A.O. Smith DW-1080, DW-1210, DW-1350, DW-1480, DW-1610 User Manual

...
Page 1
TM
Built tough with maximum efficiency
MODELS DB/DW-720-1810
NATURAL GAS-FIRED COMMERCIAL CROSS FLOW COPPER BOILERS
FOR HYDRONIC HEATING AND HOT WATER SUPPLY
WITH ELECTRONIC INTERMITTENT PILOT IGNITION AND
INSTALLATIONS
INSTALLATION • OPERATION • MAINTENANCE • LIMITED WARRANTY
WARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other
— WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance.
· Do not touch any electrical switch;
do not use any phone in your building.
· Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas
supplier, call the fire department.
— Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMA TION RELA TIVE T O YOUR SAFETY . READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE.
A DIVISION OF A.O.SMITH CORPORA TION
EL P ASO, TX McBEE, SC RENTON, WA
STRATFORD, ONTARIO
VELDHOVEN, THE NETHERLANDS
www.hotwater.com
PLEASE
PLACE THESE INSTRUCTIONS ADJACENT TO BOILER AND
PRINTED IN U.S.A. 2221 0302
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
1
SUPERSEDES PART NO. 20031 1-000 REV. 4 & 210265-000 REV . 0
PART NO. 211680-000 REV . 00
Page 2
CONTENTS
Page
FOREWORD................................................................................ 2
REPLACEMENT PAR TS .............................................................. 2-3
ROUGH-IN DIMENSIONS/CAPACITIES ...................................... 3-4
Installation Clearances.............................................................. 3
Levelling ................................................................................... 3
FEATURES................................................................................... 5
Safety Relief V alves.................................................................. 5
Electronic Intermittent PIlot Ignition Control .............................. 5
Manual Reset High T emperature Safety Limit Control ............... 5
Automatic Reset High T emperature Control .............................. 6
Thermal Balancer ..................................................................... 6
Safety Flow Switch................................................................... 6
INSTALLA TION INSTRUCTIONS ................................................. 7
Required Ability ........................................................................ 7
Location ................................................................................... 7
Air Requirements ..................................................................... 7-8
Venting the Boiler ..................................................................... 8-9
Gas Connections...................................................................... 9
Purging .................................................................................... 10-1 1
High Altitude Installations ......................................................... 11
Wiring Connections.................................................................. 1 1-12
Servicing Wiring And/Or Control .............................................. 1 2
SYSTEM EQUIPMENT INSTALLA TION ....................................... 12
Water Supply Line.................................................................... 12
Expansion T ank ........................................................................ 12
Vent V alves .............................................................................. 12
System Headers ...................................................................... 12
Cooling Piping .......................................................................... 12
Safety Flow Switch................................................................... 12-13
Circulating Pump...................................................................... 13-14
Page
Low Water Cutoff ..................................................................... 1 4
T ank T emperature Control ........................................................ 14
SYSTEM INSTALLA TION ............................................................. 14
Conventional Space Heating Installation ................................... 14-15
Installation As Boiler Replacement ............................................ 15-17
Linear-T emp Space Heating Applications.................................. 17
Linear-T emp Space Heating Installations .................................. 17-20
Wiring and Schematic Diagrams .............................................. 21-26
HOT WA TER SUPPL Y APPLICA TIONS ....................................... 27-32
Water Line Connections ........................................................... 27
Hard Water Conditions............................................................. 27
ST ART-UP AND OPERA TING INSTRUCTIONS .......................... 32
LIGHTING AND OPERATING INSTRUCTIONS ........................... 33
Internal Contaminants .............................................................. 34
Precautions .............................................................................. 34
Checking and Adjusting the Input............................................. 34
Pilot Burner .............................................................................. 34
Main Burner ............................................................................. 34-35
PRE-TROUBLESHOOTING ......................................................... 35
TROUBLESHOOTING.................................................................. 35-38
GENERAL MAINTENANCE.......................................................... 39
Relief V alve .............................................................................. 39
Venting Maintenance ................................................................ 39
Heat Exchanger Preventive Maintenance.................................. 39
Deliming ................................................................................... 39-40
Deliming Solvents..................................................................... 40
Removing Light Deposits of Scale ............................................ 40
Removal of an Existing Boiler From A Common Venting
System ................................................................................ 40
LIMITED WARRANTY .................................................................. 41
FOREWORD
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE USING APPLIANCE.
Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THAT ALL WATER AND GAS PIPING AND THE ELECTRICAL WIRING BE INSTALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
CHECK THE DIAGRAMS THOROUGHLY BEFORE STARTING INSTALLATION TO AVOID POSSIBLE ERRORS AND TO MINIMIZE TIME AND MATERIALS COST.
This design complies with the latest edition of the CSA 4.9 low-pressure boiler.
Particular attention should be given to the installation of thermometers at the locations indicated in the diagrams as these are necessary for checking the operation of the boiler.
MAKE SURE THE GAS ON WHICH THE BOILER WILL OPERA TE IS THE SAME AS THAT SPECIFIED ON THE UNIT RATING PLATE.
The boiler installation must conform to these instructions and the requirements of the local authority having jurisdiction.
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In the absence of local code requirements, the boiler installation must conform to the most current
National Fuel Gas Code, ANSI
Z223.1 and/or CAN/CSA-B149.1-00 installation codes.
ANSI Z21.13
These manuals can be purchased from the CSA International, 8501 East Pleasant Valley Road, Cleveland, OH 44131 or 178 Rexdale Boulevard, Toronto, Ontario Canada, M9W 1R3.
REPLACEMENT PARTS
Replacement parts may be ordered through A. O. Smith dealers, authorized servicers or distributors. Refer to the Yellow Pages for where to call or contact (in United States) the A.O. Smith Water Products Company, 5621 West 115th Street, Alsip, IL 60803, 1-800-433-2545 or (in Canada) A.O. Smith Enterprises Ltd., 768 Erie Street, Stratford, Ontario, Canada N5A 6T3, 800-265-8520. When ordering parts be sure to state the quantity, part number and description of the item including the complete model and serial number as it appears on the product. Refer to the parts lists for more information.
For Technical Assistance call A.O. Smith Technical Information Center at 1-800-527-1953.
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH UNIT INCORPORATES AN “O RING" WATER SEAL ASSEMBLY. THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT OF THE WATER PIPING SYSTEM. AS ON ALL BOILER INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE PROPER SUPPORT.
WARNING
UNDER NO CIRCUMSTANCES SHOULD THE EQUIPMENT ROOM WHERE THE BOILER IS INSTALLED EVER BE UNDER NEGATIVE PRESSURE. PARTICULAR CARE MUST BE TAKEN WHEN EXHAUST FANS, COMPRESSORS, AIR HANDLING EQUIPMENT, ETC., MA Y INTERFERE WITH THE COMBUSTION AND VENTILATION AIR SUPPLIES OF THIS BOILER.
2
Page 3
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
"Verify proper operation after servicing."
ROUGH-IN DIMENSIONS/
CAPACITIES
INST ALLA TION CLEARANCES
Two inch clearance is allowable from combustible construction for hot water pipes.
Sufficient clearance should be provided at one end of the boiler to permit access to heat exchanger tubes for cleaning. Maximum operating water supply pressure 160 psi. Gas supply pressure:
13.8" w.c. max., 5.5" w.c. min. Sufficient area should be provided at the front and sides of the unit
for proper servicing. Clearances of 48" in front and 24" on sides is recommended. In a utility room installation, the door shall be wide enough to allow the boiler to enter or to permit the replacement of another appliance.
These boilers are approved for installation on combustible flooring in an alcove with minimum clearance to combustibles See chart below.
W ARNING AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILA TION.
LEVELLING
Each unit should be checked after installation to be certain that it is level.
TABLE 1, ROUG H-IN DIMENSI ONS
Models
Dimensions inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm
A
46 1/2 1181 52 1/5 1326 57 3/4 1467 52 7/8 1343 58 1/2 1486 64 1/2 1638 69 1/2 1765 75 1905 82 1/2 2096
B
29 5/8 752 29 5/8 752 29 5/8 752 32 3/4 832 32 3/4 832 32 3/4 832 34 864 34 864 34 864
C
54 3/4 1391 54 3/4 1391 54 3/4 1391 58 1473 58 1473 58 1473 60 1/2 1537 60 1/2 1537 60 1/2 1537
D E 7 3/4 197 7 3/4 197 7 3/4 197 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 F 15 1/2 394 15 1/2 394 15 1/2 394 18 1/2 470 18 1/2 470 18 1/2 470 18 1/2 470 18 1/2 470 18 1/ 2 470 G H J K 2 NPT 2 NPT 2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT L 1 NPT 1 NPT 1 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT M N
W
Approx.
Shipping
Weight.
1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 2 NPT 2 NPT
17 1/4 438 17 1/4 438 17 1/4 438 18 9/16 471 18 9/16 471 18 9/16 471 19 1/8 486 19 1/8 486 19 1/8 486
4 1/4 108 4 1/4 108 4 1/4 108 4 102 4 102 4 102 4 1/2 114 4 1/2 114 4 1/2 114
2 NPT 2 NPT 2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT
12 305 14 356 14 356 16 406 16 406 18 457 18 457 18 457 20 508 15 1/2 394 16 1/2 419 16 1/2 419 17 1/4 438 17 1/4 438 17 1/4 438 13 3/4 349 13 3/4 349 13 3/4 349 32 1/8 816 31 1/8 791 32 1/8 816 30 15 /16 786 30 15/16 786 30 15/16 786 31 787 31 78 7 31 787
780 lbs 354 Kg. 950 lbs 431 Kg 950 lbs 431 Kg 1000 lbs 454 Kg 1075 lbs 48 8 Kg. 1100 lbs 499 Kg 1125 lbs 510 Kg 1150 lbs 522 Kg 1250 lbs 567 Kg
All Models 12" (305mm) 18" (457mm) 6" (155mm) 6" (155mm) 6" (155mm) Alcove
DW-1810DW-1210 DW-1350 DW-1480 DW-1610DW-720 DW-840 DW-960 DW-1080
Minimum Clearances T o Combustibles
Water Blank
T op Side Side Rear Vent Front
3
Page 4
WARNING
Your Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than 100°F (38°C). Colder inlet water temperatures will result in significant condensation developing on the heat exchanger. This situation can cause a corrosive environment for the heat exchanger, burners and venting resulting in premature damage, which could result in serious personal injury or death.
For systems that use large volumes of cold water or system utilizing heavy water draws (Cer-Temp), condensation can be prevented by using a by-pass loop. See page 16.
