York P2DHX16F12001, P3DHX12F08001, P4LBX20F19001, P2LBX16F14501 User Manual

INSTALLATION
MANUAL
CONTENTS
OIL-FIRED WARM AIR
FURNACE
P3DHX12F08001 P2DHX16F12001
(Downflow or Horizontal Models)
P2LBX16F14501 P4LBX20F19001
HEAT LOSS....................................................................2
LOCATION OF UNIT ......................................................2
AIR CONDITIONING.......................................................4
COMBUSTION AIR......................................................... 4
CHIMNEY VENTING....................................................... 4
OIL TANK........................................................................6
PIPING INSTALLATION................................................. 6
ELECTRICAL CONNECTIONS ......................................6
CIRCULATING AIR BLOWER........................................ 7
OIL BURNER..................................................................8
FURNACE INSTALLATION SET-UP.............................9
MAINTENANCE AND SERVICE...................................10
OPERATING INSTRUCTIONS .....................................10
TABLE A-1: BECKETT OIL BURNER SET-UP ...........11
TABLE A-2: DIRECT DRIVE BLOWER SET-UP .........12
TABLE A-3: BELT DRIVE BLOWER SET-UP .............12
TABLE A-4: DIRECT DRIVE BLOWER
CHARACTERISTICS....................................................13
TABLE A-5: BELT DRIVE BLOWER
CHARACTERISTICS....................................................13
GENERAL DIMENSIONS - P2LBX16F14501...............14
GENERAL DIMENSIONS - P4LBX20F19001...............14
GENERAL DIMENSIONS - P4LBX20F19001...............15
GENERAL DIMENSIONS - P3DHX12F08001.............. 15
GENERAL DIMENSIONS - P3DHX12F08001.............. 16
GENERAL DIMENSIONS - P2DHX16F12001.............. 16
GENERAL DIMENSIONS - P2DHX16F12001.............. 17
WIRING DIAGRAM: MODEL P3DHX12F08001...........18
WIRING DIAGRAM: MODEL P2DHX16F12001...........18
WIRING DIAGRAM: MODEL P2LBX16F14501...........19
WIRING DIAGRAM: MODEL P4LBX20F19001...........19
R7184 DETAILED SEQUENCE OF OPERATION........ 20
R7184 LED DIAGNOSTIC LIGHT.................................22
Table C-1: Cad Cell Resistance................................. 22
R8184N NOTES............................................................22
TABLE C-2: R7184 TROUBLESHOOTING.................23
TABLE C-3: SYSTEM AND GENERAL
TROUBLESHOOTING.................................................. 25
P4LBX20F19001 ASSEMBLY NOTES.........................28
P3DHX SERIES DOWNFLOW CONFIGURATION
NOTES.......................................................................... 28
P3DHX12F08001 VESTIBULE KIT...............................29
REPAIR PART LIST – P3DHX12F08001A................... 30
REPAIR PART LIST – P2DHX16F12001A................... 31
REPAIR PART LIST – P2LBX16F14501A...................32
REPAIR PART LIST – P4LB SERIES..........................33
REPLACEMENT PART CONTACT INFORMATION.... 34
(Lowboy Models)
Read this manual completely before beginning installation. Important: These instructions must be kept with the furnace for future reference.
1
IMPROPER INSTALLATION MAY CRE­ATE A CONDITION WHERE THE OP­ERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUST­MENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CON­SULT A QUALIFIED INSTALLER, SER­VICE AGENCY OR THE FUEL SUP­PLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THESE INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO: BUILDING, ELECTRICAL AND MECHANICAL CODES.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be cre­ated. Never store items such as the fol­lowing on, near or in contact with the furnace:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean­ers or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers, gasoline, kero­sene, cigarette lighter fluid, dry cleaning fluids, or other volatile flu­ids.
3. Paint thinners or other painting ma­terials and compounds.
4. Paper bags, boxes, or other paper or cardboard products.
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
DO NOT USE GASOLINE, CRANK­CASE OIL, OR ANY OTHER OIL CONTAINING GASOLINE AS A FUEL FOR THIS FURNACE.
INTRODUCTION
Please read these instructions com­pletely and carefully before installing and operating the furnace.
The furnace must be installed and set up by a qualified contractor.
Model P3DHX12F08001 is an oil fired
forced air multi-positional furnace, with an output capacity range of 60,000 BTU/Hr. to 90,000 BTU/Hr. Model
P2DHX16F12001 is an oil fired forced air
multi-positional furnace, with an output capacity range of 91,000 BTU/Hr. to 128,000 BTU/Hr. These models may be installed in the down-flow position, as well as both horizontal positions.
