TECHNICAL
GUIDE
ADD - ON COILS
FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS
MODELS: MC, PC, FC, HD, HC, UC 600 - 2000 CFM 1.5 - 5 TON COILS
HORIZONTAL |
FULL CASED |
DUCT |
MULTI-POSITION |
HD |
MC |
UPFLOW UNCASED
UC
UPFLOW/DOWNFLOW
FULL CASED
FC
|
UPFLOW |
HORIZONTAL CASED |
PARTIAL CASED |
HC |
PC |
258931-BTG-A-0606
DESCRIPTION
These cooling and heat pump coils are designed to be installed with UPG furnaces and to be matched with UPG cooling and heat pump outdoor units. All UPG coils utilize a TXV to provide our customers with the optimum performance and refrigerant control required for 13+ SEER systems. Coils can be ordered with a R22 TXV factory installed that can be easily converted to R410A by changing the bolton TXV.
“Flex-coils” are also available without a factory installed metering device. For added application flexibility a R22 or R410A TXV is installed, on “Flex-coils”, in the field to meet your refrigerant choice.
Upflow/Downflow Coils Full Cased and Partial Cased Coils – Designed for high-efficiency to match any system, full cased in the upflow or downflow and the partial cased in the upflow only application.
Multi-Position Coils - Designed for high-efficiency like the upflow/downflow coil but with the added flexibility that allows it to be installed any position, upflow, downflow, horizontal right or left. This coil can be easily applied to our furnace and modular air handler in any configuration.
Horizontal Duct Coils - Available for both cooling and heat pump dedicated horizontal, slab coil, applications. Field transition may be required.
Dedicated Horizontal Cased Coils – These coils are cooling only or heat pump approved for horizontal furnace or modular air handler applications. Unlike the horizontal duct coils these cased coils match the dimensions of the furnace or modular blower.
FEATURES
Thermal Expansion Valve - Provides flexibility to convert any coil to R22 or R410A refrigerant. A true bolt-on TXV, valve assembly and equalizer tube are bolt-on, no brazing required. TXV and sensing bulb are mounted inside the cased coil cabinet. (Must be field supplied for all “Flex-coils”)
MicroBlue™ Coated Fins - All coils are treated with a MicroBlue™ Hydrophilic coating to enhance the removal of condensate during the refrigeration cycle and reduce the possibility of water blow-off. The MicroBlue™ coating also reduces the growth of germ causing microbes.
All evaporator coil cabinets are thermally insulated with foil faced insulation to prevent sweating.
Internally Clean - All evaporator coils are factory leak-tested, dehydrated, sealed and shipped with a holding charge. The suction and liquid lines are sealed with rubber plugs, no cutting of connection stubs to attach line set.
Durable Finish Inside and Out - Coil casings are made of prepainted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. All internal metal parts are made of G90 pre-painted steel i.e. triangular plates, top plates, horizontal supports etc. (Coil header plates are non-painted due to the brazing process during production.)
Optimum Heat Transfer - Using the latest in heat transfer technology, staggered rows of copper tubes are mechanically expanded into aluminum fins to provide optimum air to surface contact for ample moisture removal as well as high performance ratings.
