35.035.015.015.0
28TFLA25.825.212.610.8
WSA/MCA28.027.313.611.7
MOP35.035.015.015.0
FLA= Full Load Amperes MOP= Maximum Overcurrent Protection WSA/MCA=Wire Size Amperes/Minimum Circuit Amperes
*Values are calculated based on 3–phase power
APC NetworkAIR AFX Series: Electrical Data29
Guide Specifications
GeneralSummary. The environmental control system shall be designed specifically
for precision temperature and humidity control applications. It will
automatically monitor and control heating, cooling, humidifying,
dehumidifying, and filtering functions for the conditioned space. The system
shall be built to the highest quality engineering and manufacturing standards,
and shall be subject to a functional test prior to leaving the factory. The
system shall be floor mounted and configured for up/down discharge of
conditioned airflow, with draw-through air pattern, to provide uniform air
distribution over the entire face of the coil.
Design requirements. The system shall be as described in the following
specification as manufactured by APC.
Model AFX _____________________________________.
Total cooling capacity: ________________ MBH (kW).
Return air temperature: ________________ ° F (° C).
Dry bulb: ________________ ° F (° C).
Wet bulb: ________________% RH.
Air quantity: ________________ CFM (L/s) at 0.5" (125 Pa) external static
pressure.
Humidifier capacity: ________________ kW.
Electrical supply: __________ V, ______ ph, 60 Hz.
Submittals. Submittals shall be provided with the proposal and shall
include: capacity data, electrical data physical data, electrical connection
drawing and piping connection drawing.
Quality assurance. The system shall be completely factory-tested prior to
shipment. Testing shall include, but not be limited to: Completely charging
the system with refrigerant to ensure pressurized integrity, “Hi-Pot” test, and
controls calibration and settings. Each system shall ship with a completed test
report to verify completion of factory testing procedure. The system shall be
NTRL listed.
ProductMicroprocessor. The microprocessor controller shall provide total
environmental control. The system, based on the main controller, shall offer
up to eight analog inputs, two analog outputs, twelve digital inputs and
thirteen digital outputs. The operator interface shall provide a 4-line, 80character backlit LCD display. User-friendly menu structure along with
APC NetworkAIR AFX Series: Guide Specifications31
clearly defined prompts shall allow the operator to easily move about the
program and monitor the following functions and alarm conditions.
• Status: Complete status monitoring shall be provided within the status
menu of the microprocessor controller, and shall include the following
information: current temperature, current humidity, temperature
setpoint, humidity setpoint, cooling status, heating status, humidification
status, and dehumidification status.
• Alarms: Quick access to any alarm condition shall be facilitated
through the menu structure. Presence of a new alarm shall sound an
audible alarm. A red alarm LED on the display panel shall remain
illuminated until such time that all alarms have been cleared. Alarm
annunciation shall include: loss of air, clogged filter, high head pressure,
low suction pressure, high temperature, low temperature, high humidity,
low humidity. The temperature and humidity alarm setpoints are user
adjustable.
• Setpoint: The microprocessor controller shall provide independent
setpoints for heating, cooling, humidification, and dehumidification.
Automatic setpoint cross-over protection shall prevent the setting of the
heat setpoint above the cool setpoint, and the humidify setpoint above
the dehumidify setpoint. Setpoint adjustment shall be capable of being
protected via security code.
• Configuration: Flexibility shall be offered through the use of the
configuration menu. It shall closely match the operating requirements by
changing the configuration settings. The site configuration shall be
stored in the EEPROM and be protected from unauthorized tampering
by the user selectable 4-digit security password in the security menu.
Configuration options shall include: Fahrenheit or Celsius display,
compressor minimum off-time, power-loss restart time-delay, primarysecondary transfer functions, alarm input polarity, alarm enable,
temperature deadbands, humidity deadbands, and small room delay.
• Run time: The major components within the unit (motor, humidifier
and compressor) shall have independent run-timers that monitor and
store the accumulated run-hours on the components. The run timers shall
be provided with operator-adjustable run-time alarms for proper
component maintenance.
