Application

DuraDrive Direct Coupled Actuators are designed to be used in both damper and valve control applications. The following general instructions are for damper applications, refer to the Applicable Literature table for valve literature.

The MS40-717X series actuators are over the shaft spring return actuators compatible with 2 to 10 Vdc or 4 to 20 mAdc
1
control signals.

Features

MS40-717X Series

DuraDrive™ Series Spring Return
Proportional Actuators
General Instructions
150 lb-in (17 N-m) rated torque
NEMA Type 4 housing (IEC IP56)
Custom automatic current sensing motor control
provides extended reliability and repeatable timing
Direct coupled to the damper shaft with dual
industrial hardened universal mounting clamps
Integral wiring for proportional control by 2 to 10 Vdc
or 4 to 20 mAdc
1
Clockwise or counterclockwise spring return is
determined by actuator mounting position
Accurate 92° travel digitally controlled
Integral position indication scale
Rugged die-cast housing
Oil immersed gear train provides continuous
lubrication
Integral transformer for high voltage systems
Rated for operating temperature up to 140 °F
Five year warranty
MS40-717x series actuators can be double-
mounted (gang mounting) to accommodate high torque application requirements (2 to 4 actuators).
Position feedback signal
1.
With the addition of a 500 Ohm resistor - not in-
cluded
Printed in U.S.A. 1/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6

Applicable Literature

F-Number Description Audience Purpose
Describes the globe valve actuator/linkage assembly’s features, specifications, and possible applications. Provides step-by-step mounting instructions.
Provides actuator specifications and part number cross referencing of phased out actuators with the new direct-coupled actuators.
Provides part number cross referencing of phased out actuators with the new direct­coupled actuators.
Describes Schneider Electric approved water treatment practices.
Provides charts, equations, and diagrams to assist in the configuration of valve system applications. TOOL-150, valve sizing slide rule may be purchased separately.
F-26750
F-26646
F-26752
F-26080 EN-205 Water System Guidelines
F-13755 CA-28 Control Valve Sizing F-11080 Valve Selection Chart Water
F-11366 Valve Selection Chart Steam (two-way valves only)
MX40-6XXX-2XX, MX40-7XXX-2XX Series Actuator/Linkage Assemblies General Instructions
MX40-7XXX, MX40-6XXX Series DuraDrive Actuator Selection Guide
VX-2000, VX-7000 Series MX40-7XXX, MX40-6XXX Series Ball/Linked Globe Valve Assemblies Actuator/Linkage Assemblies Selection Guide
– Sales Personnel – Application Engineers – Installers – Service Personnel – Start-up Technicians
– Sales Personnel – Application Engineers – Installers – Service Personnel – Start-up Technicians
– Sales Personnel – Application Engineers – Installers – Service Personnel – Start-up Technicians
– Application Engineers – Installers – Service Personnel – Start-up Technicians
– Application Engineers – Installers – Service Personnel – Start-up Technicians

SPECIFICATIONS

Inputs

Control Signal: 4 to 20 mAdc (with the addition of a 500 Ohm resistor - not included) or 2
to 10 Vdc. See Figure-1 through Figure-8. Power Input: See Table-1. All 24 Vac and 22-30 Vdc circuits are Class 2. All circuits 30 Vac and above are Class 1.
Impedance: 2 to 10 Vdc, 121kΩ. 4 to 20 mAdc, 500Ω. (user supplied). Connections:
Class 1 Power, 24 inch (61 cm) long, 18 AWG color coded pigtail leads. Class 2 Power & Control, 36 inch (91 cm) long, 22 AWG color coded appliance cable
leads.

Ground, 36 inch (91 cm) long, 18 AWG green/yellow pigtail lead.

Outputs

Electrical:
Position Feedback Voltage, “AO” 2 to 10 Vdc (max. 0.5 ma) output signal for position
feedback or to operate up to four additional slave actuators.
Stroke, Electronically limited to 92° ±1°. Action, Direct acting, 0° position with 4 mAdc or 2 Vdc input.

Torque See Table-1. Duty Cycle 100%. Timing See Table- 1 .