|
ACCESSORIES |
|
Visit us on the web at www.york.com for the most |
Refer to Price Manual for specific model numbers. |
|
up-to-date technical information. |
TXV Kits - Thermal expansion valve kits are available for “Flex-coil” |
|
Additional rating information can be found at |
applications and converting R22 to R410A refrigerant or as a service |
|
replacement. All TXV kits are non-braze, all connections are bolt-on |
||
www.ariprimenet.org. |
||
including the valve assembly and equalizer tube. (No orifice or any |
||
|
||
|
other metering device is to used in conjunction with the TXV). |
|
|
Coil Casing Without Coil – Coil casings are available in each |
|
|
width that can be installed with the furnace or modular air handler |
|
|
during initial installation. This option is available to allow the installer |
|
|
the flexibility to install the coil at a later date without duct modifica- |
|
|
tions. |
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
258931-BTG-A-0606
COOLING CAPACITY - Coil Only*
|
Rated |
Entering |
MBH @ Evaporator Temperature and Corresponding Pressure °F / PSIG |
||||
Model |
Air °F |
|
|
|
|
|
|
CFM |
35 / 61.5 |
|
40 / 68.5 |
45 / 76.0 |
50 / 84.0 |
||
|
(Wet Bulb) |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UPFLOW "A" TYPE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
72 |
25.3 |
|
23.1 |
20.6 |
17.9 |
|
|
|
|
|
|
|
|
FC18A |
675 |
67 |
23.4 |
|
21.1 |
18.7 |
16.1 |
PC18A |
|
|
|
|
|
|
|
62 |
19.2 |
|
12.0 |
18.7 |
12.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
15.6 |
|
13.5 |
11.3 |
8.8 |
|
|
|
|
|
|
|
|
|
|
72 |
28.1 |
|
25.7 |
22.9 |
19.9 |
|
|
|
|
|
|
|
|
FC18B |
850 |
67 |
26.0 |
|
23.5 |
20.8 |
17.9 |
PC18B |
|
|
|
|
|
|
|
62 |
21.3 |
|
18.9 |
16.4 |
13.7 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
17.3 |
|
15.0 |
12.6 |
9.8 |
|
|
|
|
|
|
|
|
|
|
72 |
35.6 |
|
32.5 |
29.0 |
25.2 |
|
|
|
|
|
|
|
|
FC24A |
675 |
67 |
32.9 |
|
29.7 |
26.3 |
22.7 |
PC24A |
|
|
|
|
|
|
|
62 |
27.0 |
|
23.9 |
20.7 |
17.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
21.9 |
|
19.0 |
15.9 |
12.4 |
|
|
|
|
|
|
|
|
|
|
72 |
35.6 |
|
32.5 |
29.0 |
25.2 |
|
|
|
|
|
|
|
|
FC24B |
850 |
67 |
32.9 |
|
29.7 |
26.3 |
22.7 |
PC24B |
|
|
|
|
|
|
|
62 |
27.0 |
|
23.9 |
20.7 |
17.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
21.9 |
|
19.0 |
15.9 |
12.4 |
|
|
|
|
|
|
|
|
FC30A |
|
72 |
38.9 |
|
35.4 |
31.6 |
27.6 |
|
|
|
|
|
|
|
|
PC30A |
1025 |
67 |
33.9 |
|
30.3 |
26.8 |
23.0 |
FC30B |
|
|
|
|
|
|
|
62 |
27.3 |
|
23.7 |
22.5 |
18.0 |
||
|
|
||||||
PC30B |
|
|
|
|
|
|
|
|
57 |
22.6 |
|
20.1 |
17.5 |
14.8 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
FC35B |
|
72 |
46.1 |
|
41.9 |
37.4 |
33.0 |
|
|
|
|
|
|
|
|
PC35B |
1025 |
67 |
36.9 |
|
32.6 |
28.6 |
24.3 |
FC35C |
|
|
|
|
|
|
|
62 |
28.9 |
|
24.2 |
26.4 |
19.7 |
||
|
|
||||||
PC35C |
|
|
|
|
|
|
|
|
57 |
24.7 |
|
22.9 |
21.1 |
19.7 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
72 |
46.0 |
|
41.9 |
37.4 |
32.9 |
|
|
|
|
|
|
|
|
FC36A |
1150 |
67 |
36.8 |
|
32.5 |
28.5 |
24.2 |
PC36A |
|
|
|
|
|
|
|
62 |
28.8 |
|
24.1 |
26.4 |
19.6 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
24.7 |
|
22.9 |
21.1 |
19.6 |
|
|
|
|
|
|
|
|
FC36B |
|
72 |
51.1 |
|
46.5 |
41.5 |
36.6 |
|
|
|
|
|
|
|
|
PC36B |
1250 |
67 |
40.9 |
|
36.1 |
31.7 |
26.9 |
FC36C |
