York CZH024 THRU 060 User Manual

Page 1
TECHNICAL GUIDE
AFFINITY R-410A SPLIT-SYSTEM AIR CONDITIONERS 18 SEER MODELS: CZH024 THRU 060
(2 THRU 5 NOMINAL TONS)
ISO 9001
LISTED
Due to continuous product improvement, specific a t ion s are subject to change without notice.
Additional rating information can be foun d at www.ariprimenet.org.
Certified Quality
Management System
350154-YTG-B-0408
DESCRIPTION
The CZH Series condensing unit is the outdoor part of a versatile air conditioning system. It is designed to be custom matched with one of our complete line of evaporator sections, each designed to serve a specific function. Matching air handlers are available for upflow, downflow, and horizontal lef t or right applic ation to provi de a complete system. Electric heaters are available if required. Add-on coils are available for use with upflow, downflow, or horizontal fur­naces. Field installed accessories are available as needed.
WARRANTY
5-year limited parts warranty. 10-year limited compressor warranty. Premium System Warranty - Limited lifetime compressor and 10­year parts when matched with an approved York Affinity furnace or UPG air handler and coil.
FEATURES
Superior Coil Protection – A stamped decorative metal coil guard completely protects coil from debris and other large dam­aging material while a polymer mesh further protects the coil against smaller particles.
Isolated Compressor Compartment – A molded composite bulkhead isolates the compressor from the rest of the u nit red uc­ing sound and vibration.
Protected Compressors – Each compressor is protected against abnormal pressures by an internal pressure relief valve and factory installed high and low pressure controls. Additional protection against moisture and debris is provided by factory installed liquid line filter driers.
Environmentally Friendly Refrigerant – Next generation refrigerant R-410A delivers environmentally friendly perfor­mance with zero ozone depletion.
Durable Finish – Automotive quality finish provides the ultimate protection from harmful U.V. rays and rust creep ensuring long­lasting high quality appearance. A powder-paint topcoat is applied over a baked-on primer, using a galvanized, zinc coated steel base material. The result is a finish that has been p roven in testing to provide 33% greater durability than conventional pow­der-coat finishes.
Lower Installed Cost – Designed to provide enhanced install­ability by featuring a slide-down control compartment and angled service valves to reduce overall install ation time and cost.
Low Operating Sound Levels – A fan design boasting technol­ogy adapted from aeronautic and defense engineering provides for whisper quiet operation by allowing airflow to flow smoothly and efficiently across the fan tips.
Filter-Drier – A factory installed, solid core liquid line filter-drier filters harmful debris and moisture from the system.
Easy Service Access – A full end, full service, access panel with handle makes for easy entry to internal components.
Composite Base - Strong and durable composite base pan resists rust and corrosion while it helps reduce vibrations and noise.
Quiet drive system - Features combination of swept-wing fan,
composite base pan, isolated compressor compartment and two-stage compressor to reduce overall sound to a mere whis­per.
Low RPM fan motor - Helps to reduce airflow noise.
Certified in accordance with the Unitary Small Equipment certifica­tion program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
350154-YTG-B-0408
Physical and Electrical Data
MODEL
CZH02411 CZH03611 CZH04811 CZH06011
Unit Supply Voltage 208-230V, 1φ, 60Hz Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 15.6 23.6 29.2 34.8 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
2
3
25 40 50 60 20 25 30 35
Multi-stage Compressor Yes Yes Yes Yes Compressor Type Scroll Scroll Scroll Scroll
Compressor Amps
Rated Load 10.3 16.7 21.2 25.6
Locked Rotor 52 82 96 118 Crankcase Heater No No No No Fan Motor Amps Rated Load 2.8 2.8 2.8 2.8 Fan Diameter Inches 24 24 24 24
Rated HP 1/3 1/3 1/3 1/3 Fan Motor
Nominal RPM 685 685 685 685
Nominal CFM 2900 3200 3100 3150
Face Area Sq. Ft. 23.58 23.58 23.58 23.58 Coil
Rows Deep 2 2 2 2
Fins / Inch 16 16 14 14 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
15 - 1 13 - 7 12 - 9 13 - 5
Charge Per Foot, Oz. 0.62 0.62 0.67 0.67 Operating Weight Lbs. 305 305 310 330
1 Rated in accordance with ARI Standard 110, utilization range “A”. 2 Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection. 3 Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection. 4 The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
VAPOR
LIQUID
2-3/8
3-1/8
6-1/2
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A B C Liquid Vapor
24 39-1/2 42 34
A
36 39-1/2 42 34 48 39-1/2 42 34
3/8”
60 39-1/2 42 34
C
B
3/4”
7/8”
2 Johnson Controls Unitary Products
Page 3
350154-YTG-B-0408
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit CZH02411 CZH03611 CZH04811 CZH06011 Approved System Thermal Expansion Valve
Factory R-410A Charge, lbs-oz 16 - 2 15 - 14 13 - 8 14 - 1
Indoor Coil
FC/MC/PC32A 1 – FC/MC/PC35B 0 – FC/MC/PC35C 0 – FC/MC/PC37A 7 24 – – FC/MC/PC43B 7 24 – – FC/MC/PC43C 7 24 – – FC/MC/PC48C 17 7 10 – FC/MC/PC48D 17 7 10 – FC/PC60C –––0 FC/MC/PC60D –––0 FC/MC62D 39 15 12 HC36B 0 – HC42C – 24 – HC60D – 1 0 UC48D 17 7 10 – UC60D –––0 AV36C 7 0 – – AV/SV48D – 1 – AV/SV60D – 0 0 F4FV060D 1 0
FOOTNOTES:
PROCEDURES:
2
1 Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224. 2 PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications. 3 A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV.
