WARNING: If the information in this manual
is not followed exactly , a fire or explosion may
result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
·Do not try to light any appliance.
·Do not touch any electrical switch;
do not use any phone in your
building.
·Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
·If you cannot reach your gas
supplier, call the fire department.
— Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTAINS
INFORMA TION RELA TIVE T O YOUR SAFETY .
READ THOROUGHLY BEFORE INSTALLING AND
USING THIS APPLIANCE.
TEXT PRINTED OR OUTLINED IN RED CONTAINS
INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ
THOROUGHLY BEFORE USING APPLIANCE.
Detailed installation diagrams are in this manual. These diagrams
will serve to provide the installer with a reference for the materials
and method of piping suggested. IT IS NECESSARY THAT ALL
WATER AND GAS PIPING AND THE ELECTRICAL WIRING BE
INSTALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
CHECK THE DIAGRAMS THOROUGHLY BEFORE STARTING
INSTALLATION TO AVOID POSSIBLE ERRORS AND TO
MINIMIZE TIME AND MATERIALS COST.
This design complies with the latest edition of the
CSA 4.9 low-pressure boiler.
Particular attention should be given to the installation of
thermometers at the locations indicated in the diagrams as these
are necessary for checking the operation of the boiler.
MAKE SURE THE GAS ON WHICH THE BOILER WILL OPERA TE
IS THE SAME AS THAT SPECIFIED ON THE UNIT RATING PLATE.
The boiler installation must conform to these instructions and the
requirements of the local authority having jurisdiction.
Where required by the authority having jurisdiction, the installation
must conform to the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
In the absence of local code requirements, the boiler installation
must conform to the most current
These manuals can be purchased from the CSA International,
8501 East Pleasant Valley Road, Cleveland, OH 44131 or 178
Rexdale Boulevard, Toronto, Ontario Canada, M9W 1R3.
REPLACEMENT PARTS
Replacement parts may be ordered through A. O. Smith dealers,
authorized servicers or distributors. Refer to the Yellow Pages for
where to call or contact (in United States) the A.O. Smith Water
Products Company, 5621 West 115th Street, Alsip, IL 60803,
1-800-433-2545 or (in Canada) A.O. Smith Enterprises Ltd., 768
Erie Street, Stratford, Ontario, Canada N5A 6T3, 800-265-8520.
When ordering parts be sure to state the quantity, part number and
description of the item including the complete model and serial
number as it appears on the product. Refer to the parts lists for
more information.
For Technical Assistance call A.O. Smith Technical Information
Center at 1-800-527-1953.
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH
UNIT INCORPORATES AN “O RING" WATER SEAL ASSEMBLY.
THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT
OF THE WATER PIPING SYSTEM. AS ON ALL BOILER
INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE
PROPER SUPPORT.
WARNING
UNDER NO CIRCUMSTANCES SHOULD THE EQUIPMENT
ROOM WHERE THE BOILER IS INSTALLED EVER BE UNDER
NEGATIVE PRESSURE. PARTICULAR CARE MUST BE TAKEN
WHEN EXHAUST FANS, COMPRESSORS, AIR HANDLING
EQUIPMENT, ETC., MA Y INTERFERE WITH THE COMBUSTION
AND VENTILATION AIR SUPPLIES OF THIS BOILER.
2
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
"Verify proper operation after servicing."
ROUGH-IN DIMENSIONS/
CAPACITIES
INST ALLA TION CLEARANCES
Two inch clearance is allowable from combustible construction for
hot water pipes.
Sufficient clearance should be provided at one end of the boiler to
permit access to heat exchanger tubes for cleaning. Maximum
operating water supply pressure 160 psi. Gas supply pressure:
13.8" w.c. max., 5.5" w.c. min.
Sufficient area should be provided at the front and sides of the unit
for proper servicing. Clearances of 48" in front and 24" on sides is
recommended. In a utility room installation, the door shall be wide
enough to allow the boiler to enter or to permit the replacement of
another appliance.
These boilers are approved for installation on combustible flooring
in an alcove with minimum clearance to combustibles See chart
below.
W ARNING
AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED
FOR PROPER COMBUSTION AND VENTILA TION.
LEVELLING
Each unit should be checked after installation to be certain that it is
level.
Your Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than
100°F (38°C). Colder inlet water temperatures will result in significant condensation developing on
the heat exchanger. This situation can cause a corrosive environment for the heat exchanger,
burners and venting resulting in premature damage, which could result in serious personal injury or
death.
For systems that use large volumes of cold water or system utilizing heavy water draws (Cer-Temp),
condensation can be prevented by using a by-pass loop. See page 16.
U.S. Gallons/Hr and Li t res/Hr at TEMPERAT URE RIS E I NDICATED
4
FEA TURES
IMPORTANT
Only qualified personnel shall perform the initial firing of the heater.
At this time the user should not hesitate to ask the individual any
questions regarding the operation and maintenance of the unit.
Lighting and Operating instructions are included at the rear of this
manual. By using this checklist the user may be able to make
minor operational adjustments and save unnecessary service calls.
However, the user should not attempt repairs which are not listed
under the USER column.
