Carrier 06E User Manual

0 (0)

Compressors and Condensing Units

Hermetic, Water-Cooled

PRELIMINARY CHECKS

Inspect shipment for damage. File claim with the shipping company if shipment is damaged or parts are missing.

Local water conditions can cause excessive fouling or pitting of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water condi­ tioning information.

PLACING THE UNIT

Locate unit on floor in a well ventilated area. Install unit where it will be warmer than condi­ tioned area. Position it to allow sufficient space for refrigerant and water connections and to seiwice compressor. Allow space at one end of condenser for tube cleaning or replacement. Place unit so suction and discharge valves can be easily reached and so oil level can be checked.

Make provision in piping layout to drain and vent condenser if system is to be shut down in winter.

Level unit and bolt it firmly to foundation.

COMPRESSOR

Remove 4 self-locking bolts from compressor­ mounting springs, and reassemble them with flanged washers and neoprene snubbers as shown in Fig. 1. Flanged washers and neoprene snubbers are shipped in a cloth bag tied to compressor. Tighten all 4 bolts. Then, loosen each until the flanged washer can be moved sidewise. Check compressor to see that it floats freely on its mounting springs.»

PIPING CONNECTIONS

Attach water supply and return line to con­ nections indicated on condensing unit (Fig. 3). Water leaving condenser should not be connected directly into sewer lines; check local codes.

Attach refrigerant liquid and suction lines to condensing unit (Fig 3),suction and discharge lines to compressor unit (Fig. 2) Discharge line muffler and check valve are factory supplied with 06E com­ pressor units Install the muffler as close to shutoff valve as possible and install the check valve in the discharge line close to the muffler, on the down­ stream side. When soldering or brazing piping to valves, disassemble the valve or wrap it in wet cloth to prevent damage by heat Allow flexibility in

Table 1 — Physical Data

COMPRESSOR UNIT 06E

 

 

 

1V022JW027

W033

W044

 

 

 

 

 

1 6ÔÔ i 640 ''650^^670

 

CONDENSING UNIT 07E

 

 

 

A022 :3027 ;B033Jp044_

OPERATING WEIGHT (Tb)

 

 

l235{TM0'[T356JT56b '

REFRIGERANT

 

 

 

 

R-22, R-502'

 

 

COMPRESSOR 66E (06EV,EW)

 

D2.50 IE265 IE275 IE?99^

 

 

 

(07EA,EB,ED):Di50i N265 i N i /5 i N299

Oil Charge, PP33-2(pt)

 

 

 

14 | i9 1 19 I 19

 

 

 

Normal Oil Pressure*

 

 

 

13 to 18 psig

 

 

 

Oil Safety Switch

 

 

Cut-in

9 to 13 psig

 

 

 

 

 

 

 

Cutout 2 to 5 psi below cut-

 

 

High-Pressure Switch

 

 

 

 

 

 

 

 

 

Cutout Range

 

 

 

300 to 400 psigt

 

 

 

 

 

 

 

 

320 pspt,

 

Differential

(cutout,

cut-in)

95 ± 1 5 psi ifixed)

 

Factory Settings!

 

 

Cutout

335 ± 6 psig

 

 

 

 

 

 

 

 

260 i 6 psig

 

 

 

 

 

Cut-In

240 t 7 ps:<3

 

 

 

 

 

 

 

 

175 3 7'ps>3‘ ■■■

 

Low-Pressure Switch

 

 

 

5 to 1 00 psig (adj )

 

Cutout Range

 

 

 

 

Differential

(cutout,

cut-in)

22 ± 8 psi (fixed)

 

Factory Settings!