• Security: The microprocessor shall have multiple security levels to
prevent unauthorized adjustment of important system parameters. A
user-selectable 4-digit password shall allow setpoint and configuration
changes.
Cabinet and frame. The cabinet and frame shall be constructed from
welded structural steel. Access panels shall be flush with the frame and
insulated with fiberglass 1" (25 mm) in thickness, 1.5lb/ft
density.
The panels are powder coated and lift off for access to the unit. A piping and
electrical access plate shall be provided in the bottom of the unit. All units
require front and left side access, 24" (610 mm) minimum.
Blower system. The unit shall be configured for draw-through air pattern, to
provide uniform air-flow over the entire face of the coil. The blower shall be
32APC NetworkAIR AFX Series: Guide Specifications
3
(0.7kg/m3) in
double-inlet centrifugal type, with forward-curving blades, dynamically and
statically balanced. Each blower shall be independently driven by a highefficiency motor. The drive package shall be designed for 200% of the fan
motor horsepower. Minimum bearing life shall be 200,000 L
motor and blower shall be mounted on a common frame which is isolated
from the vibration of the unit frame. Each blower shall discharge conditioned
air into an insulated static-regain duct located within the downflow unit.
hrs. The
10
Electrical. The electrical system shall conform to National Electrical Code
(NEC) requirements. The control voltage shall be 24 VAC, wired in
accordance with NEC Class 1 requirements. The control circuit wire shall not
be smaller than 18-gauge AWG. Each wire shall end with a service loop and
be securely fastened by an approved method. Control wires more than 6"
(150 mm) shall be color-coded or numbered every 3" (80 mm) for ease of
service tracing. All electrically-actuated components shall be easily
accessible from the front of the unit. Each high-voltage unit shall be
individually protected on all three phases. Main power shall be connected to
a circuit breaker mounted on the electrical panel. The compressor and motor
shall have overload and short-circuit protection. The electrical box shall
include all components and controls required for system operation. An
emergency cool-override manual switch shall be provided with provision for
control using a field supplied thermostat.
• Incoming power is __________V, ______ ph, 60 Hz.
Humidifier. The humidifier(s) shall be self-contained steam-generating
type, factory piped and wired, with disposable cylinder and automatic solidstate control circuit.
• Capacity: ____________lb/h (g/s).
Reheat. The reheat elements shall be low watt density resistance type, sized
to offset the sensible cooling capacity in the dehumidification mode and shall
be electrically and thermally protected by Safety Agency approved safeties.
• Reheat capacity shall be __________ MBH, _______ kW,
controlled in ________ (#) steps.
Refrigeration system. Each refrigeration system shall consist of a fully
protected scroll compressor, evaporator coil mounted over an insulated
stainless steel condensate pan, adjustable expansion valve, filter–drier, liquid
line solenoid valve, sight glass, receiver, liquid line isolation valve, low
pressure switch and manual reset high pressure switch.
Cooling coil. The evaporator coil shall use the latest heat-transfer
technology, raised lanced-aluminum fins and rifle-bored copper tubes. Coil
end-supports shall be galvanized steel. To enhance dehumidification, the coil
shall be split into two circuits by a microprocessor-controlled solenoid valve.
An insulated stainless steel drain pan for condensate shall be included.
Air filters. The air filters shall be 30% efficient per ASHRAE Standard
52.1–92, UL Class 2. The full 4" (102 mm) deep, pleated filters shall be
replaceable from the top on downflow units and from the front on upflow
units.
APC NetworkAIR AFX Series: Guide Specifications33
Individual systemsAir-cooled system. The air cooled system shall consist of an evaporator
section including evaporator coil, blower package(s), controls and electrical
section and compressor(s). The condenser section shall be as follows:
• Outdoor propeller fan condenser: The outdoor condenser casing shall
be of aluminum, and all structural supports, coil frame, motor drive
supports, and mounting legs shall be made of galvanized steel. The
condenser shall have copper tubes expanded into aluminum fins.