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter­connecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
1
1TVM902 1TVM904 1TVM905 1TVM906
TXV Kit3 - Additional Charge, Oz
Johnson Controls Unitary Products 3
Page 4
350154-YTG-B-0408
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
CZH02411
CZH03611
CZH04811
CZH06011
For notes see Page 5.
AIR HANDLER
MODEL W STAGE
1 PH 18 SEER AC WITH MV
MV12B 17 FC/MC/PC35B
MV12B 17 FC/MC/PC35C
MV12B 17 FC/MC/PC43B
MV12B 17 FC/MC/PC43C
MV12D 24 FC/MC/PC48D
MV12D 24 UC48D
MV12B 17 FC/MC/PC43B
MV12B 17 FC/MC/PC43C
MV16C 21 FC/MC/PC43C
MV12D 24 FC/MC/PC48D
MV12D 24 UC48D
MV16C 21 FC/MC/PC48C
MV16C 21 FC/MC/PC48D
MV16C 21 UC48D
MV20D 24 FC/MC/PC48D
MV20D 24 UC48D
MV12D 24 FC/MC62D
MV20D 24 FC/MC62D
MV16C 21 FC/MC/PC48C
MV16C 21 FC/MC/PC48D
MV16C 21 UC48D
MV20D 24 FC/MC/PC48D
MV20D 24 UC48D
MV20D 24 FC/MC62D
MV20D 24 FC/MC/PC60D
MV20D 24 UC60D
MV20D 24 FC/MC62D
COIL
MODEL
COOLING
1
RATED
CFM
1 620 18.2 13.8 2 800 23.6 17.2 13.80 1 620 18.2 13.8 2 800 23.6 17.2 13.80 1 620 18.5 14.0 2 800 24.0 17.5 14.00 1 620 18.5 14.0 2 800 24.0 17.5 14.00 1 645 18.9 14.3 2 835 24.6 17.9 14.45 1 645 18.9 14.3 2 835 24.6 17.9 14.45 1 775 25.6 18.0 2 1200 36.0 25.2 13.55 1 775 25.6 18.0 2 1200 36.0 25.2 13.55 1 775 25.7 18.1 2 1200 36.2 25.3 14.00 1 735 25.6 18.0 2 1135 36.0 25.2 13.95 1 735 25.6 18.0 2 1135 36.0 25.2 13.95 1 775 25.9 18.2 2 1200 36.4 25.4 14.15 1 775 25.9 18.2 2 1200 36.4 25.4 14.15 1 775 25.9 18.2 2 1200 36.4 25.4 14.15 1 770 25.8 18.1 2 1200 36.6 25.6 14.20 1 770 25.8 18.1 2 1200 36.6 25.6 14.20 1 735 25.7 18.1 2 1135 36.6 25.6 14.25 1 770 25.9 18.2 2 1200 37.0 25.9 14.35 1 1000 34.0 25.1 2 1600 46.0 35.1 12.45 1 1000 34.0 25.1 2 1600 46.0 35.1 12.45 1 1000 34.0 25.1 2 1600 46.0 35.1 12.45 1 1020 34.0 25.1 2 1600 46.0 35.1 12.35 1 1020 34.0 25.1 2 1600 46.0 35.1 12.35 1 1020 34.1 25.2 2 1600 46.5 35.5 12.50 1 1030 40.2 27.3 2 1800 55.5 40.5 11.55 1 1030 40.2 27.3 2 1800 55.5 40.5 11.55 1 1030 42.1 28.6 2 1800 58.0 42.3 12.00
NET MBH SEER EER
17.05
17.05
17.20
17.20
18.00
18.00
17.70
17.70
18.00
18.40
18.40
18.40
18.40
18.40
18.30
18.30
18.50
18.30