 

 

Cutout

2

4 +

4

psig

 

 

 

 

 

Cut-in

 

66 ± 4 psig

 

 

Low-Side Max Pressure

 

 

022

245 psig

 

 

 

CONDENSER 69RE

 

 

 

027

 

043

 

Refrigerant 22

 

 

 

 

 

139 f

Î95

 

Max Storage Capacity (lb)**

 

 

 

 

Min Operating Charge (lb)

 

 

3G

“j'y i

37

 

Max Operating Pressure

 

 

385 PC.Î9

 

 

Refrig erant Side

 

 

 

 

 

Water Side

 

 

 

 

 

250 psig

 

 

 

. 07E Condensing Unit Data

 

 

 

 

 

 

 

'Listed pressuies are above operating suction pressure

(pressure

diffeieniial

between

suction

and

discharge

pressures

of

oil

pump)

 

 

 

 

 

 

 

 

 

 

fAdjustable,

but only

by

authorized

personnel

and

with

special

tool

 

 

 

 

 

 

 

 

 

 

:j Listed settings

for

R-22

For

other refrigerants,

reset

to

pressures

corresponding

to

saturation temperatures

indicated

by

the listed pressures

 

 

 

 

 

 

 

 

 

**Condenser 80% filled with liquid refrigerant at 104 F

 

 

 

 

 

Fig. 1 — Compressor Mounting

© Carrier Corporation 1975

1276

Form 06E, 07E-5SI

Carrier 06E User Manual

M ODF*

DIAM KNOCKOUT

DISCHARGE VALVE

 

(MAY BE ROTATED 180°

 

L ODF

SUCTION VALVE

(MAY BE ROTATED 360° AT 90° INTERVALS)

2-31| OVERALL HEIGHT

'A~

OVERALL

LENGTH (INCLUDES CONTROL BOX OVERHANG)

DIAM-4 HOLES

*1 nstall pressure relief device in discharge line

06E Hermetic Compressor Unit Dimensions

Pressure relief setting is 465 psig

UNIT 06E

 

V022

W027

 

JW0j44_

tOverall width includes projection of fuse

mMENMONS

A

3-1 1 %

3-1IV«

4~VVu

 

holders

 

CONNECT TONS On ) u

 

 

iVa“'

2v; '

" 2Va ”■

 

 

IV«

 

 

M

IV,

iVa

1 Vs

Fig. 2 —06E Hermetic Compressor Units

07E Water-Cooled Condensing Unit Dimensions

UNIT 07E

 

A022

§027

§033

0044

_UNJT 07E^

 

A022

 

B027

 

B033

 

0044

 

 

 

 

 

DIMENSIONS (fi

A

6- 5

6- 5

6- 5

6-7V

CONNECTIONS (ii

K

iVs

 

IVs

 

2Vs

 

2Vs

 

C

2-1 IV

3- 0

2-1 1V2

3-2 Vs

 

L

iVs

 

IV«

 

IVs

 

iVs

Overall Width

 

l-nVs

1 -1 1V

1-1IV

2-3 Vs

 

U

2V

 

2V

 

2V

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3 — 07E Water-Cooled Condensing Units

Certified dimension drawings available on request.

HR

Table 2 — Electrical Data (60-Hertz, 3-Phase) (Circuit Breakers Selected for Units Using R-22)

VOLTS

Nomina 1

 

 

 

200

 

 

 

 

230

 

 

 

Supply Range

 

 

180-229

 

MÀX

 

 

207-264

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX

UNIT

 

 

KW

RLA

LRA

MTA

MWA

FUSE

RLA

LRA

MTA

MWA

 

FUSE

 

 

 

 

 

 

 

 

AMPS

 

 

 

 

 

AMPS

 

V022

 

24.8

g2

345

114

102

175

75

300

104

94

 

150

Compr

W027

 

33.6

103

471

144

129

225

92

410

128

115

 

200

06 E

W033

 

37.6

1 14

506

160

143

250

103

440

144

129

 

225

 

W044

 

55.1

164

690

230

206

350

150

600

210

188

 

300

 

A022

 

22.6

72

283

100

90

150

63

r 246

88

79

 

125

Cond

B027

 

31.4

96

471

134

120

200

85

410

118

106

 

175

07 E

B033

 

34.0

107

471

150

134

225

96

410

134

120

 

200

 

D044

 

50.4

159

690

222

198

350

140

600

196

175

 

300

VOLTS

Nominal

 

 

 

460

 

 

 

 

575 (See Note 5)

 

Supply Range

 

 

414-528

 

 

 

 

518-660

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX

 

 

 

 

 

MAX

UNIT

 

