•Flexible, Modular Design Fits Every Application
•User-Configurable I/O Selection to Meet Specific Control Needs
•DIN Rail Mounting Provides Easy Installation and System Expansion
•NEMA 1-Style Enclosure Available
•Three-Position Front Cover for HandsFree Access
•Built-in Quick-Release Fasteners—No Tools Required!
•Removable Input/Output Connectors for Easy Installation
•Slide-Together Power/ Communications Connections
•Optional Remote Mounting
•Push-Button Network Commissioning
×NTINUUMª
I/O Modules
The Continuum Ethernet-based intelligent building system allows you to mix and match various combinations of DIN rail-mounted modules—flexible I/O, CPU and power supply, and your choice of several user interface modules—in a single controller location to meet your building’s control and monitoring needs. With the Continuum system, as your network grows, simply add or replace I/O modules as needed.
The Continuum I/O modules feature a sleek, lightweight casing designed for natural convection cooling, and a 3-position front cover for easy, hands-free access. Built-in quickrelease fasteners at the back of each I/O module are provided for DIN rail mounting—no tools required. These fasteners also snap into a locked position for panel mounting. Input and output connectors are located at the bottom of each I/O module and are removable for easy field access and maintenance. All Continuum modules are designed for mounting in an optional NEMA 1-style Continuum enclosure.
The Continuum I/O modules communicate with the Continuum NetController CPU module using Andover LON communications. Like all Continuum modules, the I/O modules slide together via built-in connectors on either side so network expansion is quick and easy. Both power transmission and communication signals feed through these connectors. For added convenience in certain applications, such as door control or lighting control,
a single module or groups of I/O modules can be remotely located and connected using approved cable, and powered from a local 24 VDC power supply. Each I/O module features its own push-button for quick and easy network commissioning.
Downloaded from - http://www1 .guardianalarms.net
All Continuum I/O modules share the following specifications:
MECHANICAL |
|
|
Operating Environment: |
32 to 120°F, (0 to 49°C), 10 to 95%RH (non-condensing) |
|
|
|
|
Size: |
3.8”W x 6.7”H x 2.5”D (96.5 x 157.5 x 63.5mm) |
|
|
|
|
Weight: |
.75 lbs (0.34kg) |
|
|
|
|
Mounting: |
Mount on DIN rail or wall-mount using attached clips. |
|
|
Continuum NEMA 1-style enclosure available. |
|
|
|
|
B ATTERY |
|
|
Battery Backup: |
Through Continuum UPS power supply |
|
|
|
|
COMMUNICATIONS |
|
|
Communications Interface: |
LON communications with Continuum CPU module. |
|
|
Choice of bus media, RS-485 or FTT-10 for remote I/O mounting |
|
|
|
|
Comm. Error Checking: |
International Standard CRC 16 |
|
|
|
|
RS-485: |
CommunicationsSpeed: |
39k baud |
|
Bus Length: |
2,000 ft. (610m). Repeater required for longer distance or after |
|
|
every 32 nodes. |
|
Bus Media: |
Shielded, twisted pair cable. 120Ω termination required at |
|
|
both ends of the LON network (when modules are mounted |
|
|
remotely). |
|
|
|
FTT-10: |
CommunicationsSpeed: |
78k baud |
|
Bus Length: |
Up to 8858 ft. (2700m) – bus topology |
|
|
Up to 1640 ft (500m) – free topology |
|
|
Repeater required for longer distances. |
|
Bus Media: |
Refer to LON free topology documentation |
|
|
|
Power/Communications Connections:
5-position plug-in connectors on left and right sides allow Continuum modules to be directly connected to each other or remotely connected via approved cable.
CPU
3120E2 MCU with internal ROM, EEPROM, and SRAM
AGENCY LISTINGS
UL/CUL 916, FCC, CE
2
UI-8-10
I/O MODULE
The UI-8-10, Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing separate indication of alarm and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, statuspoints, and similar inputs in a control system, with a 0-5 volt input range and 10 bit A/D conversion.
A UI-8-10-10V model is also available for 0-10 volt applications. It provides the identical point type selection, but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0-10 volt range.