TABLE 2, PRESSURE DROP
Model
DW-720
DW-840
DW-960
DW-1080
DW-1210
DW-1350
DW-1480
DW-1610
DW-1810
Temp Rise
FC
Flow Rate
GPM LPM ft
20 11.1 59 223 3.5 1.1 30 16.7 39 149 1.7 0.5 40 22.2 29 111 1.0 0.3
20 11.1 69 260 4.8 1.5 30 16.7 46 173 2.1 0.6 40 22.2 34 130 1.5 0.5
20 11.1 79 297 6.8 2.1 30 16.7 52 198 3.3 1.0 40 22.2 39 149 1.9 0.6
20 11.1 89 339 4.5 1.4 30 16.7 60 226 2.1 0.6 40 22.2 45 169 1.4 0.4
20 11.1 100 379 5.3 1.6 30 16.7 67 253 2.7 0.8 40 22.2 50 190 1.6 0.5
20 11.1 112 423 6.8 2.1 30 16.7 75 282 3.2 1.0 40 22.2 56 212 1.8 0.5
20 11.1 120 453 7.9 2.4 30 16.7 80 302 3.9 1.2 40 22.2 60 226 2.1 0.6
20 11.1 130 492 9.5 2.9 30 16.7 87 328 5.0 1.5 40 22.2 65 246 3.0 0.9
20 11.1 146 554 12.0 3.7 30 16.7 98 369 6.2 1.9 40 22.2 73 277 3.9 1.2
HdLoss*
M
TABLE 3, RECOVERY CAPACITIES
MODEL BTUH KW C 11.1C 16.6C 20C 22.2C 27.7C 30C 33.3C 38.8C 40C 44.4C 50C 55.5C 60C 61.1C 66.6C 70C 72.2C 77.7C
DB/DW-720
DB/DW-840
DB/DW-960
DB/DW-1080
DB/DW-1210
DB/DW-1350
DB/DW-1480
DB/DW-1610
DB/DW-1810
INPUT
720,000 GPH 3,535 2,356 1,964 1,767 1,414 1,309 1,178 1,010 982 884 785 707 655 643 589 561 544 505
840,000 GPH 4,124 2,749 2,291 2,062 1,649 1,527 1,375 1,178 1,145 1,031 916 825 764 750 687 655 634 589
960,000 GPH 4,713 3,142 2,618 2,356 1,885 1,745 1,571 1,346 1,309 1,178 1,047 943 873 857 785 748 725 673
1,080,000 GPH 5,367 3,578 2,982 2,684 2,147 1,988 1,789 1,534 1,491 1,342 1,193 1,073 994 976 895 852 826 767
1,210,000 GPH 6,013 4,009 3,341 3,007 2,405 2,227 2,004 1,718 1,670 1,503 1,336 1,203 1,114 1,093 1,002 954 925 859
1,350,000 GPH 6,709 4,473 3,727 3,355 2,684 2,485 2,236 1,917 1,864 1,677 1,491 1,342 1,242 1,220 1,118 1,065 1,032 958
1,480,000 GPH 7,176 4,784 3,987 3,588 2,870 2,658 2,392 2,050 1,993 1,794 1,595 1,435 1,329 1,305 1,196 1,139 1,104 1,025
1,610,000 GPH 7,806 5,204 4,337 3,903 3,122 2,891 2,602 2,230 2,168 1,952 1,735 1,561 1,446 1,419 1,301 1,239 1,201 1,115
1,810,000 GPH 8,776 5,851 4,875 4,388 3,510 3,250 2,925 2,507 2,438 2,194 1,950 1,755 1,625 1,596 1,463 1,393 1,350 1,254
F 20F 30F 36F 40F 50F 54F 60F 70F 72F 80F 90F 100F 108F 110F 120F 126F 130F 140F
211 LPH 13,379 8,920 7,433 6,690 5,352 4,955 4,460 3,823 3,716 3,345 2,973 2,676 2,478 2,433 2,230 2,124 2,058 1,911
246 LPH 15,609 10,406 8,672 7,805 6,244 5,781 5,203 4,460 4,336 3,902 3,469 3,122 2,891 2,838 2,602 2,478 2,40 1 2,230
281 LPH 17,839 11,893 9,911 8,920 7,136 6,607 5,946 5,097 4,955 4,460 3,964 3,568 3,304 3,243 2,973 2,832 2,74 4 2,548
316 LPH 20,317 13,545 11,287 10,158 8,127 7,525 6,772 5,80 5 5,644 5,079 4,515 4,063 3,762 3,694 3,386 3,225 3,126 2,902
354 LPH 22,762 15,175 12,646 11,381 9,105 8,430 7,587 6,50 4 6,323 5,691 5,058 4,552 4,215 4,139 3,794 3,613 3,502 3,252
395 LPH 25,396 16,931 14,109 12,698 10,158 9,406 8,465 7,256 7,054 6,349 5,644 5,079 4,703 4,617 4,233 4,031 3,907 3,628
433 LPH 27,162 18,108 15,090 13,581 10,865 10,060 9,054 7,761 7,545 6,791 6,036 5,432 5,030 4,939 4,527 4,311 4,179 3,880
472 LPH 29,548 19,699 16,416 14,774 11,819 10,944 9,849 8,442 8,208 7,387 6,566 5,910 5,472 5,372 4,925 4,690 4,546 4,221
530 LPH 33,219 22,146 18,455 16,609 13,288 12,303 11,073 9,491 9,227 8,305 7,382 6,644 6,152 6,040 5,536 5,273 5,111 4,746
U.S. Gallons/Hr and Li t res/Hr at TEMPERAT URE RIS E I NDICATED
4
Page 5
FEA TURES
IMPORTANT
Only qualified personnel shall perform the initial firing of the heater. At this time the user should not hesitate to ask the individual any questions regarding the operation and maintenance of the unit.
Lighting and Operating instructions are included at the rear of this manual. By using this checklist the user may be able to make minor operational adjustments and save unnecessary service calls. However, the user should not attempt repairs which are not listed under the USER column.
SAFETY RELIEF V ALVES
Your local code authority may have other specific relief valve requirements not covered below.
and pilot gases are cut off during the OFF cycle. Pilot gas ignition is proven by the pilot sensor. Main burner ignition will not occur if the pilot sensor does not first sense pilot ignition.
FIGURE 2
WARNING
THE PURPOSE OF A SAFETY RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE WHICH MAY CAUSE TANK EXPLOSION, SYSTEM OR BOILER DAMAGE.
TO AVOID WATER DAMAGE A DRAIN LINE MUST BE CONNECTED TO A SAFETY RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCA TION. A DRAIN LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND IT MUST NOT CONT AIN ANY V ALVES BETWEEN THE BOILER AND THE RELIEF VALVE OR THE RELIEF VALVE AND THE DRAIN EXIT. IN ADDITION, THERE SHOULD NOT BE ANY RESTRICTIONS IN A DRAIN LINE NOR SHOULD IT BE ROUTED THROUGH AREAS WHERE FREEZING CONDITIONS MIGHT OCCUR. DO NOT THREAD OR CAP THE DRAIN LINE EXIT. RESTRICTING OR BLOCKING A DRAIN LINE WILL DEFEA T THE PURPOSE OF THE RELIEF VALVE AND MAY CREATE AN UNSAFE CONDITION. INSTALL A DRAIN LINE WITH A DOWNWARD SLOPE SUCH THAT IT NATURALLY DRAINS ITSELF.
If any safety relief valve is replaced, the replacement valve must comply with the latest version of the ASME Boiler and Pressure Vessel Code, Section IV (HEATING BOILERS). Select a relief valve with a discharge rating NOT less than the boiler input, and a set pressure NOT exceeding the working pressure of any component in the system.
An ASME rated temperature and pressure relief valve must be installed on each and every water storage tank in a hot water supply system.
The storage tank temperature and pressure relief valve must comply with the applicable construction provisions of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21 or CAN/CSA-B149.1 (latest edition). The valve must be of the automatic reset type and not embody a single-use type fusible plug, cartridge or linkage.
ELECTRONIC INTERMITTENT PILOT
IGNITION CONTROL
ALL MODELS - The solid state ignition control, fig. 2, ignites the pilot burner gas by creating a spark at the pilot assembly . Pilot gas is ignited and burns during each running cycle. The main burner
On natural gas models the igniter control continues to operate (creating a spark) until the pilot burner is ignited or the ignition system shuts down. Shut down occurs automatically if the pilot burner does not ignite within 15 seconds. The unit then waits for (5) minutes and retries ignition (standard models).
The electronic intermittent pilot ignition control and the 100% lockout control are non-adjustable devices.
(See troubleshooting steps on page 40). If pilot is not lit and sensed within the flame establishing timing for each module, the appliance will shut down.
MANUAL RESET HIGH TEMPERA TURE
SAFETY LIMIT CONTROL
This device senses water temperature in the boiler. When water temperature exceeds dial setting, power to main gas valve is interrupted and the boiler is shut down.
HOT WATER SUPPLY - Manual reset - factory set at 210°F (100°C). Water temperature must drop at least 20°F (11°C) before reset is possible.
HYDRONIC HEA TING - Manual reset - factory set at 250°F (121°C). Water temperature must drop at least 20°F (11°C) before reset is possible.
Single stage and modulating units use a combined control as shown in fig. 4.
Dual stage models are equipped with a limit like one shown in figure 3.
5
Page 6
AUTOMATIC RESET
HIGH TEMPERATURE LIMIT CONTROL
CAUTION
LIMIT CONTROLS ARE NOT TO BE USED AS THERMOSTATS.
The heater operation with above set points will be as follows:
1) When heater temperature rises to LO thermostat setting the main gas valve will close its second stage operator to drop input to approximately 50% of total input.
ALL MODELS - This limit is a safety device wired in series with the ignition system. Set the limit control dial to a minimum of 10°F (6°C) above the maximum designed system temperature. If the boiler outlet water temperature should exceed the high limit setting, the main gas valves will close but the circulator will continue to operate. Maximum adjustable setting is 240°F (116°C) for boilers and 200°F (93°C) for hot water supply heaters. The differential is adjustable from 5°F (3°C) to 45°F.
SINGLE ST AGE AND MODULATING MODELS - Are equipped with the limit like the one shown in fig. 4.
2) System conditions will determine if temperature rise at LO thermostat sensor location will continue to rise until shut-off by high limit or drop causing heater to go back to full input.
Other system design temperatures will require resetting of the dial. Total span of temperatures (HI dial cut-off point to LO dial cut-on point) should not be less than temperature drop of the system.
MODULATING MODELS ONLY These boilers are factory equipped with a modulating gas valve
that automatically controls the outlet water temperature by modulating or proportioning the rate of gas thus maintaining a desired constant outlet water temperature regardless of varying flow rates.
Gas valves either close or open to full gas input, depending upon heat requirement.
DUAL STAGE MODELS ONLY - HIGH/LOW OPERATOR These boilers are factory equipped with a (combination) temperature controller to provide high and low firing rates for smooth operation. (fig. 5).
The temperature dials should be adjusted to have the HI dial set as a limit to be 10°F (6°C) above desired boiler temperature. These boilers are shipped with the HI dial set to 200°F (93°C) with a 15°F (8°C) differential, the LO dial set to 160°F (71°C) with a 10°F (6°C) differential.
Set temperature controller for desired outlet water temperature. (fig. 6).
Adjust the set point for the desired operating temperature by turning the set point adjusting screw on the front of the case until the desired value is reached on the set point indicating dial. The set point is calibrated to be at the center of the proportioning range, (see the manufacturers instructions for complete information on testing and calibrating this control.)
THERMAL BALANCER
This device serves as a pump shutdown delay switch to balance the boiler water temperature to system temperature before the pump stops. Overshooting of boiler temperature is prevented and stack loss after shutdown is minimized.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at the water outlet of the unit to prevent main burner operation in the event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical pipe line with upward water flow. Do not install the switch where the water flow is downward.
6
Page 7
INST ALLA TION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS BOILER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
If the boiler is installed above the level of heating system terminal units, a low water cutoff device must be installed in the boiler outlet at the time of installation.
For installation locations with elevations above 2,000 feet (610 M), refer to the HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure.
CHEMICAL VAPOR CORROSION
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH UNIT INCORPORATES AN "O RING" WATER SEAL ASSEMBLY. THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT OF THE WATER PIPING SYSTEM. AS ON ALL BOILER INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE PROPER SUPPORT.
LOCATION
When installing the boiler, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practical with adequate air supply and as centralized with the piping system as possible. This location should also be such that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service [circulator replacement, control replacement, etc.].
THE BOILER MUST NOT BE INSTALLED ON CARPETING. THE BOILER SHOULD NOT BE LOCATED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING. LOCATE IT NEAR A FLOOR DRAIN. THE BOILER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE BOILER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
Heat exchanger corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, and process chemicals are typical compounds which are corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near the boiler. Also, air which is brought in contact with the water boiler should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources.