 

KW

RLA

LRA

MTA

MWA

FUSE

RLA

LRA

MTA

MWA

 

FUSE

 

 

 

 

 

 

 

 

AMPS

 

 

 

 

 

AMPS

 

V022

 

24.8

36

150

50

45

80

29

120

40

37

 

60

Compr

W027

 

33.6

45

205

63

56

100

36

164

50

45

 

80

06 E

W033

 

37.6

51

220

71

64

no

42

176

58

53

 

90

 

W044

 

55.1

76

300

106

95

150

60

240

84

75

 

125

 

A022

 

22.6

32

123

45

40

70

27

98

37

34

 

60

Cond

B027

 

31.4

43

205

60

54

90

33

164

45

42

 

70

07 E

B033

 

34.0

48

205

66

60

100

39

164

54

48

 

80

 

D044

 

50.4

70

300

98

88

150

60

240

84

75

 

125

KW

— Maximum Power Input

LRA

— Locked Rotor Amps

MTA

— Must Trip Amps

MWA

— Minimum Wire Amps Complies with NEC Section

 

430-22

RLA

— Rated Load Amps

Supply Range — Units are suitable for use on electrical systems

where voltage supplied to the unit terminals is not below or above the listed range limits

NOTES:

1 Control voltage is 115 v for all units

2

Part-winding start all

200-, 230-volt

06E

 

and

07E units;

460-,

 

575-volt 06EW044 and 07ED044 units

 

 

 

 

 

 

 

 

 

Across-the-line start:

all 460-, 575-volt

units

except

06EW044

 

and 07ED044.

 

 

 

 

 

 

 

 

 

 

 

3. Factory

wiring

is in

compliance with National

Electrical

Code

 

(NEC)

Field

wiring

must

comply

with

 

NEC

and

applicable

 

local codes Maximum incoming wire

size

to

control

center

 

terminal block is 250 MCM

 

 

 

 

 

 

 

 

 

4

The 06E compressor

unit

electrical

data

shown

in

the

table

 

does not apply to 06E compressors

used

as

an

integral part

of

 

other Carrier equipment Refer to

the

electrical

data

for

the

 

particular application

 

 

 

 

 

 

 

 

 

 

-> 5 Units for use on 575 volts are available on special order

(Continued from page 1.)

suction line so compressor suction valve may be moved aside for access to suction strainer.

A solenoid valve is necessary for single pump­ out control used on 06E and 07E units. Install the valve (field supplied) in the liquid line, just before the expansion valve. A filter-drier of adequate size should be installed in liquid line between con­ denser and solenoid valve.

Pressure relief valve located on side of con­ denser will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from valve to outdoors.

Refer to Carrier System Design Manual for standard piping techniques.

ELECTRICAL REQUIREMENTS

Eield wiring must comply with local and national codes. See Table 2.

Install a branch circuit fused disconnect of adequate size to handle starting current. The disconnect must be within sight of the unit and readily accessible, in compliance with National Electrical Code (NEC), Section 440—14.

Line power is brought into control center thru indicated opening. Connect line power supply to

terminal block TB1; connect power leads to terminals LI, L2 and L3. Connect control circuit power supply (115 volts) to terminals 1 and 15 on terminal block TB2. Refer to Eig. 4.

Wiring connections for field-supplied equip­ ment are shown on diagram attached to unit (or in wiring diagram booklet).

Discharge line limit thermostat supplied with 06EV,W compressor units is installed on discharge line as close to compressor as possible.

1. Place mounting plate on discharge line and solder in place.

2. Easten the thermostat to plate with screws supplied.

3.Cover switch with insulation and secure insula­ tion at each end with straps.

4.Connect thermostat in series with Ml and M2 overloads, between terminals 2 and 4 on termi­ nal block TB2.

 

ACCESSORIES

PACKAGE NUMBER

DESCRIPTION

07EA900021

Control Circuit Transformer

07EA900061

Gage Panel

1276

REFRIGERANT CHARGING

Evacuate, Dehydrate and Leak Test the entire refrigerant system by methods described in Carrier Standard Service Techniques Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass method to charge system. See Section 1-8 of Service Tech­ niques Manual for details.