Mechanical:

Anti-Rotation Bracket,

Standard 9" long x 13/16" wide (229 x 21 mm), included with the actuator. Optional Order AM-752 (4" long x 1-11/16" wide) for mounting the actuator in narrow

spaces.

Universal Mounting Clamps, Two clamps are required for all mounting configurations.

Standard 3/8" to 1/2" (10 to 13 mm) round and square shaft mounting clamps are

included with the actuator. Optional Order AM-753 for 5/8" (16 mm) square and 3/4" to 1" (19 to 25 mm) round damper shafts, two per package.

2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6
Minimum Damper Shaft Length,

Standard Damper shaft must be at least 4-5/8" (117 mm) long for st andard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension

(order separately).
Position Indicator, Scale numbered from 0 to 95°, provided for positio n indication. Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications. Direction of Rotation, Clockwise or counterclockwise rotation is determined by actuator mounting. The zero (0) position on the position indicator is the normal or spring return position.

Environment

Ambient Temperature Limits :

Shipping & Storage, -40 to 160°F (-40 to 71°C).

Operating, -25 to 140°F (-32 to 60°C). Humidity: 5 to 95% RH, non-condensing. Location: NEMA 1. NEMA Type 4 (IEC IP56) with customer supplied water tight conduit

connectors.

Agency Listings

UL 873: Underwriters Laboratories Inc. listed (File # E9429 Category Temperature-
Indicating and Regulating Equipment). CUL: UL Listed for use in Cana da by Underwriters Laboratories. Canadian Standards C22.2 No. 24-93. European Community: EMC Directive (2004/188/EC). Low Voltage Directive (72/23/EEC). See Table-1 for specific models. Australia: This product meets requirements to bear the C-Tick Mark according to the terms specified by the Communications Authority under th e Radiocommunications Act 1992.

Table-1 Model Chart.

Actuator Power Input Approximate 93° Rotation
Part
Number
MS40-7173 MS40-7170 120 Vac ±10%
MS40-7171 240 Vac ±10% 7.2 10.8 9.0
a
Approximate 2% torque derating per 1°F above 122°F in the drive direction.
Voltage Hz
24 Vac ±20% 50 60 5.5 7.8 4.7
22-30 Vdc 5.0 5.6 2.5
50 60
Running
Watts
ACCESSORIES
AM-620 Remote mount single/dual damper actuator kit AM-621 Round damper shaft extension kit (1/2" ID x 1" OD) for dual actuator mounting AM-703 Span adjustment AM-704 Modulation Interface, converts a PWM to 2 to 10 Vdc AM-705 Positioner, remote/minimum positioning AM-706 Positioner, flush mount digital position indicator AM-707 Digital Indication AM-708 Resistor for 500Ω modulating signal conversion AM-751 Standard anti-rotation bracket 9" long x 13/16" wide (229 x 21 mm), included with
AM-752 Optional anti-rotation bracket 4" long x 1-11/6" wide (102 x 43 mm), for narrow
AM-753 Optional universal mounting clamps for 5/8"(16 mm) square shaft, 3/4" and 1"
AM-754 Standard universal mounting clamps for 3/8" to 1/2" (10 to 13 mm) round and
AM-756 Metric conduit adaptor M20 x 1.5 to 1/2" NPT (two per package) AV-607 Dual mount rack and pinion valve linkage kit for 2-1/2" through 5" VB-8xxx series
AV -609 Dual mount rack and pinion valve linkage kit for 6" VB-8xxx series valve bodies and
TF-711-02 1/2" Sealtight water tight conduit connector (straight) TF-713-02 1/2" Sealtight water tight conduit connector (90°) X-5521 1/2" Pipe plug, included with actuator
Running Holding Powered
6.4 8.5 5.2
VA
actuator
spaces
(19 to 25 mm) round shafts (two per package)
square shafts, two included with actuator
valve bodies and 2-1/2" to 4" VB-9xxx series valve bodies except VB-9323
5" and 6" VB-9xxx series valve bodies except VB-9323
Timing in Seconds @ 70° F
(21°C) for Rated Torque
Spring Return
147 65 150 (17)
Output Torque Rating
lb.-in. (N-m)
Minimum Maximum Stall
a
545 (61.8)
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3