SAFETY RELIEF V ALVES
Your local code authority may have other specific relief valve
requirements not covered below.
and pilot gases are cut off during the “OFF” cycle. Pilot gas ignition
is proven by the pilot sensor. Main burner ignition will not occur if
the pilot sensor does not first sense pilot ignition.
FIGURE 2
WARNING
THE PURPOSE OF A SAFETY RELIEF VALVE IS TO AVOID
EXCESSIVE PRESSURE WHICH MAY CAUSE TANK
EXPLOSION, SYSTEM OR BOILER DAMAGE.
TO AVOID WATER DAMAGE A DRAIN LINE MUST BE
CONNECTED TO A SAFETY RELIEF VALVE TO DIRECT
DISCHARGE TO A SAFE LOCA TION. A DRAIN LINE MUST NOT
BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND IT
MUST NOT CONT AIN ANY V ALVES BETWEEN THE BOILER AND
THE RELIEF VALVE OR THE RELIEF VALVE AND THE DRAIN
EXIT. IN ADDITION, THERE SHOULD NOT BE ANY
RESTRICTIONS IN A DRAIN LINE NOR SHOULD IT BE ROUTED
THROUGH AREAS WHERE FREEZING CONDITIONS MIGHT
OCCUR. DO NOT THREAD OR CAP THE DRAIN LINE EXIT.
RESTRICTING OR BLOCKING A DRAIN LINE WILL DEFEA T THE
PURPOSE OF THE RELIEF VALVE AND MAY CREATE AN
UNSAFE CONDITION. INSTALL A DRAIN LINE WITH A
DOWNWARD SLOPE SUCH THAT IT NATURALLY DRAINS
ITSELF.
If any safety relief valve is replaced, the replacement valve must
comply with the latest version of the ASME Boiler and Pressure
Vessel Code, Section IV (“HEATING BOILERS”). Select a relief
valve with a discharge rating NOT less than the boiler input, and a
set pressure NOT exceeding the working pressure of any component
in the system.
An ASME rated temperature and pressure relief valve must be
installed on each and every water storage tank in a hot water supply
system.
The storage tank temperature and pressure relief valve must comply
with the applicable construction provisions of the Standard for Relief
Valves and Automatic Gas Shutoff Devices for Hot Water Supply
Systems, ANSI Z21 or CAN/CSA-B149.1 (latest edition). The valve
must be of the automatic reset type and not embody a single-use
type fusible plug, cartridge or linkage.
ELECTRONIC INTERMITTENT PILOT
IGNITION CONTROL
ALL MODELS - The solid state ignition control, fig. 2, ignites the
pilot burner gas by creating a spark at the pilot assembly . Pilot gas
is ignited and burns during each running cycle. The main burner
5
On natural gas models the igniter control continues to operate
(creating a spark) until the pilot burner is ignited or the ignition
system shuts down. Shut down occurs automatically if the pilot
burner does not ignite within 15 seconds. The unit then waits for
(5) minutes and retries ignition (standard models).
The electronic intermittent pilot ignition control and the 100% lockout
control are non-adjustable devices.
(See troubleshooting steps on page 40). If pilot is not lit and sensed
within the flame establishing timing for each module, the appliance
will shut down.
MANUAL RESET HIGH TEMPERA TURE
SAFETY LIMIT CONTROL
This device senses water temperature in the boiler. When water
temperature exceeds dial setting, power to main gas valve is
interrupted and the boiler is shut down.
HOT WATER SUPPLY - Manual reset - factory set at 210°F (100°C).
Water temperature must drop at least 20°F (11°C) before reset is
possible.
HYDRONIC HEA TING - Manual reset - factory set at 250°F (121°C).
Water temperature must drop at least 20°F (11°C) before reset is
possible.
Single stage and modulating units use a combined control as shown
in fig. 4.
Dual stage models are equipped with a limit like one shown in
figure 3.
AUTOMATIC RESET
HIGH TEMPERATURE LIMIT CONTROL
CAUTION
LIMIT CONTROLS ARE NOT TO BE USED AS THERMOSTATS.
The heater operation with above set points will be as follows:
1)When heater temperature rises to LO thermostat setting the
main gas valve will close its second stage operator to drop
input to approximately 50% of total input.
ALL MODELS - This limit is a safety device wired in series with the
ignition system. Set the limit control dial to a minimum of 10°F
(6°C) above the maximum designed system temperature. If the
boiler outlet water temperature should exceed the high limit setting,
the main gas valves will close but the circulator will continue to
operate. Maximum adjustable setting is 240°F (116°C) for boilers
and 200°F (93°C) for hot water supply heaters. The differential is
adjustable from 5°F (3°C) to 45°F.
SINGLE ST AGE AND MODULATING MODELS - Are equipped with
the limit like the one shown in fig. 4.
2)System conditions will determine if temperature rise at LO
thermostat sensor location will continue to rise until shut-off
by high limit or drop causing heater to go back to full input.
Other system design temperatures will require resetting of the dial.
Total span of temperatures (HI dial cut-off point to LO dial cut-on
point) should not be less than temperature drop of the system.
MODULATING MODELS ONLY
These boilers are factory equipped with a modulating gas valve
that automatically controls the outlet water temperature by
modulating or proportioning the rate of gas thus maintaining a
desired constant outlet water temperature regardless of varying
flow rates.