CHARGE THE SYSTEM to a clear sight glass while holding saturated condensing pressure constant at 125 F (air-cooled systems) or 105 F (water-cooled systems) Add additional refrigerant to fill con­ denser subcooler coils.

07E Condensing Units - After clear sight glass is obtained, add charge until liquid refrigerant reaches condenser liquid level test cock.

06E Compressor Units — See condenser data for additional charge required to fill subcooler.

All Units — Stamp type of refrigerant and amount of charge on unit informative plate

INITIAL START-UP

Crankcase heater should be energized a mini­ mum of 24 hours before starting unit.

Check to see that oil level is approximately 1/3 up on the compressor sight glass.

Open water supply valve and allow water to

 

reach condenser. (Turn condenser fan on when the

 

compressor unit is applied with air-cooled con­

 

denser.)

 

 

Backseat the compressor suction

and discharge

shutoff valves, open liquid line valve at receiver.

 

Start evaporator fan or chilled water pump.

 

Start Compressor — Push the

control circuit

 

START-STOP-RESET switch to “Start.” The timer motor starts immediately. Depending on the posi­ tion of the timer, the compressor start is delayed for 12 seconds to approximately 8 minutes. Check oil pressure after compressor has run a few minutes, the pressure should be 12—18 psi above the suction pressure After about 20 minutes of operation, stop the compressor. Allow it to be idle for about 5 minutes, then observe the oil level in the sight glass. If the oil level is below the bottom of the sight glass, refer to the Carrier Standard Service Techniques Manual, Chapter 1, Section 1-11, for adding oil. The proper oil level for the 06E compressor is approximately 1/3 up on sight glass.

CONTROL POWER TERMINAL STRIP (TBg)

MAIN POWER

MAIN POWER

EQUIPMENT GROUND

 

INLET,

TERMINAL

'CONNECTION

GROUND SCREW

 

BLOCK (TB|)

 

 

 

 

START-STOP-RESET

 

 

 

SWITCH

 

 

 

CONTROL CIRCUIT

 

 

 

FUSE(S)

 

 

COMPRESSOR

(2 ON 50-Hz UNITS)

 

 

CONTACTOR

CONTROL RELAYS

 

 

 

SENSOR MODULE

 

 

OUTLET FOR

 

 

WIRING TO

(SOLID STATE

 

 

 

 

COMPRESSOR

COMPRESSOR MOTOR

 

 

06E

PROTECTION)

 

 

07E

 

 

 

HIGH PRESSURE

 

 

 

SWITCH

 

 

 

LOW PRESSURE

 

 

 

SWITCH

 

 

 

TIMER MOTOR

 

 

 

(4-FUNCTION TIMER)

 

 

 

 

 

 

COMPRESSOR

 

 

 

CONTACTOR

OIL PRESSURE

 

 

(PART-WIND)

SAFETY SWITCH

 

 

 

ACCESSORY TRANSFORMER

MAIN POWER

(60-Hz UNITS ONLY)

CIRCUIT BREAKER

 

Fig. 4 — Control Center — 06E and 07E

1276

4

Timer Functions (See Fig. 5 — Tinier Cycle)

1. Switch A (contacts A-Al and A-A2) provides Time Guard® function. Start of compressor is delayed approximately 5.5 minutes after shut­ off. The minimum time between starts of compressor is 8 minutes.

2.Switch B (contacts B1 and B—B2) starts compressor and de-energizes the crankcase heater. These contacts also provide one-second time delay for part-winding start.

3.Switch E (contacts E—El) provides approxi­ mately 40-second bypass of oil-pressure switch (OPS) at start-up. Compressor will shut off if sufficient oil pressure does not build up.

4.Switch D (contacts D—Dl) bypasses the lowpressure switch (EPS) for 2.5 minutes at start­ up for winter start control.