17.30
17.30
17.30
17.00
17.00
17.00
15.30
15.30
16.00
14.50
14.50
14.65
14.65
15.25
15.25
14.90
14.90
15.00
15.40
15.40
15.40
15.40
15.40
15.30
15.30
15.40
15.30
14
.20
14.20
14.20
14.00
14.00
14.05
12.55
12.55
13.20
4 Johnson Controls Unitary Products
Page 5
350154-YTG-B-0408
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
MODEL W STAGE
COIL
MODEL
1
RATED
CFM
1 PH 18 SEER AC WITH AV/SV
CZH02411 AV36C 21 N / A
CZH03611 AV36C 21 N / A
AV/SV48D 24 N / A
CZH04811
AV/SV60D 24 N / A
CZH06011 AV/SV60D 24 N / A
1 600 18.4 13.9 2 765 23.8 17.3 14.10 1 830 25.7 18.1 2 1270 35.6 24.9 13.45 1 1135 33.1 24.4 2 1610 44.5 34.0 12.10 1 1085 33.0 24.4 2 1655 44.5 34.0 12.10 1 1145 41.5 28.2 2 1765 55.5 40.5 11.65
1 PH 18 SEER AC WITH F*F*
CZH04811 F4FV060 24 N / A
CZH06011 F4FV060 24 N / A
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1 1200 33.6 24.8 2 1600 44.5 34.0 12.15 1 1200 41.8 28.4 2 1780 55.5 40.5 11.60
COOLING NET MBH SEER EER
17.60
18.00
16.60
16.50
15.70
16.85
15.55
14.95
15.25
13.60
13.60
13.00
13.75
12.80
1 MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Variable Speed Furnaces
UNIT MODEL
VARIABLE SPEED FURNACE MODEL
CZH02411
For notes see Page 8.
PV8*A12 14 FC/MC/PC32A
PV9*A12 14 FC/MC/PC32A
P(C,V)9*B12 17 FC/MC/PC35B
P(C,V)9*B12 17 FC/MC/PC35C
PV8*A12 14 FC/MC/PC37A
PV9*A12 14 FC/MC/PC37A
P(C,V)9*B12 17 FC/MC/PC43B
P(C,V)9*B12 17 FC/MC/PC43C
P(C,V)9*B12 17 HC36B
COIL
MODEL
1
W
STAGE
RATED
CFM
TOTAL SENSIBLE
1 PH 18 SEER AC WITH VARIABLE SPEED FURNACES
1 470 17.2 13.0 2 750 23.2 16.9 13.55 1 625 18.1 13.7 2 800 23.2 16.9 13.05 1 560 17.9 13.6 2 820 23.4 17.0 13.45 1 560 17.9 13.6 2 820 23.4 17.0 13.45 1 470 17.4 13.2 2 750 23.6 17.2 13.75 1 625 18.6 14.1 2 800 23.6 17.2 13.30 1 560 18.1 13.7 2 820 24.0 17.5 13.70 1 560 18.1 13.7 2 820 24.0 17.5 13.70 1 560 17.9 13.6 2 820 23.4 17.0 13.55
COOLING
NET MBH
SEER EER
16.70
16.60
17.05
17.05
17.00
17.00
17.35
17.35
17.10
14.15
14.25
14.55
14.55
14.35
14.60
14.70
14.70
14.55
Johnson Controls Unitary Products 5
Page 6
350154-YTG-B-0408
COOLING CAP ACITY - With Variable Speed Furnaces (Continued)
UNIT MODEL
CZH03611
For notes see Page 8.