|
|
|
|
|
|
|
62 |
32.0 |
|
26.8 |
29.3 |
21.8 |
||
|
|
||||||
PC36C |
|
|
|
|
|
|
|
|
57 |
27.4 |
|
25.4 |
23.4 |
21.8 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
FC42B |
|
72 |
86.6 |
|
74.5 |
62.0 |
49.0 |
|
|
|
|
|
|
|
|
PC42B |
1400 |
67 |
69.4 |
|
58.2 |
47.4 |
36.3 |
FC42C |
|
|
|
|
|
|
|
62 |
54.1 |
|
43.0 |
35.1 |
29.3 |
||
|
|
||||||
PC42C |
|
|
|
|
|
|
|
|
57 |
46.5 |
|
40.7 |
35.1 |
29.3 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
72 |
99.4 |
|
85.5 |
71.2 |
56.2 |
|
|
|
|
|
|
|
|
FC48C |
1620 |
67 |
79.6 |
|
66.8 |
54.4 |
41.6 |
PC48C |
|
|
|
|
|
|
|
62 |
62.1 |
|
49.4 |
40.2 |
33.7 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
53.3 |
|
46.7 |
40.2 |
33.7 |
|
|
|
|
|
|
|
|
FC60C |
|
72 |
118.7 |
|
100.0 |
81.1 |
61.5 |
|
|
|
|
|
|
|
|
PC60C |
1850 |
67 |
95.0 |
|
78.4 |
61.9 |
45.4 |
FC60D |
|
|
|
|
|
|
|
62 |
74.0 |
|
58.0 |
45.7 |
36.7 |
||
|
|
||||||
PC60D |
|
|
|
|
|
|
|
|
57 |
63.6 |
|
54.8 |
45.7 |
36.7 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
* - See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
2 |
Unitary Products Group |
|
|
|
|
|
|
|
258931-BTG-A-0606 |
|
COOLING CAPACITY - COIL ONLY* |
|
|
|
|
|
|
||
Model Coil |
Rated CFM |
|
Entering Air °F |
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG |
||||
|
(Wet Bulb) |
|
|
|
|
|
||
|
|
|
35 / 61.5 |
40 / 68.5 |
45 / 76.0 |
|
50 / 84.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
FULL-CASED “A” TYPE MULTI-POSITION |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
72 |
25.8 |
23.5 |
21.0 |
|
18.2 |
|
|
|
|
|
|
|
|
|
MC18A |
550 |
|
67 |
23.7 |
21.5 |
19.0 |
|
16.4 |
|
|
|
|
|
|
|
||
|
62 |
19.5 |
17.3 |
14.9 |
|
12.6 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
15.8 |
13.5 |
11.5 |
|
9.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
28.7 |
26.1 |
23.3 |
|
20.2 |
|
|
|
|
|
|
|
|
|
MC18B |
650 |
|
67 |
26.4 |
23.9 |
21.1 |
|
18.2 |
|
|
|
|
|
|
|
||
|
62 |
21.6 |
19.2 |
16.6 |
|
14.0 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
17.5 |
15.2 |
12.8 |
|
10.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
36.3 |
33.0 |
29.5 |
|
25.6 |
|
|
|
|
|
|
|
|
|
MC24A |
850 |
|
67 |
33.4 |
30.2 |
26.7 |
|
23.1 |
MC24B |
|
|
|
|
|
|
|
|
|
62 |
27.4 |
24.3 |
21.0 |
|
17.7 |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
22.2 |
19.3 |
16.2 |
|
12.6 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
41.5 |
37.8 |
33.7 |
|
29.5 |
|
|
|
|
|
|
|
|
|
MC30A |
1025 |
|
67 |
36.2 |
32.4 |
28.6 |
|
24.5 |
MC30B |
|
|
|
|
|
|
|
|
|
62 |
29.1 |
25.3 |
24.0 |
|
19.2 |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
24.1 |
21.5 |
18.7 |
|
15.8 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
46.9 |
42.7 |
38.2 |
|
33.6 |
|
|
|
|
|
|
|
|
|
MC35B |
1025 |
|
67 |
37.6 |
33.2 |
29.1 |
|
24.7 |
MC35C |
|
|
|
|
|
|
|
|
|
62 |
29.3 |
24.6 |
26.9 |
|
20.0 |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
25.2 |
23.3 |
21.5 |
|
20.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
46.8 |
42.6 |
38.1 |
|
33.6 |
|
|
|
|
|
|
|
|
|
MC36A |
1150 |
|
67 |
37.5 |
33.1 |
29.1 |
|
24.7 |
|
|
|
|
|
|
|
||
|
62 |
29.3 |
24.6 |
26.8 |
|
20.0 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
25.1 |
23.2 |
21.4 |
|
20.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
52.0 |
47.3 |
42.3 |
|
37.3 |
|
|
|
|
|
|
|
|
|
