A. O. Smith DB-1210 Installation Manual

TM
Built tough with maximum efficiency
MODELS DB/DW-720-1810
NATURAL GAS-FIRED COMMERCIAL CROSS FLOW COPPER BOILERS
FOR HYDRONIC HEATING AND HOT WATER SUPPLY
WITH ELECTRONIC INTERMITTENT PILOT IGNITION AND
INSTALLATIONS
INSTALLATION • OPERATION • MAINTENANCE • LIMITED WARRANTY
WARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other
— WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance.
· Do not touch any electrical switch;
do not use any phone in your building.
· Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas
supplier, call the fire department.
— Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMA TION RELA TIVE T O YOUR SAFETY . READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE.
A DIVISION OF A.O.SMITH CORPORA TION
EL P ASO, TX McBEE, SC RENTON, WA
STRATFORD, ONTARIO
VELDHOVEN, THE NETHERLANDS
www.hotwater.com
PLEASE
PRINTED IN U.S.A. 2221 0302
PLACE THESE INSTRUCTIONS ADJACENT TO BOILER AND
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
1
SUPERSEDES PART NO. 20031 1-000 REV. 4 & 210265-000 REV . 0
PART NO. 211680-000 REV . 00
CONTENTS
Page
FOREWORD................................................................................ 2
REPLACEMENT PAR TS .............................................................. 2-3
ROUGH-IN DIMENSIONS/CAPACITIES ...................................... 3-4
Installation Clearances.............................................................. 3
Levelling ................................................................................... 3
FEATURES................................................................................... 5
Safety Relief V alves.................................................................. 5
Electronic Intermittent PIlot Ignition Control .............................. 5
Manual Reset High T emperature Safety Limit Control ............... 5
Automatic Reset High T emperature Control .............................. 6
Thermal Balancer ..................................................................... 6
Safety Flow Switch................................................................... 6
INSTALLA TION INSTRUCTIONS ................................................. 7
Required Ability ........................................................................ 7
Location ................................................................................... 7
Air Requirements ..................................................................... 7-8
Venting the Boiler ..................................................................... 8-9
Gas Connections...................................................................... 9
Purging .................................................................................... 10-1 1
High Altitude Installations ......................................................... 11
Wiring Connections.................................................................. 1 1-12
Servicing Wiring And/Or Control .............................................. 1 2
SYSTEM EQUIPMENT INSTALLA TION ....................................... 12
Water Supply Line.................................................................... 12
Expansion T ank ........................................................................ 12
Vent V alves .............................................................................. 12
System Headers ...................................................................... 12
Cooling Piping .......................................................................... 12
Safety Flow Switch................................................................... 12-13
Circulating Pump...................................................................... 13-14
Page
Low Water Cutoff ..................................................................... 1 4
T ank T emperature Control ........................................................ 14
SYSTEM INSTALLA TION ............................................................. 14
Conventional Space Heating Installation ................................... 14-15
Installation As Boiler Replacement ............................................ 15-17
Linear-T emp Space Heating Applications.................................. 17
Linear-T emp Space Heating Installations .................................. 17-20
Wiring and Schematic Diagrams .............................................. 21-26
HOT WA TER SUPPL Y APPLICA TIONS ....................................... 27-32
Water Line Connections ........................................................... 27
Hard Water Conditions............................................................. 27
ST ART-UP AND OPERA TING INSTRUCTIONS .......................... 32
LIGHTING AND OPERATING INSTRUCTIONS ........................... 33
Internal Contaminants .............................................................. 34
Precautions .............................................................................. 34
Checking and Adjusting the Input............................................. 34
Pilot Burner .............................................................................. 34
Main Burner ............................................................................. 34-35
PRE-TROUBLESHOOTING ......................................................... 35
TROUBLESHOOTING.................................................................. 35-38
GENERAL MAINTENANCE.......................................................... 39
Relief V alve .............................................................................. 39
Venting Maintenance ................................................................ 39
Heat Exchanger Preventive Maintenance.................................. 39
Deliming ................................................................................... 39-40
Deliming Solvents..................................................................... 40
Removing Light Deposits of Scale ............................................ 40
Removal of an Existing Boiler From A Common Venting
System ................................................................................ 40
LIMITED WARRANTY .................................................................. 41
FOREWORD
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE USING APPLIANCE.
Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THAT ALL WATER AND GAS PIPING AND THE ELECTRICAL WIRING BE INSTALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
CHECK THE DIAGRAMS THOROUGHLY BEFORE STARTING INSTALLATION TO AVOID POSSIBLE ERRORS AND TO MINIMIZE TIME AND MATERIALS COST.
This design complies with the latest edition of the CSA 4.9 low-pressure boiler.
Particular attention should be given to the installation of thermometers at the locations indicated in the diagrams as these are necessary for checking the operation of the boiler.
MAKE SURE THE GAS ON WHICH THE BOILER WILL OPERA TE IS THE SAME AS THAT SPECIFIED ON THE UNIT RATING PLATE.
The boiler installation must conform to these instructions and the requirements of the local authority having jurisdiction.
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In the absence of local code requirements, the boiler installation must conform to the most current
National Fuel Gas Code, ANSI
Z223.1 and/or CAN/CSA-B149.1-00 installation codes.
ANSI Z21.13
These manuals can be purchased from the CSA International, 8501 East Pleasant Valley Road, Cleveland, OH 44131 or 178 Rexdale Boulevard, Toronto, Ontario Canada, M9W 1R3.
REPLACEMENT PARTS
Replacement parts may be ordered through A. O. Smith dealers, authorized servicers or distributors. Refer to the Yellow Pages for where to call or contact (in United States) the A.O. Smith Water Products Company, 5621 West 115th Street, Alsip, IL 60803, 1-800-433-2545 or (in Canada) A.O. Smith Enterprises Ltd., 768 Erie Street, Stratford, Ontario, Canada N5A 6T3, 800-265-8520. When ordering parts be sure to state the quantity, part number and description of the item including the complete model and serial number as it appears on the product. Refer to the parts lists for more information.
