Compressors and Condensing Units
Hermetic, Water-Cooled
Inspect shipment for damage. File claim with the shipping company if shipment is damaged or parts are missing.
Local water conditions can cause excessive fouling or pitting of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water condi tioning information.
Locate unit on floor in a well ventilated area. Install unit where it will be warmer than condi tioned area. Position it to allow sufficient space for refrigerant and water connections and to seiwice compressor. Allow space at one end of condenser for tube cleaning or replacement. Place unit so suction and discharge valves can be easily reached and so oil level can be checked.
Make provision in piping layout to drain and vent condenser if system is to be shut down in winter.
Level unit and bolt it firmly to foundation.
COMPRESSOR
Remove 4 self-locking bolts from compressor mounting springs, and reassemble them with flanged washers and neoprene snubbers as shown in Fig. 1. Flanged washers and neoprene snubbers are shipped in a cloth bag tied to compressor. Tighten all 4 bolts. Then, loosen each until the flanged washer can be moved sidewise. Check compressor to see that it floats freely on its mounting springs.»
Attach water supply and return line to con nections indicated on condensing unit (Fig. 3). Water leaving condenser should not be connected directly into sewer lines; check local codes.
Attach refrigerant liquid and suction lines to condensing unit (Fig 3),suction and discharge lines to compressor unit (Fig. 2) Discharge line muffler and check valve are factory supplied with 06E com pressor units Install the muffler as close to shutoff valve as possible and install the check valve in the discharge line close to the muffler, on the down stream side. When soldering or brazing piping to valves, disassemble the valve or wrap it in wet cloth to prevent damage by heat Allow flexibility in
COMPRESSOR UNIT 06E |
|
|
|
1V022JW027 |
W033 |
W044 |
||||
|
|
|
|
|
1 6ÔÔ i 640 ''650^^670 |
|
||||
CONDENSING UNIT 07E |
|
|
|
A022 :3027 ;B033Jp044_ |
||||||
OPERATING WEIGHT (Tb) |
|
|
l235{TM0'[T356JT56b ' |
|||||||
REFRIGERANT |
|
|
|
|
R-22, R-502' |
|
|
|||
COMPRESSOR 66E (06EV,EW) |
|
D2.50 IE265 IE275 IE?99^ |
|
|||||||
|
|
(07EA,EB,ED):Di50i N265 i N i /5 i N299 |
||||||||
Oil Charge, PP33-2(pt) |
|
|
|
14 | i9 1 19 I 19 |
|
|
|
|||
Normal Oil Pressure* |
|
|
|
13 to 18 psig |
|
|
|
|||
Oil Safety Switch |
|
|
Cut-in |
9 to 13 psig |
|
|
|
|||
|
|
|
|
Cutout 2 to 5 psi below cut- |
|
|
||||
High-Pressure Switch |
|
|
|
|
|
|
|
|
|
|
Cutout Range |
|
|
|
300 to 400 psigt |
|
|
||||
|
|
|
|
|
|
320 pspt, |
|
|||
Differential |
(cutout, |
cut-in) |
95 ± 1 5 psi ifixed) |
|
||||||
Factory Settings! |
|
|
Cutout |
335 ± 6 psig |
|
|
|
|||
|
|
|
|
|
260 i 6 psig |
|
||||
|
|
|
|
Cut-In |
240 t 7 ps:<3 |
|
|
|
||
|
|
|
|
|
175 3 7'ps>3‘ ■■■ |
|
||||
Low-Pressure Switch |
|
|
|
5 to 1 00 psig (adj ) |
|
|||||
Cutout Range |
|
|
|
|
||||||
Differential |
(cutout, |
cut-in) |
22 ± 8 psi (fixed) |
|
||||||
Factory Settings! |
|
|
Cutout |
2 |
4 + |
4 |
psig |
|
||
|
|
|
|
Cut-in |
|
66 ± 4 psig |
|
|
||
Low-Side Max Pressure |
|
|
022 |
245 psig |
|
|
|
|||
CONDENSER 69RE |
|
|
|
027 |
|
043 |
|
|||
Refrigerant 22 |
|
|
|
|
|
139 f |
Î95 |
|
||
Max Storage Capacity (lb)** |
|
|
|
|
||||||
