Block diagram: Control data input from fieldbus when a type Rxxx fieldbus adapter is used . 202
Block diagram: Actual value selection for fieldbus when a type Rxxx fieldbus adapter is used 203
Block diagram: Control data input from fieldbus when a type Nxxx fieldbus adapter is used . 204
Block Diagram: Actual value selection for fieldbus when a type Nxxx fieldbus adapter is used 205
The chapter includes a description of the contents of the manual. In addition it
contains information about the compatibility, safety and intended audience.
Compatibility
The manual is compatible with Standard Control Program version ASXR7360. See
parameter 33.01 SOFTWARE VERSION.
Safety instructions
Follow all safety instructions delivered with the drive.
•Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given at the beginning of the
Hardware Manual.
13
Reader
Contents
•Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in this manual in the section describing the related user-adjustable
parameters.
The reader of the manual is expected to know the standard electrical wiring
practices, electronic components, and electrical schematic symbols.
The manual consists of the following chapters:
•Start-up and control through the I/O instructs in setting up the application
program, and how to start, stop and regulate the speed of the drive.
•Control panel gives instructions for using the panel.
•Program features contains the feature descriptions and the reference lists of the
user settings and diagnostic signals.
•Application macros contains a short description of each macro together with a
connection diagram.
•Actual signals and parameters describes the actual signals and parameters of the
drive.
•Fieldbus control describes the communication through the serial communication
links.
Introduction to the manual
14
•Fault tracing lists the warning and fault messages with the possible causes and
remedies.
•Analogue Extension Module, describes the communication between the drive and
the analogue I/O extension (optional).
•Additional data: actual signals and parameters contains more information on the
actual signals and parameters.
•Control block diagrams contains block diagrams concerning reference control
chains and handling of Start, Stop, Run Enable and Start Interlock.
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting
the type code and serial number of the unit in question. A listing of ABB sales,
support and service contacts can be found by navigating to www.abb.com/drives
selecting Sales, Support and Service network.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select Training courses.
and
Providing feedback on ABB Drives manuals
Your comments on our manuals are welcome. Go to www.abb.com/drives and select
Document Library – Manuals feedback form (LV AC drives).
Introduction to the manual
Start-up and control through the I/O
Chapter overview
The chapter instructs how to:
•do the start-up
•start, stop, change the direction of rotation, and adjust the speed of the motor
through the I/O interface
•perform an Identification Run for the drive.
How to start-up the drive
There are two start-up methods between which the user can select: Run the Start-up
Assistant, or perform a limited start-up. The Assistant guides the user through all
essential settings to be done. In the limited start-up, the drive gives no guidance:
The user goes through the very basic settings by following the instructions given in
the manual.
15
•If you want to run the Assistant, follow the instructions given in section How to
perform the guided start-up (covers all essential settings) on page 15.
•If you want to perform the limited start-up, follow the instructions given in
section How to perform the limited start-up (covers only the basic settings) on
page 17.
How to perform the guided start-up (covers all essential settings)
Before you start, ensure you have the motor nameplate data on hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential only
in applications which require the ultimate in motor control accuracy.)
Start-up and control through the I/O
16
POWER-UP
Apply the main power. The control panel first shows the panel
identification data …
… then the Identification Display of the drive …
… then the Actual Signal Display …
…after which the display suggests starting the Language Selection.
(If no key is pressed for a few seconds, the display starts to alternate between the
Actual Signal Display and the suggestion on selecting the language.)
The drive is now ready for the start-up.
SELECTING THE LANGUAGE
Press the FUNC key.
Scroll to the desired language by the arrow keys ( or ) and
press ENTER to accept.
(The drive loads the selected language into use, shifts back to the Actual Signal
Display and starts to alternate between the Actual Signal Display and the
suggestion on starting the guided motor set-up.)
CDP312 PANEL Vx.xx
.......
ACS800
ID NUMBER 1
1 -> 0.0 rpm O
FREQ 0.00 Hz
CURRENT 0.00 A
POWER 0.00 %
1 -> 0.0 rpm O
*** INFORMATION ***
Press FUNC to start
Language Selection
Language Selection 1/1
LANGUAGE ?
[ENGLISH]
ENTER:OK ACT:EXIT
1 -> 0.0 rpm O
*** INFORMATION ***
Press FUNC to start
guided Motor Setup
STARTING THE GUIDED MOTOR SET-UP
Press FUNC to start the guided motor set-up.
(The display shows which general command keys to use when stepping through
the assistant.)
Press ENTER to step forward.
Follow the instructions given on the display.