AIR REQUIREMENTS
WARNING
FOR SAFE OPERATION, AN AMPLE SUPPLY OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILATION IN ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILA TION, OF THE NATIONAL FUEL GAS CODE, ANSI Z223.1 OR 7.2, 7.3 OR 7.4 OF CAN/CSA B149.1-00, INSTALLA TION CODES, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES. AN INSUFFICIENT SUPPLY OF AIR MAY RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CARBONING OR SOOTING OF THE FINNED HEAT EXCHANGER, OR CREA TE A RISK OF ASPHYXIA TION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DRAIN P AN SHOULD BE INST ALLED UNDER THE BOILER. Such pans should be fabricated with sides at least 2-1/2" (64 mm) deep, with length and width at least 2" (51 mm) greater than the dimensions of the boiler and must be piped to an adequate drain.
The pan must not restrict combustion air flow.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES IN ROOMS OR AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE IGNITER OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IF INSTALLED 18 INCHES OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE BOILER.
OPEN CONT AINERS OF FLAMMABLE MA TERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE BOILER.
UNCONFINED SPACE
In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion, and draft hood dilution.
If the unconfined space is within a building of tight construction (buildings using the following construction; weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation, and draft hood dilution must be obtained from outdoors or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
CONFINED SPACE
(a) U. S. INSTALLATIONS
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2,208 mm2of per kw) of the total input of all appliances in the enclosure, but not less than 100 square inches (645 cm2).
7
Page 8
If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btu/hr (551 mm
2
per kw) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btu/hr (1101 mm
2
per kw) of the total input of
all appliances in the enclosure.
(B) CANADIAN INSTALLATIONS
Ventilation of the space occupied by the boiler(s) shall be provided by an opening for ventilation air at the highest practical point communicating with outdoors. The total cross- sectional area shall be at least 10% of the area of the combustion air opening but in no case shall the cross-sectional area be less than 10 square inches (6500 mm²).
1. DRAFT HOOD The integral draft hood, louvers or cabinetry must not be altered.
Provision must be made if the boiler is installed in confined space or a small boiler room to accommodate draft hood spillage and avoid risks described above. The upper air opening called for in the AIR REQUIREMENTS section of this manual is for this purpose.
2. VENT CONNECTION The minimum distance from adjacent public walkways, adjacent
buildings, openable windows and building openings shall not be less than those values specified in the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149.1-00, Installation Codes:
Stack or chimney must be a minimum height of 12" (305 mm) above the annual snow fall to prevent blockage.
Building materials must not come in contact with combustion products from stack or chimney, due to the degrading properties of flue products.
In addition to the above, there shall be permanent air supply opening(s) having a cross-sectional area of not less than 1 square inch per 7,000 BTUH (315 mm²/kw) up to and including 1,000,000 BTUH
plus 1 square inch per 14,000 BTU (158 mm2/kw) in excess of 1,000,000 BTUH. This opening(s) shall be located at, or ducted to, a point neither more than 18" (450 mm) nor less than 6 inches (150 mm) above the floor level.
Where power vented equipment is used in the same room as the boiler, sufficient air openings must be supplied.
UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR FOR COMBUSTION.
Where an exhaust fan is installed in the same room with a boiler, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED RISK OF ASPHYXIATION.
VENTING THE BOILER
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING THE BOILER MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
SINGLE WALL OR TYPE B VENTING MAY BE USED WITH THESE BOILERS. ALL LOCAL UTILITY, STATE/ PROVINCIAL, REGULATIONS ON VENTING MUST BE FOLLOWED.
VENT SIZING, INSTALLATION AND TERMINATION SHALL BE IN ACCORDANCE WITH PART 7, VENTING OF EQUIPMENT, OF THE NATIONAL FUEL GAS CODE, ANSI Z223.1, OR SECTION 7, VENTING SYSTEMS AND AIR SUPPLY FOR APPLIANCES, OF THE CAN/CSA B149, INSTALLATION CODES, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES.
Materials may be protected from flue products by use of metal or copper sheeting.
Flue products must have a minimum clearance of 4 feet (1.22 m) horizontally from, and in no case above or below, unless a 4-foot (1.22 m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
The Canadian B149.1-00, Installation Code specifies a 6 foot horizontal vent terminal clearance to gas and electric meters and relief devices (this clearance is specified as 4 feet in the U.S. under the National Fuel Gas Code, ANSI/Z223.1). Therefore instruction provision 1.34.1-b19(d), which specifies compliance with the 4 foot clearance, as applies in the U.S. only, and the B149.1-00 Installation Code applies in Canada.
Vent connections must be made to an adequate stack or chimney and shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or Section 7, Venting Systems and Air Supply for Appliances, of the CAN/CSA-B149.1­00, Installation Codes, or applicable provisions of the local building codes. Size and install proper size vent pipe. Do not reduce pipe size to less than that of the draft hood outlet unless permitted by local code.
Horizontal runs of vent pipe shall be securely supported by adequately placed (approximately every 4 feet [1.2 m]), noncombustible hangers suitable for the weight and design of the materials employed to prevent sagging and to maintain a minimum upward slope of 1/4" per foot (21mm/m) from the boiler to the vent terminals. Dampers or other obstructions must not be installed in the vent. Be sure that the vent connector does not extend beyond the inside wall of the chimney.
Where a continuous or intermittent back draft is found to exist the cause must be determined and corrected. A special vent cap may be required. If the back draft cannot be corrected by the normal methods or if a suitable draft cannot be obtained, a blower type flue gas exhauster may be employed to ensure proper venting and correct combustion (where permitted by local code). Contact your A. O. Smith dealer for power vent instructions.
8
Page 9
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
3. CONNECTING BOILER TO A COMMON VENT
Do not connect the boiler to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by most local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.
Where a separate vent connection is not available and the vent pipe from the boiler must be connected to a common vent with an oil burning furnace, the vent pipe should enter the common vent or chimney at a point ABOVE the flue pipe from the oil furnace.
UL/ULC listed doublewall type B-1 gas vents, through 24" (610 mm) diameter, can be installed in heated and unheated areas and can pass through floors, ceilings, partitions, walls and roofs, provided the required clearance is observed.
At the time of removal of an existing boiler, the following steps shall be performed with each appliance remaining connected to the common venting system. Perform these steps while the other appliances remaining connected to the common venting system are not in operation.
GAS CONNECTIONS
WARNING
THIS BOILER IS NOT INTENDED TO OPERA TE A T GAS SUPPL Y PRESSURE OTHER THAN SHOWN ON THE RATING PLATE. EXPOSURE TO HIGHER GAS SUPPL Y PRESSURE MA Y CAUSE DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS.
WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUTOFF VALVE OUTSIDE THE BOILER JACKET, A SUITABLE MAIN MANUAL SHUTOFF VALVE MUST BE INSTALLED IN A LOCATION COMPLYING WITH THOSE CODES.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE APPROVED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
Seal any unused openings in the common venting system.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is not blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust fans, so they will operate at maximum speed. Close fireplace dampers.
Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after five
minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
After it has been determined that each appliance remaining
connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG OR SEDIMENT TRAP) UPSTREAM OF THE GAS CONTROLS, MUST BE INCORPORATED IN THE PIPING. The dirt leg must be
readily accessible and not subject to freezing conditions. INST ALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO Z223.1 AND/OR CAN/CSA-B149.1-00.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve gas inlet.
Fittings and unions in the gas line must be metal to metal type. Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping systems at test pressures equal to or less than 1/2 psi (3.5 kPa).
The boiler and its gas connection must be leak tested before placing the boiler in operation.
Provisions for vent, bleed and gas relief lines (when applicable).
NATIONAL FUEL GAS CODE, ANSI
9
Page 10
PURGING
Gas line purging is required with new piping or systems in which air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE OF GAS SERVICE TO A VOID RISK OF FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SP ACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVA TED OR REMOVED.
2A. SIZING GAS SUPPLY LINE (For single boiler installations
and for installations of multiples of two or three of same size boilers).
Use table 1, which is taken from ANSI booklet Z223.1,
NATIONAL FUEL GAS CODE, and/or CAN/CSA-B149.1-00 to size iron pipe or equivalent gas supply line. Table 4 is based on a pressure drop of 0.3 inches of water and a specific gravity of 0.60 which is approximately for natural gas. (LP gas has an S.G. of about 1.53). If the service pressure is five inches water column or less, use one pipe size larger than specified in table 1 in order to minimize pressure drop in the line.
BEFORE PLACING THE BOILER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material acceptable for the purpose in locating gas leaks. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
1. CORRECT GAS Make sure the gas on which the boiler will operate is the same as
that specified on the boiler rating plate. Do not install the boiler if equipped for a different type gas, consult your gas supplier. These boilers are designed to operate on natural gas only.
T ABLE 4
MAXIMUM CAP ACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (BASED UPON A PRESSURE DROP OF
0.3 INCH WA TER COLUMN AND 0.6 SPECIFIC GRA VITY GAS)
Length in Feet (Meters) Nominal Iron Pipe Size, Inches (NPT)
From Gas Meter 1 /2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
10 (3) 132 278 520 1,050 1,600 3,050 4,800 8,500 17,500 20 (6) 92 190 350 730 1,100 2,100 3,300 5,900 12,000
30 (9) 73 152 285 590 890 1,650 2,700 4,700 9,700 40 (12) 63 130 245 50 0 760 1,450 2,300 4,100 8,300 50 (15) 56 115 215 44 0 670 1,270 2,000 3,600 7,400 60 (18) 50 105 195 40 0 610 1,150 1,850 3,250 6,800 70 (21) 46 96 180 370 560 1,050 1,700 3,000 6,200 80 (24) 43 90 170 350 530 990 1,600 2,800 5,800 90 (27) 40 84 160 320 490 930 1,500 2,600 5,400
100 (30) 38 79 150 305 460 870 1,400 2,500 5,100 125 (38) 34 72 130 275 410 780 1,250 2,200 4,500 150 (46) 31 64 120 250 380 710 1,130 2,000 4,100 175 (53) 28 59 1 10 225 350 650 1,050 1,850 3,800 200 (61) 26 55 100 210 320 610 980 1,700 3,500
*The heating value of natural gas is approximately 1050 Btu/ft³. Propane (L.P .) gas has a heating value of approximately 2500 Btu/ft³.
2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers
of same size or for multiple installations of two or more mixed sizes).
Capacities in cubic feet per hour of 0.60 specific gravity gas for different sizes and lengths are shown in table 4. No additional allowance is necessary for an ordinary number of fittings.
Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop.
Multipliers To Be Used W ith T able 1 When Applying The
Gravity Factor To Other Than .60 Specific Gravity
Specific Specific
Gravity Multiplier Gravity Multiplier
.35 1.31 1.00 .78 .40 1.23 1.10 .74 .45 1.16 1.20 .71 .50 1.10 1.30 .68 .55 1.04 1.40 .66
*.60 (Nat.) 1.00 *1.50 (Prop.) .63
.65 .96 1.60 .61 .70 .93 1.70 .59 .75 .90 1.80 .58 .80 .87 1.90 .56 .85 .84 *2.00 (Butane) .55 .90 .82 2.10 .54
*Use these correction factors if exact specific gravity of the gas is not known.
TABLE 5
10
Page 11
Applications of the gravity factor converts the figures given in table 1 to capacities with another gas of different specific gravity. Such application is accomplished by multiplying the capacities given in table 1 by the multipliers shown in table 5.
To determine the size of each section of gas piping in a system within the range of table 4 proceed as follows:
HIGH ALTITUDE INSTALLATIONS
IN CANADA
Acceptance of these models for use at altitudes above 2000 feet (610 m) is based on field test of the individual installation by the provincial/state authority having jurisdiction.
Determine the gas demand of each appliance to be attached to the piping system. When table 4 is to be used to select the piping size, calculate the gas demand in terms of cubic feet per hour for each piping system outlet. The gas demand for an appliance can be found by dividing its heat input rate by the gass heating value.
Obtain or determine the length of piping from the gas meter or service regulator to the appliance(s).