Model P2LBX16F14501 is a rear-breech
lowboy model with an output range of 130,000 to 143,000 BTUH. Model
P4LBX20F19001 is a rear-breech low-
boy model with an output range of 168,000 to 188,000 BTUH.
All models are listed with the Canadian Standards Association, (CSA), and com-
ply with the standards of both the United States and Canada for use with No. 1 (Stove) and No. 2 (Furnace) Oil.
In the United States, the installation of the furnace and related equipment shall be installed in accordance with the regu-
lations of NFPA No. 31, Installation of Oil Burning Equipment, as well as in accor-
dance with local codes.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of
CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in
accordance with local codes.
When installation or application ques­tions arise, regulations prescribed in the National Codes and Local Regulations take precedence over the general in­structions provided with this installation manual. When in doubt, please consult your local authorities.
All P*DHX models are shipped assem­bled, pre-wired, ready for down-flow op­eration. P*DHX furnace models are air conditioning ready. The furnace should be carefully inspected for damage when being unpacked.
The P2LBX16F14501 model is shipped assembled, pre-wired, and ready for lowboy furnace applications. The P2LBX16F14501 model is air condition­ing ready.
The P4LBX20F19001 is shipped in two pieces, a furnace section and a blower section, and must be assembled at the installation site. Some field wiring is re­quired. The P4LBX20F19001 is shipped as a heating only furnace; however, air conditioning may be added with the addi­tion of field-installed controls.
HEAT LOSS
To determine the correct furnace and firing rate for an application, it is neces­sary to calculate the maximum hourly heat loss of the building based on local design conditions. In new construction, the heat loss should be calculated on a room-by-room basis to enable proper sizing of the trunk and branch ductwork. In retrofit applications, a building shell (overall) heat loss calculation may be used.
In the United States, Manual J. "Load Calculation Conditioning Contractors of America, (ACCA), describes a suitable procedure for calculating the maximum hourly heat loss.
In Canada, the maximum hourly heat loss may be calculated in accordance with the procedures described in the manuals of the Heating, Refrigeration and Air Conditioning Institute (HRAI), or by other method prescribed by authori­ties having jurisdiction that are suitable for local conditions.
" published by the Air
titled,
LOCATION OF UNIT
The furnace should be located such that the flue connection to the chimney is short, direct and consists of as few el­bows as possible. When possible, the unit should be centralized with respect to the supply and return air ductwork. A central location minimizes the trunk duct sizing.
Minimum installation clearances are listed in Table 1.
NOTE: The recommended installation
clearances do not necessarily take into consideration the clearances necessary to replace the air filter or perform other routine maintenance.
2
Table 1: Clearance to Combustibles
Furnace P2LBX P3DHX12F08001 P2DHX16F12001
Location Upflow Downflow Horizontal Downflow Horizontal
Top 3 in. 0 in. 6 in. 0 in. 3 in.
Bottom 0 in. 0 in. 1 in. 1 in. 1 in.
S/A
Plenum
0 in. 1 in. 1 in. 1 in. 3 in.
Rear 1 in.1 1 in. 1 in. 1 in. 1 in
Sides 6 in.2 1 in. 1 in. 1 in. 0 in.
Front 24 in. 6 in.1 24 in. 16 in.1 24 in.
Flue Pipe 9 in.3 9 in.3 9 in.3 9 in.3 9 in.3
Enclosure Standard Closet - - - Closet Alcove
1 24 inches is required for servicing.
2
18 inches is required on one side as service access to rear.
3
18 inches required in some U.S. jurisdictions
DOWN-FLOW INSTALLATION
All P*DHX furnace models have been assembled for installation in the down­flow position. Maintain all clearances to combustibles as outlined in Table 1. P*DHX models have available sub-bases for installations on combustible floors. The sub-bases provide a means of effec­tively mating the supply air plenum with the furnace, and providing the necessary one-inch clearance to combustibles around the supply air plenum.
Fig. 1: Typical Suspended Application
HORIZONTAL INSTALLATION
P*DHX furnaces models may be in­stalled in either of the horizontal posi­tions; warm air discharging left or warm air-discharging right by following these steps:
1. Rotate the furnace 90° to the de­sired position.
2. Remove the three nut and washer sets fastening the oil burner assem­bly to the furnace. Rotate the oil burner assembly to be in the normal upright position.
3. Re-align the oil burner assembly to the combustion chamber (fire-pot), and then secure into place with the three nut and washer sets.
IMPORTANT: Model P3DHX12F08001
has an auxiliary limit control that must be in the upper position. Be sure that the auxiliary limit control is above the oil
burner assembly.
NON-SUSPENDED INSTALLATION
Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requires a clearance of 1 inch. This can be done by using a non­combustible material such as one inch thick channel iron or similar material. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. Use shims made of noncombustible material.