(BLACK DENOTES CLOSED CONTACTS)

TIMER POSITION DURING

0 MIN OR

UNIT OPERATION-

 

8 MIN

 

»TT?*

-'E-El-

40 SEC +5

2-6 SEC

-xA-

---

150 SEC

Fig. 5 — Timer Cycle

PROTECTION DEVICES

High-Pressure Switch — Check by throttling con­ denser water or blocking air flow on air-cooled units, allowing head pressure to rise gradually. Check discharge pressure constantly throughout procedure. Compressor should shut off within 10 psi of values shown in Table 1.

Low-Pressure Switch — Check by slowly closing suction shutoff valve or by completely closing liquid line shutoff valve. A decrease of suction pressure will follow. Compressor should shut off within 4 psi of values shown in Table 1.

Oil Pressure Switch (OPS) protects against damage from loss of oil and failure of pressure buildup during start-up. Switch time delay (approximately 35 seconds) is derived from being properly wired to the ambient and voltage insensitive Time Guard timer. If OPS locks out unit, d eterm in e a n d c o rre ct th e ca u se (such as loss of compressor oil or flooded compressor) b efo re re sta rtin g u n it Restart by pushing the control circuit switch on unit control box to “Stop” then to “Reset.” Failure to correct the cause of the OPS lockout will constitute abuse.

E q u ip m e n t fa ilu re d u e to a b u se is n o t co v ere d b y

th e W a rra n ty .

Time Guard Control protects compressor against short cycling. See Start Compressor.

Crankcase Heater prevents absorption of liquid refrigerant by oil in crankcase during brief or extended shutdown periods. Source of 115-volt power is the auxiliary control power, independent of the main unit power. This assures compressor protection even when main unit power disconnect switch is off.

N ev er

o p en

a n y sw itch

o r d isc o n n ec t

th a t

w ill

d e - e n e rg ize

th e

cra n k ca s e

h ea ter

u n le ss

u n it

is

b ein g

ser vic ed

o r is

to

b e sh u t

d o w n

fo r

a

p ro lo n g ed

p er io d

A fte r

a

p ro lo n g ed

sh u td o w n

o r

a

se rvic e

jo b , e n e rg ize

th e

cra n k ca s e

h e a ter

fo r

2 4

h o u rs b efo re sta r tin g th e co m p resso r .

Compressor Motor Protection consists of 3 tem­ perature sensors embedded in motor windings and connected to a solid state module in unit control box.

When an overtemperature condition causes module to shut compressor off, push control circuit STOP switch. Investigate cause of compressor shut­ down and correct. After compressor cools, push control circuit START-RESET switch. Compressor will restart after Time Guard delay period.

SOLID STATE MODULE is checked by applying unit control voltage to terminals T1 and T2 (see label diagram), then checking for continuity across terminals Ml and M2. If no continuity between Ml and M2, check temperature sensor resistance using a volt-ohmmeter. If all sensors check below 95 ohms (180 F) and there is no continuity between module terminals Ml and M2, replace module.

C A U T I O N :

D o

n o t u se

a b a tte ry

p o w e red

te st

la m p to

ch ec k

se n so r s

E x ce ssiv e

c u r ren t

ca n

ca u se d a m a g e

 

 

 

 

If one sensor fails, it can be jumpered out of the circuit with a 75 ohm, or higher, resistor (rated at 2 watts or higher) across the proper sensor terminal and common terminal. If a short to ground in sensor circuit is indicated, replace compressor motor.

CAPACITY CONTROL SYSTEM

Capacity Control Valve(s) is controlled by suction pressure and actuated by discharge pressure. Each valve controls 2 cylinders. On start-up, controlled cylinders do not load up until differential between suction and discharge pressure is 10 psi (see Fig. 6).

D o

 

n o t u se

a u to m a tic p u m p d o w n

co n tro l

o n

0 6 E ,

0

7 E u n its

e q u ip p ed w ith

u n lo a d er

va lve s .

U se

sin g le

 

p u m p o u t

o r so le n o id

d ro p (m in im u m

p ro ­

te ctio n )

c o n tr o l

 

 

 

 

Capacity Control Valve Adjustments

CONTROL SET POINT (cylinder load point) is adjustable from 0 psig to 85 psig. Pressure differ­ ential between cylinder load-up point and cylinder unload point is adjustable from 6 psi to 22 psi.

Loading...
+ 11 hidden pages