Min Operating Charge (lb) |
|
|
3G |
“j'y i |
37 |
|
||||
Max Operating Pressure |
|
|
385 PC.Î9 |
|
|
|||||
Refrig erant Side |
|
|
|
|
|
|||||
Water Side |
|
|
|
|
|
250 psig |
|
|
|
|
. 07E Condensing Unit Data |
|
|
|
|
|
|
|
|||
'Listed pressuies are above operating suction pressure |
(pressure |
|||||||||
diffeieniial |
between |
suction |
and |
discharge |
pressures |
of |
oil |
|||
pump) |
|
|
|
|
|
|
|
|
|
|
fAdjustable, |
but only |
by |
authorized |
personnel |
and |
with |
special |
|||
tool |
|
|
|
|
|
|
|
|
|
|
:j Listed settings |
for |
R-22 |
For |
other refrigerants, |
reset |
to |
||||
pressures |
corresponding |
to |
saturation temperatures |
indicated |
by |
|||||
the listed pressures |
|
|
|
|
|
|
|
|
|
|
**Condenser 80% filled with liquid refrigerant at 104 F |
|
|
|
|
|
Fig. 1 — Compressor Mounting
© Carrier Corporation 1975 |
1276 |
Form 06E, 07E-5SI |
M ODF* |
DIAM KNOCKOUT |
DISCHARGE VALVE |
|
(MAY BE ROTATED 180° |
|
L ODF
SUCTION VALVE
(MAY BE ROTATED 360° AT 90° INTERVALS)
2-31| OVERALL HEIGHT
'A~
OVERALL
LENGTH (INCLUDES CONTROL BOX OVERHANG)
DIAM-4 HOLES
*1 nstall pressure relief device in discharge line
06E Hermetic Compressor Unit Dimensions
Pressure relief setting is 465 psig |
UNIT 06E |
|
V022 |
W027 |
|
JW0j44_ |
tOverall width includes projection of fuse |
mMENMONS |
A |
3-1 1 % |
3-1IV« |
4~VVu |
|
holders |
|
|||||
CONNECT TONS On ) u |
|
|
iVa“' |
2v; ' |
" 2Va ”■ |
|
|
|
IV« |
||||
|
|
M |
IV, |
iVa |
1 Vs |
Fig. 2 —06E Hermetic Compressor Units
07E Water-Cooled Condensing Unit Dimensions
UNIT 07E |
|
A022 |
§027 |
§033 |
0044 |
_UNJT 07E^ |
|
A022 |
|
B027 |
|
B033 |
|
0044 |
|
|
|
|
|
||||||||||
DIMENSIONS (fi |
A |
6- 5 |
6- 5 |
6- 5 |
6-7V |
CONNECTIONS (ii |
K |
iVs |
|
IVs |
|
2Vs |
|
2Vs |
|
C |
2-1 IV |
3- 0 |
2-1 1V2 |
3-2 Vs |
|
L |
iVs |
|
IV« |
|
IVs |
|
iVs |
Overall Width |
|
l-nVs |
1 -1 1V |
1-1IV |
2-3 Vs |
|
U |
2V |
|
2V |
|
2V |
|
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Certified dimension drawings available on request.
HR
Table 2 — Electrical Data (60-Hertz, 3-Phase) (Circuit Breakers Selected for Units Using R-22)
VOLTS |
Nomina 1 |
|
|
|
200 |
|
|
|
|
230 |
|
|
|
|
Supply Range |
|
|
180-229 |
|
MÀX |
|
|
207-264 |
|
|
|
|||
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
MAX |
|
UNIT |
|
|
KW |
RLA |
LRA |
MTA |
MWA |
FUSE |
RLA |
LRA |
MTA |
MWA |
|
FUSE |
|
|
|
|
|
|
|
|
AMPS |
|
|
|
|
|
AMPS |
|
V022 |
|
24.8 |
g2 |
345 |
114 |
102 |
175 |
75 |
300 |
104 |
94 |
|
150 |
Compr |
W027 |
|
33.6 |
103 |
471 |
144 |
129 |
225 |
92 |
410 |
128 |
115 |
|
200 |
06 E |
W033 |
|
37.6 |
1 14 |
506 |
160 |
143 |
250 |
103 |
440 |
144 |
129 |
|
225 |
|
W044 |
|
55.1 |
164 |
690 |
230 |
206 |
350 |
150 |
600 |
210 |
188 |
|
300 |
|
A022 |
|
22.6 |
72 |
283 |
100 |
90 |
150 |
63 |
r 246 |
88 |
79 |
|
125 |
Cond |
B027 |
|
31.4 |
96 |
471 |
134 |
120 |
200 |
85 |
410 |
118 |
106 |
|
175 |
07 E |
B033 |
|
34.0 |
107 |
471 |
150 |
134 |
225 |
96 |
410 |
134 |
120 |
|
200 |
|
D044 |
|
50.4 |
159 |
690 |
222 |
198 |
350 |
140 |
600 |
196 |
175 |
|
300 |
VOLTS |
Nominal |
|
|
|
460 |
|
|
|
|
575 (See Note 5) |
|
|||
Supply Range |
|
|
414-528 |
|
|
|
|
518-660 |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
MAX |
|
|
|
|
|
MAX |
UNIT |
|
|
KW |
RLA |
LRA |
MTA |
MWA |
FUSE |
RLA |
LRA |
MTA |
MWA |
|
FUSE |
|
|
|
|
|
|
|
|
AMPS |