3
SUSPENDED INSTALLATION
Refer to Figure 1. Maintain clearances to combustibles as outlined in Table 1. The furnace may be suspended by field fabri­cating a cradle of angle iron and threaded rod. Secure the furnace with 2 inch minimum slotted angle or equiva­lent, as shown in Figure 1. The furnace must be supported in such a way as to not allow twisting or sagging of the cabi­net. Position the supports so as to not interfere with accessing the burner and blower compartments. Suggestion; as a measure to prevent fuel oil from accumu­lating in locations other than the fire pot, as could be the case in the event of noz­zle drip, install the furnace with an ap­proximate 2 degree slope from the oil burner casing towards the fire pot.
AIR CONDITIONING
If the furnace is used in conjunction with air conditioning, the furnace shall be installed in parallel with or upstream from the evaporator coil to avoid condensation in the heat exchanger. In a parallel installation, the dampers or air controlling means must prevent chilled air from en­tering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifically approved for such service.
Generally, a six-inch clearance between the air conditioning evaporator coil and the heat exchanger will provide adequate airflow through the evaporator coil.
The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evaporator coil. Re­fer to Appendix B for recommended wir­ing and electrical connections of the air conditioning controls.
COMBUSTION AIR
When a furnace is installed in the full basement of a typical frame or brick house, infiltration is normally adequate to provide air for combustion and draft op­eration. If the furnace is installed in a closet or utility room, two (2) ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bathroom). One opening shall be located 6" from the top and bottom of the enclosure at the front of the furnace. For furnaces located in buildings of unusually tight construc-
4
tion, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communi­cating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. Size all of the open­ings and associated ductwork by the standards provided in the latest Oil In­stallation Code editions; NFPA 31 in the United States, CAN/CSA B139 in Can­ada. Take all fuel burning appliances in the area into consideration when calcu­lating combustion and ventilation air re­quirements.
The Model CAS-2B-90E Furnace Boot manufactured by Field Controls, Inc. may be used with the furnace to obtain com­bustion air directly from outdoors. Use of this device does not alter the need for ventilation air; however, it does provide a good direct source of combustion air and is connected directly to the oil burner.
CHIMNEY VENTING
The chimney must be sized correctly and be in good repair. If the chimney is over­sized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.
If the chimney serves the P3DHX12F08001 furnace only, the vent should be sized at 4-inch minimum, 5­inch maximum. If the chimney serves the P2DHX16F12001 or P2LBX16F14501 furnace only, the vent should be sized at 4-inch minimum, 6-inch maximum. If the chimney serves the P4LBX20F19001 furnace only, the vent should be sized at 5-inch minimum, 7-inch maximum. The data provided in Table 3 is based on dedicated venting. If the furnace is to be co-vented with other appliances, refer to
NFPA 211, Standard for Chimneys, Fire-
places, Vents, and Solid Fuel-Burning Appliances, NFPA 31, Standard for the Installation of Oil Burning Equipment or CAN/CSA B139, Installation Code For Oil Burning Equipment for correct sizing
information.
NOTE: This furnace is approved for use with L-Vent.
NOTE: Maximum temperature for L­Vent is 575°F (300°C).
IMPORTANT: The chimney must be
capable of providing sufficient draft at all times for the safe removal of the prod­ucts of combustion.
The chimney should be tested under “winter” conditions; doors and windows closed, all other fossil fuel burning appli­ances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot over­come the competition for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re­evaluate the availability of combustion and ventilation air, and take corrective action.
The flue pipe should be as short as pos­sible with horizontal pipes sloping up­ward toward the chimney at a rate of one-quarter inch to the foot. The flue pipe should not be smaller in cross sec­tional area than the flue collar on the furnace. The flue pipe may be reduced in size to fit a smaller diameter chimney with the use of a tapered reducer fitting at the chimney inlet. The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regula­tions, to the requirements of the National Building Code.
See Figure 2 and Table 2 for common chimney problems and their remedies.
THE FURNACE MUST BE CON­NECTED TO A FLUE HAVING SUFFI­CIENT DRAFT AT ALL TIMES TO EN­SURE SAFE AND PROPER OPERA­TION OF THE APPLIANCE.
The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deteriora­tion during the annual inspection and servicing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been in­stalled. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment. In Canada, refer to the latest edition of CAN/CSA B139 for rules gov­erning the installation of oil burning equipment.
Fig. 2: Common Chimney Problems
Table 2: Common Chimney Problems
Refer to Figure 2
Key Trouble Diagnostic Remedy
Top of chimney lower than sur-
A
rounding ob­jects
Chimney Cap
B
or ventilator.
Coping restricts
C
opening.
Observation
Observation Remove
Observation
Extend chimney above all sur­rounding ob­jects within 30 feet.