VARIABLE SPEED FURNACE MODEL
PV8*A12 14 FC/MC/PC37A
PV9*A12 14 FC/MC/PC37A
PV8*B16 17 FC/MC/PC43B
PV8*B16 17 FC/MC/PC43C
PV8*C16 21 FC/MC/PC43C
PV8*C20 21 FC/MC/PC43C
P(C,V)9*B12 17 FC/MC/PC43B
P(C,V)9*B12 17 FC/MC/PC43C
P(C,V)9*C16 21 FC/MC/PC43C
P(C,V)9*C20 21 FC/MC/PC43C
PV8*C16 21 FC/MC/PC48C
PV8*C16 21 FC/MC/PC48D
PV8*C16 21 UC48D
PV8*C20 21 FC/MC/PC48C
PV8*C20 21 FC/MC/PC48D
PV8*C20 21 UC48D
P(C,V)9*C16 21 FC/MC/PC48C
P(C,V)9*C16 21 FC/MC/PC48D
P(C,V)9*C16 21 UC48D
P(C,V)9*C20 21 FC/MC/PC48C
P(C,V)9*C20 21 FC/MC/PC48D
P(C,V)9*C20 21 UC48D
P(C,V)9*D20 24 FC/MC/PC48D
P(C,V)9*D20 24 UC48D
PV8*C20 21 FC/MC62D
P(C,V)9*C20 21 FC/MC62D
COIL
MODEL
1
W
STAGE
RATED
1 750 25.4 17.9 2 1185 35.8 25.0 13.25 1 780 25.6 18.0 2 1200 35.6 24.9 13.00 1 750 25.4 17.9 2 1200 36.0 25.2 13.70 1 750 25.4 17.9 2 1200 36.0 25.2 13.70 1 640 24.6 17.3 2 1200 36.2 25.3 13.80 1 780 25.7 18.1 2 1200 36.0 25.2 13.50 1 770 25.6 18.0 2 1185 35.6 24.9 13.25 1 770 25.6 18.0 2 1185 35.6 24.9 13.25 1 770 25.7 18.1 2 1175 35.8 25.0 13.60 1 790 25.8 18.1 2 1195 36.0 25.2 13.65 1 640 24.7 17.4 2 1200 36.4 25.4 14.00 1 640 24.7 17.4 2 1200 36.4 25.4 14.00 1 640 24.7 17.4 2 1200 36.4 25.4 14.00 1 780 25.9 18.2 2 1200 36.2 25.3 13.55 1 780 25.9 18.2 2 1200 36.2 25.3 13.55 1 780 25.9 18.2 2 1200 36.2 25.3 13.55 1 770 25.9 18.2 2 1175 36.2 25.3 13.80 1 770 25.9 18.2 2 1175 36.2 25.3 13.80 1 770 25.9 18.2 2 1175 36.2 25.3 13.80 1 790 25.9 18.2 2 1195 36.2 25.3 13.75 1 790 2 1195 36.2 25.3 13.75 1 790 25.9 18.2 2 1195 36.2 25.3 13.75 1 775 25.9 18.2 2 1220 36.4 25.4 13.90 1 775 25.9 18.2 2 1220 36.4 25.4 13.90 1 780 26.0 18.3 2 1200 36.6 25.6 13.70 1 790 26.0 18.3 2 1195 36.6 25.6 13.90
CFM
COOLING
NET MBH
TOTAL SENSIBLE
25.9 18.2
SEER EER
17.50
17.50
17.80
17.80
17.70
17.90
17.60
17.60
18.00
17.90
18.20
18.20
18.20
18.35
18.35
18.35
18.40
18.40
18.40
18.20
18.20
18.20
18.30
18.30
18.35
18.20
14.80
14.75
14.90
14.90
14.80
15.10
14.85
14.85
15.30
15.05
15.15
15.15
15.15
15.45
15.45
15.45
15.60
15.60
15.60
15.25
15.25
15.25
15.40
15.40
15.40
15.25
6 Johnson Controls Unitary Products
Page 7
COOLING CAP ACITY - With Variable Speed Furnaces (Continued)
UNIT MODEL
CZH03611
CZH04811
For notes see Page 8.
VARIABLE SPEED FURNACE MODEL
P(C,V)9*D20 24 FC/MC62D
PV8*C16 21 HC42C
PV8*C20 21 HC42C
P(C,V)9*C16 21 HC42C
P(C,V)9*C20 21 HC42C
PV8*C16 21 FC/MC/PC48C
PV8*C16 21 FC/MC/PC48D
PV8*C16 21 UC48D
PV8*C20 21 FC/MC/PC48C
PV8*C20 21 FC/MC/PC48D
PV8*C20 21 UC48D
P(C,V)9*C16 21 FC/MC/PC48C
P(C,V)9*C16 21 FC/MC/PC48D
P(C,V)9*C16 21 UC48D
P(C,V)9*C20 21 FC/MC/PC48C
P(C,V)9*C20 21 FC/MC/PC48D
P(C,V)9*C20 21 UC48D
P(C,V)9*D20 24 FC/MC/PC48D
P(C,V)9*D20 24 UC48D
PV8*C20 21 FC/MC62D
,V)9*C20 21 FC/MC62D
P(C
P(C,V)9*D20 24 FC/MC62D
P(C,V)9*D20 24 HC60D
COIL
MODEL
1
W
STAGE
RATED