Headers and connections shall be copper. The coil shall be pressure
tested and sealed for shipment. The condenser motors shall have
permanently lubricated sealed ball bearings, with internal overload
protection, and operate on __________-V, _____ -ph, 60-Hz power.
Motors shall be mounted inside the condenser casing for weather
protection, and shall be wired to a terminal strip in a weather-proof panel
on the unit. The direct drive, aluminum fan blade and painted steel hub
assembly, shall be protected by a heavy-gauge, vinyl-coated, steel-wire
fan guard. On multiple units, each fan section shall be separated by fullwidth baffles to prevent bypass air. The condenser shall be sized for
_________ ° F (° C) ambient, and condensing temperature controls shall
be fan speed for –20° F (–29° C) winter ambient. Flooded controls for –
40° F (– 40° C) optional.
• Indoor floor-mounted centrifugal fan condenser: The indoor floor
mounted condenser shall be a draw-through design and include quiet
belt-driven double-inlet centrifugal blower(s), and a condenser coil with
copper tubes expanded into aluminum fins. Belt(s) shall be sized for
200% of the system horsepower. All components shall be housed in a
corrosion-resistant, heavy-gauge, steel cabinet to match the evaporator
section in finish and construction, equipment with 1" (25 mm) supply
and return air-duct flanges. The condenser shall be sized for _______ ° F
(° C) ambient with condensing temperature controls for – 40°F (– 40°
C). The condenser section shall be remotely mounted suitable for
___________- V, _______ -ph, 60-Hz power.
• Models with air cooled condensing units: The air-cooled system shall
consist of an evaporator section including evaporator coil, blower
package(s), controls and electrical system. The remote air-cooled
condensing unit, including compressor(s), shall be housed outdoors in a
weather-resistant cabinet that shall allow service access through a
hinged panel. The condenser coil shall have rifled copper tubes and
enhanced aluminum fins. The coil shall be pressure-tested, and sealed
for shipment. The condensing unit shall be equipped with scroll
compressor(s) and crankcase heater(s), service valves, high and low
pressure controls, receiver with fusible plug, liquid shut–off valve and
charging port, liquid line filter–drier, and sight glass. The direct drive,
propeller fan, condensing unit motor(s) shall have permanently
lubricated sealed ball bearing, with internal overload protection, shall
operate on _______ -V,_______ -ph, 60-Hz power, and shall be mounted
inside the unit casing for weather protection. The standard condensing
unit shall be sized for 95° F (35° C) ambient, and controls shall be
flooded suitable for – 20° F (–29° C) winter ambient. Optional controls
for –30° F (–34° C) shall included insulated and heated receiver. The
condensing unit shall be field-wired and-piped to the evaporator section
and shall be suitable for remote outdoor installation.
34APC NetworkAIR AFX Series: Guide Specifications
Water-and glycol-cooled systems. The water/glycol-cooled systems shall
consist of an evaporator section including evaporator coil, b
contro
ls and electrical section, compressor(s), and a water/glycol-cooled
lower package(s),
condenser section. The condenser shall be stainless steel brazed plate design
and shall be controlled by 2-way (3-way optional) head pressure-regulated
valve(s). Maximum water pressure is 150 psi (1030 kPa).
• Outside heat exchanger (drycooler) for glycol cooled systems only:
The drycooler casing shall be of aluminum, and all structural supports,
coil frame, motor-drive supports, and mounting legs shall be made of
galvanized steel. The drycooler coil shall have copper tubes expanded
into aluminum fins. Headers and connections shall be copper. The coil
shall be pressure-tested and sealed for shipment. The drycooler motors
shall have permanently lubricated, sealed, ball bearings, and internal
overload protection. Motors shall be mounted inside the drycooler
casing for weather protection and wired to a terminal strip in a weatherproof panel on the unit. The direct-drive, aluminum fan blade and
painted steel hub assembly, shall be protected by a heavy-gauge, vinylcoated, steel-wire fan guard. On multiple fan units, each fan section shall