TYPICAL APPLICATIONS (wiring diagrams)

MS40-7170
Black
White
L1
L2
120 Vac
GRDGreen/Yellow
2 to 10 Vdc
Yellow/Black
Gray
AI
COM
+
-
1
Control
Signal
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue AO
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
2
3
Figure-1 Typical MS40-7170 2 to 10 Vdc Wiring Diagram.
Figure-2 Typical MS40-7170 4 to 20 mA Wiring Diagram.
Position Feedback (-)
Signal 2 to 10 Vdc (+)
4 to 20 mA
+
Control
Signal
-
Yellow/Black
500 Ohm
Gray
Blue AO
Black
120 Vac
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
White
AI
COM
L1
L2
GRDGreen/Yellow
MS40-7170
1
2
3
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6
MS40-7171
Brown
Light Blue
L1
L2
240 Vac
GRDGreen/Yellow
Yellow/Black
Gray
AI
COM
2 to 10 Vdc
+
-
Control
Signal
1
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue AO
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
2
3
Figure-3 Typical MS40-7171 2 to 10 Vdc Wiring Diagram.
MS40-7171
Brown
Light Blue
L1
L2
240 Vac
GRDGreen/Yellow
Yellow/Black
Gray
AI
COM
4 to 20 mA
+
-
500 Ohm
1
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue AO
Control
Signal
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
2
3
Figure-4 Typical MS40-7171 4 to 20 mA Wiring Diagram.
MS40-7173
Red
Black
24H (DC+)
24G (DC-)
24 Vac or 22-30 Vdc
GRDGreen/Yellow
Yellow/Black
Gray
AI
COM
+
-
2 to 10 Vdc
1
Transformer
Control
Signal
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue AO
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
2
3
Figure-5 Typical MS40-7173 2 to 10 Vdc Wiring Diagram.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 5
MS40-7173
Red
Black
24H (DC+)
24G (DC-)
24 Vac Transformer
or 22-30 Vdc
GRDGreen/Yellow
4 to 20 mA
Yellow/Black
Gray
AI
COM
+
-
500 Ohm
1
Position Feedback (-)
Signal 2 to 10 Vdc (+)
Blue AO
Control
Signal
1 Unused conduit port must remain plugged with a water
tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
3 Keep AI, COM and AO wiring less than 30 meters
length to meet CE requirements.
2
3
Figure-6 Typical MS40-7173 4 to 20 mA Wiring Diagram.
2 to 10 Vdc
Control
Signal
GRD
MS40-717X
Power
GRD
1
1
2
MS40-717X
1 Unused conduit port must remain plugged with a
water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 See table for power wire designations.
3 Both actuators must be set to operate in the same
direction.
3
3
(+)
(-)
Yellow/Black
AI
Gray COM
Blue
AO
Yellow/Black
AI
Gray COM
Blue
AO
Position Feedback (-)
Signal 2 to 10 Vdc (+)
4 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
5 Keep AI, COM and AO wiring less than 30 meters
length to meed CE requirements.
445
5
Green/Yellow
Green/Yellow
Power Wiring Identification.
Voltage Designation Wire Color
24 Vac or
22-30 Vdc
24H (DC+) Red 24G (DC-) Black
120 Vac
L1 Black L2 White
240 Vac
L1 Brown L2 Light Blue
Figure-7 Two Actuators on the Same Damper Shaft.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6
4 to 20 mA DC
Figure-8 T y pical 4 to 20 mAdc Control Wiring For Two Actuators On The Same Damper Shaft.
Power Wiring Identification.
Voltage Designation Wire Color
24 Vac or
22-30 Vdc
24H (DC+) Red
24G (DC-) Black
120 Vac
L1 Black L2 White
240 Vac
L1 Brown L2 Light Blue
Controller
(+) 4 to 20 mA DC
(-) Common DC
Yellow/Black
500 Ohm
Gray
Blue
AI
COM
AO
MS40-717X
1
4
3
5
GRD
Green/Yellow
Yellow/Black
Position Feedback (-)
Signal 2 to 10 Vdc (+)
1 Unused conduit port must remain plugged with a
water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating.
2 See table for power wire designations.
3 Both actuators must be set to operate in the same
direction.
Gray
Blue
AI
COM
AO
MS40-717X
3
1
5
4
Green/Yellow
4 Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs from current models. See Table 4 on page 14. Consult label on product to confirm wiring codes.
5 Keep AI, COM and AO wiring less than 30 meters
length to meed CE requirements.
GRD
Power
2
INSTALLATION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
Requirements Job wiring diagrams
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 7
If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Tools (not provided)
– Socket wrench 1/2 inch, used for universal mounting clamp nuts – Open-end wrench 10 mm, used for installing AM-676 universal shaft extension – Slotted screwdriver, used for installing anti-rotation brackets – Allen wrench 3/16", used for manual override
Appropriate accessories
– Water tight 1/2 inch conduit seals TAC part number TF-711-02 or T&B #5332
(straight, TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.
– Water tight 1/2 inch flexible conduit (e.,g. Anaconda: Sealtight) or 20 mm flexible
water tight conduit when using AM-756 metric conduit adapter with appropriate metric water tight seals.
– Water tight 1/2" flexible conduit (Anaconda: Sealtight) or 20 mm flexible water tight
conduit when using AM-756 metric conduit adaptor
– Two #8 1/2" (13 mm) sheet metal screws for mounting (optional)
Training: Installer must be a qualified, experienced technician