For Technical Assistance call A.O. Smith Technical Information Center at 1-800-527-1953.
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH UNIT INCORPORATES AN “O RING" WATER SEAL ASSEMBLY. THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT OF THE WATER PIPING SYSTEM. AS ON ALL BOILER INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE PROPER SUPPORT.
WARNING
UNDER NO CIRCUMSTANCES SHOULD THE EQUIPMENT ROOM WHERE THE BOILER IS INSTALLED EVER BE UNDER NEGATIVE PRESSURE. PARTICULAR CARE MUST BE TAKEN WHEN EXHAUST FANS, COMPRESSORS, AIR HANDLING EQUIPMENT, ETC., MA Y INTERFERE WITH THE COMBUSTION AND VENTILATION AIR SUPPLIES OF THIS BOILER.
2
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
"Verify proper operation after servicing."
ROUGH-IN DIMENSIONS/
CAPACITIES
INST ALLA TION CLEARANCES
Two inch clearance is allowable from combustible construction for hot water pipes.
Sufficient clearance should be provided at one end of the boiler to permit access to heat exchanger tubes for cleaning. Maximum operating water supply pressure 160 psi. Gas supply pressure:
13.8" w.c. max., 5.5" w.c. min. Sufficient area should be provided at the front and sides of the unit
for proper servicing. Clearances of 48" in front and 24" on sides is recommended. In a utility room installation, the door shall be wide enough to allow the boiler to enter or to permit the replacement of another appliance.
These boilers are approved for installation on combustible flooring in an alcove with minimum clearance to combustibles See chart below.
W ARNING AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILA TION.
LEVELLING
Each unit should be checked after installation to be certain that it is level.
TABLE 1, ROUG H-IN DIMENSI ONS
Models
Dimensions inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm
A
46 1/2 1181 52 1/5 1326 57 3/4 1467 52 7/8 1343 58 1/2 1486 64 1/2 1638 69 1/2 1765 75 1905 82 1/2 2096
B
29 5/8 752 29 5/8 752 29 5/8 752 32 3/4 832 32 3/4 832 32 3/4 832 34 864 34 864 34 864
C
54 3/4 1391 54 3/4 1391 54 3/4 1391 58 1473 58 1473 58 1473 60 1/2 1537 60 1/2 1537 60 1/2 1537
D E 7 3/4 197 7 3/4 197 7 3/4 197 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 7 1/2 191 F 15 1/2 394 15 1/2 394 15 1/2 394 18 1/2 470 18 1/2 470 18 1/2 470 18 1/2 470 18 1/2 470 18 1/ 2 470 G H J K 2 NPT 2 NPT 2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT L 1 NPT 1 NPT 1 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT M N
W
Approx.
Shipping
Weight.
1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 2 NPT 2 NPT
17 1/4 438 17 1/4 438 17 1/4 438 18 9/16 471 18 9/16 471 18 9/16 471 19 1/8 486 19 1/8 486 19 1/8 486
4 1/4 108 4 1/4 108 4 1/4 108 4 102 4 102 4 102 4 1/2 114 4 1/2 114 4 1/2 114
2 NPT 2 NPT 2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT
12 305 14 356 14 356 16 406 16 406 18 457 18 457 18 457 20 508 15 1/2 394 16 1/2 419 16 1/2 419 17 1/4 438 17 1/4 438 17 1/4 438 13 3/4 349 13 3/4 349 13 3/4 349 32 1/8 816 31 1/8 791 32 1/8 816 30 15 /16 786 30 15/16 786 30 15/16 786 31 787 31 78 7 31 787
780 lbs 354 Kg. 950 lbs 431 Kg 950 lbs 431 Kg 1000 lbs 454 Kg 1075 lbs 48 8 Kg. 1100 lbs 499 Kg 1125 lbs 510 Kg 1150 lbs 522 Kg 1250 lbs 567 Kg
DW-1810DW-1210 DW-1350 DW-1480 DW-1610DW-720 DW-840 DW-960 DW-1080
Minimum Clearances T o Combustibles
Water Blank
T op Side Side Rear Vent Front
All Models 12" (305mm) 18" (457mm) 6" (155mm) 6" (155mm) 6" (155mm) Alcove
3
WARNING
Your Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than 100°F (38°C). Colder inlet water temperatures will result in significant condensation developing on the heat exchanger. This situation can cause a corrosive environment for the heat exchanger, burners and venting resulting in premature damage, which could result in serious personal injury or death.
For systems that use large volumes of cold water or system utilizing heavy water draws (Cer-Temp), condensation can be prevented by using a by-pass loop. See page 16.