Gas valves either close or open to full gas input, depending upon
heat requirement.
DUAL STAGE MODELS ONLY - HIGH/LOW OPERATOR
These boilers are factory equipped with a (combination) temperature
controller to provide high and low firing rates for smooth operation.
(fig. 5).
The temperature dials should be adjusted to have the HI dial set as
a limit to be 10°F (6°C) above desired boiler temperature. These
boilers are shipped with the HI dial set to 200°F (93°C) with a 15°F
(8°C) differential, the LO dial set to 160°F (71°C) with a 10°F (6°C)
differential.
Set temperature controller for desired outlet water temperature.
(fig. 6).
Adjust the set point for the desired operating temperature by turning
the set point adjusting screw on the front of the case until the desired
value is reached on the set point indicating dial. The set point is
calibrated to be at the center of the proportioning range, (see the
manufacturers instructions for complete information on testing and
calibrating this control.)
THERMAL BALANCER
This device serves as a pump shutdown delay switch to balance
the boiler water temperature to system temperature before the pump
stops. Overshooting of boiler temperature is prevented and stack
loss after shutdown is minimized.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at
the water outlet of the unit to prevent main burner operation in the
event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical
pipe line with upward water flow. Do not install the switch where
the water flow is downward.
6
INST ALLA TION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS BOILER REQUIRES
ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN
IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING,
GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
If the boiler is installed above the level of heating system terminal
units, a low water cutoff device must be installed in the boiler outlet
at the time of installation.
For installation locations with elevations above 2,000 feet (610 M),
refer to the HIGH ALTITUDE INSTALLATIONS section of this
manual for input reduction procedure.
CHEMICAL VAPOR CORROSION
WARNING
THE INLET/OUTLET WATER MANIFOLD ON YOUR A. O. SMITH
UNIT INCORPORATES AN "O RING" WATER SEAL ASSEMBLY.
THE MANIFOLD IS NOT DESIGNED TO SUPPORT THE WEIGHT
OF THE WATER PIPING SYSTEM. AS ON ALL BOILER
INSTALLA TIONS, SPECIAL CARE MUST BE TAKEN TO ENSURE
PROPER SUPPORT.
LOCATION
When installing the boiler, consideration must be given to proper
location. Location selected should be as close to the stack or
chimney as practical with adequate air supply and as centralized
with the piping system as possible. This location should also be
such that the gas ignition system components are protected from
water (dripping, spraying, etc.) during appliance operation and
service [circulator replacement, control replacement, etc.].
THE BOILER MUST NOT BE INSTALLED ON CARPETING.
THE BOILER SHOULD NOT BE LOCATED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE BOILER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE BOILER
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.
Heat exchanger corrosion and component failure can be caused
by the heating and breakdown of airborne chemical vapors. Spray
can propellants, cleaning solvents, refrigerator and air conditioning
refrigerants, swimming pool chemicals, calcium and sodium
chloride, waxes, and process chemicals are typical compounds
which are corrosive. These materials are corrosive at very low
concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near the boiler. Also, air
which is brought in contact with the water boiler should not contain
any of these chemicals. If necessary, uncontaminated air should
be obtained from remote or outside sources.
AIR REQUIREMENTS
WARNING
FOR SAFE OPERATION, AN AMPLE SUPPLY OF AIR MUST BE
PROVIDED FOR PROPER COMBUSTION AND VENTILATION
IN ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION
AND VENTILA TION, OF THE NATIONAL FUEL GAS CODE, ANSI
Z223.1 OR 7.2, 7.3 OR 7.4 OF CAN/CSA B149.1-00,
INSTALLA TION CODES, OR APPLICABLE PROVISIONS OF THE
LOCAL BUILDING CODES. AN INSUFFICIENT SUPPLY OF AIR
MAY RESULT IN A YELLOW, LUMINOUS BURNER FLAME,
CARBONING OR SOOTING OF THE FINNED HEAT
EXCHANGER, OR CREA TE A RISK OF ASPHYXIA TION. DO NOT
OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION
AIR.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
DRAIN P AN SHOULD BE INST ALLED UNDER THE BOILER. Such
pans should be fabricated with sides at least 2-1/2" (64 mm) deep,
with length and width at least 2" (51 mm) greater than the
dimensions of the boiler and must be piped to an adequate drain.
The pan must not restrict combustion air flow.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES IN
ROOMS OR AREAS WHERE GASOLINE, OTHER FLAMMABLE
LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE
STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS
ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE
IGNITED BY THE IGNITER OR MAIN BURNER FLAMES
CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT
OPERATION OF GAS APPLIANCES IF INSTALLED 18 INCHES
OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK
IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE BOILER.
OPEN CONT AINERS OF FLAMMABLE MA TERIAL SHOULD NOT
BE STORED OR USED IN THE SAME ROOM WITH THE BOILER.
UNCONFINED SPACE
In buildings of conventional frame, brick or stone construction,
unconfined spaces may provide adequate air for combustion, and
draft hood dilution.
If the unconfined space is within a building of tight construction
(buildings using the following construction; weather stripping, heavy
insulation, caulking, vapor barrier, etc.), air for combustion,
ventilation, and draft hood dilution must be obtained from outdoors
or spaces freely communicating with the outdoors. The installation
instructions for confined spaces in tightly constructed buildings must
be followed to ensure adequate air supply.