Precautions General

Warning:
Electrical shock hazard! Disconnect the power supply (line power) before and during
installation to prevent electric shock and equipment damage.
Make all connections in accordance with the wiring diagram and in accordance with
national and local electrical codes. Use copper conductors only.
Caution:
Avoid electrical noise interference. Do not install near large contactors, electrical
machinery, or welding equipment.
Avoid locations where excessive moisture, corrosive fumes, vibration, or explosive
vapors are present.

Federal Communications Commission (FCC)

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installations. This equipment generates, uses, and can radiate radio frequency energy and may cause harmful interference if not installed and used in accordance with the instructions. Even when instructions are followed, there is no guarantee that interference will not occur in a particular installation. If this equipment causes harmful interference to radio or television reception— which can be determined by turnin g the equipment off and on—the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
Consult the dealer or an experienced radio/television technician for help.

Canadian Department of Communications (DOC)

Note: This class B digital apparatus meets all requirements of the Canadian Interference­Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material broilleur du Canada.

European Standard EN 55022

Warning: This is a class B (European Classification) product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Location Caution:

To maintain NEMA Type 4 rating, use water tight 1/2" flexible conduit only, with 1/2"
conduit connector of the water tight type, TAC part number TF-71 1-02 or T&B #5332 (straight), TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.
For metric conduit applications using AM-756 conduit adapters, use the appropriate
metric water tight seals to maintain compliance with IP56 or NEMA Type 4 rating.
Use a water tight 1/2" pipe plug in any unused actuator conduit ports and seal with
water tight tape to stay in compliance with NEMA Type 4 or IP56 rating. Use TAC part number X-5521, Grinnell #8700159257 (black), Grinnell #8700159851 (galvanized), or equivalent. Actuators with unused conduit ports are shipped with the unused port plugged.
8 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6

Mounting Mount the TAC DuraDrive Actuator directly on the damper shaft in locations that clear the

Figure-9 Long Damper Shaft Dimensions.
Min. 4-5/8" (117 mm)
maximum dimensions of the actuator case and allow the actuator to be mounted flush to the surface of the terminal box and perpendicular to the damper shaft.
Note: Some terminal boxes have sheet metal screw heads or other protrusions near the damper shaft. In these cases, a spacer or shim may be added under the mounting tab of the actuator to make the actuator perpendicular to the shaft.
Caution: To remain in NEMA 2 compliance the MS40-715X and MS40-707X series actuators should be mounted with conduit end down.

Damper Actuator Sizing

Correct sizing of the actuator is necessary for proper control of dampers. The area of damper that can be controlled by a given actuator is dependent upon the quality of the damper, the pressure drop across the damper in the closed position, and the velocity of the air flow through the damper. To obtain actual damper torque requirements, contact the damper manufacturer.