TABLE 2, PRESSURE DROP
Model
DW-720
DW-840
DW-960
DW-1080
DW-1210
DW-1350
DW-1480
DW-1610
DW-1810
Temp Rise
FC
Flow Rate
GPM LPM ft
20 11.1 59 223 3.5 1.1 30 16.7 39 149 1.7 0.5 40 22.2 29 111 1.0 0.3
20 11.1 69 260 4.8 1.5 30 16.7 46 173 2.1 0.6 40 22.2 34 130 1.5 0.5
20 11.1 79 297 6.8 2.1 30 16.7 52 198 3.3 1.0 40 22.2 39 149 1.9 0.6
20 11.1 89 339 4.5 1.4 30 16.7 60 226 2.1 0.6 40 22.2 45 169 1.4 0.4
20 11.1 100 379 5.3 1.6 30 16.7 67 253 2.7 0.8 40 22.2 50 190 1.6 0.5
20 11.1 112 423 6.8 2.1 30 16.7 75 282 3.2 1.0 40 22.2 56 212 1.8 0.5
20 11.1 120 453 7.9 2.4 30 16.7 80 302 3.9 1.2 40 22.2 60 226 2.1 0.6
20 11.1 130 492 9.5 2.9 30 16.7 87 328 5.0 1.5 40 22.2 65 246 3.0 0.9
20 11.1 146 554 12.0 3.7 30 16.7 98 369 6.2 1.9 40 22.2 73 277 3.9 1.2
HdLoss*
M
TABLE 3, RECOVERY CAPACITIES
MODEL BTUH KW C 11.1C 16.6C 20C 22.2C 27.7C 30C 33.3C 38.8C 40C 44.4C 50C 55.5C 60C 61.1C 66.6C 70C 72.2C 77.7C
DB/DW-720
DB/DW-840
DB/DW-960
DB/DW-1080
DB/DW-1210
DB/DW-1350
DB/DW-1480
DB/DW-1610
DB/DW-1810
INPUT
720,000 GPH 3,535 2,356 1,964 1,767 1,414 1,309 1,178 1,010 982 884 785 707 655 643 589 561 544 505
840,000 GPH 4,124 2,749 2,291 2,062 1,649 1,527 1,375 1,178 1,145 1,031 916 825 764 750 687 655 634 589
960,000 GPH 4,713 3,142 2,618 2,356 1,885 1,745 1,571 1,346 1,309 1,178 1,047 943 873 857 785 748 725 673
1,080,000 GPH 5,367 3,578 2,982 2,684 2,147 1,988 1,789 1,534 1,491 1,342 1,193 1,073 994 976 895 852 826 767
1,210,000 GPH 6,013 4,009 3,341 3,007 2,405 2,227 2,004 1,718 1,670 1,503 1,336 1,203 1,114 1,093 1,002 954 925 859
1,350,000 GPH 6,709 4,473 3,727 3,355 2,684 2,485 2,236 1,917 1,864 1,677 1,491 1,342 1,242 1,220 1,118 1,065 1,032 958
1,480,000 GPH 7,176 4,784 3,987 3,588 2,870 2,658 2,392 2,050 1,993 1,794 1,595 1,435 1,329 1,305 1,196 1,139 1,104 1,025
1,610,000 GPH 7,806 5,204 4,337 3,903 3,122 2,891 2,602 2,230 2,168 1,952 1,735 1,561 1,446 1,419 1,301 1,239 1,201 1,115
1,810,000 GPH 8,776 5,851 4,875 4,388 3,510 3,250 2,925 2,507 2,438 2,194 1,950 1,755 1,625 1,596 1,463 1,393 1,350 1,254
F 20F 30F 36F 40F 50F 54F 60F 70F 72F 80F 90F 100F 108F 110F 120F 126F 130F 140F
211 LPH 13,379 8,920 7,433 6,690 5,352 4,955 4,460 3,823 3,716 3,345 2,973 2,676 2,478 2,433 2,230 2,124 2,058 1,911
246 LPH 15,609 10,406 8,672 7,805 6,244 5,781 5,203 4,460 4,336 3,902 3,469 3,122 2,891 2,838 2,602 2,478 2,40 1 2,230
281 LPH 17,839 11,893 9,911 8,920 7,136 6,607 5,946 5,097 4,955 4,460 3,964 3,568 3,304 3,243 2,973 2,832 2,74 4 2,548
316 LPH 20,317 13,545 11,287 10,158 8,127 7,525 6,772 5,80 5 5,644 5,079 4,515 4,063 3,762 3,694 3,386 3,225 3,126 2,902
354 LPH 22,762 15,175 12,646 11,381 9,105 8,430 7,587 6,50 4 6,323 5,691 5,058 4,552 4,215 4,139 3,794 3,613 3,502 3,252
395 LPH 25,396 16,931 14,109 12,698 10,158 9,406 8,465 7,256 7,054 6,349 5,644 5,079 4,703 4,617 4,233 4,031 3,907 3,628
433 LPH 27,162 18,108 15,090 13,581 10,865 10,060 9,054 7,761 7,545 6,791 6,036 5,432 5,030 4,939 4,527 4,311 4,179 3,880
472 LPH 29,548 19,699 16,416 14,774 11,819 10,944 9,849 8,442 8,208 7,387 6,566 5,910 5,472 5,372 4,925 4,690 4,546 4,221
530 LPH 33,219 22,146 18,455 16,609 13,288 12,303 11,073 9,491 9,227 8,305 7,382 6,644 6,152 6,040 5,536 5,273 5,111 4,746
U.S. Gallons/Hr and Li t res/Hr at TEMPERAT URE RIS E I NDICATED
4
FEA TURES
IMPORTANT
Only qualified personnel shall perform the initial firing of the heater. At this time the user should not hesitate to ask the individual any questions regarding the operation and maintenance of the unit.
Lighting and Operating instructions are included at the rear of this manual. By using this checklist the user may be able to make minor operational adjustments and save unnecessary service calls. However, the user should not attempt repairs which are not listed under the USER column.
SAFETY RELIEF V ALVES
Your local code authority may have other specific relief valve requirements not covered below.
and pilot gases are cut off during the OFF cycle. Pilot gas ignition is proven by the pilot sensor. Main burner ignition will not occur if the pilot sensor does not first sense pilot ignition.
FIGURE 2
WARNING
THE PURPOSE OF A SAFETY RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE WHICH MAY CAUSE TANK EXPLOSION, SYSTEM OR BOILER DAMAGE.
TO AVOID WATER DAMAGE A DRAIN LINE MUST BE CONNECTED TO A SAFETY RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCA TION. A DRAIN LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND IT MUST NOT CONT AIN ANY V ALVES BETWEEN THE BOILER AND THE RELIEF VALVE OR THE RELIEF VALVE AND THE DRAIN EXIT. IN ADDITION, THERE SHOULD NOT BE ANY RESTRICTIONS IN A DRAIN LINE NOR SHOULD IT BE ROUTED THROUGH AREAS WHERE FREEZING CONDITIONS MIGHT OCCUR. DO NOT THREAD OR CAP THE DRAIN LINE EXIT. RESTRICTING OR BLOCKING A DRAIN LINE WILL DEFEA T THE PURPOSE OF THE RELIEF VALVE AND MAY CREATE AN UNSAFE CONDITION. INSTALL A DRAIN LINE WITH A DOWNWARD SLOPE SUCH THAT IT NATURALLY DRAINS ITSELF.