Motor Setup 1/10
ENTER: Ok/Continue
ACT: Exit
FUNC: More Info
Motor Setup 2/10
MOTOR NAMEPLATE DATA
AVAILABLE?
ENTER:Yes FUNC:Info
Start-up and control through the I/O
How to perform the limited start-up (covers only the basic settings)
Before you start, ensure you have the motor nameplate data at your hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential
only in applications which require the ultimate in motor control accuracy.)
POWER-UP
17
Apply the main power. The control panel first shows the panel
identification data …
… then the Identification Display of the drive …
… then the Actual Signal Display …
…after which the display suggests starting the Language Selection.
(If no key is pressed for a few seconds, the display starts to alternate between the
Actual Signal Display and the suggestion on starting the Language Selection.)
Press ACT to remove the suggestion on starting the language
selection.
The drive is now ready for the limited start-up.
MANUAL START-UP DATA ENTERING (parameter group 99)
Select the language. The general parameter setting procedure is
described below.
The general parameter setting procedure:
- Press PAR to select the Parameter Mode of the panel.
- Press the double-arrow keys ( or ) to scroll the parameter groups.
- Press the arrow keys ( or ) to scroll parameters within a group.
- Activate the setting of a new value by ENTER.
- Change the value by the arrow keys ( or ), fast change by the doublearrow keys ( or ).
- Press ENTER to accept the new value (brackets disappear).
CDP312 PANEL Vx.xx
.......
ACS800
ID NUMBER 1
1 -> 0.0 rpm O
REQ 0.00 Hz
F
CURRENT 0.00 A
POWER 0.00 %
1 -> 0.0 rpm O
*** INFORMATION ***
Press FUNC to start
Language Selection
1 -> 0.0 rpm O
FREQ 0.00 Hz
CURRENT 0.00 A
POWER 0.00 %
1 -> 0.0 rpm O
99 START-UP DATA
01 LANGUAGE
ENGLISH
1 -> 0.0 rpm O
99 START-UP DATA
01 LANGUAGE
[ENGLISH]
Start-up and control through the I/O
18
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
HzkW
r/minA
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
input
voltage
Select the Application Macro. The general parameter setting
procedure is given above.
The default value FACTORY is suitable in most cases.
Select the motor control mode. The general parameter setting
procedure is given above.
DTC is suitable in most cases. The SCALAR control mode is recommended
- for multimotor drives when the number of the motors connected to the drive is
variable
- when the nominal current of the motor is less than 1/6 of the nominal current of
the inverter
- when the inverter is used for test purposes with no motor connected.
Enter the motor data from the motor nameplate:
1 -> 0.0 rpm O
99 START-UP DATA
02 APPLICATION MACRO
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
04 MOTOR CTRL MODE
[DTC]
Note: Set the motor data to
exactly the same value as
on the motor nameplate.
For example, if the motor
nominal speed is 1440 rpm
on the nameplate, setting
the value of parameter
99.08 MOTOR NOM
SPEED to 1500 rpm
results in the wrong
operation of the drive.
- motor nominal voltage
Allowed range: 1/2 · U
each of the nominal voltage ranges: 415 VAC for 400 VAC units, 500 VAC for 500
VAC units and 690 VAC for 600 VAC units.)
- motor nominal current
Allowed range: approx. 1/6 · I
99.04 = SCALAR))
- motor nominal frequency
Range: 8 … 300 Hz
- motor nominal speed
Range: 1 …18000 rpm
-motor nominal power
Range: 0 …9000 kW
Start-up and control through the I/O
N
… 2 · U
2hd
of ACS800. (UN refers to the highest voltage in
N
… 2 · I
of ACS800 (0 … 2 · I
2hd
if parameter
2hd
1 -> 0.0 rpm O
99 START-UP DATA
05 MOTOR NOM VOLTAGE
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
06 MOTOR NOM CURRENT
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
07 MOTOR NOM FREQ
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
08 MOTOR NOM SPEED
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
09 MOTOR NOM POWER
[ ]
19
When the motor data has been entered, two displays (warning and
information) start to alternate. Move to next step without pressing
any key.
1 -> 0.0 rpm O
ACS800
** WARNING **
ID MAGN REQ
Note: If you select STANDARD ID Run, the brake is opened when
the Start command is given from the control panel and the brake
remains open until the STANDARD ID Run is completed. If you
select ID MAGN, the brake is kept closed during the ID Run
sequence.
1 -> 0.0 rpm I
*** Information ***
Press green button
to start ID MAGN
Select the motor identification method.