S P E C I F I C A T I O N S
|
|
ELECTRICAL |
|
|
|
|
|
|
|
Power Consumption: |
0.7 watts at 24VDC max.; when provided by Continuum power supply module. |
||
|
|
|
|
|
||
|
|
|
Overload Protection: |
0.5A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. |
||
|
|
|
|
|
|
|
|
|
INPUTS |
|
|
|
|
|
|
|
Number of Inputs: |
8 Universal inputs; 10 bit resolution |
|
|
|
|
|
|
|
||
|
|
|
Input Types: |
Voltage, Thermistor, Digital, Counter, and Supervised |
||
|
|
|
|
|
||
|
|
|
Input Protection: |
24V AC/DC allowed to any single input (40V TVS on each input – UI-8-10-10V model only) |
||
|
|
|
|
|
|
|
|
|
|
Input Impedance |
UI-8-10 (0-5V): |
5 MΩ w/pullup disabled; 10 KΩ w/pullup enabled |
|
|
|
|
|
UI-8-10-10V (0-10V): |
4.4 KΩ |
|
|
|
|
|
|
|
|
|
|
|
Input Connections: |
Two-piece, 13-position removable terminal block |
|
|
|
|
|
|
|
|
|
|
|
|
Voltage: |
|
UI-8-10 (0-5V) |
UI-8-10-10V (0-10V) |
|
|
|
|
Range: |
0-5 volts |
0-10 volts |
|
|
|
|
Resolution: |
5 mV |
10 mV |
|
|
|
|
Accuracy: |
±15 mV (±0.3% FSR) |
±40 mV (±0.4% FSR) |
|
|
|
|
|
|
|
|
|
|
Thermistor: |
Type: |
10 KΩ, Type III Thermistor |
|
|
|
|
|
Range: |
-30 to 230°F (-34 to 110°C) |
|
|
|
|
|
Resolution: |
40 to 100°F range |
0.20°F typical |
|
|
|
|
|
(4 to 38°C) |
(0.11°C typical) |
|
|
|
|
Accuracy: |
40 to 100°F range |
± 1.0°F |
|
|
|
|
|
(4 to 38°C) |
(±0.55°C) |
|
|
|
|
|
|
|
|
|
|
Digital & Counter: |
Input Type: |
Contact Closure |
|
|
|
|
|
Frequency: |
4 Hz max. |
|
|
|
|
|
Pulse Width: |
125 mS min. |
|
|
|
|
|
|
|
|
|
|
|
Supervised: |
Input Type: |
Single or Double Resistor Supervision, Parallel or Series Circuit |
|
|
|
|
|
|
|
|
|
|
USER LEDS/SWITCHES |
|
|
|
|
|
|
|
Status Indicator LEDS |
|
|
|
|
|
|
|
Power |
Power Indicator |
|
|
|
|
|
Comm |
TD Indicator |
|
|
|
|
|
Status |
Service/Wink Indicator |
|
|
|
|
|
|
|
|
|
|
|
Push-Button Switches |
|
|
|
|
|
|
|
Commission |
|
|
|
|
|
|
Reset |
|
|
|
M O D E L S |
|
|
|
|
|
|
|
|
UI-8-10 |
8 Universal inputs; 0-5 Volt input range |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
UI-8-10-10V |
8 Universal inputs; 0-10 Volt input range |
|
|
|
|
|
|
|
|
|
3
DI-8
I/O MODULE
The DI-8, Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs—each can be software configured to accept a digital (contact closure or 0-5 volt input) or counter signal. Counter frequency is 10Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications.
40V bipolar transorbs on all eight inputs protect against high voltage short duration transient events. The DI-8 is designed to
accept dry contact inputs or 0-5 volts, but can withstand up to 24 VAC/DC continuous voltage on four channels.
S P E C I F I C A T I O N S
ELECTRICAL |
|
|
|
Power Consumption: |
0.8 watts at 24VDC max; when provided byContinuum power supply module. |
||
|
|
||
Overload Protection: |
0.5A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection |
||
|
|
|
|
INPUTS |
|
|
|
Number of Inputs: |
8 Digital inputs |
|
|
|
|
|
|
Input Types: |
Digital or Counter, software selectable |
|
|
|
|
||
Input Protection: |
24V AC/DC applied to 4 channels max. (40V TVS on each input) |
||
|
|
|
|
Input Impedance: |
10KΩ pull-up resistor referenced to +5 volts |
|
|
|
|
|
|
Inputs Connections: |
Two-piece, 13-position removable terminal block |
|
|
|
|
|
|
Digital: |
Input Type: |
Contact closure or 0-5V input |
|
|
Pulse Width: |
50mS min |
|
|
Current: |
0.5mA |
|
|
|
|
|
Counter: |
Input Type: |
Contact closure or 0-5V input |
|
|
Channels 1 and 2 in HI-speed mode (selectable via dip switch): |
||
|
|
Frequency: |
10KHz max. |
|
|
Pulse Width: |
50 µS min. |
|
|
Current: |
0.5mA |
|
Channels 3 through 8; and Channel 1 and 2 in LO-speed mode: |
||
|
|
Frequency: |
10Hz max. |
|
|
Pulse Width: |
50mS min. |
|
|
Currrent: |
0.5mA |
|
|
|
|
USER LEDS/SWITCHES |
|
|
|
Status Indicator LEDS |
|
|
|
|
Power |
Power Indicator |
|
|
Comm |
TD Indicator |
|
|
Status |
Service/Wink Indicator |
|
|
Input Status 1-8 |
Input Status Indicator (Closed circuit=ON) |
|
|
|
|
|
Push-Button Switches |
Commission |
|
|
|
Reset |
|
|
|
|
|
|
4
DI-6-AC
I/O MODULE
The DI-6-AC, Continuum’s digital AC input module, has six digital (“wet”) AC inputs for cost-effective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6-AC monitors the absence or presence of AC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 24-120V (above 20 volts = ON; below 12 volts = OFF).