be separated by full-width baffles to prevent bypass air. The drycooler
shall be sized for 95° F (35° C) ambient, and operate on _______ -V,
______ -ph, 60-Hz power.
• Indoor floor mounted drycooler: The indoor floor-mounted drycooler
shall be a draw-through design and include a quiet belt-driven, double
inlet centrifugal blower(s), and a condenser coil with copper tubes
expanded into aluminum fins. Belt(s) shall be sized for 200% of the
system horsepower. All components shall be housed in a corrosionresistant, heavy-gauge, steel cabinet to match the evaporator section in
finish and construction, equipped with 1" (25 mm) supply and return air
duct flanges. The drycooler section shall be sized _________° F (° C)
ambient. The drycooler section shall be remotely mounted suitable for
__________ -V, ______ -ph, 60-Hz power.
• Single pump package for glycol cooled systems only: The pump
package shall be comprised of a centrifugal pump in a vented enclosure
with pump starter, separate drycooler fan and pump circuit breakers,
Aquastat, and fan cycling contractor(s) to control the fluid temperature.
The controls shall be mounted in a weather-tight box. An expansion tank
and Airtrol fitting shall be supplied for field installation. The pump size
shall be sized for ______ GPM (L/s) at ________ ft (m) external head,
and operate on _______-V, ______ -ph, 60-Hz power.
• Dual pump package for glycol cooled system only: The dual pump
package shall consist of two centrifugal pumps in an enclosure. Pump
starters, automatic pump switch-over controls, lead-lag pump selector
switch, separate drycooler fan and pump circuit breakers, aquastat, and
fan cycling contractor to control the fluid temperature shall be mounted
in a separate weather-tight box. An expansion tank and airtrol fitting
shall be supplied for field installation. Each pump shall be sized for
______GPM(L/s) at ______ft (m) external head, and operate on
______-V, ______ -ph, 60-Hz power.
APC NetworkAIR AFX Series: Guide Specifications35
OptionsSmoke detector(s). Smoke detector(s) shall be factory-installed in the
return air to sense concentrations of smoke and send a signal to the
microprocessor to shut down the unit and activate a visual and audible alarm.
Firestat. A firestat shall be factory-installed in the return air to sense heat
and send a signal to the microprocessor shutting down the unit and activating
a visual and audible alarm.
Water detector(s). Water detector(s) shall be factory-wired and shipped in
the bottom of the unit to sense water and send a signal to the microprocessor,
giving the operator possible alarm indications options for shutdown. The
water detector has a 15 ft (5 m) cable for mounting in the subfloor.
Remote sensor(s). The temperature and humidity sensors shall be shipped
loose in a 2" × 4" × 1.5" (51 mm × 102 mm × 38 mm) box and 50 ft (15 m) of
cable supplied for connection to the unit mounted controller.
Remote shutdown. A relay shall be factory installed in the unit with a two
pin terminal block to be field wired to a ______(24, 120, or 220 VAC) signal
which will shut down the unit control circuit when the signal is received.
Essential/non-essential lockout. An essential/non-essential lockout relay
shall be factory-installed and wired to a two-pin terminal block to prevent
operation of reheat or humidifier operation when a ______ (24, 120, or 220
VAC) signal is received.
Floorstand. An adjustable floorstand fabricated form heavy gauge steel
shall be provided. The height shall be adjustable from 6” to 36” (115 mm to
915 mm) on Upflow units and 12” to 36” (230 mm to 915 mm) on Downflow
units. Pedestals and vibration pads shall be included. Each pedestal shall be a
3/4" (19 mm) threaded rod, capable of a 2000-lb. (910 kg) vertical load. Zone
4 seismic floorstands shall ship loose and shall be _______ in (mm) high, up
to 36" (915 mm).