If any safety relief valve is replaced, the replacement valve must comply with the latest version of the ASME Boiler and Pressure Vessel Code, Section IV (HEATING BOILERS). Select a relief valve with a discharge rating NOT less than the boiler input, and a set pressure NOT exceeding the working pressure of any component in the system.
An ASME rated temperature and pressure relief valve must be installed on each and every water storage tank in a hot water supply system.
The storage tank temperature and pressure relief valve must comply with the applicable construction provisions of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21 or CAN/CSA-B149.1 (latest edition). The valve must be of the automatic reset type and not embody a single-use type fusible plug, cartridge or linkage.
ELECTRONIC INTERMITTENT PILOT
IGNITION CONTROL
ALL MODELS - The solid state ignition control, fig. 2, ignites the pilot burner gas by creating a spark at the pilot assembly . Pilot gas is ignited and burns during each running cycle. The main burner
5
On natural gas models the igniter control continues to operate (creating a spark) until the pilot burner is ignited or the ignition system shuts down. Shut down occurs automatically if the pilot burner does not ignite within 15 seconds. The unit then waits for (5) minutes and retries ignition (standard models).
The electronic intermittent pilot ignition control and the 100% lockout control are non-adjustable devices.
(See troubleshooting steps on page 40). If pilot is not lit and sensed within the flame establishing timing for each module, the appliance will shut down.
MANUAL RESET HIGH TEMPERA TURE
SAFETY LIMIT CONTROL
This device senses water temperature in the boiler. When water temperature exceeds dial setting, power to main gas valve is interrupted and the boiler is shut down.
HOT WATER SUPPLY - Manual reset - factory set at 210°F (100°C). Water temperature must drop at least 20°F (11°C) before reset is possible.
HYDRONIC HEA TING - Manual reset - factory set at 250°F (121°C). Water temperature must drop at least 20°F (11°C) before reset is possible.
Single stage and modulating units use a combined control as shown in fig. 4.
Dual stage models are equipped with a limit like one shown in figure 3.
AUTOMATIC RESET
HIGH TEMPERATURE LIMIT CONTROL
CAUTION
LIMIT CONTROLS ARE NOT TO BE USED AS THERMOSTATS.
The heater operation with above set points will be as follows:
1) When heater temperature rises to LO thermostat setting the main gas valve will close its second stage operator to drop input to approximately 50% of total input.
ALL MODELS - This limit is a safety device wired in series with the ignition system. Set the limit control dial to a minimum of 10°F (6°C) above the maximum designed system temperature. If the boiler outlet water temperature should exceed the high limit setting, the main gas valves will close but the circulator will continue to operate. Maximum adjustable setting is 240°F (116°C) for boilers and 200°F (93°C) for hot water supply heaters. The differential is adjustable from 5°F (3°C) to 45°F.
SINGLE ST AGE AND MODULATING MODELS - Are equipped with the limit like the one shown in fig. 4.
2) System conditions will determine if temperature rise at LO thermostat sensor location will continue to rise until shut-off by high limit or drop causing heater to go back to full input.
Other system design temperatures will require resetting of the dial. Total span of temperatures (HI dial cut-off point to LO dial cut-on point) should not be less than temperature drop of the system.
MODULATING MODELS ONLY These boilers are factory equipped with a modulating gas valve
that automatically controls the outlet water temperature by modulating or proportioning the rate of gas thus maintaining a desired constant outlet water temperature regardless of varying flow rates.
Gas valves either close or open to full gas input, depending upon heat requirement.
DUAL STAGE MODELS ONLY - HIGH/LOW OPERATOR These boilers are factory equipped with a (combination) temperature controller to provide high and low firing rates for smooth operation. (fig. 5).
The temperature dials should be adjusted to have the HI dial set as a limit to be 10°F (6°C) above desired boiler temperature. These boilers are shipped with the HI dial set to 200°F (93°C) with a 15°F (8°C) differential, the LO dial set to 160°F (71°C) with a 10°F (6°C) differential.
Set temperature controller for desired outlet water temperature. (fig. 6).
Adjust the set point for the desired operating temperature by turning the set point adjusting screw on the front of the case until the desired value is reached on the set point indicating dial. The set point is calibrated to be at the center of the proportioning range, (see the manufacturers instructions for complete information on testing and calibrating this control.)
THERMAL BALANCER
This device serves as a pump shutdown delay switch to balance the boiler water temperature to system temperature before the pump stops. Overshooting of boiler temperature is prevented and stack loss after shutdown is minimized.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at the water outlet of the unit to prevent main burner operation in the event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical pipe line with upward water flow. Do not install the switch where the water flow is downward.
6
INST ALLA TION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS BOILER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
If the boiler is installed above the level of heating system terminal units, a low water cutoff device must be installed in the boiler outlet at the time of installation.
For installation locations with elevations above 2,000 feet (610 M), refer to the HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure.
CHEMICAL VAPOR CORROSION
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH UNIT INCORPORATES AN "O RING" WATER SEAL ASSEMBLY. THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT OF THE WATER PIPING SYSTEM. AS ON ALL BOILER INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE PROPER SUPPORT.
LOCATION
When installing the boiler, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practical with adequate air supply and as centralized with the piping system as possible. This location should also be such that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service [circulator replacement, control replacement, etc.].
THE BOILER MUST NOT BE INSTALLED ON CARPETING. THE BOILER SHOULD NOT BE LOCATED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING. LOCATE IT NEAR A FLOOR DRAIN. THE BOILER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE BOILER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
Heat exchanger corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, and process chemicals are typical compounds which are corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near the boiler. Also, air which is brought in contact with the water boiler should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources.