Make opening as large as inside of chim­ney.
Obstruction in chimney
D
Joist protruding
E
into chimney.
Break in chim-
F
ney lining.
Collection of soot at narrow
G
space in flue opening.
H Offset
Two or more
I
openings to the same chimney.
Loose-seated
J
pipe in flue opening.
Smoke pipe
K
extends into chimney.
Failure to ex­tend the length
L
of flue partition to the floor.
Loose-fitted
M
clean-out door.
DRAFT REGULATOR CONTROL
This device is used in conjunction with conventional chimney venting. This control (or draft regulator) automatically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, must be installed within the same room or enclosure as the furnace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters from the furnace breeching and installed in accordance to the instructions supplied with the regulator.
Can be found by light and mirror reflecting conditions in chimney.
Lowering a light on an extension cord.
Smoke test ­build smudge fire blocking off other opening, watching for smoke to es­cape.
Lower light on extension cord.
Lower light on extension cord.
Found by in­spection from basement.
Smoke test.
Measurement of pipe from within or obser­vation of pipe by means of a lowered light.
By inspection or smoke test.
Smoke test.
Use weight to break and dis­lodge.
Must be han­dled by compe­tent masonry contractor.
Must be han­dled by compe­tent masonry contractor.
Clean out with weighted brush or bag of loose gravel on end of line.
Change to straight or to long offset.
The least im­portant opening must be closed, using some other chimney flue.
Leaks should be eliminated by cementing all pipe open­ings.
Length of pipe must be re­duced to allow end of pipe to be flush with inside of tile.
Extend partition to floor level.
Close all leaks with cement.
5
Table 3: Minimum Chimney Base
Temperatures (°F)
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance < R6
0.50 300 400 535 725
0.65 275 340 430 535
0.75 260 320 380 475
0.85 250 300 355 430
1.00 245 300 355 430
1.10 245 290 345 400
1.20 240 275 320 365
1.50 240 275 320 365
1.65 235 270 300 345
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance > R6
0.50 185 200 220 250
0.65 175 185 205 220
0.75 175 185 195 210
0.85 165 185 195 205
1.00 165 185 195 205
1.10 165 185 195 205
1.20 165 180 190 200
1.50 165 175 185 195
1.65 165 175 180 190
< -
less than
, > -
greater than
OIL TANK
Oil storage tanks must be selected and installed in compliance with applicable codes; in the United States, NFPA 31,
Standard for the Installation of Oil Burn­ing Equipment, Chapter 2. and in Can- ada, CAN/CSA-B139, Installation Code for Oil Burning Equipment, Section 6.
Observe all local codes and by-laws.
In general, the oil tank must be properly supported and remain stable in both empty and full condition. The oil tank must be fitted with vent and supply pipes to the outdoors. Refer to the above­mentioned codes for sizing. The vent pipe must be no less than 1¼ inches I.P.S., and terminate with an appropriate vent cap in a location where it will not be blocked. The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery.
If located indoors, the tank should nor­mally be in the lowest level, (cellar, basement, etc.). It must be equipped with a shut-off valve at the tank outlet used for the oil supply. The oil tank must be located as to not block the furnace / room exit pathway. Observe all clear­ances specified in the above-mentioned codes.
PIPING INSTALLATION
In the United States, NFPA 31, Standard for the Installation of Oil Burning Equip­ment, Chapter 2.
In Canada, the entire fuel system should be installed in accordance with the re­quirements of CAN/CSA B139, and local regulations. Use only approved fuel oil tanks piping, fittings and oil filters.
Ensure that all fittings used in a copper oil line system are high quality flare fit­tings. Do not use compression fittings.
Do not use Teflon tape on any fittings.
Pressurized or gravity feed installations must not exceed 3 PSIG. Pressures greater than 10 PSIG may cause dam­age to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds 11½ feet, it may be necessary to use a pressure-regulating device ap­proved for this purpose.
The furnace may be installed with a one­pipe system with gravity feed or lift. The maximum allowable lift on a single line system is 8 feet. Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting, bend and compo­nent in the line. In general, keep single line systems short as possible. 2-stage oil pumps are not available for either the P*HMX or P*LBX furnaces. The following chart shows the allowable line lengths (horizontal + vertical) for single and two­line oil piping systems. All distances are in feet.
Table 4: Oil Lines
Copper Tubing Oil Line Length (Feet)
Lift
(Feet)
0 53 100 68 100
1 49 100 65 100
2 45 100 63 100
3 41 100 60 100
4 37 100 58 100
Single-Pipe Two-Pipe
OD
½” OD
OD
½” OD
Continue
5 33 100 55 100
6 29 100 53 100
7 25 99 50 100
8 21 83 48 100
9 17 68 45 100
10 13 52 42 100
12 - - - - - - 37 100
14 - - - - - - 32 100
16 - - - - - - 27 100
18 - - - - - - 22 88
In retrofit applications, where an existing oil line system is in place, a vacuum check will help determine the efficacy of the existing oil line system The vacuum in a system should not exceed 6” Hg. for a single pipe system, nor 12” Hg. for a two-pipe system.