1 775 26.0 18.3 2 1220 36.8 25.7 14.05 1 640 24.6 17.3 2 1200 36.2 25.3 13.85 1 780 25.7 18.1 2 1200 36.0 25.2 13.50 1 770 25.6 18.0 2 1175 36.0 25.2 13.75 1 790 25.8 18.1 2 1195 36.0 25.2 13.65 1 880 33.0 24.4 2 1500 45.0 34.4 11.95 1 880 33.0 24.4 2 1500 45.0 34.4 11.95 1 880 33.0 24.4 2 1500 45.0 34.4 11.95 1 1030 34.1 25.2 2 1610 45.5 34.8 12.05 1 1030 34.1 25.2 2 1610 45.5 34.8 12.05 1 1030 34.1 25.2 2 1610 45.5 34.8 12.05 1 1090 34.6 25.6 2 1600 45.5 34.8 11.85 1 1090 34.6 25.6 2 1600 45.5 34.8 11.85 1 1090 34.6 25.6 2 1600 45.5 34.8 11.85 1 1010 33.9 25.0 2 1580 45.5 34.8 12.05 1 1010 33.9 25.0 2 1580 45.5 34.8 12.05 1 1010 33.9 25.0 2 1580 45.5 34.8 12.05 1 985 33.8 25.0 2 1560 45.5 34.8 12.20 1 985 33.8 25.0 2 1560 45.5 34.8 12.20 1 1030 34.2 25.3 2 1610 46.0 35.1 12.20 1 1010 34.1 25.2 2 1580 46.0 35.1 12.15 1 985 33.9 25.0 2 1560 46.0 35.1 12.30 1 985 32.3 23.9 2 1560 44.0 33.6 11.85
CFM
COOLING
NET MBH
TOTAL SENSIBLE
350154-YTG-B-0408
SEER EER
18.25
17.80
18.05
18.25
17.90
16.90
16.90
16.90
17.10
17.10
17.10
17.50
17.50
17.50
16.90
16.90
16.90
16.95
16.95
17.20
16.80
17.00
16.25
15.30
14.85
15.20
15.25
15.05
13.90
13.90
13.90
14.15
14.15
14.15
14.50
14.50
14.50
13.95
13.95
13.95
13.95
13.95
14.25
14.00
14.00
13.25
Johnson Controls Unitary Products 7
Page 8
350154-YTG-B-0408
COOLING CAP ACITY - With Variable Speed Furnaces (Continued)
UNIT MODEL
CZH06011
1 MC coils available with a factory installed horizontal drain pan.
VARIABLE SPEED FURNACE MODEL
PV8*C20 21 FC/PC60C
PV8*C20 21 FC/MC/PC60D
PV8*C20 21 UC60D
P(C,V)9*C20 21 FC/PC60C
P(C,V)9*C20 21 FC/MC/PC60D
P(C,V)9*C20 21 UC60D
P(C,V)9*D20 24 FC/MC/PC60D
P(C,V)9*D20 24 UC60D
PV8*C20 21 FC/MC62D
P(C,V)9*C20 21 FC/MC62D
P(C,V)9*D20 24 FC/MC62D
P(C,V)9*D20 24 HC60D
COIL
MODEL
1
W
STAGE
RATED
1 1120 41.0 27.8 2 1730 55.0 40.1 11.40 1 1120 41.0 27.8 2 1730 55.0 40.1 11.40 1 1120 41.0 27.8 2 1730 55.0 40.1 11.40 1 1075 40.4 27.4 2 1650 54.0 39.4 11.25 1 1075 40.4 27.4 2 1650 54.0 39.4 11.25 1 1075 40.4 27.4 2 1650 54.0 39.4 11.25 1 1020 40.2 27.3 2 1620 54.0 39.4 11.45 1 1020 40.2 27.3 2 1620 54.0 39.4 11.45 1 1120 42.8 29.1 2 1730 57.0 41.6 11.70 1 1075 42.4 28.8 2 1650 56.5 41.2 11.65 1 1020 42.0 28.5 2 1620 56.5 41.2 11.80 1 1020 40.1 27.2 2 1620 54.5 39.7 11.50
CFM
COOLING
NET MBH
TOTAL SENSIBLE
SEER EER
15.45
15.45
15.45
15.25
15.25
15.25
15.25
15.25
16.10
15.95
15.90
15.30
12.75
12.75
12.75
12.55
12.55
12.55
12.55
12.55
13.35
13.25
13.20
12.55
ACCESSORIES*
Hard Start Kit (024-31994-000, 024-31995-000) - Provides
increased starting torque for areas with low voltage. TXV Kits - 1TVM9 series thermal expansion valves precisely
meter refrigerant for optimum performance Dehumidistat (2HU16700124) - Provides increased dehu-
midification when matched with variable speed furnace or air handler.
Room Thermostats - A wide selection of compatible thermo­stats are available to provide optimum performance and fea­tures for any installation.
1 Heat Stage only, manual, mechanical thermostat. Add sub­base for 3H/2C.
3H/2C, manual changeover electronic non-programmable thermostat.
3H/2C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
3H/2C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the
price book or consult factory.
SOUND POWER RATINGS*
UNIT MODEL (dBA)
024 71 036 73 048 72 060 74
* Rated in accordance with ARI 270-95 Standards.
COLOR GRILLES
CHOICE OF SEVERAL COLOR COIL GRILLES TO
COMPLIMENT ANY HOME.