CONFINED SPACE
(a) U. S. INSTALLATIONS
When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN OR
WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE TOP AND
ONE IN OR WITHIN 12 INCHES (30 CM) OF THE ENCLOSURE
BOTTOM. Each opening shall have a free area of at least one
square inch per 1000 Btuh (2,208 mm2of per kw) of the total input
of all appliances in the enclosure, but not less than 100 square
inches (645 cm2).
7
If the confined space is within a building of tight construction, air for
combustion, ventilation, and draft hood dilution must be obtained
from outdoors. When directly communicating with the outdoors or
communicating with the outdoors through vertical ducts, two
permanent openings, located in the aforementioned manner, shall
be provided. Each opening shall have a free area of not less than
one square inch per 4000 Btu/hr (551 mm
2
per kw) of the total
input of all appliances in the enclosure. If horizontal ducts are
used, each opening shall have a free area of not less than one
square inch per 2000 Btu/hr (1101 mm
2
per kw) of the total input of
all appliances in the enclosure.
(B) CANADIAN INSTALLATIONS
Ventilation of the space occupied by the boiler(s) shall be provided
by an opening for ventilation air at the highest practical point
communicating with outdoors. The total cross- sectional area shall
be at least 10% of the area of the combustion air opening but in no
case shall the cross-sectional area be less than 10 square inches
(6500 mm²).
1.DRAFT HOOD
The integral draft hood, louvers or cabinetry must not be altered.
Provision must be made if the boiler is installed in confined space
or a small boiler room to accommodate draft hood spillage and
avoid risks described above. The upper air opening called for in
the AIR REQUIREMENTS section of this manual is for this purpose.
2.VENT CONNECTION
The minimum distance from adjacent public walkways, adjacent
buildings, openable windows and building openings shall not be
less than those values specified in the National Fuel Gas Code,
ANSI Z223.1 and/or CAN/CSA B149.1-00, Installation Codes:
Stack or chimney must be a minimum height of 12" (305 mm)
above the annual snow fall to prevent blockage.
Building materials must not come in contact with combustion
products from stack or chimney, due to the degrading properties of
flue products.
In addition to the above, there shall be permanent air supply
opening(s) having a cross-sectional area of not less than 1 square
inch per 7,000 BTUH (315 mm²/kw) up to and including 1,000,000
BTUH
plus 1 square inch per 14,000 BTU (158 mm2/kw) in excess
of 1,000,000 BTUH. This opening(s) shall be located at, or ducted
to, a point neither more than 18" (450 mm) nor less than 6 inches
(150 mm) above the floor level.
Where power vented equipment is used in the same room as the
boiler, sufficient air openings must be supplied.
UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR
FOR COMBUSTION.
Where an exhaust fan is installed in the same room with a boiler,
sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN
INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED
RISK OF ASPHYXIATION.
VENTING THE BOILER
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING THE
BOILER MUST BE FOLLOWED TO AVOID CHOKED
COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH
CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND
ASPHYXIATION.
SINGLE WALL OR TYPE B VENTING MAY BE USED WITH
THESE BOILERS. ALL LOCAL UTILITY, STATE/ PROVINCIAL,
REGULATIONS ON VENTING MUST BE FOLLOWED.
VENT SIZING, INSTALLATION AND TERMINATION SHALL BE
IN ACCORDANCE WITH PART 7, VENTING OF EQUIPMENT,
OF THE NATIONAL FUEL GAS CODE, ANSI Z223.1, OR SECTION
7, VENTING SYSTEMS AND AIR SUPPLY FOR APPLIANCES,
OF THE CAN/CSA B149, INSTALLATION CODES, OR
APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES.
Materials may be protected from flue products by use of metal or
copper sheeting.
Flue products must have a minimum clearance of 4 feet (1.22 m)
horizontally from, and in no case above or below, unless a 4-foot
(1.22 m) horizontal distance is maintained, from electric meters,
gas meters, regulators and relief equipment.
The Canadian B149.1-00, Installation Code specifies a 6 foot
horizontal vent terminal clearance to gas and electric meters and
relief devices (this clearance is specified as 4 feet in the U.S. under
the National Fuel Gas Code, ANSI/Z223.1). Therefore instruction
provision 1.34.1-b19(d), which specifies compliance with the 4 foot
clearance, as applies in the U.S. only, and the B149.1-00 Installation
Code applies in Canada.
Vent connections must be made to an adequate stack or chimney
and shall be in accordance with Part 7, Venting of Equipment, of
the National Fuel Gas Code, ANSI Z223.1, or Section 7, Venting
Systems and Air Supply for Appliances, of the CAN/CSA-B149.100, Installation Codes, or applicable provisions of the local building
codes. Size and install proper size vent pipe. Do not reduce pipe
size to less than that of the draft hood outlet unless permitted by
local code.
Horizontal runs of vent pipe shall be securely supported by
adequately placed (approximately every 4 feet [1.2 m]),
noncombustible hangers suitable for the weight and design of the
materials employed to prevent sagging and to maintain a minimum
upward slope of 1/4" per foot (21mm/m) from the boiler to the vent
terminals. Dampers or other obstructions must not be installed in
the vent. Be sure that the vent connector does not extend beyond
the inside wall of the chimney.