AIR REQUIREMENTS
WARNING
FOR SAFE OPERATION, AN AMPLE SUPPLY OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILATION IN ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILA TION, OF THE NATIONAL FUEL GAS CODE, ANSI Z223.1 OR 7.2, 7.3 OR 7.4 OF CAN/CSA B149.1-00, INSTALLA TION CODES, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES. AN INSUFFICIENT SUPPLY OF AIR MAY RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CARBONING OR SOOTING OF THE FINNED HEAT EXCHANGER, OR CREA TE A RISK OF ASPHYXIA TION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DRAIN P AN SHOULD BE INST ALLED UNDER THE BOILER. Such pans should be fabricated with sides at least 2-1/2" (64 mm) deep, with length and width at least 2" (51 mm) greater than the dimensions of the boiler and must be piped to an adequate drain.
The pan must not restrict combustion air flow.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES IN ROOMS OR AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE IGNITER OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IF INSTALLED 18 INCHES OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE BOILER.
OPEN CONT AINERS OF FLAMMABLE MA TERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE BOILER.
UNCONFINED SPACE
In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion, and draft hood dilution.
If the unconfined space is within a building of tight construction (buildings using the following construction; weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation, and draft hood dilution must be obtained from outdoors or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
CONFINED SPACE
(a) U. S. INSTALLATIONS
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2,208 mm2of per kw) of the total input of all appliances in the enclosure, but not less than 100 square inches (645 cm2).
7
If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btu/hr (551 mm
2
per kw) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btu/hr (1101 mm
2
per kw) of the total input of
all appliances in the enclosure.
(B) CANADIAN INSTALLATIONS
Ventilation of the space occupied by the boiler(s) shall be provided by an opening for ventilation air at the highest practical point communicating with outdoors. The total cross- sectional area shall be at least 10% of the area of the combustion air opening but in no case shall the cross-sectional area be less than 10 square inches (6500 mm²).
1. DRAFT HOOD The integral draft hood, louvers or cabinetry must not be altered.
Provision must be made if the boiler is installed in confined space or a small boiler room to accommodate draft hood spillage and avoid risks described above. The upper air opening called for in the AIR REQUIREMENTS section of this manual is for this purpose.
2. VENT CONNECTION The minimum distance from adjacent public walkways, adjacent
buildings, openable windows and building openings shall not be less than those values specified in the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149.1-00, Installation Codes:
Stack or chimney must be a minimum height of 12" (305 mm) above the annual snow fall to prevent blockage.
Building materials must not come in contact with combustion products from stack or chimney, due to the degrading properties of flue products.
In addition to the above, there shall be permanent air supply opening(s) having a cross-sectional area of not less than 1 square inch per 7,000 BTUH (315 mm²/kw) up to and including 1,000,000 BTUH
plus 1 square inch per 14,000 BTU (158 mm2/kw) in excess of 1,000,000 BTUH. This opening(s) shall be located at, or ducted to, a point neither more than 18" (450 mm) nor less than 6 inches (150 mm) above the floor level.
Where power vented equipment is used in the same room as the boiler, sufficient air openings must be supplied.
UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR FOR COMBUSTION.
Where an exhaust fan is installed in the same room with a boiler, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED RISK OF ASPHYXIATION.
VENTING THE BOILER
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING THE BOILER MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
SINGLE WALL OR TYPE B VENTING MAY BE USED WITH THESE BOILERS. ALL LOCAL UTILITY, STATE/ PROVINCIAL, REGULATIONS ON VENTING MUST BE FOLLOWED.
VENT SIZING, INSTALLATION AND TERMINATION SHALL BE IN ACCORDANCE WITH PART 7, VENTING OF EQUIPMENT, OF THE NATIONAL FUEL GAS CODE, ANSI Z223.1, OR SECTION 7, VENTING SYSTEMS AND AIR SUPPLY FOR APPLIANCES, OF THE CAN/CSA B149, INSTALLATION CODES, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES.
Materials may be protected from flue products by use of metal or copper sheeting.
Flue products must have a minimum clearance of 4 feet (1.22 m) horizontally from, and in no case above or below, unless a 4-foot (1.22 m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
The Canadian B149.1-00, Installation Code specifies a 6 foot horizontal vent terminal clearance to gas and electric meters and relief devices (this clearance is specified as 4 feet in the U.S. under the National Fuel Gas Code, ANSI/Z223.1). Therefore instruction provision 1.34.1-b19(d), which specifies compliance with the 4 foot clearance, as applies in the U.S. only, and the B149.1-00 Installation Code applies in Canada.
Vent connections must be made to an adequate stack or chimney and shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or Section 7, Venting Systems and Air Supply for Appliances, of the CAN/CSA-B149.1­00, Installation Codes, or applicable provisions of the local building codes. Size and install proper size vent pipe. Do not reduce pipe size to less than that of the draft hood outlet unless permitted by local code.
Horizontal runs of vent pipe shall be securely supported by adequately placed (approximately every 4 feet [1.2 m]), noncombustible hangers suitable for the weight and design of the materials employed to prevent sagging and to maintain a minimum upward slope of 1/4" per foot (21mm/m) from the boiler to the vent terminals. Dampers or other obstructions must not be installed in the vent. Be sure that the vent connector does not extend beyond the inside wall of the chimney.
Where a continuous or intermittent back draft is found to exist the cause must be determined and corrected. A special vent cap may be required. If the back draft cannot be corrected by the normal methods or if a suitable draft cannot be obtained, a blower type flue gas exhauster may be employed to ensure proper venting and correct combustion (where permitted by local code). Contact your A. O. Smith dealer for power vent instructions.
8
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
3. CONNECTING BOILER TO A COMMON VENT
Do not connect the boiler to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by most local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.
Where a separate vent connection is not available and the vent pipe from the boiler must be connected to a common vent with an oil burning furnace, the vent pipe should enter the common vent or chimney at a point ABOVE the flue pipe from the oil furnace.