Color Grill Color Description
1CP1136 Terra Cotta All 1CP0236 Jet Black All 1CP0336 Stone All 1CP0436 Bermuda All 1CP0536 Gunmetal All 1CP0636 Chocolate All
8 Johnson Controls Unitary Products
Page 9
350154-YTG-B-0408
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH02411 INDOOR COIL MODEL NO. FC48D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 550 600 650
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 18.6 19.9 18.9 21.7 23.9 19.0 19.9 19.1 21.8 24.4 19.4 20.0 19.3 22.0 24.9 S.C. 18.6 17.5 14.9 14.8 11.7 19.2 18.5 15.6 15.5 12.1 19.7 19.4 16.2 16.2 12.5
K.W. 0.76 0.75 0.76 0.74 0.74 0.75 0.75 0.75 0.73 0.74 0.75 0.75 0.75 0.73 0.74
T.C. 17.8 18.8 18.0 20.6 22.8 18.3 18.9 18.3 20.9 23.2 18.7 19.1 18.5 21.1 23.6 S.C. 17.9 17.1 14.5 14.4 11.3 18.4 17.9 15.1 15.1 11.8 18.9 18.6 15.8 15.9 12.2 K.W. 0.93 0.92 0.93 0.91 0.90 0.92 0.92 0.92 0.90 0.90 0.91 0.91 0.92 0.90 0.90
T.C. 17.1 17.6 17.1 19.5 21.6 17.5 17.9 17.4 19.9 22.0 17.9 18.2 17.7 20.2 22.3 S.C. 17.2 16.8 14.0 14.0 10.9 17.7 17.3 14.7 14.8 11.4 18.1 17.9 15.4 15.5 11.9 K.W. 1.09 1.09 1.09 1.08 1.06 1.08 1.08 1.09 1.07 1.06 1.07 1.08 1.08 1.06 1.05
T.C. 16.4 16.5 16.2 18.5 20.5 16.8 16.9 16.6 18.9 20.8 17.1 17.2 16.9 19.4 21.0 S.C. 16.5 16.4 13.6 13.7 10.5 17.0 16.8 14.3 14.4 11.1 17.4 17.2 15.0 15.1 11.7 K.W. 1.26 1.26 1.26 1.24 1.22 1.24 1.25 1.25 1.24 1.22 1.24 1.24 1.25 1.23 1.21
T.C. 15.3 15.4 14.9 17.0 19.0 15.7 15.8 15.2 17.3 19.1 16.0 16.2 15.5 17.7 19.3 S.C. 15.4 15.2 13.0 13.2 10.1 15.8 15.6 13.6 13.9 10.5 16.2 16.0 14.3 14.5 11.0 K.W. 1.48 1.49 1.49 1.47 1.45 1.47 1.48 1.48 1.47 1.45 1.46 1.47 1.48 1.46 1.45
T.C. 14.2 14.3 13.6 15.5 17.5 14.6 14.7 13.9 15.8 17.6 15.0 15.1 14.1 16.1 17.7 S.C. 14.4 14.1 12.4 12.8 9.6 14.7 14.5 13.0 13.4 10.0 15.1 14.9 13.5 13.9 10.4 K.W. 1.70 1.71 1.71 1.70 1.68 1.69 1.70 1.70 1.69 1.67 1.68 1.69 1.70 1.68 1.67
T.C. 13.1 13.2 12.3 14.0 15.9 13.5 13.6 12.5 14.3 16.0 13.9 14.0 12.7 14.5 16.1 S.C. 13.3 13.0 11.8 12.3 9.2 13.6 13.4 12.3 12.9 9.5 14.0 13.8 12.8 13.4 9.7 K.W. 1.92 1.93 1.93 1.92 1.91 1.91 1.92 1.93 1.91 1.90 1.91 1.91 1.92 1.91 1.90
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Air Handler Coil
AV36C 0.97 0.97 0.99 MV12B FC/MC/PC35B 0.96 0.97 1.01 MV12B FC/MC/PC35C 0.96 0.97 1.01 MV12B FC/MC/PC35B 0.98 0.98 1.02 MV12B FC/MC/PC35C 0.98 0.98 1.02 MV12D FC/MC/PC48D 1.00 1.00 1.00 MV12D UC48D 1.00 1.00 1.00
T.C. S.C. KW
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 0.91 0.91 0.98 PV9*A12 FC/MC/PC32A 0.96 0.96 1.02 P(C,V)9*B12 FC/MC/PC35B 0.95 0.95 0.99 P(C,V)9*B12 FC/MC/PC35C 0.95 0.95 0.99 PV8*A12 FC/MC/PC37A 0.92 0.92 0.98 PV9*A12 FC/MC/PC37A 0.98 0.99 1.03 P(C,V)9*B12 FC/MC/PC43B 0.96 0.96 0.99 P(C,V)9*B12 FC/MC/PC43C 0.96 0.96 0.99 P(C,V)9*B12 HC36B 0.95 0.95 0.99