In table 1, select the row showing the distance to the most remote outlet or the next longer distance if the table does not give the exact length. This is the only distance used in determining the size of any section of gas piping. If the gravity factor is to be applied, the values in the selected row of table 4 are multiplied by the appropriate multiplier from table 5.
Total the gas demands of all appliances on the piping system.
Enter table 4, on the left hand side, at the row equal to or just exceeding the distance to the most remote outlet. Select the pipe size in the row with a capacity equal to or just exceeding the total gas demand. This is the required main gas supply line size leading away from the gas meter or regulator. To determine the pipe size required for each branch outlet leading away from the main supply line, determine the gas demand for that outlet. Enter table 4 on the same row, and select the branch pipe size for a capacity equal to or just exceeding the demand at that outlet. The main line can be resized for a lesser capacity after each branch outlet, since the gas demand is reduced. Total the gas demands of all remaining appliances branching off downstream on the main gas line. Re-enter table 4 in the same row and select the appropriate pipe size with adequate capacity. Repeat the branch sizing and main line re-sizing for any remaining appliances in the system.
EXAMPLE Job Condition: Determining the required gas pipe size for a system composed of
two A. O. Smith 720 boilers and two 960 boilers to be installed as a multiple group, 50 lineal feet from meter. Gas to be used has a .60 specific gravity and heating value of 1,000 Btu per cubic foot.
IN THE U.S.A.
WARNING
INSTALLATIONS ABOVE 2000 FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICES IN ACCORDANCE WITH SECTION
8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI Z223.1). FAILURE TO REPLACE THE ORIFICES WILL RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE RESUL TING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
Y ou should contact your gas supplier for any specific changes which may be required in your area.
Ratings specified by manufacturers for most boilers apply for elevations up to 2000 feet (610 m). For elevations above 2000 feet (610 m) ratings must be reduced by a rate of 4% for each 1000 feet (305 m) above sea level.
Example: A Dura-Max is rated at 720,000 Btu/hr. (211 kw) input at sea level. To operate the boiler at 5000 feet (1524 m) it must be derated by 20% (4% x 5) to a new rating of 576,000 Btu/hr. (169 kw) input.
The input reduction is primarily achieved by reducing the size of the main burner orifices. T o do this, the main burner orifices require replacement with orifices sized for the particular installation elevation. When ordering, be sure to state the model number and the altitude of the location where the boiler is being installed.
Upon field deration of the boiler, adjustment to the gas pressure regulator is required. See CHECKING AND ADJUSTING THE INPUT in this manual for inlet and manifold pressure requirements.
Also, due to the input rating reduction required at high altitudes, the output rating of the appliance is also reduced and should be compensated for in the sizing of the equipment for applications.
WIRING CONNECTIONS
1. CONVENTIONAL INSTALLATIONS Solution:
Two 720 Boilers = 1,440,000 Btuh (422 kw) Two 960 Boilers = 1,920,000 Btuh (562 kw) Total Btuh Input = 3,360,000 Btuh = (984 kw)
Total Btuh Input = 3,360,000 Btuh = 3,360 cf/h Btu per Cubic Foot of Gas 1,000
With a cubic foot per hour demand of 3,360 and with 50 lineal feet of gas supply line, table 4 shows a pipe size of 3" is required.
NOTE: For other than .60 specific gravity, apply multiplier factor
as shown in table 5.
All electrical work must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1, CSA C22.1, Electrical Code.
The electrical connections must be made so that the circulator will operate before the gas valve opens. At no time may the controlling system allow the burner to fire when there is no water flow through the boilers.
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. Make
the ground connection to the screw provided in the electrical supply junction box on the boiler.
11
Page 12
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C WIRE OR ITS EQUIVALENT, EXCEPT FOR THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250°C.
SERVICING WIRING AND/OR CONTROL
SYSTEM HEADERS
Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with minimum pressure drop for several circuits, manifolds should be larger than system loops.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
SYSTEMS EQUIPMENT
INSTALLATION
The following is a brief description of the equipment required for installations noted in this manual. All installations must comply with local codes.
The boilers described in this manual may be used for space heating or for the heating of potable water. If the heater is to be used for hydronic space heating, follow the descriptions given for equipment required for installation on pages 12 through 31. However, if units are to be used for heating potable water, the information describing specific systems is found starting on page 32. Installations must comply with all local codes.
WATER SUPPLY LINE
These boilers can be used ONLY in a forced circulation hot water heating system. Since most forced circulation systems will be of the closed type, install the water supply line as shown on piping diagrams, figs. 10 and 14.
The circuits should be spaced on the header at a minimum of 3" (76 mm) center to center. Install a balancing cock in each return line.
Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow.
COOLING PIPING
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. See figure 7.
FIGURE 7
Fast filling of large pipe, old radiator installations (where high pressures are not available) requires bypassing of the pressure reducing valve. Generally, pressure purging is not possible with a well pump system. High point air venting is essential. For details, refer to OPERATING INSTRUCTIONS section of this manual.
If the system is of the open type, a pressure reducing valve will not be required as the water supply to the system will be controlled by a manually operated valve. An overhead surge tank is required. MINIMUM PRESSURE OF 15 PSI MUST BE MAINTAINED ON THE BOILER AT ALL TIMES to ensure avoidance of potential damage to the boiler which may not be covered by the warranty.
EXP ANSION T ANK
If the system is of the closed type, install an expansion tank as shown in fig. 10. system is very important and is directly related to the total water volume of the system. Refer to ASME or other reliable specifications for sizing.
An air separator as shown in the piping diagrams is recom- mended especially for modern commercial hydronic systems.
The sizing of the expansion tank for a closed
VENT VALVES
It is recommended that automatic, loose key or screwdriver type vent valves be installed at each convector or radiator.
Water temperature in the heating system must be reduced to less than 100°F before cooling system is started, or damage to the chiller unit may occur.
The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A
Primary/secondary pumping of both the chiller(s) and the boiler(s) is an excellent winter-summer change-over method, because cooling flow rates are much more than heating flow rates. In this way each system (heating or cooling) is circulated independently.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at the water outlet of the unit to prevent main burner operation in the event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical pipe line with upward water flow. Do not install the switch where the water flow is downward.
For best performance mount the switch in a section of pipe where there is a straight run of at least 5 pipe diameters on each side of the flow switch (i.e. do not locate adjacent to valves, elbows, orifices, etc.).
12
Page 13
FIGURE 8
The flow switch shall be mounted in the top opening of the reducing tee and provide adequate paddle length in the flow stream. For example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For 2" or 3" pipe use the paddle segments as supplied. For other pipe sizes (i.e. 2-1/2") trim the paddle to the proper pipe size, see fig. 8. If a standard tee is used, install a face or hex bushing in the top opening. The paddle must be adjusted or trimmed to the size of the pipe in which it will be installed.
CAUTION
The paddle must not touch any part of the tee into which it is installed. Screw the flow switch in position so the flat of the paddle is at right angles to the flow. The arrow on the side case must point in the direction of the flow.
To adjust the flow rate setting:
1. Remove the flow switch cover.
2. For higher flow rateturn the range adjusting screw clockwise.
3. For lower flow rateturn the range adjusting screw counterclockwise.
Where units are installed in multiples, each boiler must be individually protected by a safety flow switch.
THE CIRCULATING PUMP MUST BE PROPERLY SIZED FOR YOUR APPLICATION.
Water hardness, system pressure drop and temperature rise across the boiler all affect how large a circulating pump must be.
Running "hard water" too slowly through the boiler can result in damage due to lime or scale accumulation.
Running "soft water" too quickly through the boiler can result in damage due to velocity flow erosion.
T able 4 has been designed to assist in determining operating ranges. Use this chart as a guide when sizing pumps.
FIGURE 9
CIRCULA TING PUMP
Dura-Max boilers are designed to operate over a wide range of temperatures and flow rates.
Although each circulator that requires oil is oiled and operated by the manufacturer, IT MUST BE OILED AGAIN BEFORE BEING OPERATED. Oil the three oil cups (2 on the motor, 1 on the pump) as instructed on the oil tube supplied with the unit, fig. 9.
13
Page 14
Thereafter, during the heating season, lubricate the three oil cups at least once every four months. Combination heating/cooling systems or water heating (Cer-temp) systems should be lubricated every four months year-round.
all cases, that the water temperature be set for the lowest temperature which satisfies the user's hot water needs. This will also provide the most energy efficient operation of the water heater and minimize scale formation.
Use 2 or 3 teaspoonfuls in bearing oil cups, fig. 9, and 10 or 12 drops in the motor oil cups. Use No. 20 non-detergent motor oil.
Follow the same oiling procedure if a replacement circulator is installed into the system.
LOW WATER CUTOFF
A low water cutoff is a safety device which is installed in the boiler piping to prevent the boiler from firing in the event of inadequate water levels in the boiler system.
Where required by local code, this optional device is to be installed in the boiler piping at a level above that of the heat exchanger.
A float type or an electronic probe type low water cutoff may be used. The manufacturers installation instructions must be followed.
A hot water boiler installed above radiating level or as required by the Authority having jurisdiction, must be provided with a low water cutoff device at the time of boiler installation.
T ANK TEMPERATURE CONTROL
The water temperature in the storage tank is controlled by the Tank Temperature Control. The sensing element is mounted inside the hot water storage tank, see fig. 24.
SETTING THE WATER TEMPERATURE AT 120°F (49°C) WILL REDUCE THE RISK OF SCALDS. Some states require settings at specific lower temperatures. T able 6 below shows the approximate time-to-burn relationship for normal adult skin.
Temperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
Over 170°F (77°C) Nearly instantaneous 160°F (71°C) About 1/2 second 150°F (65°C) About 1-1/2 seconds 140°F (60°C) Less than 5 seconds 130°F (55°C) About 30 seconds 120°F or less (49°C) More than 5 minutes
TABLE 6
USE ANTI-SCALD V ALVE(S) in the hot water system to reduce the risks of scalds at points of use such as lavatories, sinks and bathing facilities.
A change in water temperature in the storage tank lower than the Tank Temperature Control setting will cause the sensor to close its contacts and consequently, energize the boiler.
If the Tank Temperature Control is out of calibration, replace it with a new one; do not attempt to repair this control.
DANGER
HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSON'S AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED, OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER T AP OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HA VE ACCESS TO SET TEMPERATURES.
The tank temperature control is adjustable from 100°F to 220°F (38°C to 104°C). It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in
SYSTEM INSTALLATION
GENERAL
If the system is to be filled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent a downdraft entering the boiler or freezing air from contacting the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system. Damage due to freezing is not covered by the warranty.
Good practice requires that all piping, etc., be properly supported.
CONVENTIONAL SP ACE HEA TING INST ALLA TION
Modern fin type boilers are exceptionally fast heating units. The low water volumes in relation to firing rates require special attention to water flow rates for smooth, efficient operation. These considerations for the A. O. Smith copper heat exchanger boilers are covered below.
Refer to page 5 for tables on these units showing flow rate vs. pressure drop and temperature rise”.
Figure 10 shows a typical installation of the boiler. A system with several flow controlled zones, or with a 3-way mixing
valve system which could present a flow rate to the boiler of less than that required for a maximum of 50°F (10°C) temperature rise at the minimum firing rate, should be designed with compensating bypasses at the boiler.
14
Page 15
A system bypass should be installed as shown in fig. 10 to prevent boiler circulation starvation when the system zones call for reduced flow.
This bypass may also be used with multiple boilers manifolded for reverse-return flow. The system bypass would be installed from boiler outlet to suction side of pump.
Standard Dura-Max models are factory equipped for Single Stage Firing only.
Dura-Max models may be factory equipped for Dual Stage Firing. The gas valve automatically steps gas input down from full input to approximately 50% total input. System conditions will then
determine if boiler will shut down or if unit will return smoothly to full input.
Dura-Max models may also be equipped with modulation which automatically adjusts the boiler output to match the system heat loss and variations of system water flow. Minimum firing rate is 50%.