Where a continuous or intermittent back draft is found to exist the
cause must be determined and corrected. A special vent cap may
be required. If the back draft cannot be corrected by the normal
methods or if a suitable draft cannot be obtained, a blower type
flue gas exhauster may be employed to ensure proper venting and
correct combustion (where permitted by local code). Contact your
A. O. Smith dealer for power vent instructions.
8
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR
CONTAMINATION AND UNSAFE CONDITIONS.
Vent connectors serving appliances vented by natural draft shall
not be connected into any portion of mechanical draft systems
operating under positive pressure.
3.CONNECTING BOILER TO A COMMON VENT
Do not connect the boiler to a common vent or chimney with solid
fuel burning equipment. This practice is prohibited by most local
building codes as is the practice of venting gas fired equipment to
the duct work of ventilation systems.
Where a separate vent connection is not available and the vent
pipe from the boiler must be connected to a common vent with an
oil burning furnace, the vent pipe should enter the common vent or
chimney at a point ABOVE the flue pipe from the oil furnace.
UL/ULC listed doublewall type B-1 gas vents, through 24" (610
mm) diameter, can be installed in heated and unheated areas and
can pass through floors, ceilings, partitions, walls and roofs,
provided the required clearance is observed.
At the time of removal of an existing boiler, the following steps
shall be performed with each appliance remaining connected to
the common venting system. Perform these steps while the other
appliances remaining connected to the common venting system
are not in operation.
GAS CONNECTIONS
WARNING
THIS BOILER IS NOT INTENDED TO OPERA TE A T GAS SUPPL Y
PRESSURE OTHER THAN SHOWN ON THE RATING PLATE.
EXPOSURE TO HIGHER GAS SUPPL Y PRESSURE MA Y CAUSE
DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR
EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS
THROUGH IMPROPER TESTING OF GAS LINES OR
EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE
GAS VALVES MUST BE CHECKED FOR SAFE OPERATION.
MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY
REGULATORS AND THE SAFETY VENT VALVES ARE
PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF
THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT
BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW
STORMS.
WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUTOFF
VALVE OUTSIDE THE BOILER JACKET, A SUITABLE MAIN
MANUAL SHUTOFF VALVE MUST BE INSTALLED IN A
LOCATION COMPLYING WITH THOSE CODES.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE
APPROVED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS
PIPE IS CLEAN ON THE INSIDE.
— Seal any unused openings in the common venting system.
— Visually inspect the venting system for proper size and
horizontal pitch and determine there is not blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
— Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes dryers
and any appliance not connected to the common venting
system. Turn on any exhaust fans, such as range hoods and
bathroom exhaust fans, so they will operate at maximum speed.
Close fireplace dampers.
— Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so appliance will
operate continuously.
— Test for spillage at the draft hood relief opening after five
minutes of main burner operation. Use the flame of a match
or candle, or smoke from a cigarette, cigar or pipe.
— After it has been determined that each appliance remaining
connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning appliance to their
previous conditions of use.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG
OR SEDIMENT TRAP) UPSTREAM OF THE GAS CONTROLS,
MUST BE INCORPORATED IN THE PIPING. The dirt leg must be
readily accessible and not subject to freezing conditions. INST ALL
IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING
GAS SUPPLIERS. REFER TO
Z223.1 AND/OR CAN/CSA-B149.1-00.
To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve gas inlet.
Fittings and unions in the gas line must be metal to metal type.
Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compound to the first two
threads. Use compounds resistant to the action of liquefied
petroleum gases.
The boiler and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi (3.5 kPa).
The boiler must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping systems at test pressures equal to
or less than 1/2 psi (3.5 kPa).
The boiler and its gas connection must be leak tested before placing
the boiler in operation.
Provisions for vent, bleed and gas relief lines (when applicable).
NATIONAL FUEL GAS CODE, ANSI
9
PURGING
Gas line purging is required with new piping or systems in which
air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS
EXPERIENCED IN THIS TYPE OF GAS SERVICE TO A VOID RISK
OF FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT
ENTER CONFINED AREAS OR SP ACES WHERE IGNITION CAN
OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL
SOURCES OF IGNITION MUST BE INACTIVA TED OR REMOVED.
2A. SIZING GAS SUPPLY LINE (For single boiler installations
and for installations of multiples of two or three of same size
boilers).
Use table 1, which is taken from ANSI booklet Z223.1,
NATIONAL
FUEL GAS CODE, and/or CAN/CSA-B149.1-00 to size iron pipe
or equivalent gas supply line. Table 4 is based on a pressure drop
of 0.3 inches of water and a specific gravity of 0.60 which is
approximately for natural gas. (LP gas has an S.G. of about 1.53).
If the service pressure is five inches water column or less, use one
pipe size larger than specified in table 1 in order to minimize pressure
drop in the line.
BEFORE PLACING THE BOILER IN OPERATION, CHECK FOR
GAS LEAKAGE. Use soap and water solution or other material
acceptable for the purpose in locating gas leaks. DO NOT USE
MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION FOR THIS PURPOSE.