Damper Shaft Sizing

Use the “Long Damper Shaft” mounting instructions if the damper shaft is at least 4-5/8" (1 17 mm) long.
Use the “Short Damper Shaft” mounting instructions if the damper shaft is shorter than 4-5/8" or the area around the damper shaft is too narrow to allow standard mounting, as described in the “Long Damper Shaft” mounting section. See Figure-9 for minimum shaft length.
Caution: The MS40-717X actuator is not designed to be used on aluminum damper shafts, solid steel shafts smaller than 1/2" diameter round or 1/2" square, or hollow steel shafts smaller than 3/4" round. The actuator can produce up to 545 in-lbs (61.8. N-m) maximum stall torque, which could result in the actuator snapping off an aluminum damper shaft or an improperly sized steel damper shaft. Refer to Tab le-2 for nominal damper shaft sizes.
Table-2 Steel Damper Shaft Specifications.
Damper Shaft Shape Damper Shaft Type O.D. (Nominal)
Solid bar 1/2" to 1" 0
3/4" 0.375
13/16" 0.683
Round
Square Solid bar 1/2" to 5/8" 0
a
Damper shaft sizes over 1/2" (13 mm) O.D. require AM-753 universal mounting clamps.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 9
Hollow tubing
27/32" 0.626
7/8" 0.805
15/16" 0.808
a
I.D. (Maximum)
1" 0.930

Mounting the Actuator for Clockwise or Counterclockwise Dampers

The zero (0) position on the position indicator is the normal or spring return position. When the actuator is mounted with the “R” side facing the installer and the control signal increases the actuator will rotate in the counterclockwise direction. When the actuator is mounted with the “L” side facing the installer and the control signal increases the actuator will rotate in the clockwise direction.
Long Damper Shafts
1. Move the damper to its normal position. Verify the controller action is set to match the damper application (normally closed or normally open). See TYPICAL APPLICATIONS (wiring diagrams).
– For normally closed damper, when damper is closed the actuator position indicator
should be at 0°. When damper is open the actuator position indicator should be at 90°.
– For normally opened damper, when damper is open the actuator position indicator
should be at 0°. When damper is closed the actuator position indicator should be at 90°.
Note: The actuator comes equipped with two AM-754 universal mounting clamps. For damper shafts larger than 1/2" (13 mm) in diameter, the AM-753 universal mounting clamps are required (order separately). The AM-753 clamps accommodate round shaft sizes ranging from 3/4" to 1" (19 to 25 mm) or 5/8" (16 mm) square shafts.
2. Slide the actuator over the shaf t an d in to its desired final mounting position.
– If the damper shaft rotates clockwise to the closed position, mount the actuator with
the side marked “R” facing the installer. See Figure-10.
– If the damper shaft rotates counterclockwise to the closed position, mount the
actuator with the side marked “L” facing the installer. See Figure-11.
3. Hand tighten the nuts on both of the actuator’s universal mounting clamps.
4. Align the actuator at 90° (perpendicular) to the damper shaft. See Figure-12.
5. Slide the anti-rotation bracket pin into the mounting slot on the actuator and drill mounting holes. See Figure-12 . For narrow spaces the AM-752 anti-rotation bracket is recommended (order separately).
6. Attach one side of the anti-rotation bracket to the mounting surface with one of the screws provided. Leave the screw loose so that the bracket can be rotated. See Figure-10 for clockwise or Figure-11 for counterclockwise spring return.
7. Pivot the anti-rotation bracket away from the actuator. See Figure-10 or Figure-11.
8. Loosen the universal mounting clamps, making sure not to move the damper shaft. Rotate the actuator approximately 5° in the direction which would open the damper. See Figure-10 or Figure-11.
9. Tighten all of the universal mounting clamp nuts with a 1/2" socket wrench. Apply 4 to 6 ft -lbs (5 to 8 N-m) of torque.
10. Manually rotate the actuator toward the full-closed position to apply pressure to the damper seals. See Figure-10 or Figure-11.
11. Pivot the anti-rotation bracket into place and secure the other side of the bracket onto the mounting surface using the other screw provided with the actuator. See Figure-10 or Figure-11.
12. V erify that the damper is in its full-closed position and actuator at 90° (perpendicular) to the damper shaft. See Figure-10 or Figure-11.
10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6
Figure-10 Long Damper Shaft Mounting with Clockwise Spring Return for Normally Closed Damper.
R
1
1
5
CENTERLINE
1 Two AM-754 Universal Mounting Clamp Assemblies
are provided with each actuator. Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip. Two Universal Mounting Clamp Assemblies are required for all mounting configurations.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 11
Figure-11 Long Damper Shaft Mounting with Counterclockwise Spring Return for Normally Closed Damper.
1
5
CENTERLINE
1 Two AM-754 Universal Mounting Clamp Assemblies
are provided with each actuator. Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip. Two Universal Mounting Clamp Assemblies are required for all mounting configurations.
Figure-12 Mounting Anti-rotation Bracket to Actuator.
AM-751 Anti-rotation bracket
90
Actuator mounting slot
90
12 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6