Air Deflector. A 90° air deflector shall ship loose and shall be _______ in.
(mm) high.
Top-discharge plenum. A top-discharge plenum shall be supplied with a
gasket material for mounting to an upflow unit. Manually adjustable, doubledeflecting grilles shall be provided on 3 or 4 sides. A combination of sound
lining and insulation material shall be used. Plenum height shall be 20" in
(508 mm) or 24" (610 mm).
Duct flange. A 1" (25 mm) duct flange shall be factory-installed on the top
of the upflow unit at the blower outlet.
Redundant group control. ________ (up to 6) units shall be capable of
being connected together to form a redundant group. The master
microprocessor controller shall monitor the status of the slave
microprocessor controllers and determine—based on run time alarm
conditions and local requirements, which the units in the redundant group
shall run.
Remote display panel. A remote microprocessor control display with
keypad shall be shipped loose in a 12" × 8" × 3"
(300 mm × 200 mm × 80 mm) box and 50 ft (15 m) of cable supplied for
connection to the units’ microprocessor logic board.
36APC NetworkAIR AFX Series: Guide Specifications
Monitoring system. The PC-based Supervisor System shall be shipped
loose for single-terminal monitoring and control of up to 120 units. The
program shall be run through Windows® and shall have status screens for
individual unit conditions, mode of operation and alarms. The System shall
graphically present temperature and relative humidity over time.
Temperature, relative humidity, alarm history, etc. shall be recorded for
future reference.
Environmental monitoring unit. An “EMU” shall ship loose complete
with one 12' (305 mm) probe and network connection.
Hot water reheat. The unit shall be supplied with factory installed copper
tube, aluminum fin, hot water reheat coil in place of electrical heater
elements. Capacity shall be ______ MBH (kW) with ______ GPM (L/s) of
_______ ° F (° C) entering hot water temperature. Hot water shall be
controlled with an on/off solenoid valve.
Steam re heat. The unit shall be supplied with a factory-installed copper
tube, aluminum-fin-reheat steam-coil in place of electrical heater elements.
Capacity shall be _______MBH (kW) with 5 psi (35 kPa) of saturated steam.
Steam shall be controlled with an on/off solenoid valve.
Hot gas reheat. The unit shall be supplied with a factory-installed copper
tube and aluminum fin hot gas reheat coil, in place of electrical heater
elements. Air-cooled systems using hot gas reheat shall also include flooded
condenser pressure controls. This is not available with remote-condensing
units.
Premium efficiency motor(s). Each motor shall have a premium
efficiency of no less than _______% per NEMA MG1-12.55.
High efficiency filter(s). Filters shall be_______% efficient per ASHRAE
Standard 52.1-92, UL Class2. The full 4" (102 mm) deep, pleated filters shall
be replaceable from the top on downflow units and from the front on upflow
units.
be installed upstream of the final filters to lengthen service life.
Condensate pump, factory installed . A factory installed and wired
condensate pump shall pump 36 gal/h (0.06 L/s) at 15' (4.6 m) head.
Condensate pump, ship loose. A condensate pump shall ship loose for
field installation and wiring. Wiring shall be 120 VAC plug-in type. A check
valve is also shipped loose. It shall have a capacity of 60 gal/h (0.06 L/s) at
15 ft (4.6 m) head.
350 PSI water regulating valves. The condensing temperature shall be
automatically controlled by 2-way (3-way) 350 psi (2400 kPa) water
regulating valve(s).
Flared connections for filter-drier. Flared connections shall be factory-
installed on either side of the filter-drier to allow easy replacement.
Hot gas bypass. The unit shall be supplied with a factory installed hot gas
bypass system to maintain efficient compressor operation during periods of
low load. The valve shall automatically control the amount of hot gas
bypassed to maintain the proper system capacity.