1.CORRECT GAS
Make sure the gas on which the boiler will operate is the same as
that specified on the boiler rating plate. Do not install the boiler if
equipped for a different type gas, consult your gas supplier. These
boilers are designed to operate on natural gas only.
T ABLE 4
MAXIMUM CAP ACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (BASED UPON A PRESSURE DROP OF
0.3 INCH WA TER COLUMN AND 0.6 SPECIFIC GRA VITY GAS)
Length in Feet (Meters)Nominal Iron Pipe Size, Inches (NPT)
*The heating value of natural gas is approximately 1050 Btu/ft³.
Propane (L.P .) gas has a heating value of approximately 2500 Btu/ft³.
2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers
of same size or for multiple installations of two or more mixed
sizes).
Capacities in cubic feet per hour of 0.60 specific gravity gas for
different sizes and lengths are shown in table 4. No additional
allowance is necessary for an ordinary number of fittings.
Where it is necessary to use more than the average number of
pipe fittings i.e. elbows, tees, and valves in gas supply line, use a
pipe larger than specified to compensate for increased pressure
drop.
Multipliers To Be Used W ith T able 1 When Applying The
*Use these correction factors if exact specific gravity of the gas is not known.
TABLE 5
10
Applications of the gravity factor converts the figures given in table
1 to capacities with another gas of different specific gravity. Such
application is accomplished by multiplying the capacities given in
table 1 by the multipliers shown in table 5.
To determine the size of each section of gas piping in a system
within the range of table 4 proceed as follows:
HIGH ALTITUDE INSTALLATIONS
IN CANADA
Acceptance of these models for use at altitudes above 2000 feet
(610 m) is based on field test of the individual installation by the
provincial/state authority having jurisdiction.
• Determine the gas demand of each appliance to be attached to
the piping system. When table 4 is to be used to select the
piping size, calculate the gas demand in terms of cubic feet per
hour for each piping system outlet. The gas demand for an
appliance can be found by dividing its heat input rate by the
gas’s heating value.
• Obtain or determine the length of piping from the gas meter or
service regulator to the appliance(s).
• In table 1, select the row showing the distance to the most remote
outlet or the next longer distance if the table does not give the
exact length. This is the only distance used in determining the
size of any section of gas piping. If the gravity factor is to be
applied, the values in the selected row of table 4 are multiplied
by the appropriate multiplier from table 5.
•Total the gas demands of all appliances on the piping system.
Enter table 4, on the left hand side, at the row equal to or just
exceeding the distance to the most remote outlet. Select the
pipe size in the row with a capacity equal to or just exceeding
the total gas demand. This is the required main gas supply line
size leading away from the gas meter or regulator. To determine
the pipe size required for each branch outlet leading away from
the main supply line, determine the gas demand for that outlet.
Enter table 4 on the same row, and select the branch pipe size
for a capacity equal to or just exceeding the demand at that
outlet. The main line can be resized for a lesser capacity after
each branch outlet, since the gas demand is reduced. Total the
gas demands of all remaining appliances branching off
downstream on the main gas line. Re-enter table 4 in the same
row and select the appropriate pipe size with adequate capacity.
Repeat the branch sizing and main line re-sizing for any
remaining appliances in the system.
EXAMPLE
Job Condition:
Determining the required gas pipe size for a system composed of
two A. O. Smith 720 boilers and two 960 boilers to be installed as
a multiple group, 50 lineal feet from meter. Gas to be used has a
.60 specific gravity and heating value of 1,000 Btu per cubic foot.
IN THE U.S.A.
WARNING
INSTALLATIONS ABOVE 2000 FEET REQUIRE REPLACEMENT
OF THE BURNER ORIFICES IN ACCORDANCE WITH SECTION
8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI Z223.1).
FAILURE TO REPLACE THE ORIFICES WILL RESULT IN
IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE
RESUL TING IN THE PRODUCTION OF INCREASED LEVELS OF
CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH
COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
Y ou should contact your gas supplier for any specific changes which
may be required in your area.
Ratings specified by manufacturers for most boilers apply for
elevations up to 2000 feet (610 m). For elevations above 2000 feet
(610 m) ratings must be reduced by a rate of 4% for each 1000 feet
(305 m) above sea level.
Example: A Dura-Max is rated at 720,000 Btu/hr. (211 kw) input at
sea level. To operate the boiler at 5000 feet (1524 m) it must be
derated by 20% (4% x 5) to a new rating of 576,000 Btu/hr. (169
kw) input.
The input reduction is primarily achieved by reducing the size of
the main burner orifices. T o do this, the main burner orifices require
replacement with orifices sized for the particular installation
elevation. When ordering, be sure to state the model number and
the altitude of the location where the boiler is being installed.
Upon field deration of the boiler, adjustment to the gas pressure
regulator is required. See CHECKING AND ADJUSTING THE
INPUT in this manual for inlet and manifold pressure requirements.
Also, due to the input rating reduction required at high altitudes,
the output rating of the appliance is also reduced and should be
compensated for in the sizing of the equipment for applications.