MC36B |
1250 |
|
67 |
41.7 |
36.8 |
32.3 |
|
27.4 |
|
|
|
|
|
|
|
||
|
62 |
32.5 |
27.3 |
29.8 |
|
22.2 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
27.9 |
25.8 |
23.8 |
|
22.2 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
53.4 |
48.6 |
43.4 |
|
38.3 |
|
|
|
|
|
|
|
|
|
MC36C |
1250 |
|
67 |
42.8 |
37.8 |
33.1 |
|
28.2 |
|
|
|
|
|
|
|
||
|
62 |
33.4 |
28.1 |
30.6 |
|
22.8 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
28.7 |
26.5 |
24.5 |
|
22.8 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
88.4 |
76.0 |
63.3 |
|
50.0 |
|
|
|
|
|
|
|
|
|
MC42B |
1400 |
|
67 |
70.8 |
59.4 |
48.4 |
|
37.0 |
MC42C |
|
|
|
|
|
|
|
|
|
62 |
55.2 |
43.9 |
35.8 |
|
29.9 |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
47.4 |
41.5 |
35.8 |
|
29.9 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
100.5 |
86.4 |
72.0 |
|
56.8 |
|
|
|
|
|
|
|
|
|
MC48C |
1650 |
|
67 |
80.4 |
67.5 |
55.0 |
|
42.1 |
MC48D |
|
|
|
|
|
|
|
|
|
62 |
62.7 |
49.9 |
40.7 |
|
34.0 |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
53.9 |
47.2 |
40.7 |
|
34.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
119.9 |
101.0 |
80.0 |
|
62.2 |
|
|
|
|
|
|
|
|
|
MC60D |
1825 |
|
67 |
96.0 |
79.2 |
62.6 |
|
45.8 |
|
|
|
|
|
|
|
||
|
62 |
74.8 |
58.6 |
46.2 |
|
37.0 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
64.3 |
55.4 |
46.2 |
|
37.0 |
|
|
|
|
|
|
|
|
|
|
|
|
72 |
124.8 |
105.2 |
85.3 |
|
64.7 |
|
|
|
|
|
|
|
|
|
MC61D |
2000 |
|
67 |
99.9 |
82.5 |
65.2 |
|
47.7 |
|
|
|
|
|
|
|
||
|
62 |
77.9 |
61.1 |
48.1 |
|
38.6 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
57 |
66.9 |
57.7 |
48.1 |
|
38.6 |
|
|
|
|
|
|
|
|
|
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
Unitary Products Group |
3 |
258931-BTG-A-0606
COOLING CAPACITY - Coil Only*
|
RATED |
ENTERING |
|
MBH @ Evaporator Temperature and Corresponding Pressure °F/ PSIG |
||||
MODEL |
AIR °F |
|
|
|
|
|
|
|
CFM |
|
35 / 61.5 |
|
40 / 68.5 |
45 / 76.0 |
50 / 84.0 |
||
|
(Wet Bulb) |
|
|
|||||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
HORIZONTAL DUCT TYPE |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
72 |
|
35.3 |
|
32.4 |
28.7 |
24.9 |
|
|
|
|
|
|
|
|
|
HD24A |
815 |
67 |
|
32.6 |
|
29.4 |
26.0 |
22.5 |
|
|
|
|
|
|
|
||
62 |
|
26.7 |
|
23.7 |
20.5 |
17.2 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
|
21.7 |
|
18.8 |
15.7 |
12.3 |
|
|
|
|
|
|
|
|
|
|
|
72 |
|
57.9 |
|
52.7 |
47.1 |
41.5 |
|
|
|
|
|
|
|
|
|
HD36B |
1192 |
67 |
|
46.4 |
|
41.1 |
35.9 |
30.4 |
|
|
|
|
|
|
|
||
62 |
|
36.2 |
|
30.4 |
26.5 |
24.7 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
|
31.1 |
|
28.7 |
26.5 |
24.7 |
|
|
|
|
|
|
|
|
|
|
|
72 |
|
83.4 |
|
71.7 |
59.7 |
47.1 |
|
|
|
|
|
|
|
|
|
HD48C |
1610 |
67 |
|
66.8 |
|
56.1 |
45.6 |
34.9 |
|
|
|
|
|
|
|
||
62 |
|
52.1 |
|
41.5 |
33.7 |
28.3 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
|
44.7 |
|
39.2 |
33.7 |
28.3 |
|
|
|
|
|
|
|
|
|
|
|
72 |
|
133.0 |
|
112.4 |
90.9 |
69.2 |
|
|
|
|
|
|
|
|
|
HD60D |
2100 |
67 |
|
106.5 |
|
87.9 |
69.4 |
50.0 |
|
|
|
|
|
|
|
||
62 |
|
83.0 |
|
65.0 |
51.3 |
41.1 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
|
71.2 |
|
61.4 |
51.3 |
41.1 |
|
|
|
|
|
|
|
|
|
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
Notes:
• MC coils available with a factory installed horizontal drain pan option (H).