APC NetworkAIR AFX Series: Guide Specifications37
Dimensional Data
Downflow—6–8 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data39
Downflow—10–18 ton
*All dimensions in inches (mm)
40APC NetworkAIR AFX Series: Dimensional Data
Downflow—20–28 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data41
Upflow front-return—6–8 ton
*All dimensions in inches (mm)
42APC NetworkAIR AFX Series: Dimensional Data
Upflow front-return—10–18 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data43
Upflow front-return—20–28 ton
*All dimensions in inches (mm)
44APC NetworkAIR AFX Series: Dimensional Data
Upflow rear-return—6–8 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data45
Upflow rear-return—10–18 ton
*All dimensions in inches (mm)
46APC NetworkAIR AFX Series: Dimensional Data
Upflow rear-return—20–28 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data47
Indoor rear-discharge centrifugal condenser—6–8 ton
*All dimensions in inches (mm)
48APC NetworkAIR AFX Series: Dimensional Data
Indoor rear-discharge centrifugal condenser—10–18 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data49
Indoor rear-discharge centrifugal condenser—20–28 ton
*All dimensions in inches (mm)
50APC NetworkAIR AFX Series: Dimensional Data
Indoor top-discharge centrifugal condenser—6–8 ton
*All dimensions in inches (mm)
APC NetworkAIR AFX Series: Dimensional Data51
Indoor top-discharge centrifugal condenser—10 –18 ton
*All dimensions in inches (mm)
52APC NetworkAIR AFX Series: Dimensional Data
Indoor top-discharge centrifugal condenser—20 –28 ton
HP (kW)1/2" (.37)3/4" (.56)1" (.75)1.5" (1.1)2" (1.5)
VOLTAGEFLAMCAFLAMCAFLAMCAFLAMCAFLAMCA
208/1/605.46.87.69.58.811.011.013.813.216.5
230/1/604.96.16.98.68.010.010.012.512.015.0
208/3/602.43.03.54.44.65.86.68.37.59.4
230/3/602.22.83.24.04.25.36.07.56.88.5
460/3/601.11.41.62.02.12.63.03.83.44.3
575/3/600.91.11.31.61.72.12.43.02.73.4
FLA= Full Load Amperes MCA=Minimum Circuit Amperes
*Values are calculated based on 3-phase power
APC NetworkAIR AFX Series: Pump Specifications69
Guidelines for Installation
The AFX series provides reliable, accurate temperature and humidity control
of computer rooms, laboratories, and other environments that require close
tolerance control. The unit incorporates the latest system design innovations
to provide you with optimum efficiency, reliability, and accuracy of control.
The AFX system will provide years of trouble-free service, if it is installed
and maintained by technically qualified personnel.
Room preparationDuring the design of the room, consideration should be given to the
following factors: ease of entry for the system, floor-loading factors, and
accessibility of piping and wiring.
The room must be sealed with a vapor barrier to minimize migration of
moisture. Polyethylene film (plastic sheeting) is a good vapor barrier for
ceiling and wall applications. Rubber- or plastic-based paints should be
applied to concrete floors and walls. The room should be thoroughly
insulated to minimize thermal loads and make-up air (if required) should be
preconditioned to reduce additional temperature, filtration, and moisture
loads.
A room using a raised-floor plenum for air distribution should have at least
9" (300 mm) of clear space between the false floor and sub-floor for a
finished floor height of 12" (380 mm). Pay special attention to the location of
pipe chases, electrical conduits and other obstructions under the floor. These
objects can block air circulation and cause loss of air pressure, thus reducing
system efficiency and causing hot spots in your room.
Minimum clear space of 18" (460 mm) is to be provided for units over 15
tons (53 kW).
APC should be notified before installation if the unit is incorrect for the
application.
Unit locationThe location of the unit is important for efficient and balanced environmental
control in your room. The air conditioner should be located as close as
possible to the largest heat load. In rooms having a high aspect ratio, mount
the unit along the longest wall to ensure even air distribution. If improperly
installed, erratic control or mechanical failure can and will result if the unit
does not obtain proper air volume and distribution.