WIRING CONNECTIONS
1.CONVENTIONAL INSTALLATIONS
Solution:
Two 720 Boilers= 1,440,000 Btuh(422 kw)
Two 960 Boilers= 1,920,000 Btuh(562 kw)
Total Btuh Input= 3,360,000 Btuh= (984 kw)
Total Btuh Input= 3,360,000 Btuh = 3,360 cf/h
Btu per Cubic Foot of Gas 1,000
With a cubic foot per hour demand of 3,360 and with 50 lineal feet
of gas supply line, table 4 shows a pipe size of 3" is required.
NOTE: For other than .60 specific gravity, apply multiplier factor
as shown in table 5.
11
All electrical work must be electrically bonded to ground in
accordance with the requirements of the authority having jurisdiction
or, in the absence of such requirements, with the National Electrical
Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1,
CSA C22.1, Electrical Code.
The electrical connections must be made so that the circulator will
operate before the gas valve opens. At no time may the controlling
system allow the burner to fire when there is no water flow through
the boilers.
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK
OF ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. Make
the ground connection to the screw provided in the electrical supply
junction box on the boiler.
IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE
APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED
WITH TYPE 105°C WIRE OR ITS EQUIVALENT, EXCEPT FOR
THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250°C.
SERVICING WIRING AND/OR CONTROL
SYSTEM HEADERS
Split systems with individual supply and return lines from the boiler
room should normally have this piping connected to supply and
return manifold headers near the boiler. To achieve good water
distribution with minimum pressure drop for several circuits,
manifolds should be larger than system loops.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
Verify proper operation after servicing.
SYSTEMS EQUIPMENT
INSTALLATION
The following is a brief description of the equipment required for
installations noted in this manual. All installations must comply
with local codes.
The boilers described in this manual may be used for space heating
or for the heating of potable water. If the heater is to be used for
hydronic space heating, follow the descriptions given for equipment
required for installation on pages 12 through 31. However, if units
are to be used for heating potable water, the information describing
specific systems is found starting on page 32. Installations must
comply with all local codes.
WATER SUPPLY LINE
These boilers can be used ONLY in a forced circulation hot water
heating system. Since most forced circulation systems will be of
the closed type, install the water supply line as shown on piping
diagrams, fig’s. 10 and 14.
The circuits should be spaced on the header at a minimum of 3"
(76 mm) center to center. Install a balancing cock in each return line.
Manifold headers are recommended for split systems with or without
zone valves and also those installations with zone circulators. If
the system is to be split at remote points, good practice requires
special attention be given to main pipe sizing to allow balancing of
water flow.
COOLING PIPING
The boiler, when used in connection with a refrigeration system,
must be installed so the chilled medium is piped in parallel with the
boiler with appropriate valves to prevent the chilled medium from
entering the boiler. See figure 7.
FIGURE 7
Fast filling of large pipe, old radiator installations (where high
pressures are not available) requires bypassing of the pressure
reducing valve. Generally, pressure purging is not possible with a
well pump system. High point air venting is essential. For details,
refer to OPERATING INSTRUCTIONS section of this manual.
If the system is of the open type, a pressure reducing valve will not
be required as the water supply to the system will be controlled by
a manually operated valve. An overhead surge tank is required.
MINIMUM PRESSURE OF 15 PSI MUST BE MAINTAINED ON
THE BOILER AT ALL TIMES to ensure avoidance of potential
damage to the boiler which may not be covered by the warranty.
EXP ANSION T ANK
If the system is of the closed type, install an expansion tank as
shown in fig. 10.
system is very important and is directly related to the total water
volume of the system. Refer to ASME or other reliable specifications
for sizing.
An air separator as shown in the piping diagrams is recom- mended
especially for modern commercial hydronic systems.
The sizing of the expansion tank for a closed
VENT VALVES
It is recommended that automatic, loose key or screwdriver type
vent valves be installed at each convector or radiator.
Water temperature in the heating system must be reduced to less
than 100°F before cooling system is started, or damage to the
chiller unit may occur.
The boiler piping system of a hot water boiler connected to heating
coils located in air handling units where they may be exposed to
refrigerated air circulation must be equipped with flow control valves
or other automatic means to prevent gravity circulation of the boiler
water during the cooling cycle.
A
Primary/secondary pumping of both the chiller(s) and the boiler(s)
is an excellent winter-summer change-over method, because
cooling flow rates are much more than heating flow rates. In this
way each system (heating or cooling) is circulated independently.
SAFETY FLOW SWITCH
The safety flow switch is a safety device which must be installed at
the water outlet of the unit to prevent main burner operation in the
event of inadequate water flow through the boiler.
This switch may be mounted in a horizontal pipe line or a vertical
pipe line with upward water flow. Do not install the switch where
the water flow is downward.
For best performance mount the switch in a section of pipe where
there is a straight run of at least 5 pipe diameters on each side of
the flow switch (i.e. do not locate adjacent to valves, elbows, orifices,
etc.).
12
FIGURE 8
The flow switch shall be mounted in the top opening of the reducing
tee and provide adequate paddle length in the flow stream. For
example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For
2" or 3" pipe use the paddle segments as supplied. For other pipe
sizes (i.e. 2-1/2") trim the paddle to the proper pipe size, see fig. 8.
If a standard tee is used, install a face or hex bushing in the top
opening. The paddle must be adjusted or trimmed to the size of
the pipe in which it will be installed.
CAUTION
The paddle must not touch any part of the tee into which it is
installed. Screw the flow switch in position so the flat of the paddle
is at right angles to the flow. The arrow on the side case must
point in the direction of the flow.