Coil
T.C. S.C. KW
Johnson Controls Unitary Products 9
Page 10
350154-YTG-B-0408
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH02411 INDOOR COIL MODEL NO. FC48D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 700 800 900
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 23.1 25.7 25.0 28.6 30.7 24.3 26.0 26.1 28.8 31.1 25.5 26.3 27.1 28.9 31.6 S.C. 22.6 21.4 17.9 18.3 14.5 23.8 23.1 19.5 19.1 15.3 25.0 24.8 21.0 20.0 16.1
K.W. 1.12 1.14 1.14 1.16 1.17 1.13 1.14 1.14 1.16 1.18 1.15 1.15 1.15 1.17 1.19
T.C. 22.5 24.3 23.9 27.1 29.2 23.5 24.7 24.7 27.4 29.7 24.5 25.1 25.5 27.6 30.1 S.C. 21.9 20.9 17.5 17.8 14.0 23.0 22.4 18.9 18.7 14.8 24.0 23.8 20.3 19.7 15.5 K.W. 1.31 1.32 1.32 1.34 1.35 1.31 1.32 1.32 1.34 1.36 1.33 1.33 1.33 1.35 1.37
T.C. 21.8 22.9 22.8 25.6 27.7 22.6 23.4 23.4 26.0 28.2 23.4 23.8 23.9 26.4 28.7 S.C. 21.3 20.4 17.2 17.3 13.6 22.1 21.6 18.4 18.4 14.3 22.9 22.7 19.6 19.4 15.0 K.W. 1.49 1.50 1.50 1.52 1.53 1.49 1.50 1.50 1.52 1.54 1.51 1.51 1.51 1.54 1.55
T.C. 21.2 21.5 21.8 24.0 26.2 21.8 22.1 22.1 24.6 26.7 22.4 22.5 22.3 25.2 27.2 S.C. 20.6 20.0 16.8 16.8 13.1 21.3 20.9 17.9 18.0 13.7 21.9 21.7 18.9 19.1 14.4 K.W. 1.67 1.68 1.67 1.70 1.72 1.67 1.68 1.68 1.70 1.72 1.69 1.69 1.69 1.72 1.73
T.C. 20.1 20.3 20.4 22.6 24.5 20.6 20.9 20.7 23.0 25.0 21.2 21.4 20.9 23.5 25.5 S.C. 19.5 19.0 16.2 16.3 12.6 20.1 19.8 17.2 17.3 13.2 20.7 20.5 18.2 18.4 13.8 K.W. 1.93 1.93 1.93 1.95 1.97 1.93 1.94 1.93 1.96 1.98 1.95 1.95 1.94 1.97 1.99
T.C. 19.0 19.2 19.1 21.2 22.9 19.5 19.7 19.3 21.5 23.4 20.0 20.2 19.5 21.8 23.9 S.C. 18.5 18.1 15.5 15.8 12.0 19.0 18.8 16.6 16.7 12.6 19.6 19.4 17.6 17.6 13.2 K.W. 2.17 2.18 2.17 2.20 2.23 2.18 2.18 2.18 2.21 2.23 2.20 2.20 2.19 2.22 2.24
T.C. 17.9 18.0 17.7 19.8 21.3 18.4 18.5 17.9 20.0 21.8 18.9 19.1 18.1 20.2 22.2 S.C. 17.4 17.2 14.9 15.3 11.5 17.9 17.8 15.9 16.1 12.1 18.4 18.3 16.9 16.9 12.6 K.W. 2.42 2.42 2.42 2.45 2.48 2.43 2.43 2.42 2.45 2.48 2.45 2.45 2.44 2.47 2.50
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Air Handler Coil T.C. S.C. KW AV36C 0.97 0.97 0.99 MV12B FC/MC/PC35B 0.96 0.96 1.00 MV12B FC/MC/PC35C 0.96 0.96 1.00 MV12B FC/MC/PC35B 0.98 0.98 1.01 MV12B FC/MC/PC35C 0.98 0.98 1.01 MV12D FC/MC/PC48D 1.00 1.00 1.00 MV12D UC48D 1.00 1.00 1.00
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 0.94 0.94 1.01 PV9*A12 FC/MC/PC32A 0.94 0.94 1.04 P(C,V)9*B12 FC/MC/PC35B 0.95 0.95 1.02 P(C,V)9*B12 FC/MC/PC35C 0.95 0.95 1.02 PV8*A12 FC/MC/PC37A 0.96 0.96 1.01 PV9*A12 FC/MC/PC37A 0.96 0.96 1.04 P(C,V)9*B12 FC/MC/PC43B 0.98 0.98 1.03 P(C,V)9*B12 FC/MC/PC43C 0.98 0.98 1.03 P(C,V)9*B12 HC36B 0.95 0.95 1.01