INST ALLA TION AS BOILER REPLACEMENT
Installation as boiler replacement on an old system with large water volume may result in condensation within the boiler on cold starts. This condensing of water vapor in the combustion area can be prevented if a portion of the system water flow is diverted past the boiler to cause an increase in boiler temperature rise.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
WHEN BLOW DOWN VALVE IS REQUIRED, INSTALL IN PLACE OF THE DRAIN VAL VE SHOWN.
DB INST ALLATION
FIGURE 10
15
Page 16
NOTES:
1. BUILDING TEMPERATURE CONTROLS SUPPLY ELECTRIC POWER TO BUILDING CIRCULA T OR.
2. MAIN FLOW SWITCH PROVES MAIN WATER FLOW BEFORE ENERGIZING, SEQUENCING AND RESETTING CONTROLS.
3. OUTDOOR THERMOSTAT REQUIRED IF BUILDING CONTROLS DO NOT PROVIDE AUTOMATIC SHUT-DOWN OF RESET CONTROLS DURING WARM WEATHER.
16
Page 17
BYP ASS BALANCING
With systems where water temperature can be expected to drop appreciably due to long standby periods, or heavy draw down, a bypass pipe of at least 1" size with a balancing cock should be installed between the boiler inlet and outlet (see fig. 10). When the system first starts, the valve should be slowly opened until the condensing ceases. This adjustment remains at a permanent setting to establish required temperature rise across the boiler.
LINEAR-TEMP SP ACE HEA TING APPLICA TIONS
Controlling of these systems is decided mainly by the type of building system controlling that is desired. A single boiler installation might be controlled directly from space temperature thermostat(s). Multiple boiler installations are more effective when the boilers are sequenced in and out of operation by some form of main water temperature controller. With one or two boilers, individual control set at progressive temperature may be used. For more than two boilers, electronic sequencing controlling is recommended.
Individual controls, or the separate stages of a step controller, should fire a boiler and also start the boiler loop circulator whenever that boiler is fired. Some large installations may require the firing of more than one boiler per stage.
The system or primary circulator may or may not be controlled by the boiler sequencer. When this pump is operated through the first switch of any type of step controller, care should be taken to determine if a motor starter is needed due to insufficient switch capacity.
Figure 11 shows a typical field wiring diagram for a single stage boiler LINEAR-TEMP installation. The boiler may be controlled by a main temperature controller as shown or may include outdoor reset if desired.
The following figs. 11 thru 13 are shown as layouts for various choices of controls often found in commercial heating. These layouts are not intended to be wiring diagrams and only show the relation of one device to another in the system.
Figure 11 is a typical layout of controls for two boilers with two circulators and thermal balancers plus optional outdoor reset control.
Figure 12 is shown as a typical control group for various multiple boiler installations, and is not intended to imply that this is the only arrangement to be considered. Commercial size installations are always best when designed to individual building requirements.
If the primary pump is controlled by a manual switch or any other controllers, the electric current supply to the boiler group should be through the primary pump controller. The fast response of A.O. Smith boilers eliminates any need to maintain boiler temperature when the system is satisfied. Wiring should always prevent firing of boiler(s) when there is no water flow in the mains.
Installation diagrams show safety flow switches in the outlet piping from each boiler as good protection against any boiler being fired when the boiler loop circulator is not in operation.
These safety flow switches will also provide some protection if there is a loss of water.
LINEAR-TEMP multiple boiler installations are especially adapted to the use of outdoor reset for main water temperatures. This feature is not mandatory but offers smooth, efficient operation of a modern system.
Outdoor reset systems should utilize an automatic shutdown control if there is a continuous recirculating main and/or if the entire building is not under control of space temperature thermostats. A single bulb outdoor sensing control will serve this requirement. This precaution will prevent overheating of halls, stairways or other uncontrolled areas. There are occasions when outdoor temperatures are temporarily too warm for even a moderate amount of heating in these areas.
Space temperature controlling can be varied to meet the building requirements. Either the single thermostat, as shown, or multiple zone thermostats should control a common relay. This relay controls electric power to the system primary circulator and to the main water temperature controller. This provides for water movement in the system before the main temperature controller can start the secondary circulating pump or fire the boiler.
FIGURE 13
LINEAR-TEMP SPACE HEATING INSTALLA TIONS
A. New Installation The A.O. Smith LINEAR-TEMP system has been designed to
provide efficient, trouble-free operation of these boilers with any of the following conditions:
unknown system flow rate.
varying flow rates as with zoned systems and 3-way valve
system.
multiple boiler installations. Figure 14 shows piping and accessory arrangement for 1 or more
boilers pumped independently of the primary system mains. Pipe sizing and boiler loop pump selection data, are shown in table 4 for several different temperature rises across various boiler sizes.
Total heating requirements for the building can be supplied by a series of boiler loops all connecting to a common pipe joining the system supply and return mains. The supply and return branches of each boiler loop must join the common pipe only a short nipple length apart. The different sets of branches should be installed reasonably close together, but not necessarily to the short nipple length as required for the supply and return of each set. These branches may be made with tees or with welded connections.
The installer is reminded that the total boiler flow rates do not have to match the system flow rate. Flow rates through heat
17
Page 18
generator type boilers establish temperature rises. The deciding factor in choice of boiler temperature rise relates to the boiler inlet temperature. Boiler outlet, minus system temperature drop, is boiler inlet temperature. THE BOILER TEMPERATURE RISE SHOULD NOT RAISE THE OUTLET TEMPERATURE UP T O THE MAXIMUM 250°F (115°C) SETTING OF THE LIMIT CONTROL.
If inlet temperature (plus temperature rise) of any boiler on the group exceeds 240°F (115°C), that boiler and all downstream boilers will shut down (cycle on and off).
B. Commercial Boiler Replacements Application of LINEAR-TEMP to a commercial boiler replacement
with an old multiple pump installation is an excellent way to modernize the system. The A. O. Smith boiler(s) should be installed on a pipe loop with a separate circulating pump. Use table 7 to determine pipe sizes and operating ranges.
The following illustration shows how the system headers should be connected to pipe loop that is installed with the replacement
TABLE 7, DuraMax Pump Performance Requirements
Model
DW-720
DW-840
DW-960
DW-1080
DW-1210
DW-1350
DW-1480
DW-1610
DW-1810
* - Head loss includes the loss through 40 feet (12 m ) of pipe and normal f i t t in gs.
Water
Category
Soft
Normal
Hard Hard
Soft
Normal
Hard Hard
Soft Normal Normal
Hard
Soft Normal Normal
Hard
Soft Normal
Hard
Soft Normal
Hard
Soft Normal
Hard Hard
Soft Normal
Hard Hard
Soft Normal
Hard Hard
Temp Rise
FC
35 19.4 34 127 3.7 1.1 2" #0012 (1/7 HP) 25 13.9 47 178 6.2 1.9 2" #120 ( 1/6 HP) 18 10.0 65 248 12.6 3.8 2" #1935 (1/3 HP) 18 10.0 65 248 7.4 2.3 2 1/2" #121 (1/4 HP)
35 19.4 39 149 5.9 1.8 2" #0012 (1/7 HP) 25 13.9 55 208 8.9 2.7 2" #120 ( 1/6 HP) 18 10.0 76 289 15.1 4.6 2" #1935 (1/3 HP) 18 10.0 76 289 10.2 3.1 2 1/2" #1935 (1/3 HP)
35 19.4 45 170 6.6 2.0 2" #0012 (1/7 HP) 25 13.9 63 238 12.1 3.7 2" #1935 (1/3 HP) 25 13.9 63 238 7.6 2.3 2 1/2" #121 (1/4 HP) 18 10.0 87 330 12.9 3.9 2 1/2" #1935 (1/2 HP)
35 19.4 51 193 7.0 2.1 2" #120 ( 1/6 HP) 25 13.9 72 271 13.1 4.0 2" #1935 (1/3 HP) 25 13.9 72 271 7.1 2.2 2 1/2" #121 (1/4 HP) 19 10.6 94 356 11.3 3.4 2 1/2" #1935 (1/2 HP)
35 19.4 57 217 4.7 1.4 2 1/2" #120 (1/6 HP) 25 13.9 80 303 8.8 2.7 2 1/2" #121 (1/4 HP) 19 10.6 105 399 13.4 4.1 2 1/2" #1935 (1/2 HP)
35 19.4 64 242 6.0 1.8 2 1/2" #121 (1/4 HP) 25 13.9 89 339 10.5 3.2 2 1/2" #1935 (1/3 HP) 18 10.0 124 470 18.9 5.8 2 1/2" #1935 (3/4 HP)
35 19.4 68 259 6.3 1.9 2 1/2" #121 (1/4 HP) 25 13.9 96 362 12.7 3.9 2 1/2" #1935 (1/2 HP) 18 10.0 133 503 20.5 6.2 2 1/2" #1935 (3/4 HP) 18 10.0 133 503 12.2 3.7 3" #133 (3/4 HP)
35 19.4 74 281 8.0 2.4 2 1/2" #121 (1/4 HP) 25 13.9 104 394 13.6 4.1 2 1/2" #1935 (1/2 HP) 20 11.1 130 492 20.7 6.3 2 1/2" #1935 (3/4 HP) 20 11.1 130 492 12.4 3.8 3" #133 (3/4 HP)
38 21.1 77 291 8.2 2.5 2 1/2" #121 (1/4 HP) 28 15.6 104 395 13.8 4.2 2 1/2" #1935 (1/2 HP) 22 12.2 133 503 20.9 6.4 2 1/2" #1935 (3/4 HP) 22 12.2 133 503 12.6 3.8 3" #133 (3/4 HP)
Flow Rate HdLoss*
GPM LPM ft
boiler(s). Make-up water connections, and accessories are not shown.
Supply and return headers of the old system should be connected to the boiler loop with a pair of tees set close together. The boiler loop pump and the boiler(s) should be wired to operate only when any of the system pumps are in operation. The number of zone pumps that may be in operation at any particular time will take their required flow rate out from the first tee in the boiler piping. This water will be circulated through the proper branches from the supply header to the zones calling for heat. The water will be brought back to the return header and then into the second tee in the boiler pipe loop. There will be no conflict between the boiler pump and the zone pumps when the two tees in the boiler loop are placed close together.
Normal use of flow control valves is required to prevent cross circulation of zones as with any multiple pump system.
Large systems with multiple boilers should include main water temperature controls (with or without outdoor reset) to sequence the boiler on and off, in relation to the load on the system.
Pipe Size Taco Circulator
M Sched. 40 Models
Pressure drop includes the loss through 40' (12 m) of pipe and normal fittings.
Water Category Grain Hardness per Gal.
Soft 1 through 7.5 Normal 7.6 through 17 Hard Over 17
Taco pumps shown. Equivalent Armstrong, Bell & Gossett or Grundfos acceptable. Always ensure adequate support for pump and piping.
18
Page 19
TABLE 8.
NO. SUGGESTED ITEMS FOR INSTALLATION
1. SHORT PIPE NIPPLE AND PAIR OF BOILER LOOP TEES IN PIPING BETWEEN SYSTEM SUPPLY AND RETURN - ONE SET PER EACH BOILER
2. BOILER PIPE LOOP (See Piping Sizing Data Table 3.)
3. BOILER CIRCULATING PUMP (See Piping Sizing Data Table 3.)
4. THERMOMETER
5. PRESSURE GAUGE
6. LOW WATER CUT-OFF (If Required By Local Code.)
7. SAFETY FLOW SWITCH
8. RELIEF VALVE (Furnished with Boiler)
9. BOILER INLET - OUTLET
10. SYSTEM SUPPLY TEMPERATURE THERMOMETER
11. DRAIN OR BLOW-DOWN VALVE
FIGURE 14
19
Page 20
USE ONY TYPE 105°C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED.
BOILER CONVENTIONAL SYSTEM
FIGURE 15
USE ONY TYPE 105°C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED.