UL/ULC listed doublewall type B-1 gas vents, through 24" (610 mm) diameter, can be installed in heated and unheated areas and can pass through floors, ceilings, partitions, walls and roofs, provided the required clearance is observed.
At the time of removal of an existing boiler, the following steps shall be performed with each appliance remaining connected to the common venting system. Perform these steps while the other appliances remaining connected to the common venting system are not in operation.
GAS CONNECTIONS
WARNING
THIS BOILER IS NOT INTENDED TO OPERA TE A T GAS SUPPL Y PRESSURE OTHER THAN SHOWN ON THE RATING PLATE. EXPOSURE TO HIGHER GAS SUPPL Y PRESSURE MA Y CAUSE DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS.
WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUTOFF VALVE OUTSIDE THE BOILER JACKET, A SUITABLE MAIN MANUAL SHUTOFF VALVE MUST BE INSTALLED IN A LOCATION COMPLYING WITH THOSE CODES.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE APPROVED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
Seal any unused openings in the common venting system.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is not blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust fans, so they will operate at maximum speed. Close fireplace dampers.
Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after five
minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
After it has been determined that each appliance remaining
connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG OR SEDIMENT TRAP) UPSTREAM OF THE GAS CONTROLS, MUST BE INCORPORATED IN THE PIPING. The dirt leg must be
readily accessible and not subject to freezing conditions. INST ALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO Z223.1 AND/OR CAN/CSA-B149.1-00.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve gas inlet.
Fittings and unions in the gas line must be metal to metal type. Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping systems at test pressures equal to or less than 1/2 psi (3.5 kPa).
The boiler and its gas connection must be leak tested before placing the boiler in operation.
Provisions for vent, bleed and gas relief lines (when applicable).
NATIONAL FUEL GAS CODE, ANSI
9
PURGING
Gas line purging is required with new piping or systems in which air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE OF GAS SERVICE TO A VOID RISK OF FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SP ACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVA TED OR REMOVED.
2A. SIZING GAS SUPPLY LINE (For single boiler installations
and for installations of multiples of two or three of same size boilers).
Use table 1, which is taken from ANSI booklet Z223.1,
NATIONAL FUEL GAS CODE, and/or CAN/CSA-B149.1-00 to size iron pipe or equivalent gas supply line. Table 4 is based on a pressure drop of 0.3 inches of water and a specific gravity of 0.60 which is approximately for natural gas. (LP gas has an S.G. of about 1.53). If the service pressure is five inches water column or less, use one pipe size larger than specified in table 1 in order to minimize pressure drop in the line.
BEFORE PLACING THE BOILER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material acceptable for the purpose in locating gas leaks. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
1. CORRECT GAS Make sure the gas on which the boiler will operate is the same as
that specified on the boiler rating plate. Do not install the boiler if equipped for a different type gas, consult your gas supplier. These boilers are designed to operate on natural gas only.
T ABLE 4
MAXIMUM CAP ACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (BASED UPON A PRESSURE DROP OF
0.3 INCH WA TER COLUMN AND 0.6 SPECIFIC GRA VITY GAS)
Length in Feet (Meters) Nominal Iron Pipe Size, Inches (NPT)
From Gas Meter 1 /2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
10 (3) 132 278 520 1,050 1,600 3,050 4,800 8,500 17,500 20 (6) 92 190 350 730 1,100 2,100 3,300 5,900 12,000
30 (9) 73 152 285 590 890 1,650 2,700 4,700 9,700 40 (12) 63 130 245 50 0 760 1,450 2,300 4,100 8,300 50 (15) 56 115 215 44 0 670 1,270 2,000 3,600 7,400 60 (18) 50 105 195 40 0 610 1,150 1,850 3,250 6,800 70 (21) 46 96 180 370 560 1,050 1,700 3,000 6,200 80 (24) 43 90 170 350 530 990 1,600 2,800 5,800 90 (27) 40 84 160 320 490 930 1,500 2,600 5,400
100 (30) 38 79 150 305 460 870 1,400 2,500 5,100 125 (38) 34 72 130 275 410 780 1,250 2,200 4,500 150 (46) 31 64 120 250 380 710 1,130 2,000 4,100 175 (53) 28 59 1 10 225 350 650 1,050 1,850 3,800 200 (61) 26 55 100 210 320 610 980 1,700 3,500
*The heating value of natural gas is approximately 1050 Btu/ft³. Propane (L.P .) gas has a heating value of approximately 2500 Btu/ft³.
2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers
of same size or for multiple installations of two or more mixed sizes).
Capacities in cubic feet per hour of 0.60 specific gravity gas for different sizes and lengths are shown in table 4. No additional allowance is necessary for an ordinary number of fittings.
Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop.
Multipliers To Be Used W ith T able 1 When Applying The
Gravity Factor To Other Than .60 Specific Gravity
Specific Specific
Gravity Multiplier Gravity Multiplier
.35 1.31 1.00 .78 .40 1.23 1.10 .74 .45 1.16 1.20 .71 .50 1.10 1.30 .68 .55 1.04 1.40 .66
*.60 (Nat.) 1.00 *1.50 (Prop.) .63
.65 .96 1.60 .61 .70 .93 1.70 .59 .75 .90 1.80 .58 .80 .87 1.90 .56 .85 .84 *2.00 (Butane) .55 .90 .82 2.10 .54
*Use these correction factors if exact specific gravity of the gas is not known.
TABLE 5
10
Applications of the gravity factor converts the figures given in table 1 to capacities with another gas of different specific gravity. Such application is accomplished by multiplying the capacities given in table 1 by the multipliers shown in table 5.
To determine the size of each section of gas piping in a system within the range of table 4 proceed as follows:
HIGH ALTITUDE INSTALLATIONS
IN CANADA
Acceptance of these models for use at altitudes above 2000 feet (610 m) is based on field test of the individual installation by the provincial/state authority having jurisdiction.