NOTE: The oil burner requires the use of
a bypass plug when converting from single-pipe to two-pipe oil piping sys­tems. See burner manufacturer’s instruc­tions.
All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. For best results, in­stall the oil filter as close to the burner as possible. When using an indoor oil tank, the oil filter may be installed at the tank downstream from the shut-off valve. If firing the furnace under the 0.65 gph rate, a 7 to 10 micron line filter should be installed as close to the oil burner as possible.
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association (CSA). All models except for the P4LBX20F19001 are fac­tory wired and require minimal field wir­ing. The P4LBX20F19001 model is pre­wired except for the wiring connections to the blower motor. The wires from the furnace section are routed through the grommet in the blower section blower division panel, and then connected to the blower motor. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations. In Can­ada, all field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail.
The furnace should be wired to a sepa­rate and dedicated circuit in the main electrical panel; however, accessory equipment such as electronic air clean-
6
ers and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. The service switch is nec­essary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device.
The power requirements for all models:
120 VAC, 1 , 60 Hz.
Maximum fuse size for the P*DHX mod­els and P2LBX16F14501 model: 15 amps. Maximum fuse size for the P4LBX20F19001 model: 20 amps.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the furnace circuit. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by expo­sure to high voltage from the auto­generating windings of the direct drive motor.
Thermostat wiring connections and air conditioning contactor low voltage con­nections are shown in the wiring dia­grams. Some micro-electronic thermo­stats require additional controls and wir­ing. Refer to the thermostat manufac­turer's instructions.
The thermostat should be located ap­proximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room tem­peratures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
Normal heat anticipator setting: for the P*LBX models is 0.1 A. Normal heat anticipator setting: for the P*DHX models is 0.4 A .For more precise adjustment, the heat anticipator may be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To re­duce the risk of damaging the heat an­ticipator, do not measure circuit without first removing one of the two wires first.
To determine the heating circuit amper­age draw:
1. Disconnect one of the “R” or “W” wires from the thermostat terminal.
2. Connect an ammeter between the wire and the thermostat terminal to which it was attached.
3. Note the amperage reading when the heating contacts are closed.
HEAT
(System switch must be on “
” if
so equipped.
4. Re-connect the thermostat wire. If the thermostat is serving a combina­tion heating and air conditioning sys­tem, pay particular attention to polarity.
5. When the thermostat is reconnected and re-plumbed, adjust the heat an­ticipator setting to match the ob­served amperage reading.
CIRCULATING AIR BLOWER
Both P*DHX and the P2LBX16F14501 furnace models are equipped with a di­rect drive blower system. Direct drive blower speed adjustments are not nor­mally required in properly sized extended plenum duct systems. The motor RPM and air CFM delivery will vary automati­cally to accommodate conditions within the usual range of external static pres­sures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reason­able system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over- amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem.
Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagram in Appendix B or the wir­ing diagram label affixed to the furnace.
THE NEUTRAL WIRE (normally the white wire) IS NEVER MOVED TO AD­JUST THE BLOWER SPEED.
DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DES­IGNATED NEUTRAL TERMINAL.
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommo­dating both wires on a single motor tap. It is also acceptable to connect the se­lected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to se­cure the wire nut and wires with a few wraps of electricians tape.
If the joining of the blower speed wiring is done in the furnace junction box, tape off both ends of the unused wire.
The P4LBX20F19001 furnace model is equipped with a belt drive blower sys­tem. The blower speed (RPM) and resul­tant airflow can be varied by adjusting the variable speed motor pulley.
DISCONNECT THE POWER SUPPLY TO THE FURNACE BEFORE OPEN­ING THE BLOWER ACCESS DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURE TO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECT­EDLY, CREATING A RISK OF DEATH OR PERSONAL INJURY.
Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformers. The unused motor taps auto-generate sufficiently high volt­ages to damage accessory equip­ment.
Do not start the burner or blower fan unless the blower access door is se­curely in place.
7
OIL BURNER
P*LBX furnaces are equipped with Beckett AF Series oil burners with the Beckett CleanCut pump and R7184B oil primary control. P*DHX furnaces are equipped with Beckett AF Series oil burners with the R8184N oil primary con­trol. The oil burner must align properly with the cerafelt fiber chamber (firepot). The cerafelt fiber chamber is initially quite soft, but hardens and becomes quite brittle after the first firing. The fire­pot is held in place by a retaining bracket; however, it is possible for the firepot to shift if subjected to rough han­dling during transit.