Short Damper Shafts

See Figure-13 for installation of actuator using the AM-676 Universal Shaft Extension. Installation requires AM-676 Universal Shaft Extension and AM-753 Universal Mounting Clamps for 3/4" to 1" (19 to 25 mm) shafts, these items must be ordered separately.
1. Loosen the V -clamp nut s on the AM-676 universa l shaft extension.
2. Fit the universal shaft extension fully onto the damper shaft. Tighten the universal shaft extension V-clamp nuts with a 10 mm open-end wrench. Apply 4 to 6 ft. lbs (5 to 8 N-m) of torque.
3. Move the damper to its normal position. Verify the controller action is set to match the damper application. See TYPICAL APPLICAT IONS (wiring diagrams).
– For normally closed damper: when damper is closed, actuator position indicator
should be at 0°. When damper is open, actuator position indicator should be at 90°.
– For normally opened damper: when damper is open, actuator position indicator
should be at 0°. When damper is closed, actuator position indicator should be at 90°.
4. Remove the mounting clamps from the actuator and replace them with the AM-753 universal mounting clamps.
5. Loosen the nuts on both of the AM-753 universal mounting clamps on the damper actuator.
– If the damper shaft rotates clockwise to the closed position, mount the actuator with
the side marked “R” facing the installer. See Figure-10.
– If the damper shaft rotates counterclockwise to the closed position, mount the
actuator with the side marked “L” facing the installer. See Figure-11.
6. Assemble the damper actuator onto the universal shaft extension, allowing the extension to slide through the actuator’s universal mounting clamps. Make sure the actuator is 90° (perpendicular) to the damper shaft. Then, hand tighten the nuts on both of the actuator’s universal mounting clamps. See Figure-12
Note: If the universal shaft extension protrudes excessively above the damper actuator's top universal mounting clamp:
remove the damper actuator from the universal shaft extension,
remove the extension from the damper shaft,
shorten the universal shaft extension by cutting it to the desired length,
then proceed to follow mounting instructions.
7. Slide the anti-rotation bracket pin into the mounting slot on the actuator. See Figure-12. For narrow spaces, the AM-752 anti-rotation bracket is recommended (order separately).
8. Position the actuator and bracket in the desired final mounting position on the mounting surface and drill mounting holes. See Figure-13.
9. Attach one side of the anti-rotation bracket to the mounting surface with one of the screws provided. Leave the screw loose so that the bracket can be rotated. See Figure-10 for clockwise or Figure-11 for counterclockwise spring return.
10. Pivot the anti-rotation bracket away from the actuator. See Figure-10 or Figure-11.
11. Loosen the universal mounting clamps, making sure not to move the damper shaft. Rotate the actuator approximately 5° in the direction which would open the damper. See Figure-10 or Figure-11.
12. Tighten all of the universal mounting clamp nuts with a 1/2" socket wrench. Apply 4 to 6 ft-lbs (5 to 8 N-m) of torque.
13. Manually rotate the actuator toward the full-closed position to apply pressure to the damper seals. See Figure-10 or Figure-11.
14. Pivot the anti-rotation bracket into place and secure the other side of the bracket onto the mounting surface using the other screw provided with the actuator. See Figure-10 or Figure-11.
15. V erify that the damper is in its full-closed position and actuator at 90° (perpendicular) to the damper shaft. See Figure-10 or Figure-11.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 13
Wiring Requirements Control and Power Leads
Figure-13 Installation of Universal Shaft Extension.
Actuator
Anti-rotation Bracket (included with actuator)
AM-753 Universal Mounting Clamps
Duct
V-clamp
Mounting Surface
Damper Shaft
AM-676 Universal Shaft Extension
1
1 The AM-676 extends the
damper shaft approximately 9" (229 mm).
Remove blue plastic thread protectors before installing conduit fittings. See Figure-1 through Figure 8 for typical wiring applications and Table-3 for maximum wire lengths.
Caution: The 24 Vac model contains a half-wave rectifier power supply and must not be powered by transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies. Refer to EN-206 Guidelines for Powering Multiple Full-Wave and
Half-Wave Rectifier Devices from a Common Transformer, F-26363, for further information.
Note: Class 2 control and power lead wiring must be routed separately from line voltage
wiring and any other non-class 2 circuits.
Table-3 Control and Power Wiring Data.
Actuator
Voltage
24 Vac and
22-30 Vdc
240 Vac MS40-7171
Table-4 Wire Color Codes for Models Manufactured before December, 2007.
Part Number
MS40-7173-0-0-0
Old Design
MS40-7170-0-0-0
Old Design
MS40-7171-0-0-0
Old Design
N/A: Not Applicable
14 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6
Power
Voltage
24 Vac N/A N/A Green/Yellow Black Black/Blue White Red Black
120 Vac Black White Green/Yellow N/A N/A White Red Black
240 Vac Brown
L1 L2 Ground 24 H 24 G
Light Blue
Green/Yellow N/A N/A White Red Black
Part
Number
MS40-7173
Maximum Wire Run in ft. (m)
(5% Voltage Drop)
14 AWG 16 AWG 18 AWG
981
(299)
Analog
Input
617
(188)
500 Ohms Common
388
(118)120 Vac MS40-7170