Determine the gas demand of each appliance to be attached to the piping system. When table 4 is to be used to select the piping size, calculate the gas demand in terms of cubic feet per hour for each piping system outlet. The gas demand for an appliance can be found by dividing its heat input rate by the gass heating value.
Obtain or determine the length of piping from the gas meter or service regulator to the appliance(s).
In table 1, select the row showing the distance to the most remote outlet or the next longer distance if the table does not give the exact length. This is the only distance used in determining the size of any section of gas piping. If the gravity factor is to be applied, the values in the selected row of table 4 are multiplied by the appropriate multiplier from table 5.
Total the gas demands of all appliances on the piping system.
Enter table 4, on the left hand side, at the row equal to or just exceeding the distance to the most remote outlet. Select the pipe size in the row with a capacity equal to or just exceeding the total gas demand. This is the required main gas supply line size leading away from the gas meter or regulator. To determine the pipe size required for each branch outlet leading away from the main supply line, determine the gas demand for that outlet. Enter table 4 on the same row, and select the branch pipe size for a capacity equal to or just exceeding the demand at that outlet. The main line can be resized for a lesser capacity after each branch outlet, since the gas demand is reduced. Total the gas demands of all remaining appliances branching off downstream on the main gas line. Re-enter table 4 in the same row and select the appropriate pipe size with adequate capacity. Repeat the branch sizing and main line re-sizing for any remaining appliances in the system.
EXAMPLE Job Condition: Determining the required gas pipe size for a system composed of
two A. O. Smith 720 boilers and two 960 boilers to be installed as a multiple group, 50 lineal feet from meter. Gas to be used has a .60 specific gravity and heating value of 1,000 Btu per cubic foot.
IN THE U.S.A.
WARNING
INSTALLATIONS ABOVE 2000 FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICES IN ACCORDANCE WITH SECTION
8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI Z223.1). FAILURE TO REPLACE THE ORIFICES WILL RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE RESUL TING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
Y ou should contact your gas supplier for any specific changes which may be required in your area.
Ratings specified by manufacturers for most boilers apply for elevations up to 2000 feet (610 m). For elevations above 2000 feet (610 m) ratings must be reduced by a rate of 4% for each 1000 feet (305 m) above sea level.
Example: A Dura-Max is rated at 720,000 Btu/hr. (211 kw) input at sea level. To operate the boiler at 5000 feet (1524 m) it must be derated by 20% (4% x 5) to a new rating of 576,000 Btu/hr. (169 kw) input.
The input reduction is primarily achieved by reducing the size of the main burner orifices. T o do this, the main burner orifices require replacement with orifices sized for the particular installation elevation. When ordering, be sure to state the model number and the altitude of the location where the boiler is being installed.
Upon field deration of the boiler, adjustment to the gas pressure regulator is required. See CHECKING AND ADJUSTING THE INPUT in this manual for inlet and manifold pressure requirements.
Also, due to the input rating reduction required at high altitudes, the output rating of the appliance is also reduced and should be compensated for in the sizing of the equipment for applications.
WIRING CONNECTIONS
1. CONVENTIONAL INSTALLATIONS Solution:
Two 720 Boilers = 1,440,000 Btuh (422 kw) Two 960 Boilers = 1,920,000 Btuh (562 kw) Total Btuh Input = 3,360,000 Btuh = (984 kw)
Total Btuh Input = 3,360,000 Btuh = 3,360 cf/h Btu per Cubic Foot of Gas 1,000
With a cubic foot per hour demand of 3,360 and with 50 lineal feet of gas supply line, table 4 shows a pipe size of 3" is required.
NOTE: For other than .60 specific gravity, apply multiplier factor
as shown in table 5.
11
All electrical work must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1, CSA C22.1, Electrical Code.
The electrical connections must be made so that the circulator will operate before the gas valve opens. At no time may the controlling system allow the burner to fire when there is no water flow through the boilers.
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. Make
the ground connection to the screw provided in the electrical supply junction box on the boiler.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C WIRE OR ITS EQUIVALENT, EXCEPT FOR THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250°C.
SERVICING WIRING AND/OR CONTROL
SYSTEM HEADERS
Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with minimum pressure drop for several circuits, manifolds should be larger than system loops.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
SYSTEMS EQUIPMENT
INSTALLATION
The following is a brief description of the equipment required for installations noted in this manual. All installations must comply with local codes.
The boilers described in this manual may be used for space heating or for the heating of potable water. If the heater is to be used for hydronic space heating, follow the descriptions given for equipment required for installation on pages 12 through 31. However, if units are to be used for heating potable water, the information describing specific systems is found starting on page 32. Installations must comply with all local codes.
WATER SUPPLY LINE
These boilers can be used ONLY in a forced circulation hot water heating system. Since most forced circulation systems will be of the closed type, install the water supply line as shown on piping diagrams, figs. 10 and 14.
The circuits should be spaced on the header at a minimum of 3" (76 mm) center to center. Install a balancing cock in each return line.
Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow.
COOLING PIPING
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. See figure 7.
FIGURE 7
Fast filling of large pipe, old radiator installations (where high pressures are not available) requires bypassing of the pressure reducing valve. Generally, pressure purging is not possible with a well pump system. High point air venting is essential. For details, refer to OPERATING INSTRUCTIONS section of this manual.
If the system is of the open type, a pressure reducing valve will not be required as the water supply to the system will be controlled by a manually operated valve. An overhead surge tank is required. MINIMUM PRESSURE OF 15 PSI MUST BE MAINTAINED ON THE BOILER AT ALL TIMES to ensure avoidance of potential damage to the boiler which may not be covered by the warranty.
EXP ANSION T ANK
If the system is of the closed type, install an expansion tank as shown in fig. 10. system is very important and is directly related to the total water volume of the system. Refer to ASME or other reliable specifications for sizing.