A DI-6-AC-HV model is also available for sensing higher voltages—120-240V. Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.
S P E C I F I C A T I O N S
|
|
ELECTRICAL |
|
|
|
|
|
|
|
Power Consumption: |
0.7 watts at 24VDC max.; when provided by Continuum power supply module. |
||
|
|
|
|
|
||
|
|
|
Overload Protection: |
0.5A rese-ttable fuse with transient voltage suppressor (TVS) and reverse polarity protection |
||
|
|
|
|
|
|
|
|
|
INPUTS |
|
|
|
|
|
|
|
Number of Inputs: |
6 Digital AC voltage inputs |
|
|
|
|
|
|
|
||
|
|
|
Input Protection: |
2500V isolation on each input. Each input has a 270V MOV. |
||
|
|
|
|
|
|
|
|
|
|
Input Connections: |
Two-piece, 13-position removable terminal block |
|
|
|
|
|
|
|
|
|
|
|
|
AC Inputs |
|
DI-6-AC |
DI-6-AC-HV |
|
|
|
|
AC Input Range: |
20-132 Vrms |
90-250 Vrms |
|
|
|
|
AC Input Current: |
5 mA max. |
2 mA max. |
|
|
|
|
|
|
|
|
|
|
AC Voltage “ON” Threshold: |
|
16 Vrms |
75 Vrms |
|
|
|
|
|
(Above this voltage is considered “ON”) |
|
|
|
|
|
|
|
|
|
|
|
AC Voltage “OFF” Threshold: |
|
8 Vrms |
30 Vrms |
|
|
|
|
|
(Below this voltage is considered “OFF”) |
|
|
|
|
|
|
|
|
|
|
|
Input Resistance (±5%): |
|
30KΩ |
200KΩ |
|
|
|
|
|
|
|
|
|
|
Maximum Turn ON Time: |
|
20 mS |
20 mS |
|
|
|
|
|
|
|
|
|
|
Maximum Turn OFF Time: |
|
60 mS |
60 mS |
|
|
|
|
|
|
|
|
|
|
DC Input Voltage Range: |
|
20-132V |
90-250V |
|
|
|
|
|
|
|
|
|
|
DC Input Current: |
|
5mA max. |
2mA max. |
|
|
|
|
|
|
|
|
|
|
DC Voltage “ON” Threshold: |
|
20V |
90V |
|
|
|
|
|
(Above this voltage is considered “ON”) |
|
|
|
|
|
|
|
|
|
|
|
DC Voltage “OFF” Threshold: |
|
12V |
45V |
|
|
|
|
|
(Below this voltage is considered “OFF”) |
|
|
|
|
|
|
|
|
|
|
USER LEDS/SWITCHES |
|
|
|
|
|
|
|
Status Indicator LEDS |
|
|
|
|
|
|
|
Power |
Power Indicator |
|
|
|
|
|
Comm |
TD Indicator |
|
|
|
|
|
Status |
Service/Wink Indicator |
|
|
|
|
|
Input Status 1-6 |
Input Status Indicator (Above voltage threshold = ON) |
|
|
|
|
|
|
|
|
|
|
|
Push-Button Switches |
|
|
|
|
|
|
|
Commission |
|
|
|
|
|
|
Reset |
|
|
|
M O D E L S |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
DI-6-AC |
|
6 Digital AC Inputs, 24/120V input signal |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
DI-6-AC-HV |
|
6 Digital AC Inputs, 120/240V input signal |
|
|
|
|
|
|
|
|
5