BEFORE OPERATING THE FUR­NACE CHECK BURNER ALIGNMENT WITH COMBUSTION CHAMBER. THE END CONE OF THE AIR TUBE MUST BE CENTRED TO THE AC­COMODATING RING PROVIDED IN THE DESIGN OF THE COMBUSTION CHAMBER. ADJUST ALIGNMENT AS NECESSARY BEFORE THE FIRST FIRING.
OIL BURNER NOZZLES
All furnace models are certified for multi­ple firing rates. Choose the firing rate that most closely matches the calculated heat loss of the building. Models, firing rates and nozzles are listed in Appendix A: AF Burner Set-Up.
Fig. 4: Horizontal Smoke Test Port Location Fig. 5: Vertical Smoke Test Port Location
BURNER ELECTRODES
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation. The electrode tips should be adjusted to a gap of 5/32”, 1/16” ahead of the nozzle, 5/16” above the centerline of the nozzle. The “Z” dimension (front edge of the burner head to the front face of the nozzle is 1-1/8 inches.
Electrode positioning should be checked before the first firing of the furnace.
The electrode porcelains should be free of cracks, the electrode tips should be tapered and free of burrs, and the con­tact rods must be clean and be in firm contact with the ignition transformer con­tact springs. The electrodes must not come into contact with the burner head.
OIL BURNER SET-UP
The burner air supply is adjusted to
maintain the fuel to air ratio to obtain
ideal combustion conditions. A lack of air causes "soft" and "sooty" flames, result­ing in soot build-up throughout the heat exchanger passages. Excess combus­tion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency.
PREPARATIONS:
Drill a ¼” test port in the venting, ideally at least 2 flue pipe diameters away from the furnace breeching, if venting horizon­tally from the furnace, (typically P*LBX) or from the flue pipe elbow if venting vertically (typically P*DHX) before reach­ing the furnace. (see Figures 4 and 5).
The test port will allow flue gas samples to be taken and stack temperatures to be measured.
Before starting the burner, check the burner alignment with the combustion chamber (fire pot), check that the correct nozzle is tightened into place, and that the burner electrodes are properly posi­tioned.
The Beckett burner bulk air band should be closed, and the air shutter initial set­ting should be approximately 7.00.
Note A: Locate hole at least 6 inches on
the furnace side of the draft control.
Note B: Ideally, hole should be at least
12 inches from breeching or elbow.
PROCEDURE:
Start the burner and allow it to run at least ten minutes. Set the air shutter to give a good flame visually. The combus­tion air supply to the burner is controlled by adjusting the air shutter on the left side of the burner, and, if necessary, the bulk air band. To adjust, loosen the bolt on the movable shutter. Move the shutter gradually until a good flame (visually) has been achieved. Re-snug the bolt.
Check the initial draft setting as the fur­nace warms up. The draft may be meas­ured at the test port. The final breech draft should be - 0.02 inches w.c. to provide adequate over-fire draft.
8
Check the oil pump pressure. Standard operating pressure is 100 PSIG.
After reaching steady state, take a smoke test. If not indicating a trace, set the combustion air controls to provide a trace.
Typically, the CO
reading will range
2
from 11.5% to 13.5%.
After the air adjustments have been completed, and the air shutter or air ad­justment plate has been secured, re­check the breech draft and take another smoke test to ensure that the values have not changed.
SMOKE TEST NOTE:
If oily or yellow smoke spots are found on the smoke test filter paper, it is usu­ally a sign of unburned fuel. This indi­cates poor combustion. This type of problem may be caused by excess draft, excess air, or contaminated fuel. Do not ignore this indicator.
STACK TEMPERATURE:
Stack temperature will vary depending on fuel input, circulating air blower speed, and burner set up, etc. In gen­eral, stack temperature should typically range between 380°F to 550°F, assum­ing that the combustion air is approxi­mately room temperature (65°F - 70°F). In general, lower stack temperature indi­cates greater efficiency; however, ex­cessively low stack temperature can lead to condensation forming in the chimney and / or venting. Sulphur and similar contaminants in the fuel oil will mix with condensation to form acids. Acids and resultant chemical salts will cause rapid deterioration of the chimney and venting components, and may attack the fur­nace.
If the flue gases are below the range, it may be necessary to slow down the blower fan. If the flue gases are above the range, the blower fan may require speeding up. Stack temperature varies directly with the system temperature rise. System temperature rise is the difference between the furnace outlet temperature and furnace inlet temperature as meas­ured in the vicinity of the connection be­tween the plenum take-offs and the trunk ducts. Typical temperature rise values range between 70°F and 85°F.