COOLING CAPACITY - COIL ONLY*
|
Rated |
Entering Air °F |
|
MBH @ EVAPORATOR TEMPERATURE AND |
|
|||
Model |
|
|
CORRESPONDING PRESSURE °F / PSIG |
|
||||
CFM |
(Wet Bulb) |
|
|
|
|
|
|
|
|
|
|
35/61.5 |
|
40/68.5 |
45/76.0 |
|
50/84.0 |
|
|
|
|
|
|
|
|
|
|
|
72 |
26.4 |
|
24.0 |
21.5 |
|
18.6 |
|
|
|
|
|
|
|
|
|
HC18A |
600 |
67 |
24.3 |
|
22.0 |
19.4 |
|
16.8 |
|
|
|
|
|
|
|
||
62 |
20.0 |
|
17.7 |
15.3 |
|
12.9 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
16.1 |
|
14.0 |
11.8 |
|
9.2 |
|
|
|
|
|
|
|
|
|
|
|
72 |
42.7 |
|
38.9 |
34.7 |
|
30.6 |
|
|
|
|
|
|
|
|
|
HC30A |
1000 |
67 |
34.3 |
|
30.3 |
26.5 |
|
22.5 |
|
|
|
|
|
|
|
||
62 |
26.7 |
|
22.5 |
24.5 |
|
19.8 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
22.9 |
|
21.2 |
19.6 |
|
18.3 |
|
|
|
|
|
|
|
|
|
|
|
72 |
73.4 |
|
63.1 |
52.5 |
|
41.5 |
|
|
|
|
|
|
|
|
|
HC36B |
1200 |
67 |
58.8 |
|
49.3 |
40.2 |
|
30.7 |
|
|
|
|
|
|
|
||
62 |
45.8 |
|
36.4 |
29.7 |
|
24.8 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
39.3 |
|
34.4 |
28.1 |
|
23.2 |
|
|
|
|
|
|
|
|
|
|
|
72 |
84.9 |
|
73.0 |
60.1 |
|
48.1 |
|
|
|
|
|
|
|
|
|
HC42C |
1400 |
67 |
68.0 |
|
58.9 |
46.5 |
|
35.6 |
|
|
|
|
|
|
|
||
62 |
53.1 |
|
42.2 |
34.4 |
|
28.8 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
45.5 |
|
40.0 |
32.0 |
|
26.7 |
|
|
|
|
|
|
|
|
|
|
|
72 |
112.8 |
|
95.0 |
77.0 |
|
58.4 |
|
|
|
|
|
|
|
|
|
HC60C |
1800 |
67 |
90.3 |
|
74.5 |
58.8 |
|
43.1 |
|
|
|
|
|
|
|
||
62 |
70.3 |
|
55.1 |
43.4 |
|
34.9 |
||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
57 |
60.4 |
|
52.1 |
40.4 |
|
31.9 |
|
|
|
|
|
|
|
|
|
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
4 |
Unitary Products Group |
|
|
|
|
|
|
258931-BTG-A-0606 |
|
COOLING CAPACITY - COIL ONLY* |
|
|
|
|
|
||
Model Coil |
Rated CFM |
Entering Air °F (Wet Bulb) |
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG |
||||
|
|
|
|
|
|||
|
|
|
35 / 61.5 |
40 / 68.5 |
45 / 76.0 |
|
50 / 84.0 |
|
|
|
|
|
|
|
|
|
|
|
uncased upflow |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
72 |
23.3 |
21.3 |
19.0 |
|
17.5 |
|
|
|
|
|
|
|
|
UC18A |
60 |
67 |
21.5 |
19.5 |
17.3 |
|
14.9 |
UC18B |
|
|
|
|
|
|
|
62 |
17.7 |
15.6 |
13.5 |
|
11.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
14.4 |
12.4 |
10.4 |
|
8.0 |
|
|
|
|
|
|
|
|
|
|
72 |
27.4 |
25.0 |
22.3 |
|
19.4 |
|
|
|
|
|
|
|
|