Service accessAt least 24" (610 mm) of clear space must be left in front of the unit for
routine service (belts, filters, humidifier). We strongly recommend
approximately 34" (860 mm) clearance in front of the unit.
Receiving the unitYour AFX unit has been completely tested and inspected prior to shipment.
To ensure that you have received the unit in excellent condition, perform a
careful inspection of the crating and the unit immediately upon receipt.
APC NetworkAIR AFX Series: Guidelines for Installation71
Verify that all parts ordered were received as specified and that the unit is the
correct size and voltage necessary to fulfill your environmental control
needs. Report any damage discovered to the freight carrier. If necessary,
contact the APC field service department for help in repairing or replacing
damaged parts. While APC is not responsible for damage incurred in transit,
we want to make sure that you have no undue delays in your system start-up.
RiggingThe unit is manufactured with a formed steel frame for maximum strength
and unit integrity. However, as with all electrical and mechanical equipment,
you must take care with proper rigging of your unit.
When using a forklift to move the unit, use the shipping skid to protect the
bottom of the unit. When using chains, cables or rope to lift the unit, use
spreader bars to prevent damage to the finished panel.
FloorstandInstall a threaded pedestal into each leg of the floorstand. Use the washer and
nut on each panel to tighten against the floorstand leg.
Utility connectionsAll connections are made through the bottom left of the unit (the left side of
upflow discharge units) for ease of service connections. Refer to the
installation manual for pipe sizes and specific locations for your unit.
Power unitThe AFX unit uses 3-phase power for operation. Bring the service cable
through the bottom left of the unit and through the bulkhead hole into the
electrical box to the circuit breaker provided on he left side of the electrical
box. The ground lug is located near the 3-phase high-voltage connector. THE
UNIT MUST BE UTILITY GROUNDED OR THE WARRANTY IS
VOID.
Humidifier
connections
The humidifier inlet connection is in the bottom of the mechanical section. A
1/4" compression connection is supplied with the unit.
Condensate drainCondensate from the evaporator pan and discharge from the humidifier
flushing system drain through a 7/8" ID drain trap in the bottom of the unit.
Water supply to
humidifier
1. The humidifier fill valve orifice is sized for supply water pressure from
30 PSIG (210 kPa) to 85 PSIG (590 kPa).
2. For cases above 90 PSIG (630 kPa), install a pressure-reducing valve in
the water feed line to the unit.
3. With extremely dirty or muddy water sources, proper filtration is
required on the units incoming water line.
4. DO NOT use softened water with the humidifier. Softened water is too
conductive.
5. DO NOT use completely demineralized water with the humidifier. The
minerals allow the electrode principle to work.
6. DO NOT use a hot water source. Doing so will cause deposits that will
eventually block the fill valve orifices.
72APC NetworkAIR AFX Series: Guidelines for Installation
7. Water supplies with high conductivity (above 700 µΩ) must be preconditioned for proper operation and longevity of the humidifier.
Water su pplyA 16- to 20-mesh strainer must be installed in the water supply to the water
and glycol units to prevent clogging of brazed plate condenser. This is a field
item.
OTE: Because of an ongoing program dedicated to product improvement,
N
specifications are subject to revisions without notice. APC assumes no
responsibility, and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
APC NetworkAIR AFX Series: Guidelines for Installation73
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
•Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents in the APC
Knowledge Base, and to submit customer support requests.
–www.apc.com
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
–www.apc.com/support
Global support with FAQs, knowledge base, and e-support.
•Contact an APC Customer Support center by telephone or e-mail.
–Regional centers:
(Corporate Headquarters)
.
APC Headquarters
(U.S. and Canada)
(1) (800) 800-4272 (toll free)
Latin America(1) (401) 789-5735 (United States)
Europe, Middle East,
Africa
(353) (91) 702020 (Ireland)
Japan(03) 5434-2021 Guidance 3
–Local, country-specific centers: go to www.apc.com/support/contact for contact information.
•Contact the APC representative or other distributor from whom you purchased your APC product for information