|
|
|
|
|
AMPS |
|
V022 |
|
24.8 |
36 |
150 |
50 |
45 |
80 |
29 |
120 |
40 |
37 |
|
60 |
Compr |
W027 |
|
33.6 |
45 |
205 |
63 |
56 |
100 |
36 |
164 |
50 |
45 |
|
80 |
06 E |
W033 |
|
37.6 |
51 |
220 |
71 |
64 |
no |
42 |
176 |
58 |
53 |
|
90 |
|
W044 |
|
55.1 |
76 |
300 |
106 |
95 |
150 |
60 |
240 |
84 |
75 |
|
125 |
|
A022 |
|
22.6 |
32 |
123 |
45 |
40 |
70 |
27 |
98 |
37 |
34 |
|
60 |
Cond |
B027 |
|
31.4 |
43 |
205 |
60 |
54 |
90 |
33 |
164 |
45 |
42 |
|
70 |
07 E |
B033 |
|
34.0 |
48 |
205 |
66 |
60 |
100 |
39 |
164 |
54 |
48 |
|
80 |
|
D044 |
|
50.4 |
70 |
300 |
98 |
88 |
150 |
60 |
240 |
84 |
75 |
|
125 |
KW |
— Maximum Power Input |
LRA |
— Locked Rotor Amps |
MTA |
— Must Trip Amps |
MWA |
— Minimum Wire Amps Complies with NEC Section |
|
430-22 |
RLA |
— Rated Load Amps |
Supply Range — Units are suitable for use on electrical systems
where voltage supplied to the unit terminals is not below or above the listed range limits
NOTES:
1 Control voltage is 115 v for all units
2 |
Part-winding start all |
200-, 230-volt |
06E |
|
and |
07E units; |
460-, |
||||||
|
575-volt 06EW044 and 07ED044 units |
|
|
|
|
|
|
|
|
||||
|
Across-the-line start: |
all 460-, 575-volt |
units |
except |
06EW044 |
||||||||
|
and 07ED044. |
|
|
|
|
|
|
|
|
|
|
|
|
3. Factory |
wiring |
is in |
compliance with National |
Electrical |
Code |
||||||||
|
(NEC) |
Field |
wiring |
must |
comply |
with |
|
NEC |
and |
applicable |
|||
|
local codes Maximum incoming wire |
size |
to |
control |
center |
||||||||
|
terminal block is 250 MCM |
|
|
|
|
|
|
|
|
|
|||
4 |
The 06E compressor |
unit |
electrical |
data |
shown |
in |
the |
table |
|||||
|
does not apply to 06E compressors |
used |
as |
an |
integral part |
of |
|||||||
|
other Carrier equipment Refer to |
the |
electrical |
data |
for |
the |
|||||||
|
particular application |
|
|
|
|
|
|
|
|
|
|
-> 5 Units for use on 575 volts are available on special order
(Continued from page 1.)
suction line so compressor suction valve may be moved aside for access to suction strainer.
A solenoid valve is necessary for single pump out control used on 06E and 07E units. Install the valve (field supplied) in the liquid line, just before the expansion valve. A filter-drier of adequate size should be installed in liquid line between con denser and solenoid valve.
Pressure relief valve located on side of con denser will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from valve to outdoors.
Refer to Carrier System Design Manual for standard piping techniques.
Eield wiring must comply with local and national codes. See Table 2.
Install a branch circuit fused disconnect of adequate size to handle starting current. The disconnect must be within sight of the unit and readily accessible, in compliance with National Electrical Code (NEC), Section 440—14.
Line power is brought into control center thru indicated opening. Connect line power supply to
terminal block TB1; connect power leads to terminals LI, L2 and L3. Connect control circuit power supply (115 volts) to terminals 1 and 15 on terminal block TB2. Refer to Eig. 4.
Wiring connections for field-supplied equip ment are shown on diagram attached to unit (or in wiring diagram booklet).
Discharge line limit thermostat supplied with 06EV,W compressor units is installed on discharge line as close to compressor as possible.