ONE BOILER LINEAR-TEMP SYSTEM
FIGURE 16
20
Page 21
DURA-MAX - SINGLE ST AGE FIRING - UNITED STATES MODELS WITH PUMP.
120 VOLT SYSTEM CONTROLLER
DURA-MAX - PUMP MOUNT - SINGLE ST AGE - SCHEMATIC DIAGRAM
21
Page 22
DURA-MAX - DUAL ST AGE FIRING - UNITED STA TES MODELS WITH PUMP.
120 VOLT SYSTEM CONTROLLER
DURA-MAX - PUMP MOUNT - DUAL ST AGE - SCHEMA TIC DIAGRAM
22
Page 23
DURA-MAX - MODULA TED FIRING - UNITED STA TES MODELS
WITH PUMP. 120 VOLT SYSTEM CONTROLLER
DURA-MAX - PUMP MOUNTED - MODULA TING - SCHEMA TIC DIAGRAM
23
Page 24
DURA-MAX - SINGLE ST AGE FIRING - UNITED STA TES & CANADIAN MODELS
WITHOUT PUMP. 120 VOLT SYSTEM CONTROLLER
DURA-MAX - SINGLE ST AGE FIRING - SCHEMA TIC DIAGRAM
24
Page 25
DURA-MAX - DUAL ST AGE FIRING - UNITED STATES & CANADIAN MODELS
WITHOUT PUMP. 120 VOLT SYSTEM CONTROLLER
DURA-MAX - DUAL ST AGE FIRING - SCHEMA TIC DIAGRAM
25
Page 26
DURA-MAX - MODULA TED FIRING - UNITED ST ATES & CANADIAN MODELS
WITHOUT PUMP. 120 VOLT SYSTEM CONTROLLER
DURA-MAX - MODULA TED FIRING - SCHEMA TIC DIAGRAM
26
Page 27
HOT W A TER SUPPL Y APPLICA TIONS
Cer-T emp 80 Recovery Systems
Where excessive heat exchanger condensation exists due to continued low water inlet temperatures, a bypass balance loop must be installed (see page 15).
WATER LINE CONNECTIONS
This section provides detailed installation diagrams for typical methods of application for the unit using a Cer-Temp 80 Recovery System (for one temperature water).
This equipment must be protected against loss of water or loss of water flow by the installation of a safety flow switch in the outlet piping from the boiler. Piping and wiring diagrams show the application of this accessory for this purpose.
These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary for installation. It is essential that all water and gas piping, vent connections, electrical wiring, and check and flow regulating valves be installed as shown on the diagrams.
ONE DURA-MAX (MODEL DW) COMMERCIAL BOILER WITH VERTICAL T ANK
CAUTION
TO PREVENT CONDENSATION THE MINIMUM BOILER INLET TEMPERATURE IS 100°F (38°C)
HARD W A TER CONDITIONS
Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. When water softening or water treatment is not practical, a comparatively easy method of periodic lime removal from the unit must be employed.
WARNING
Lime accumulation can reduce the life of the equipment, reduce efficiency and waste fuel. Boiler failure due to lime or scale build­up voids the warranty.
These units are so constructed that lime removal is simple and complete, see PREVENTIVE MAINTENANCE.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
SEE PAGE 31 FOR ADDITIONAL PIPING INFORMATION.
IMPORTANT
SAFETY FLOW SWITCH AS SHOWN TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.
* SAFETY RELIEF VAL VE RA TING SHOULD NOT EXCEED PRESSURE
CAPACITY OF ANY COMPONENT IN THE SYSTEM.
CAUTION
PUMP MUST BE RATED FOR SYSTEM OPERATING TEMPERATURES AND PRESSURE.
SEE TABLE 7 FOR GUIDE TO PIPE AND PUMP SIZING.
+ BALL VALVES ARE SHOWN FOR SERVICING BOILER, HOWEVER,
LOCAL CODES SHALL GOVERN THEIR USAGE.
27
Page 28
ONE DURA-MAX (MODEL DW) COMMERCIAL BOILER WITH HORIZONT AL T ANK
CAUTION
TO PREVENT CONDENSATION THE MINIMUM BOILER INLET TEMPERATURE IS 100°F (38°C)
IMPORTANT
SAFETY FLOW SWITCH AS SHOWN TO PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
SEE PAGE 31 FOR ADDITIONAL PIPING INFORMATION.
PUMP MUST BE RATED FOR SYSTEM OPERATING TEMPERA-
CAUTION
TURES AND PRESSURE.
SEE TABLE 7 FOR GUIDE TO PIPE AND PUMP SIZING.
* SAFETY RELIEF VALVE RATING SHOULD NOT EXCEED PRES
SURE CAP ACITY OF ANY COMPONENT IN THE SYSTEM.
+ BALL VALVES ARE SHOWN FOR SERVICING BOILER,
HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.
FIGURE 21
28
Page 29
29
TWO DURA-MAX (MODEL DW) HOT WATER SUPPL Y BOILERS WITH VERTICAL TANK
CAUTION
TO PREVENT CONDENSATION THE MINIMUM BOILER INLET TEMPERATURE IS 100°F (38°C)
SEE PAGE 31 FOR ADDITIONAL PIPING INFORMA TION.
CAUTION
PUMP MUST BE RATED FOR SYSTEM OPERATING TEMPERATURE AND PRESSURE.
* SAFETY RELIEF VALVE RATING SHOULD NOT EXCEED
PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM. INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
+ BALL VALVES ARE SHOWN FOR SERVICING BOILER,
HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE. ALL PIPING MUST BE SUPPORTED.
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.
NOTE: THERMOMETERS, RELIEF VAL VES,CIRCULAT ORS,
SAFETY FLOW SWITCHES AND TANK CONTROLS ARE AVAILABLE THROUGH A.O.SMITH.
FIGURE 22
Guide To Pipe and Pump Sizing
Two (2) Boiler Systems
Common
Manifold Pipe Boiler Pipe Size
Model Size "A" (Min.) "B" (Min.) and Pump
720, 840 2-1/2"
NPT See Table 7
960-1810 3"
NPT
Pipe and pump capacities for two (2) boiler systems based on 100 equivalent feet (30 meters) heater to tank loop.
Page 30
30
TWO DURA-MAX (MODEL DW) HOT WATER SUPPL Y BOILERS WITH HORIZONTAL T ANK
CAUTION
TO PREVENT CONDENSATION THE MINIMUM BOILER INLET TEMPERATURE IS 100°F (38°C)
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.
NOTE: THERMOMETERS, RELIEF VALVES, CIRCULATORS, SAFETY FLOW SWITCHES AND TANK CONTROLS ARE AV AILABLE THROUGH A.O.SMITH.
CAUTION
PUMP MUST BE RATED FOR SYSTEM OPERATING TEMPERATURE AND PRESSURE.
* SAFETY RELIEF VALVE RATING SHOULD NOT EXCEED
PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
+ BALL VALVES ARE SHOWN FOR SERVICING BOILER,
HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.
ALL PIPING MUST BE SUPPORTED.
SEE PAGE 31 FOR ADDITIONAL PIPING INFORMA TION.
FIGURE 23
Guide To Pipe and Pump Sizing
Two (2) Boiler Systems
Common
Manifold Pipe Boiler Pipe Size
Model Size "A" (Min.) "B" (Min.) and Pump
720, 840 2-1/2"
NPT See Table 7
960-1810 3"
NPT
Pipe and pump capacities for two (2) boiler systems based on 100 equivalent feet (30 meters) heater to tank loop.
Page 31
MANIFOLDING OF MODEL TJV-120M & TJV-200M T ANKS
NOTE: PIPE SIZES BETWEEN MANIFOLDS AND BOILER(S) TO BE SELECTED FROM THE CER-TEMP 80 DIAGRAM FOR THE HEATER MODEL TO BE INSTALLED.
ALL PIPING FROM TEES TO BE EQUIDIST ANT TO TANKS. INSTALL IN ACCORDANCE WITH ALL LOCAL CODES. PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED
*
PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM. PIPE RELIEF V ALVES TO OPEN DRAIN.
NOTE: METRIC SIZING IS FOR COMPARISON ONL Y - ALL UNITS CONSTRUCTED WITH TANK FITTING MEASURED IN INCHES.
A.O. SMITH TJV-120M & TJV-200M TANKS WITH: PART NO. 170354 FOR TWO T ANK MANIFOLD KIT PART NO. 170355 FOR THREE T ANK MANIFOLD KIT
TANK TEMPERATURE CONTROL SHOULD BE LOCATED APPROXIMATELY
**
6" ABOVE PATH OF WATER ACROSS BOTTOM OF TANK AND ON SAME SIDE AS RETURN LINE FROM BOILERS. IF TANK OPENING NOT A V AILABLE, USE REMOTE BULB CONTROL.
FIGURE 24
31
Page 32
TWO HORIZONT AL T ANK INST ALLATION
THREE HORIZONT AL T ANK INST ALLA TION
ST ART-UP AND OPERA TING
INSTRUCTIONS
WARNING
After placing boiler into operation, the ignition system safety shutoff device must be tested by the following test method.
1. Reset Manual High Temperature Safety Limit Control (High
Limit) to the lowest setting. (See figures 3 or 4, pages 5 or 6).
FIGURE 25
2. Reset System Controller to maximum setting, causing a call for heat and allowing unit to run until High Limit trips.
3. Reset Manual High Temperature Safety Limit Control to original temperature setting.
4. Push the reset button, unit should run.
5. Reset system controller to desired temperature.
If unit fails to run, see "TROUBLESHOOTING" section in this manual.
These units are so constructed that lime removal is simple and complete, see PREVENTIVE MAINTENANCE.
32
Page 33
LIGHTING AND OPERA TING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
"WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE."
WARNING: HOT WA TER CAN PRODUCE 3rd DEGREE BURNS IN 6 SECONDS A T 140° F. (60° C).
IN CASE OF POWER FAILURE DO NOT ATTEMPT TO OPERATE BOILER. IMPROPER INSTALLA TION, ADJUSTMENT, ALTERATION, SER VICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. REFER TO THE USER'S INFORMATION MANUAL PROVIDED WITH THIS BOILER. INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INST ALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
A. THIS APPLIANCE IS EQUIPPED WITH AN IGNITION DEVICE WHICH AUTOMA TICALL Y
LIGHTS THE PILOT . DO NOT TR Y T O LIGHT THE PILOT BY HAND. BEFORE OPERATING: SMELL ALL AROUND THE APPLIANCE AREA FOR GAS. BE
B.
SURE TO SMELL NEXT TO THE FLOOR BECAUSE SOME GAS IS HEA VIER THAN AIR AND WILL SETTLE ON THE FLOOR. WHAT TO DO IF YOU SMELL GAS
DO NOT TRY TO LIGHT ANY APPLIANCE.
DO NOT TOUCH ANY ELECTRIC SWITCH;
DO NOT USE ANY PHONE IN YOUR BUILDING.
IMMEDIATEL Y CALL YOUR GAS SUPPLIER FROM A NEIGHBORS PHONE. FOLLOW THE GAS SUPPLIERS INSTRUCTIONS.
IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT .
C. USE ONLY YOUR HAND TO PUSH IN OR TURN THE GAS CONTROL KNOB. NEVER
USE TOOLS. IF THE KNOB WILL NOT PUSH IN OR TURN BY HAND, DONT TRY TO REPAIR IT. CALL A QUALIFIED SERVICE TECHNICIAN. FORCE OR ATTEMPTED REPAIR MAY RESULT IN A FIRE OR EXPLOSION.
D. DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER W A TER. IMMEDIA TEL Y
CALL QUALIFIED SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WA TER.