To adjust the flow rate setting:
1.Remove the flow switch cover.
2.For higher flow rate—turn the range adjusting screw clockwise.
3. For lower flow rate—turn the range adjusting screw
counterclockwise.
Where units are installed in multiples, each boiler must be
individually protected by a safety flow switch.
THE CIRCULATING PUMP MUST BE PROPERLY SIZED FOR
YOUR APPLICATION.
Water hardness, system pressure drop and temperature rise across
the boiler all affect how large a circulating pump must be.
Running "hard water" too slowly through the boiler can result in
damage due to lime or scale accumulation.
Running "soft water" too quickly through the boiler can result in
damage due to velocity flow erosion.
T able 4 has been designed to assist in determining operating ranges.
Use this chart as a guide when sizing pumps.
FIGURE 9
CIRCULA TING PUMP
Dura-Max boilers are designed to operate over a wide range of
temperatures and flow rates.
13
Although each circulator that requires oil is oiled and operated by
the manufacturer, IT MUST BE OILED AGAIN BEFORE BEING
OPERATED. Oil the three oil cups (2 on the motor, 1 on the pump)
as instructed on the oil tube supplied with the unit, fig. 9.
Thereafter, during the heating season, lubricate the three oil cups
at least once every four months. Combination heating/cooling
systems or water heating (Cer-temp) systems should be lubricated
every four months year-round.
all cases, that the water temperature be set for the lowest
temperature which satisfies the user's hot water needs. This will
also provide the most energy efficient operation of the water heater
and minimize scale formation.
Use 2 or 3 teaspoonfuls in bearing oil cups, fig. 9, and 10 or 12
drops in the motor oil cups. Use No. 20 non-detergent motor oil.
Follow the same oiling procedure if a replacement circulator is
installed into the system.
LOW WATER CUTOFF
A low water cutoff is a safety device which is installed in the boiler
piping to prevent the boiler from firing in the event of inadequate
water levels in the boiler system.
Where required by local code, this optional device is to be installed
in the boiler piping at a level above that of the heat exchanger.
A float type or an electronic probe type low water cutoff may be
used. The manufacturers installation instructions must be followed.
A hot water boiler installed above radiating level or as required by
the Authority having jurisdiction, must be provided with a low water
cutoff device at the time of boiler installation.
T ANK TEMPERATURE CONTROL
The water temperature in the storage tank is controlled by the Tank
Temperature Control. The sensing element is mounted inside the
hot water storage tank, see fig. 24.
SETTING THE WATER TEMPERATURE AT 120°F (49°C) WILL
REDUCE THE RISK OF SCALDS. Some states require settings at
specific lower temperatures. T able 6 below shows the approximate
time-to-burn relationship for normal adult skin.
TemperatureTime to Produce 2nd & 3rd
SettingDegree Burns on Adult Skin
Over 170°F (77°C)Nearly instantaneous
160°F (71°C)About 1/2 second
150°F (65°C)About 1-1/2 seconds
140°F (60°C)Less than 5 seconds
130°F (55°C)About 30 seconds
120°F or less (49°C)More than 5 minutes
TABLE 6
USE ANTI-SCALD V ALVE(S) in the hot water system to reduce the
risks of scalds at points of use such as lavatories, sinks and bathing
facilities.
A change in water temperature in the storage tank lower than the
Tank Temperature Control setting will cause the sensor to close its
contacts and consequently, energize the boiler.
If the Tank Temperature Control is out of calibration, replace it with
a new one; do not attempt to repair this control.
DANGER
HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC
DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD
BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR
DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS
VARIES WITH THE PERSON'S AGE AND TIME OF EXPOSURE.
THE SLOWER RESPONSE TIME OF CHILDREN, AGED, OR
DISABLED PERSONS INCREASES THE HAZARDS TO THEM.
NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER T AP
OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A
CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB
OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HA VE ACCESS TO
SET TEMPERATURES.
The tank temperature control is adjustable from 100°F to 220°F
(38°C to 104°C). It is recommended that lower water temperatures
be used to avoid the risk of scalding. It is further recommended, in
SYSTEM INSTALLATION
GENERAL
If the system is to be filled with water for testing or other purposes
during cold weather and before actual operation, care must be taken
to prevent a downdraft entering the boiler or freezing air from
contacting the system. Failure to do so may cause the water in the
system to freeze with resulting damage to the system. Damage
due to freezing is not covered by the warranty.
Good practice requires that all piping, etc., be properly supported.
CONVENTIONAL SP ACE HEA TING INST ALLA TION
Modern fin type boilers are exceptionally fast heating units. The
low water volumes in relation to firing rates require special attention
to water flow rates for smooth, efficient operation. These
considerations for the A. O. Smith copper heat exchanger boilers
are covered below.
Refer to page 5 for tables on these units showing “flow rate vs.
pressure drop and temperature rise”.
Figure 10 shows a typical installation of the boiler.
A system with several flow controlled zones, or with a 3-way mixing
valve system which could present a flow rate to the boiler of less
than that required for a maximum of 50°F (10°C) temperature rise
at the minimum firing rate, should be designed with compensating
bypasses at the boiler.
14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.