CHECKOUT

THEORY OF OPERATION

This procedure is for checking out a normally closed actuator that is typically mounted unpowered. It is possible to mount the actuator with power applied for special applications.
Note: To check out a normally opened actuator the procedure is the same as below, except the initial position is open and closed when powered.
After the entire system has been installed and the actuator has been powered up, the following check can be made for proper system operation. Check for correct operation of the damper while actuator is being stroked.

1. Apply power to the actuator and control system.

2. Set the controller to cause the actuator to drive open (set override controller output to maximum).

3. Check to see that the actuator travels to the full-open position.

4. Set the controller to cause the actuator to drive closed (set override controller output to minimum).

5. Check to see that the actuator travels to the fully closed position.

Note: If anticipated damper operation does not occur, verify the Long Damper Shaft or Short Damper Shaft mounting procedures. Also, verify that the controller has the proper action (direct or reverse) to match the damper required operation.

MAINTENANCE

FIELD REPAIR

The actuator is, by means of dual mounting clamps, directly mounted onto the damper shaft. The anti-rotation bracket supplied with the actuator prevents lateral movement of the actuator. The damper actuator is not provided with and does not require any limiting switches, but is electronically protected against overloading.
The angle of rotation is electronically limited to 92° ±1°. When reaching the damper or actuator end position, the motor stops automatically. The position of the actuator is indicated by means of scale reading 0 to 95°.
Regular maintenance of the total system is recommended to assure sustained optimum performance. The MS40-717X actuator is maintenance free.
None. Replace with functional actuator.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 15

DIMENSIONAL DATA

Figure-14 MS40-717X Damper Actuator.

4"
(102)
4"
(102)
1-27/64"
(36)
10-27/32 (275)
R
On October 1st, 2009, TAC became the Buildings bus iness of i ts pare nt company Sc hneider Elec tric. This do cument r e flect s the visual identi ty of Schneider Electric, ho wev er t he re remains references to TAC as a corp orate brand in the body copy. As ea ch document i s updated, the body co py will be changed to reflect app r opriate
g
Figure-14 dimensions are in inches (mm).
corpo rate bra nd ch a n
Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
F-26748-6
es.
Schneider Electric
1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940
www.schneider-electric.com/buildings
Loading...