LIGHTING INSTRUCTIONS
1. MAKE SURE BOILER AND SYSTEM ARE FILLED WITH WATER AND ALL AIR HAS BEEN EXPELLED FROM APPLIANCE.
2. TURN OFF ELECTRIC POWER TO THE BOILER. SET SYSTEM TEMPERATURE CONTROLLER TO LOWEST SETTING. PURGE ALL GAS LINES OF AIR.
3. CLOSE MAIN VALVE, FIRING V AL VE, PILOT MANUAL V AL VE. "W AIT FIVE (5) MINUTES TO CLEAR OUT ANY GAS. THEN SMELL FOR GAS, STOP! FOLLOW "B" IN THE SAFETY INFORMATION ABOVE ON THIS LABEL. IF YOU DO NOT SMELL GAS, GO THE NEXT STEP."
4. OPEN MAIN VAL VE, FIRING V AL VE AND PILOT MANUAL VAL VE.
5. TURN ON ELECTRIC POWER AND SET SYSTEM TEMPERATURE CONTROLLER TO DESIRED OPERA TING TEMPERATURE. WHEN CONTROLLER CALLS FOR HEAT, THE CIRCULATING PUMP WILL OPERATE AND THE PILOT BURNER WILL BE SPARK IGNITED. MAIN GAS VAL VES WILL OPEN AND MAIN BURNER WILL THEN IGNITE. NOTE: TRAIL FOR IGNITION IS (15) SECONDS. NOTE: IF PILOT FAILS TO IGNITE, TURN OFF BOILER AND CONSULT YOUR "INSTALLATION AND USERS MANUAL" FOR ADJUSTMENTS AND TROUBLE­SHOOTING.
6. IF THE APPLIANCE WILL NOT OPERATE, FOLLOW THE INSTRUCTIONS "TO TURN OFF GAS TO APPLIANCE" CALL YOUR SERVICE TECHNICIAN OR GAS SUPPLIER.
TO TURN OFF GAS T O APPLIANCE
A. TURN OFF ELECTRICAL POWER TO BOILER. B. CLOSE MAIN VALVE, FIRING VALVE AND PILOT MANUAL VALVE. C. SET SYSTEM TEMPERATURE CONTROLLER TO LOWEST SETTING.
211 186-000 REV .01
33
Page 34
INTERNAL CONTAMINANTS
The system must be internally cleaned and flushed after a new or replacement unit has been installed to remove contaminants that may have accumulated during installation. This is doubly important when a replacement unit is installed into an existing system where Stop Leak or other boiler additives have been used.
All systems should be completely flushed with a grease removing solution to assure trouble-free operation. Pipe joint compounds, soldering paste, grease on tubing and pipe all tend to contaminate a system.
FIGURE 26
Failure to clean and flush the system can cause solids to form on the inside of the heat exchanger, can produce acid concentrations that become corrosive, can allow excessive amounts of air or other gases to form which could block circulation, foul system accessories and damage circulator seals and impellers.
It is recommended that after installation, the boiler and system when filled should include the proper percentage of cleaning solution related to approximate water volume of the system. Fire and circulate for about one hour and then flush clean with fresh water. Commercial grease removing solutions are available.
PRECAUTIONS
If the unit is exposed to the following, do not operate boiler until all corrective steps have been made by a qualified serviceman:
1. Exposure to fire.
2. If damaged.
3. Firing without water.
4. Sooting.
If the heater has been exposed to flooding it must be replaced.
IMPORTANT
ONLY QUALIFIED PERSONNEL SHALL PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE USER SHOULD NOT HESITATE TO ASK THE INSTALLER ANY QUESTIONS REGARDING THE OPERATION AND MAINTENANCE OF THE UNIT.
PILOT BURNER
The pilot flame should envelop 3/8 to 1/2 inch (10 to 12 mm) of the top of the insulated rod on the pilot burner, fig. 26. Normally, the pilot flame will be correct when the pilot manual valve is in the full ON position. Check pilot burner every 3 months for proper flame characteristics.
FIGURE 27
T o adjust the pilot flame, remove the screw on the pilot gas regulator , fig. 27, to expose the adjustment screw. Turn the adjusting screw clockwise
to decrease the length of the flame.
to increase the length of the flame or counterclockwise
MAIN BURNER
Check main burner every three months for proper flame characteristics, fig. 28.
CHECKING AND ADJUSTING THE INPUT
NOTE: For high altitude installations, calculate the input rate in accordance with the procedure in the HIGH ALTITUDE INSTALLATIONS in the OPERATING INSTRUCTIONS section.
1. Attach a pressure gauge or a manometer to the gauge port. Check for correct manifold pressure. PRESSURE SHOULD NOT EXCEED VALUE INDICATED ON RATING PLATE.
2. Use this formula to clock the meter. Be sure that other gas consuming appliances are not ON during this interval.
3600
x H = Btuh
T T = Time in seconds to burn one cubic foot of gas.
H = Gas heating value (Btu per cubic foot of gas). Btuh = Actual boiler input per hour.
IMPORTANT
UNDER NO CIRCUMSTANCES SHALL THE GAS PRESSURE MEASURED AT THE BURNER MANIFOLD EXCEED THAT STATED ON THE BOILER RATING PLATE. OVERFIRING WILL RESUL T IN DAMAGE TO THE BOILER, AS WELL AS INCREASED RISK OF FIRE, SOOTING AND ASPHYXIATION.
TYPICAL AND MAIN BURNER FLAMES
FIGURE 28
The main burner should display the following characteristics:
Provide complete combustion of gas.
Cause rapid ignition and carryover of flame across entire
burner.
Give reasonably quiet operation during initial ignition, operation and extinction.
Cause no excessive lifting of flame from burner ports.
If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or blocks the air openings to the burner or boiler.
NOTE: Cleaning of main burners. Shut off all gas and electric to unit. Complete burner tray assembly may be removed by disconnecting
union assembly, pilot line connection at main burner and sliding tray out of cabinet.
34
Page 35
1. Remove main burners from unit.
2. Check that burner venturi and ports are free of foreign matter.
3. Clean burners with bristle brush and/or vacuum cleaner 3/4" DO NOT distort burner ports or pilot location.
4. Reinstall burners in unit. Making sure front and rear of burners are installed correctly in burner support brackets.
PRE-TROUBLE-SHOOTING
Before any extensive trouble-shooting, perform the following: Ensure that:
Also check for good flow of combustion and ventilating air to the unit. Maintain a clear area around the boiler at all times.
After placing the boiler in operation check the ignition system safety shutoff devices for proper operation. To accomplish this with the main burners operating, close the pilot adjusting valve on the left side of the manifold. Within four seconds the main burners and pilot should extinguish and the spark igniter on the pilot assembly should begin sparking. If this does not occur immediately, discontinue gas supply by closing main manual shutoff and call a qualified serviceman to correct the situation. If the burners extinguish, and pilot assembly begins sparking, the system is operating correctly so discontinue electrical power, open pilot adjusting valve, and light boiler in accordance with lighting and operating instructions.
For installations above 2000 feet (600 m), refer to HIGH ALTITUDE INSTALLATIONS in the installation section.
Power (120 vac) is supplied to the appliance.System control (tank temperature control, thermostat, etc.) is
calling for appliance operation (call for heat).
Other contacts (switches) are closed (transformer relay, low
water cutoff, flow switch, limit controls, pressure switches, etc.)
Gas supply pressure is within the maximum and minimum
operating ranges listed on the appliance rating plate/label.
Voltage (24 vac) is supplied by transformer.Appliance is wired according to wiring diagram.
NOTE: Cross wiring the 24 volt circuit of the relay will short the
transformer.
All wire terminals/connectors are firmly attached to valves,
modules, switches, limit controls, etc.
There has been no damage caused by freezing, inoperative
pumps, etc.
TROUBLE-SHOOTING
SYSTEM OPERATION
CHECKOUT SEQUENCE CORRECT INCORRECT CAUSE REMEDY
Set tank/system temperature Circulating pump Pump and burner Temp. control Replace. control (thermostat) 20°F (12°C) and burner remain on. (thermostat) defective. below tank water temperature. shutoff. System wiring Correct wiring.
incorrect With thermal Circulating pump Pump wired for Correct wiring. balancer, pump on. continuous operation. off delay of Burner on. Gas valve stuck Correct or replace approximately or defective. valve. two minutes. System wiring is Correct wiring.
incorrect.
Set tank/system temperature Circulating pump Circulating pump Auto reset high limit Replace. (If problem control (thermostat) 20°F and burner on. on. control set too low. proven to be at this (12°C) above tank/system control by applying water temperature. Auto reset high limit control jumper to terminals).
differential too wide.
System wiring is Correct wiring.
incorrect.
Manual reset high limit Depress reset
switch has activated. button.
Gas valve or wiring
defective.
Circulating pump Power off or system Check power supply and burner off. wiring is incorrect. and wiring.
Temp. control Replace.
(thermostat) defective.
Burner on. System wiring is Correct wiring.
incorrect.
Boiler outlet temperature Circulating pump. Circulating pump Auto reset high limit control Replace. exceeds 210°F (98°C) hot water and burner on. defective, or set too supply, 250°F (120°C) hydronic high (max. should supply. be set at 200°F [93°C] hot
water supply, 240°F
[115°C] hydronic supply).
Set tank/system temperature System maintains control (thermostat) for desired desired water water temperature. temperature.
35
Page 36
CHECKING HONEYWELL S8600H OR S8610M (NAT. GAS) INTERMITTENT IGNITION CONTROLS
NO SPARK AT PILOT BURNER
NO
Replace ignition module Is voltage (24 Vac) across the 24 V terrminals on module
during call for heat”?
YES
Is voltage (24 Vac) across the PV & MV/PV terminals on call for heat”?
NO
NOTE: S8610M will automatically reset every five (5) minutes. For S8600H pilot valve will be de-energized if module goes into lockout condition. Reset system by turning electrical power off or by turning system controller to off or down below call for heat. Wait one minute then turn system on.
YES
Turn on gas supply. Turn off power supply. Turn on power supply.
NO Is ignition cable firmly plugged into pilot assembly Securely connect cable and module? and/or ground wire.
Is ground wire firmly attached to pilot assembly and GND terminal on module?
YES
Replace cable and/or NO Are ignition cable and ground wire in good condition (not ground wire. brittle, burnt, or cracked)?
YES
Ensure ground strap is the closest metal to the igniter/ sensor rod (electrode) to prevent the spark from
shorting out to other metal parts (pilot screen, pilot Carefully bend down- shield, etc.). wards top of ground NO strap to achieve Ignition cable must not touch metal surfaces or current 1/8" spark gap. carrying wires.
Is there a 1/8" gap between ground strap and electrode?
YES
NO Replace ignition Is the ceramic insulator surrounding the electrode cracked module. or broken?
YES
Replace pilot burner assembly.
36
Page 37
SPARK AT PILOT BURNER BUT PILOT WILL NOT LIGHT
Ensure all manual shutoff valves are fully open; All filters are clean; All gas connections are gas tight; Pilot tubing is not damaged, obstructed or kinked; and pilot orifice is unclogged. Check for air in gas line, purge (bleed) line if necessary.
NO
Attach wires firmly. Are the wires securely attached to the pilot operator on the gas
control and to the PV & MV/PV terminals on the ignition module?
YES
Install a pressure gauge in the pilot tubing line between the gas
NO control and the pilot burner assembly. Ensure that the pilot
Replace gas valve. adjustment screw (under cap) is adjusted to a position that will
permit gas to flow. Is pilot gas flowing during ignition attempt?
YES
Turn on power supply. Turn off power supply.
NO Is ignition cable firmly plugged into pilot assembly and module? Securely connect cable Is ground wire firmly attached to pilot assembly and GND and/or ground wire. terminal on module?
YES
Replace cable and/or NO Are ignition cable and ground wire in good condition (not brittle, ground wire. burnt, or cracked)?
YES
Ensure ground strap is the closest metal to the igniter/sensor Carefully bend down- rod (electrode) to prevent the spark from shorting out wards top of ground NO to other metal parts (pilot screen, pilot shield, etc.). strap to achieve Ignition cable must not touch metal surfaces or current carrying 1/8" spark gap. wires.