The default value ID MAGN (ID Magnetisation) is suitable for most applications. It is applied
in this basic start-up procedure. If your selection is ID Magnetisation, move to next step
without pressing any key.
The ID Run (STANDARD or REDUCED) should be selected if:
- The operation point is near zero speed constantly, and/or
- Operation at torque range above the motor nominal torque within a wide speed range and
without any measured speed feedback is required.
If your selection is ID Run, continue by following the separate instructions given a few pages
ahead in section How to perform the ID Run on page 22.
IDENTIFICATION MAGNETISATION (with Motor ID Run selection ID MAGN)
Press the LOC/REM key to change to local control (L shown on the
first row).
Press to start the Identification Magnetisation. The motor is
magnetised at zero speed for 20 to 60 s. Three warnings are
displayed:
The first warning is displayed when the magnetisation starts.
The second warning is displayed while the magnetisation is on.
The third warning is displayed after the magnetisation is completed.
1 L -> 1242.0 rpm I
** WARNING **
MOTOR STARTS
1 L-> 0.0 rpm I
** WARNING **
ID MAGN
1 L-> 0.0 rpm O
** WARNING **
ID DONE
Start-up and control through the I/O
20
forward
direction
reverse
direction
DIRECTION OF ROTATION OF THE MOTOR
Check the direction of rotation of the motor.
- Press ACT to get the status row visible.
- Increase the speed reference from zero to a small value by
pressing REF and then the arrow keys (, , or ).
- Press to start the motor.
- Check that the motor is running in the desired direction.
- Stop the motor by pressing .
To change the direction of rotation of the motor:
- Disconnect the main power from the drive, and wait 5 minutes for
the intermediate circuit capacitors to discharge. Measure the
voltage between each input terminal (U1, V1 and W1) and earth
with a multimeter to ensure that the frequency converter is
discharged.
- Exchange the position of two motor cable phase conductors at the
motor terminals or at the motor connection box.
- Verify your work by applying the main power and repeating the
check as described above.
SPEED LIMITS AND ACCELERATION/DECELERATION TIMES
Set the minimum speed.
1 L->[xxx] rpm I
FREQ xxx Hz
CURRENT xx A
POWER xx %
1 L-> 0.0 rpm O
20 LIMITS
01 MINIMUM SPEED
[ ]
Set the maximum speed.
Set the acceleration time 1.
Note: Check also acceleration time 2, if two acceleration times will
be used in the application.
Set the deceleration time 1.
Note: Set also deceleration time 2, if two deceleration times will be
used in the application.
The drive is now ready for use.
1 L-> 0.0 rpm O
20 LIMITS
02 MAXIMUM SPEED
[ ]
1 L-> 0.0 rpm O
22 ACCEL/DECEL
02 ACCELER TIME 1
[ ]
1 L-> 0.0 rpm O
22 ACCEL/DECEL
03 DECELER TIME 1
[ ]
Start-up and control through the I/O
How to control the drive through the I/O interface
The table below instructs how to operate the drive through the digital and analogue
inputs, when:
•the motor start-up is performed, and
•the default (factory) parameter settings are valid.
PRELIMINARY SETTINGS
21
Ensure the Factory macro is active.
If you need to change the direction of rotation, change the setting of
parameter 10.03 to REQUEST.
Ensure the control connections are wired according to the connection
diagram given for the Factory macro.
Ensure the drive is in external control mode. Press the LOC/REM key to
change between external and local control.
STARTING AND CONTROLLING THE SPEED OF THE MOTOR
Start by switching digital input DI1 on.
Regulate the speed by adjusting the voltage of analogue input AI1.
CHANGING THE DIRECTION OF ROTATION OF THE MOTOR
Forward direction: Switch digital input DI2 off.
See parameter 99.02.
See chapter Application
macros.
In External control, there is
no L visible on the first row
of the panel display.
1 -> 0.0 rpm I
REQ 0.00 Hz
F
CURRENT 0.00 A
POWER 0.00 %
1 -> 500.0 rpm I
FREQ 16.66 Hz
CURRENT 12.66 A
POWER 8.33 %
1 -> 500.0 rpm I
FREQ 16.66 Hz
CURRENT 12.66 A
POWER 8.33 %
Reverse direction: Switch digital input DI2 on.
STOPPING THE MOTOR
Switch off digital input DI1.