1. Place mounting plate on discharge line and solder in place.
2. Easten the thermostat to plate with screws supplied.
3.Cover switch with insulation and secure insula tion at each end with straps.
4.Connect thermostat in series with Ml and M2 overloads, between terminals 2 and 4 on termi nal block TB2.
|
ACCESSORIES |
PACKAGE NUMBER |
DESCRIPTION |
07EA900021 |
Control Circuit Transformer |
07EA900061 |
Gage Panel |
1276
REFRIGERANT CHARGING
Evacuate, Dehydrate and Leak Test the entire refrigerant system by methods described in Carrier Standard Service Techniques Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass method to charge system. See Section 1-8 of Service Tech niques Manual for details.
CHARGE THE SYSTEM to a clear sight glass while holding saturated condensing pressure constant at 125 F (air-cooled systems) or 105 F (water-cooled systems) Add additional refrigerant to fill con denser subcooler coils.
07E Condensing Units - After clear sight glass is obtained, add charge until liquid refrigerant reaches condenser liquid level test cock.
06E Compressor Units — See condenser data for additional charge required to fill subcooler.
All Units — Stamp type of refrigerant and amount of charge on unit informative plate
Crankcase heater should be energized a mini mum of 24 hours before starting unit.
Check to see that oil level is approximately 1/3 up on the compressor sight glass.
Open water supply valve and allow water to |
|
|
reach condenser. (Turn condenser fan on when the |
|
|
compressor unit is applied with air-cooled con |
|
|
denser.) |
|
|
Backseat the compressor suction |
and discharge |
là |
shutoff valves, open liquid line valve at receiver. |
|
|
Start evaporator fan or chilled water pump. |
|
|
Start Compressor — Push the |
control circuit |
|
START-STOP-RESET switch to “Start.” The timer motor starts immediately. Depending on the posi tion of the timer, the compressor start is delayed for 12 seconds to approximately 8 minutes. Check oil pressure after compressor has run a few minutes, the pressure should be 12—18 psi above the suction pressure After about 20 minutes of operation, stop the compressor. Allow it to be idle for about 5 minutes, then observe the oil level in the sight glass. If the oil level is below the bottom of the sight glass, refer to the Carrier Standard Service Techniques Manual, Chapter 1, Section 1-11, for adding oil. The proper oil level for the 06E compressor is approximately 1/3 up on sight glass.
CONTROL POWER TERMINAL STRIP (TBg) |
MAIN POWER |
MAIN POWER |
EQUIPMENT GROUND |
|
INLET, |
TERMINAL |
'CONNECTION |
GROUND SCREW |
|
BLOCK (TB|) |
|
|
|
|
|
START-STOP-RESET |
|
|
|
SWITCH |
|
|
|
CONTROL CIRCUIT |
|
|
|
FUSE(S) |
|
|
COMPRESSOR |
(2 ON 50-Hz UNITS) |
|
|
CONTACTOR |
CONTROL RELAYS |
|
|
|
SENSOR MODULE |
|
|
OUTLET FOR |
|
|
WIRING TO |
|
(SOLID STATE |
|
|
|
|
|
COMPRESSOR |
|
COMPRESSOR MOTOR |
|
|
06E |
PROTECTION) |
|
|
07E |
|
|
|
|
HIGH PRESSURE |
|
|
|
SWITCH |
|
|
|
LOW PRESSURE |
|
|
|
SWITCH |
|
|
|
TIMER MOTOR |
|
|
|
(4-FUNCTION TIMER) |
|
|
|
|
|
|
COMPRESSOR |
|
|
|
CONTACTOR |
OIL PRESSURE |
|
|
(PART-WIND) |
SAFETY SWITCH |
|
|
|
ACCESSORY TRANSFORMER |
MAIN POWER |
(60-Hz UNITS ONLY) |
CIRCUIT BREAKER |
|
Fig. 4 — Control Center — 06E and 07E |
1276 |
4 |
Timer Functions (See Fig. 5 — Tinier Cycle)
1. Switch A (contacts A-Al and A-A2) provides Time Guard® function. Start of compressor is delayed approximately 5.5 minutes after shut off. The minimum time between starts of compressor is 8 minutes.
2.Switch B (contacts B1 and B—B2) starts compressor and de-energizes the crankcase heater. These contacts also provide one-second time delay for part-winding start.
3.Switch E (contacts E—El) provides approxi mately 40-second bypass of oil-pressure switch (OPS) at start-up. Compressor will shut off if sufficient oil pressure does not build up.