Is there a 1/8" gap between ground strap and electrode?
YES
NO Replace pilot Is the ceramic insulator surrounding the electrode in good burner. condition (not cracked or broken)?
Replace ignition Is there excessive draft conditions that may cause pilot burner module. ignition problems?
NO
YES
Correct draft problems in a manner that would ensure adequate combustion and ventilation air and proper pilot burner performance.
37
Page 38
PILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHT
Correct the situation by consulting N O the installation or users manual Does the pilot flame cover 3/8° to 1/2" on how to adjust pilot flame. (10 mm to 12 mm) of igniter/sensor rod?
YES Replace ignition NO NO module. Is voltage (24 Vac) across Does spark stay on for more than 30 seconds
terminals MV and MV/PV? after the pilot is “proven” (lit)?
YES
Attach wires NO Are the wires securely attached to the main firmly. valve operator on the gas control and to
terminals MV and MV/PV on ignition module? YES
YES
Replace main gas valve.
Ensure the ground wire and igntion cable are separate from each other (prevents shorting out).
NO Replace cable and/or Are they in good condition (not brittle, ground wire. burnt or cracked?
YES
NO Is the ceramic insulater surrounding the Replace pilot burner. igniter/sensor rod in good condition (not
broken or cracked)?
YES
Clean rod or replace NO Is the igniter/sensor rod in good condition pilot burner if necessary. (not worn, corroded, sooted or damaged)?
YES
Replace ignition module.
38
Page 39
GENERAL MAINTENANCE
These boilers are designed to give many years of efficient and satisfactory service when properly operated and maintained. To assure continued good performance, the following recommendations are made.
The area around the unit should be kept clean and free from lint and debris. Sweeping the floor around the boiler should be done carefully. This will reduce the dust and dirt which may enter the burner and pilot air passages, causing improper combustion and sooting.
CAUTION
DO NOT USE A NYLON BRUSH OR OTHER STATIC CREATING MATERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM HEATING SURFACES AND VENT.
SUCH DEPOSITS ARE FLAMMABLE AND MAY BE IGNITED BY ST A TIC ELECTRICITY. USE A METAL BRUSH TO MINIMIZE THE DANGER OF EXPLOSION
1. Turn off the electrical power, main manual gas shutoff and pilot valves.
Allow boiler parts to cool before disassembly.
THE FLOW OF COMBUSTION AND VENTILATION AIR TO THE BOILER MUST NOT BE OBSTRUCTED.
THE BOILER AREA MUST BE KEPT CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Any safety devices including low water cutoffs used in conjunction with this boiler should receive periodic (every six months) inspection to assure proper operation. A low water cutoff device of the float type should be flushed every six months. All relief valves should be inspected and manually operated at least twice a year. More frequent inspections may be necessary depending on water conditions.
Periodic checks, at least twice a year, should be made for water and/or gas leaks.
More frequent inspections may be necessary depending on water conditions.
The boiler mounted gas and electrical controls have been designed to give both dependable service and long life. However, malfunction can occur, as with any piece of equipment. It is therefore recommended that all components be checked periodically by a qualified serviceman for proper operation.
RELIEF V ALVE
The safety relief valve should be opened at least twice a year to check its working condition. This will aid in assuring proper pressure relief protection. Lift the lever at the top of the valve several times until the valve seats properly and operate freely.
2. Remove the internal flue collector and vent pipe running to the chimney.
Check parts and chimney for obstructions and clean as
necessary.
3. Remove burners from boiler and other metal parts as required to clean as necessary.
Refer to parts list supplied with this manual for disassembly aid.
4. Clean and reinstall the parts removed in steps 2 and 3.
Be sure the vent pipe has a minimum upward pitch of one quarter inch per foot of length and is sealed as necessary .
5. Restore electrical power and gas supply to boiler.
Check for gas leaks and proper boiler and vent operation.
HEA T EXCHANGER
PREVENTIVE MAINTENANCE
In most water supply systems some solids exist. As the water is heated, these tend to drop out depositing as scale or lime. This scale is relatively easy to remove before the unit becomes clogged.
WARNING
Lime accumulation can reduce the life of the equipment, reduce efficiency and waste fuel. Boiler failure due to lime or scale build­up voids the warranty.
See section on CIRCULA TING PUMP to ensure you have selected the proper size pump for your situation.
DELIMING
DANGER
THE WA TER P ASSING OUT OF THE V AL VE DURING CHECKING OPERATION MAY BE EXTREMELY HOT . BEFORE OPERATING RELIEF VALVE MAKE SURE DRAIN LINE IS INSTALLED TO DIRECT DISCHARGE TO A SAFE LOCATION SUCH AS AN OPEN DRAIN, TO AVOID SCALDING OR WATER DAMAGE.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL V AL VE TO THE APPLIANCE.
VENTING MAINTENANCE
Qualified servicers should follow this procedure when the boiler’s external heating surfaces and vent pipe need cleaning.
The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, boilers and on cooking utensils.
The usage of water softening equipment greatly reduces the hardness of water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.
Figure 29 shows typical piping arrangement for gravity deliming of lime deposits. For systems using recirculating deliming pumps contact your A. O. Smith distributor.
Lime build-up may be seen when viewing the interior of the inlet/ outlet manifold through the pressure relief valve tapping.
39
Page 40
The time between cleaning will vary from two to six months depending upon water conditions and usage. A change of approximately 5°F in the normal temperature rise through the boiler is usually an indication that scale should be removed. For long life, copper or brass is recommended for all valves, pipe and fittings used between gate valves “A” and “B” and the boiler, see fig. 29.
12. Close drain cock and open valves "A" and "B". Purge system of air. Restore electric and gas supply.
AMOUNT OF UN
720, 840, 960, 1080 3 gallons (12 L) 1210, 1350 4 gallons (16 L) 1480, 1610, 1810 6 gallons (24 L)
LIME REQUIRED
MECHANICAL REMOV AL OF DEPOSITS
To service heat exchanger tubes remove cover panel from far side of water connections. This will expose the heat exchanger return bends. Return bends may be removed using a standard 9/16" deep socket ratchet exposing the tube ends. Inspect to ensure tubes are free of scale and deposits. If scaled, remove deposits with a stiff wire brush or mechanical tube cleaner to bare metal. Install new "O" rings and install return bends. Flush system.
REMOV AL OF AN EXISTING BOILER FROM A
COMMON VENTING SYSTEM
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common existing system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
DELIMING SOL VENTS
A. O. Smith recommends the use of UNLIME for deliming. UNLIME is a patented food grade acid.
UN
LIME may be obtained from your dealer, distributor or the
A.O. Smith Water Products Company, Part No. 4763 (1 gal. [4 L]) packed 4 gallons (16 L) per case, Part No. 4813 (5 gal. [20 L]) single container.
CAUTION
Read the instructions on the label of the UN
LIME container.
REMOVING LIGHT DEPOSITS OF SCALE
1. Shut off electric and gas supply to the burner.
2. Close gate valves "A" and "B", see fig. 29.
3. Open drain cock and drain unit.
4. Install standpipe in tee of inlet/outlet line, see fig. 29.
5. Close drain cock.
6. Slowly pour required amount of UNLIME shown in table below into unit through standpipe. Direct solution into suitable container with hose.
7. Continue to fill until foaming action stops. For heavy deposits pour through twice.
8. When foaming action has stopped completely, allow 10 to 15 minutes for UNLIME to dissolve any remaining scale in the unit.
9. Open the drain cock and drain all UNLIME from unit.
10. Remove 12" standpipe and install plug fitting. Close drain cock. Open valve "A" allowing fresh water to flow through unit and drain out hose for 5 minutes.
11. Close valve "A", open drain cock, remove standpipe and hose assembly and install plug fitting.
Seal any unused openings in the common venting system. Visually inspect the venting system for proper size and horizontal
pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows and all doors between the space in which the appliance remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149, Installation Codes. When resizing any portion of the common venting system, the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix F in the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
40
Page 41
DURA-MAX LIMITED WARRANTY
A. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this hydronic boiler:
1. If within TEN years after initial installation of the boiler, the heat exchanger shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor, at his option will exchange or repair such part or portion. This term is reduced to FIVE years if this boiler is used for volume hot water supply purposes other than hydronic space heating.
a. This warranty is extended to the owner for all other parts or portion during the FIRST year following initial installation of this boiler. b. The warranty on the repair or replacement of the part or portion will be limited to the unexpired term of the original warranty.
2. CONDITIONS AND EXCEPTIONS This warranty shall apply only when the boiler is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed instructions provided with it and good industry practices. In addition, an appropriately sized safety relief valve certified to the ASME Boiler and Pressure Vessel Code must have been installed and fresh water used for filling and makeup purposes;
a. This warranty shall apply only when the boiler is used:
(1) owned by the original purchaser; (2) in its original installation location; (3) sized in accordance with proper sizing techniques for commercial boilers; (4) bearing a rating plate which has not been altered, defaced or removed except as required by the warrantor; (5) fired at the factory rated input using the fuel stated on the rating plate; (6) maintained in accordance with the instructions printed in the manual included with the heater. (7) at temperatures not exceeding the maximum setting of its operative and/or high limit control; (8) at water pressure not exceeding the working pressure shown on the boiler; (9) when filled with boiler water, free to circulate at all times and with the heat exchanger free of damaging scale deposits; (10) in a non-corrosive and non-contaminated atmosphere; (11) in the United States, its territories or possessions, and Canada; (12) at a water velocity flow rate, not exceeding or below the boiler's designed rates; (13) indoor installation only.
b. Any accident to the boiler, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form will void this warranty .
3. SERVICE AND REP AIR EXPENSE Under this limited warranty the warrantor will provide only a replacement part. The owner is responsible for all other costs. Such costs may include but are not limited to:
a. Labor charges for service removal, repair or reinstallation of the component part; b. Shipping, delivery, handling, and administrative charges for forwarding the replacement part from the nearest distributor and returning the claimed
defective part to such distributor.
c. All cost necessary or incidental for any material and/or permits required for installation of the replacement.
4. LIMIT A TIONS ON IMPLIED WARRANTIES Implied warranties, including any warranty of merchantability imposed on the sale of this boiler under state law are limited to one (1) year duration for the boiler or any of its parts. Some states or provinces do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
5. CLAIM PROCEDURE Any claim under the warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantors products. If this is not practical, the owner should contact:
a. The warrantor will only honor replacement with identical or similar parts thereof which are manufactured or distributed by the warrantor. b. Dealer replacements are made subject to in-warranty validation by warrantor.
6. DISCLAIMERS NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE W ARRANTOR WITH RESPECT TO THE MERCHANT ABILITY OF THE BOILER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT.
a. Some states or provinces do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may
not apply to you.
b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the boilers rating plate. Owner_________________________________________________________________________________________________________________________ Installation Address________________________________________________________________________________________________________________ City and State or Province _______________________________________________________________________ Postal/Zip Code _______________________ Date Installed ___________ Model No. __________________________ Serial No. ________________________________ Dealers Name____________________________________________________________________________________________________________________ Dealers Address______________________________________________________________________________Phone No. ____________________________
U.S. Customers Canadian Customers A. O. Smith Corporation A. O. Smith Enterprises Ltd. 5621 West 1 15th Street P . O. Box, 310 - 768 Erie Street Alsip, IL 60803 Stratford, Ontario N5A 6T3 T elephone: 800 323-2636 T elephone: 800 265-8520
FILL IN WARRANTY AND KEEP FOR FUTURE REFERENCE
41
Page 42
42
Page 43
43
Page 44
PHONE: 800-433-2545 FAX: 800-433-2515
www.hotwater.com E-Mail: parts@hotwater.com
REPLACEMENT P ARTS
5621 W. 115TH STREET, ALSIP, IL 60803