An air separator as shown in the piping diagrams is recom- mended especially for modern commercial hydronic systems.
The sizing of the expansion tank for a closed
VENT VALVES
It is recommended that automatic, loose key or screwdriver type vent valves be installed at each convector or radiator.
Water temperature in the heating system must be reduced to less than 100°F before cooling system is started, or damage to the chiller unit may occur.
The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A
Primary/secondary pumping of both the chiller(s) and the boiler(s) is an excellent winter-summer change-over method, because cooling flow rates are much more than heating flow rates. In this way each system (heating or cooling) is circulated independently.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at the water outlet of the unit to prevent main burner operation in the event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical pipe line with upward water flow. Do not install the switch where the water flow is downward.
For best performance mount the switch in a section of pipe where there is a straight run of at least 5 pipe diameters on each side of the flow switch (i.e. do not locate adjacent to valves, elbows, orifices, etc.).
12
FIGURE 8
The flow switch shall be mounted in the top opening of the reducing tee and provide adequate paddle length in the flow stream. For example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For 2" or 3" pipe use the paddle segments as supplied. For other pipe sizes (i.e. 2-1/2") trim the paddle to the proper pipe size, see fig. 8. If a standard tee is used, install a face or hex bushing in the top opening. The paddle must be adjusted or trimmed to the size of the pipe in which it will be installed.
CAUTION
The paddle must not touch any part of the tee into which it is installed. Screw the flow switch in position so the flat of the paddle is at right angles to the flow. The arrow on the side case must point in the direction of the flow.
To adjust the flow rate setting:
1. Remove the flow switch cover.
2. For higher flow rateturn the range adjusting screw clockwise.
3. For lower flow rateturn the range adjusting screw counterclockwise.
Where units are installed in multiples, each boiler must be individually protected by a safety flow switch.
THE CIRCULATING PUMP MUST BE PROPERLY SIZED FOR YOUR APPLICATION.
Water hardness, system pressure drop and temperature rise across the boiler all affect how large a circulating pump must be.
Running "hard water" too slowly through the boiler can result in damage due to lime or scale accumulation.
Running "soft water" too quickly through the boiler can result in damage due to velocity flow erosion.
T able 4 has been designed to assist in determining operating ranges. Use this chart as a guide when sizing pumps.
FIGURE 9
CIRCULA TING PUMP
Dura-Max boilers are designed to operate over a wide range of temperatures and flow rates.
13
Although each circulator that requires oil is oiled and operated by the manufacturer, IT MUST BE OILED AGAIN BEFORE BEING OPERATED. Oil the three oil cups (2 on the motor, 1 on the pump) as instructed on the oil tube supplied with the unit, fig. 9.
Thereafter, during the heating season, lubricate the three oil cups at least once every four months. Combination heating/cooling systems or water heating (Cer-temp) systems should be lubricated every four months year-round.
all cases, that the water temperature be set for the lowest temperature which satisfies the user's hot water needs. This will also provide the most energy efficient operation of the water heater and minimize scale formation.
Use 2 or 3 teaspoonfuls in bearing oil cups, fig. 9, and 10 or 12 drops in the motor oil cups. Use No. 20 non-detergent motor oil.
Follow the same oiling procedure if a replacement circulator is installed into the system.
LOW WATER CUTOFF
A low water cutoff is a safety device which is installed in the boiler piping to prevent the boiler from firing in the event of inadequate water levels in the boiler system.
Where required by local code, this optional device is to be installed in the boiler piping at a level above that of the heat exchanger.
A float type or an electronic probe type low water cutoff may be used. The manufacturers installation instructions must be followed.
A hot water boiler installed above radiating level or as required by the Authority having jurisdiction, must be provided with a low water cutoff device at the time of boiler installation.
T ANK TEMPERATURE CONTROL
The water temperature in the storage tank is controlled by the Tank Temperature Control. The sensing element is mounted inside the hot water storage tank, see fig. 24.
SETTING THE WATER TEMPERATURE AT 120°F (49°C) WILL REDUCE THE RISK OF SCALDS. Some states require settings at specific lower temperatures. T able 6 below shows the approximate time-to-burn relationship for normal adult skin.
Temperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
Over 170°F (77°C) Nearly instantaneous 160°F (71°C) About 1/2 second 150°F (65°C) About 1-1/2 seconds 140°F (60°C) Less than 5 seconds 130°F (55°C) About 30 seconds 120°F or less (49°C) More than 5 minutes
TABLE 6
USE ANTI-SCALD V ALVE(S) in the hot water system to reduce the risks of scalds at points of use such as lavatories, sinks and bathing facilities.
A change in water temperature in the storage tank lower than the Tank Temperature Control setting will cause the sensor to close its contacts and consequently, energize the boiler.
If the Tank Temperature Control is out of calibration, replace it with a new one; do not attempt to repair this control.
DANGER
HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSON'S AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED, OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER T AP OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HA VE ACCESS TO SET TEMPERATURES.
The tank temperature control is adjustable from 100°F to 220°F (38°C to 104°C). It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in
SYSTEM INSTALLATION
GENERAL
If the system is to be filled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent a downdraft entering the boiler or freezing air from contacting the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system. Damage due to freezing is not covered by the warranty.
Good practice requires that all piping, etc., be properly supported.
CONVENTIONAL SP ACE HEA TING INST ALLA TION
Modern fin type boilers are exceptionally fast heating units. The low water volumes in relation to firing rates require special attention to water flow rates for smooth, efficient operation. These considerations for the A. O. Smith copper heat exchanger boilers are covered below.
Refer to page 5 for tables on these units showing flow rate vs. pressure drop and temperature rise”.
Figure 10 shows a typical installation of the boiler. A system with several flow controlled zones, or with a 3-way mixing
valve system which could present a flow rate to the boiler of less than that required for a maximum of 50°F (10°C) temperature rise at the minimum firing rate, should be designed with compensating bypasses at the boiler.
14
Loading...
+ 30 hidden pages