If the venting from the furnace to the chimney is long, or exposed to cold am­bient temperatures, it may be necessary to use L-Vent as the vent connector to reduce stack temperature loss to prevent condensation. The venting should be inspected annually to ensure that it is intact.
9
FURNACE INSTALLATION SET-UP
The furnace must be set up as the final step in the installation.
A) The oil burner must be set up follow­ing the procedures outlined above.
B) The furnace should operate within a temperature rise of 85°F ±15°F. To de­termine the temperature rise, measure the supply air and return air tempera­tures when the furnace has reached steady state conditions. This is the point at which the supply air temperature stops increasing relative to the return air tem­perature. The furnace may have to run 10 to 15 minutes to reach steady state conditions. The measurements may be made with duct thermometers or thermo­couples used in conjunction with multi­meters with temperature measurement capabilities.
The return air should be measured at a point where the thermometer will be well within the air stream near the furnace return air inlet. Actual location is not par­ticularly critical; however, avoid locations where the temperature readings could be affected by humidifier bypass ducts, the inside radius of elbows, etc.
The supply air temperature should be measured at a point where the ther­mometer will be well within the air stream near the furnace supply air outlet. Usu­ally, the side mid-point of the supply air plenum take-off is ideal, providing it is out of the line of sight to the heat ex­changer. If the thermometer is within the line of sight of the heat exchanger, the supply air readings may be skewed by radiant heat from the heat exchanger. If the plenum take-off is unsuitable, the supply air temperature may be measured within the first 18 inches of the first seg­ment of supply air trunk duct.
If the temperature rise is outside the rec­ommended range, it may be adjusted on direct drive equipped units by selecting alternate circulation fan motor speeds, on belt drive equipped units by adjusting the variable speed motor pulley. If the temperature rise is too high, speed the fan up. If the temperature rise is too low, slow the fan down.
C) Keep in mind that the stack tem­perature varies directly with the tempera­ture rise. The higher the temperature rise, the higher the stack temperature will be, resulting in lower efficiency. The lower the temperature rise, the lower the stack temperature will be, which, in some cases, may allow condensation to form in the chimney and other vent parts.
D) Test the high limit control to ensure that it is operating correctly. For direct drive equipped units, this may be done by temporarily removing the circulator fan heating wire or neutral wire. For belt drive equipped units, temporarily remove the fan belt. Turn of electrical power to the furnace before working with the mo­tor wires or fan belt. Be sure to protect any removed wires from shorting out on metal furnace parts. If the high limit test is successful, shut off the electrical power to the furnace, restore the proper motor wiring. Finally, restore power to the furnace.
E) Adjust the “Fan Off” setting on the L6064A or L4064W fan limit controller. In most cases, the “Fan Off” temperature should be 90° to 100°F as indicated on the thermometer used to measure the supply air temperature. Once the “Fan Off” setting has been established, set the “Fan On” setting. In most cases, the “Fan On” setting should be approximately 30°F higher than the Fan Off” setting.
NOTE: The L4064W fan/limit controller has an auxiliary “fan on” function that activates when the thermostat is calling for heat. The controller is designed to start the circulating fan in 20 to 30 sec­onds. Adjust the “fan on” setting on the controller dial 30°F higher than the “fan off” setting even though the circulating fan will normally be started by the auxil­iary “fan on” function.
F) Operate the furnace through a minimum of three full heating cycles. During this time, check for fuel oil leaks, gross air leakage from the supply air ductwork, unusual noises originating anywhere within the heating system which may cause some concern or an­noyance to the home owner, etc.
G) Be sure that the homeowner is familiar with the furnace. The homeowner should be aware of the location of electrical circuit breaker or fuse, the location of any electrical switches controlling the furnace, the location of the oil tank shut-off valve and how to operate the valve. The home­owner should be informed where the oil tank gauge is located and how to read it.
It would be beneficial to review safety issues with the home owner, such as the danger of storing combustibles too close to the furnace, hanging anything on the furnace vent pipe, and especially the dangers of indiscriminately pressing the burner reset button.
IMPORTANT: Be sure that the home
owner knows where the burner reset switch is located, and is aware that the reset switch is not to be activated more than once without a thorough look for the cause of the problem, (lack of fuel, etc.). Be sure that the homeowner knows when to quit trying to start the furnace during these conditions and who to call for emergency service.
MAINTENANCE AND SERVICE
A: Routine Maintenance By Home Owner
Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation con­tractor, the most important routine ser­vice performed by the homeowner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced monthly. The fur­nace is factory equipped with a semi­permanent type filter. If the filter is dam­aged, replace with filters of the same size and type.
During the routine service, inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advice your service or installation con­tractor.
B: Annual Service By Contractor
A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Replace the clean-out yoke assemblies and clean-out covers.