1 <- 500.0 rpm I
REQ 16.66 Hz
F
CURRENT 12.66 A
POWER 8.33 %
1 -> 500.0 rpm O
REQ 0.00 Hz
F
CURRENT 0.00 A
POWER 0.00 %
Start-up and control through the I/O
22
99 START-UP DATA
10 MOTOR ID RUN
[STANDARD]
1 L ->1242.0 rpm O
1 L ->1242.0 rpm O
ACS800
**WARNING**
ID RUN SEL
How to perform the ID Run
The drive performs the ID Magnetisation automatically at the first start. In most
applications there is no need to perform a separate ID Run. The ID Run (Standard or
Reduced) should be selected if:
•The operation point is near zero speed, and/or
•Operation at torque range above the motor nominal torque within a wide speed
range and without any measured speed feedback is required.
The Reduced ID Run is to be performed instead of the Standard if it is not possible to
disengage the driven machine from the motor.
Note: If you select STANDARD ID Run, the brake is opened when the Start
command is given from the control panel and the brake remains open until the
STANDARD ID Run is completed. If you select ID MAGN, the brake is kept closed
during the ID Run sequence.
ID Run Procedure
Note: If parameter values (Group 10 to 98) are changed before the ID Run, check
that the new settings meet the following conditions:
•20.01 MINIMUM SPEED <
0 rpm
•20.02 MAXIMUM SPEED > 80% of motor rated speed
•20.03 MAXIMUM CURRENT >
100% · I
hd
•20.04 MAXIMUM TORQUE > 50%
•Ensure that the panel is in the local control mode (L displayed on the status row).
Press the LOC/REM key to switch between modes.
•Change the ID Run selection to STANDARD or REDUCED.
•Press ENTER to verify selection. The following message will be displayed:
Start-up and control through the I/O
23
•To start the ID Run, press the key. The Start Interlock (digital input DI_IL) and
Run Enable signals (parameter 16.01 RUN ENABLE) must be active.
Warning when the ID Run is
started
1 L -> 1242.0 rpm I
ACS800
**WARNING**
MOTOR STARTS
In general it is recommended not to press any control panel keys during the ID run.
However:
•The Motor ID Run can be stopped at any time by pressing the control panel stop
key ().
•After the ID Run is started with the start key (), it is possible to monitor the
actual values by first pressing the ACT key and then a double-arrow key ().
Warning during the ID RunWarning after a successfully
completed ID Run
1 L -> 1242.0 rpm I
ACS800
**WARNING**
ID RUN
1 L -> 1242.0 rpm I
ACS800
**WARNING**
ID DONE
Start-up and control through the I/O
24
Start-up and control through the I/O
Control panel
1 L -> 1242.0 rpm I
F
REQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
ACTPA RFU NCDR IV E
ENTER
LOCRESETREF
REM
I0
1367
524
The LCD type display has 4 lines of 20 characters.
The language is selected at start-up (parameter 99.01).
The control panel has four operation modes:
- Actual Signal Display Mode (ACT key)
- Parameter Mode (PAR key)
- Function Mode (FUNC key)
- Drive Selection Mode (DRIVE key)
The use of single arrow keys, double arrow keys and
ENTER depend on the operation mode of the panel.
The drive control keys are:
No.Use
1Start
2Stop
3Activate reference setting
4Forward direction of rotation
5Reverse direction of rotation
6Fault reset
7Change between Local / Remote (external)
control
Chapter overview
The chapter describes how to use the control panel CDP 312R.
The same control panel is used with all ACS800 series drives, so the instructions
given apply to all ACS800 types. The display examples shown are based on the
Standard Control Program; displays produced by other application programs may
differ slightly.
Overview of the panel
25
Control panel
26
Parameter Mode
Function Mode
Drive Selection Mode
Act. signal / Fault history
Enter selection mode
Accept new signal
Group selection
Parameter selection
Enter change mode
Accept new value
Fast value change
Slow value change
Function start
Drive selection
Enter change mode
Accept new value
Actual Signal Display Mode
ENTER
ENTER
ENTER
ENTER
selection
ID number change
Status row
Status row
ACT
PAR
FUNC
DRIVE
1 L -> 1242.0 rpm O
F
REQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
1 L -> 1242.0 rpm O
10 START/STOP/DIR
01 EXT1 STRT/STP/DIR
DI1,2
1 L -> 1242.0 rpm O
Motor Setup
Application Macro
Speed Control EXT1
ACS800
ASXR7260 xxxxxx
ID NUMBER 1
Act. signal / Fault message
scrolling
Actual signal names
and values
Parameter group
Parameter
Parameter value
Status row
List of functions
Device type
SW loading package
name and ID number
Row selection
Page selection
Drive ID number
Drive control status
L = Local control
R = Remote control
“ “ = External control
Drive status
I = Running
O = Stopped
“ “ = Run disabled
1 L -> 1242.0 rpm I
Direction of rotation
-> = Forward
<- = Reverse
Drive reference
Panel operation mode keys and displays
The figure below shows the mode selection keys of the panel, and the basic
operations and displays in each mode.