UC24A |
800 |
67 |
25.3 |
22.9 |
20.3 |
|
17.5 |
UC24B |
|
|
|
|
|
|
|
62 |
20.8 |
18.4 |
15.9 |
|
13.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
16.9 |
14.6 |
12.2 |
|
9.4 |
|
|
|
|
|
|
|
|
|
|
72 |
35.2 |
32.0 |
28.6 |
|
24.8 |
|
|
|
|
|
|
|
|
UC30A |
1000 |
67 |
32.4 |
28.6 |
25.3 |
|
21.9 |
UC30B |
|
|
|
|
|
|
|
62 |
26.6 |
23.6 |
21.5 |
|
18.7 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
25.2 |
22.7 |
20.2 |
|
17.6 |
|
|
|
|
|
|
|
|
|
|
72 |
46.8 |
42.7 |
37.9 |
|
33.0 |
|
|
|
|
|
|
|
|
UC36A |
1150 |
67 |
43.1 |
39.2 |
34.9 |
|
30.4 |
|
|
|
|
|
|
||
62 |
35.3 |
32.1 |
28.6 |
|
24.9 |
||
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
57 |
33.3 |
26.9 |
26.9 |
|
23.4 |
|
|
|
|
|
|
|
|
|
|
72 |
49.3 |
44.9 |
39.9 |
|
34.7 |
|
|
|
|
|
|
|
|
UC36B |
1200 |
67 |
45.4 |
41.3 |
36.7 |
|
32.0 |
UC36C |
|
|
|
|
|
|
|
62 |
37.2 |
33.8 |
30.1 |
|
26.2 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
35.0 |
28.3 |
28.3 |
|
24.6 |
|
|
|
|
|
|
|
|
|
|
72 |
86.7 |
73.0 |
59.2 |
|
44.9 |
|
|
|
|
|
|
|
|
UC42B |
1400 |
67 |
69.4 |
57.2 |
45.2 |
|
33.1 |
UC42C |
|
|
|
|
|
|
|
62 |
54.0 |
42.3 |
33.4 |
|
26.8 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
46.4 |
40.0 |
33.4 |
|
26.8 |
|
|
|
|
|
|
|
|
|
|
72 |
62.4 |
56.8 |
50.5 |
|
44.4 |
|
|
|
|
|
|
|
|
UC48C |
1600 |
67 |
57.4 |
53.2 |
46.5 |
|
40.5 |
UC48D |
|
|
|
|
|
|
|
62 |
47.1 |
42.8 |
38.1 |
|
33.2 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
44.3 |
40.3 |
35.8 |
|
31.2 |
|
|
|
|
|
|
|
|
|
|
72 |
95.4 |
82.1 |
68.4 |
|
54.0 |
|
|
|
|
|
|
|
|
UC60C |
1800 |
67 |
76.4 |
64.1 |
52.2 |
|
39.9 |
UC60D |
|
|
|
|
|
|
|
62 |
59.6 |
47.4 |
38.6 |
|
32.4 |
||
|
|
||||||
|
|
|
|
|
|
|
|
|
|
57 |
51.2 |
44.8 |
38.6 |
|
32.4 |
|
|
|
|
|
|
|
|
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
APPLICATION FACTOR-RATED CFM VS. ACTUAL CFM
% OF RATED AIR FLOW |
80% |
90% |
RATED CFM |
110% |
120% |
|
|
|
|
|
|
CAPACITY FACTOR |
0.96 |
0.98 |
1.00 |
1.02 |
1.03 |
|
|
|
|
|
|
NOTE:Do not exceed minimum/maximum CFM limits shown under Air Flow Data.
APPLICATION LIMITATIONS
These units must be installed in accordance with all national and local safety codes.
Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp. ºF |
Dry Bulb Temp. ºF |
||
Min. |
Max. |
Min. |
Max. |
|
|
|
|
57 |
72 |
65 |
95 |
|
|
|
|
Unitary Products Group |
5 |