Most circulating fan motors are perma­nently lubricated by the motor manufac­turer. These motors will have no oil ports. If the blower motor does contain oil ports, under normal operating condi­tions it will not require oiling for the first two years. Oil sparingly; a few drops in each oil port with SAE 20 non-detergent oil. Oiling is most easily done with a "tele-spout" oiler. This oiler has a long flexible plastic spout. DO NOT OVER­LUBRICATE. Excess oil may result in premature electric motor failure.
Inspect the blower fan. Clean it if neces­sary.
Oil Burner Maintenance: Follow the in­structions of the oil burner manufacturer. (See oil burner manufacturer's instruc­tions supplied with furnace). The oil burner nozzle should be replaced annu­ally. We recommend that the oil filter be changed on an annual basis.
The venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent pipe and fittings. The barometric draft regula­tor should open and close freely.
All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functional­ity. The fan control functions should be checked to ensure that all fan speeds are operating properly.
After the furnace warms sufficiently, the circulation fan will start.
The furnace will continue to run until the thermostat call for heat is satisfied.
Set the thermostat below room tempera­ture. The oil burner will stop.
The air circulation blower will continue to run until the furnace has cooled suffi­ciently.
To Shut Down Unit
Set the thermostat to the lowest possible setting. Set the manual switch (if in­stalled) in the Electrical Power Supply Line to "OFF".
NOTE: If the furnace is to be shut down
for an extended period of time, close the oil supply valve to the oil burner.
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE FUR­NACE IS FULL OF VAPOUR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. NEVER BURN GAR­BAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.
THE Combustion chamber (firepot) IS FRAGILE. use care when inspecting and cleaning this area.
The heat exchanger should be inspected periodically and cleaned if necessary. if
cleaning is necessary, SHUT OFF POWER TO THE FURNACE and re-
move the burner. Using a stiff brush with a wire handle, brush off scale and soot from inside the drum and flue pipe. To clean the heat exchanger radiator, re­move the covers on the front or inner front panel, and then loosen the brass nuts on the radiator clean-out yoke as­sembly. Do not remove the brass nuts. The yoke assembly, once loosened, may be removed to gain access to the heat exchanger outer radiator.
10
OPERATING INSTRUCTIONS
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply.
To Light Unit
Set the thermostat above room tempera­ture to call for heat. The burner will start. NOTE: If the furnace has been off for an extended period of time, it may be nec­essary to press the RESET button on the primary combustion control relay, (once only). If pressing the reset button does not start the furnace, refer to Appendix C, Troubleshooting.
TABLE A-1: BECKETT OIL BURNER SET-UP
FURNACE
MODEL
P3DHX12F08001
P2DHX16F12001
OUTPUT
BTU/Hr.
60,000 3 AF76BNHS 0.50 / 80°A 100 PSIG 0.50 GPH F3 1 3-3/8 in.
78,000 2 AF76BNHS 0.65 / 80°A 100 PSIG 0.65 GPH F3 1 3-3/8 in.
90,000 AF76BNHS 0.75 / 80°A 100 PSIG 0.75 GPH F3
91,000 AF76XN 0.75 / 80°A 100 PSIG 0.75 GPH F3 2-3/4 in.
101,000 AF76XN 0.85 / 80°A 100 PSIG 0.85 GPH F3 2-3/4 in.
117,000 2 AF76XN 1.00 / 60°A 100 PSIG 1.00 GPH F3 2-3/4 in.
128,000 AF76YB 1.10 / 70°A 100 PSIG 1.10 GPH F6 2-3/4 in.
BURNER
MODEL
BECKETT AF SERIES OIL BURNERS
NOZZLE
(Delavan)
PUMP
PRESSURE
FLOW
RATE
HEAD
1
3-3/8 in.
STATIC
PLATE
P2LBX16F14501
143,000
2
AF65YB 1.20 / 60°A 100 PSIG 1.20 GPH F6 2-3/4 in.
168,000 AF81WF 1.50 / 70°B 100 PSIG 1.50 GPH F16 2-3/4 in.
130,000 AF65YB 1.10 / 70°A 100 PSIG 1.10 GPH F6 2-3/4 in.
P4LBX20F19001
1
Used with ceramic insulator.
2
Factory supplied nozzle.
3
Requires a low firing rate baffle.
188,000
2
AF81WF 1.65 / 70°B 100 PSIG 1.65 GPH F16 2-3/4 in.
In the United States, the R. W. Beckett “AF” Burner may be equipped with Beckett’s “Inlet Air Shut-Off”, Beckett Part No. AF/A 5861, to increase efficiency. It reduces the amount of air passing through the oil burner, combustion chamber, breeching, etc. up the chimney between burner cycles.
NOTE: THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP.
11