4.Switch D (contacts D—Dl) bypasses the lowpressure switch (EPS) for 2.5 minutes at start up for winter start control.
(BLACK DENOTES CLOSED CONTACTS) |
TIMER POSITION DURING |
0 MIN OR |
UNIT OPERATION- |
|
|
8 MIN |
|
»TT?*
-'E-El-
40 SEC +5
2-6 SEC
-xA- |
--- |
150 SEC |
Fig. 5 — Timer Cycle
PROTECTION DEVICES
High-Pressure Switch — Check by throttling con denser water or blocking air flow on air-cooled units, allowing head pressure to rise gradually. Check discharge pressure constantly throughout procedure. Compressor should shut off within 10 psi of values shown in Table 1.
Low-Pressure Switch — Check by slowly closing suction shutoff valve or by completely closing liquid line shutoff valve. A decrease of suction pressure will follow. Compressor should shut off within 4 psi of values shown in Table 1.
Oil Pressure Switch (OPS) protects against damage from loss of oil and failure of pressure buildup during start-up. Switch time delay (approximately 35 seconds) is derived from being properly wired to the ambient and voltage insensitive Time Guard timer. If OPS locks out unit, d eterm in e a n d c o rre ct th e ca u se (such as loss of compressor oil or flooded compressor) b efo re re sta rtin g u n it Restart by pushing the control circuit switch on unit control box to “Stop” then to “Reset.” Failure to correct the cause of the OPS lockout will constitute abuse.
E q u ip m e n t fa ilu re d u e to a b u se is n o t co v ere d b y
th e W a rra n ty .
Time Guard Control protects compressor against short cycling. See Start Compressor.
Crankcase Heater prevents absorption of liquid refrigerant by oil in crankcase during brief or extended shutdown periods. Source of 115-volt power is the auxiliary control power, independent of the main unit power. This assures compressor protection even when main unit power disconnect switch is off.
N ev er |
o p en |
a n y sw itch |
o r d isc o n n ec t |
th a t |
w ill |
||||
d e - e n e rg ize |
th e |
cra n k ca s e |
h ea ter |
u n le ss |
u n it |
is |
|||
b ein g |
ser vic ed |
o r is |
to |
b e sh u t |
d o w n |
fo r |
a |
||
p ro lo n g ed |
p er io d |
A fte r |
a |
p ro lo n g ed |
sh u td o w n |
o r |
a |
||
se rvic e |
jo b , e n e rg ize |
th e |
cra n k ca s e |
h e a ter |
fo r |
2 4 |
h o u rs b efo re sta r tin g th e co m p resso r .
Compressor Motor Protection consists of 3 tem perature sensors embedded in motor windings and connected to a solid state module in unit control box.
When an overtemperature condition causes module to shut compressor off, push control circuit STOP switch. Investigate cause of compressor shut down and correct. After compressor cools, push control circuit START-RESET switch. Compressor will restart after Time Guard delay period.
SOLID STATE MODULE is checked by applying unit control voltage to terminals T1 and T2 (see label diagram), then checking for continuity across terminals Ml and M2. If no continuity between Ml and M2, check temperature sensor resistance using a volt-ohmmeter. If all sensors check below 95 ohms (180 F) and there is no continuity between module terminals Ml and M2, replace module.
C A U T I O N : |
D o |
n o t u se |
a b a tte ry |
p o w e red |
te st |
la m p to |
ch ec k |
se n so r s |
E x ce ssiv e |
c u r ren t |
ca n |
ca u se d a m a g e |
|
|
|
|
If one sensor fails, it can be jumpered out of the circuit with a 75 ohm, or higher, resistor (rated at 2 watts or higher) across the proper sensor terminal and common terminal. If a short to ground in sensor circuit is indicated, replace compressor motor.
Capacity Control Valve(s) is controlled by suction pressure and actuated by discharge pressure. Each valve controls 2 cylinders. On start-up, controlled cylinders do not load up until differential between suction and discharge pressure is 10 psi (see Fig. 6).
D o |
|
n o t u se |
a u to m a tic p u m p d o w n |
co n tro l |
o n |
|
0 6 E , |
0 |
7 E u n its |
e q u ip p ed w ith |
u n lo a d er |
va lve s . |
U se |
sin g le |
|
p u m p o u t |
o r so le n o id |
d ro p (m in im u m |
p ro |
|
te ctio n ) |
c o n tr o l |
|
|
|
|
CONTROL SET POINT (cylinder load point) is adjustable from 0 psig to 85 psig. Pressure differ ential between cylinder load-up point and cylinder unload point is adjustable from 6 psi to 22 psi.