Status row
The figure below describes the status row digits.
Control panel
Drive control with the panel
ACTPA R
FUNC
LOC
REM
0
I
The user can control the drive with the panel as follows:
•start, stop, and change direction of the motor
•give the motor speed reference or torque reference
•give a process reference (when the process PID control is active)
•reset the fault and warning messages
•change between local and external drive control.
The panel can be used for control of the drive control always when the drive is under
local control and the status row is visible on the display.
How to start, stop and change direction
Step ActionPress KeyDisplay
1.To show the status row.1 ->1242.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
27
2.To switch to local control.
(only if the drive is not under local control, i.e. there is no L
on the first row of the display.)
3.To stop1 L ->1242.0 rpm O
4.To start1 L ->1242.0 rpm I
5.To change the direction to reverse.1 L <-1242.0 rpm I
6.To change the direction to forward.1 L ->1242.0 rpm I
1 L ->1242.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
FREQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
FREQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
Control panel
28
ACTPAR
FUNC
LOC
REM
REF
ENTER
How to set speed reference
Step ActionPress KeyDisplay
1.To show the status row.1 ->1242.0 rpm I
F
REQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
2.To switch to local control.
(Only if the drive is not under local control, i.e. there is no L
on the first row of the display.)
1 L ->1242.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
3.To enter the Reference Setting function.1 L ->[1242.0 rpm]I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
4.To change the reference.
(slow change)
1 L ->[1325.0 rpm]I
F
REQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
(fast change)
5.To save the reference.
(The value is stored in the permanent memory; it is
restored automatically after power switch-off.)
1 L -> 1325.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
Control panel
Actual signal display mode
ACT
ENTER
ENTER
ACT
FUNCDRIVE
PAR
In the Actual Signal Display Mode, the user can:
•show three actual signals on the display at a time
•select the actual signals to display
•view the fault history
•reset the fault history.
The panel enters the Actual Signal Display Mode when the user presses the ACT
key, or if he does not press any key within one minute.
How to select actual signals to the display
Step ActionPress keyDisplay
1.To enter the Actual Signal Display Mode. 1 L -> 1242.0 rpm I
F
REQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
29
2.To select a row (a blinking cursor indicates the selected
row).
3.To enter the actual signal selection function. 1 L -> 1242.0 rpm I
4.To select an actual signal.
To change the actual signal group.
5.aTo accept the selection and to return to the Actual Signal
Display Mode.
5.bTo cancel the selection and keep the original selection.
The selected keypad mode is entered.
1 L -> 1242.0 rpm I
FREQ 45.00 Hz
URRENT 80.00 A
C
POWER 75.00 %
1 ACTUAL SIGNALS
04 CURRENT
80.00 A
1 L -> 1242.0 rpm I
1 ACTUAL SIGNALS
05 TORQUE 70.00 %
1 L -> 1242.0 rpm I
FREQ 45.00 Hz
ORQUE 70.00 %
T
POWER 75.00 %
1 L -> 1242.0 rpm I
FREQ 45.00 Hz
C
URRENT 80.00 A
POWER 75.00 %
Control panel
30
ACT
ACT
ACT
RESET
How to display the full name of the actual signals
Step ActionPress keyDisplay
1.To display the full name of the three actual signals.Hold 1 L -> 1242.0 rpm I
F
REQUENCY
CURRENT
POWER
2.To return to the Actual Signal Display Mode.Release 1 L -> 1242.0 rpm I
FREQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
How to view and reset the fault history
Note: The fault history cannot be reset if there are active faults or warnings.
Step ActionPress keyDisplay
1.To enter the Actual Signal Display Mode. 1 L -> 1242.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
2.To enter the Fault History Display. 1 L -> 1242.0 rpm I
1 LAST FAULT
+OVERCURRENT
6451 H 21 MIN 23 S
3.To select the previous (UP) or the next fault/warning
(DOWN).
1 L -> 1242.0 rpm I
2 LAST FAULT
+OVERVOLTAGE
1121 H 1 MIN 23 S
To clear the Fault History.1 L -> 1242.0 rpm I
2 LAST FAULT
H MIN S
4.To return to the Actual Signal Display Mode. 1 L -> 1242.0 rpm I
REQ 45.00 Hz
F
CURRENT 80.00 A
POWER 75.00 %
Control panel
Loading...
+ 250 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.