Coil
T.C. S.C. KW
10 Johnson Controls Unitary Products
Page 11
350154-YTG-B-0408
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH03611 INDOOR COIL MODEL NO. FC62D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 750 800 850
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 25.4 26.8 27.2 29.7 32.8 25.9 27.0 27.3 30.1 33.0 26.4 27.2 27.5 30.4 33.2 S.C. 25.0 22.9 19.4 19.3 15.3 25.6 23.7 19.9 19.8 15.7 26.1 24.6 20.4 20.2 16.1
K.W. 1.00 0.99 0.99 0.96 0.93 0.99 0.98 0.98 0.95 0.92 0.97 0.97 0.97 0.94 0.91
T.C. 24.3 25.5 25.7 28.3 31.2 24.9 25.7 25.9 28.6 31.3 25.4 26.0 26.1 28.9 31.5 S.C. 24.0 22.3 18.8 18.7 14.8 24.6 23.1 19.4 19.2 15.3 25.1 23.8 19.9 19.7 15.7
K.W. 1.24 1.23 1.23 1.20 1.17 1.22 1.22 1.22 1.19 1.16 1.21 1.21 1.21 1.18 1.16
T.C. 23.3 24.2 24.3 26.9 29.5 23.8 24.5 24.5 27.2 29.7 24.3 24.7 24.8 27.5 29.8 S.C. 23.0 21.8 18.3 18.2 14.4 23.6 22.4 18.8 18.7 14.9 24.1 23.0 19.3 19.2 15.3
K.W. 1.47 1.47 1.47 1.44 1.41 1.46 1.46 1.46 1.43 1.41 1.45 1.45 1.45 1.42 1.40
T.C. 22.2 22.9 22.8 25.4 27.9 22.7 23.2 23.1 25.8 28.0 23.3 23.5 23.4 26.1 28.2 S.C. 22.0 21.2 17.7 17.6 14.0 22.6 21.7 18.2 18.2 14.5 23.1 22.2 18.8 18.7 14.9
K.W. 1.71 1.71 1.71 1.68 1.65 1.70 1.70 1.70 1.67 1.65 1.69 1.69 1.69 1.66 1.64
T.C. 20.8 21.3 21.0 23.6 26.0 21.3 21.7 21.3 23.8 26.1 21.9 22.1 21.5 24.1 26.2 S.C. 20.6 20.0 16.8 16.8 13.4 21.2 20.5 17.4 17.4 13.7 21.7 21.0 17.9 17.9 14.1 K.W. 2.03 2.03 2.03 2.01 1.98 2.02 2.02 2.02 2.00 1.97 2.00 2.01 2.01 1.99 1.97
T.C. 19.4 19.7 19.3 21.7 24.1 20.0 20.2 19.5 22.0 24.2 20.5 20.7 19.7 22.2 24.3 S.C. 19.2 18.8 16.0 16.1 12.8 19.8 19.3 16.6 16.6 13.0 20.4 19.8 17.1 17.1 13.3 K.W. 2.34 2.33 2.34 2.32 2.30 2.33 2.33 2.33 2.31 2.29 2.31 2.32 2.32 2.30 2.28
T.C. 18.0 18.2 17.5 19.9 22.2 18.6 18.8 17.7 20.1 22.3 19.1 19.3 18.0 20.4 22.4 S.C. 17.8 17.6 15.2 15.3 12.2 18.4 18.1 15.8 15.8 12.3 19.0 18.5 16.4 16.3 12.5 K.W. 2.65 2.64 2.65 2.63 2.62 2.64 2.64 2.65 2.63 2.61 2.62 2.63 2.64 2.62 2.60
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Air Handler Coil
AV36C 1.00 1.00 1.01 MV12B FC/MC/PC43B 1.00 0.99 1.03 MV12B FC/MC/PC43C 1.00 0.99 1.03 MV16C FC/MC/PC43C 1.00 1.00 1.03 MV12D FC/MC/PC48D 1.00 0.99 1.00 MV12D UC48D 1.00 0.99 1.00 MV16C FC/MC/PC48C 1.01 1.01 1.01 MV16C FC/MC/PC48D 1.01 1.01 1.01 MV16C UC48D 1.01 1.01 1.01 MV20D FC/MC/PC48D 1.00 1.00 1.01 MV20D UC48D 1.00 1.00 1.01 MV12D FC/MC62D 1.00 1.00 1.00 MV20D FC/MC62D 1.01 1.01 1.01
Variable Speed Furnace
PV8*A12 FC/MC/PC37A 0.99 0.99 1.03 PV9*A12 FC/MC/PC37A 1.00 0.99 1.04 PV8*B16 FC/MC/PC43B 0.99 0.99 1.02 PV8*B16 FC/MC/PC43C 0.99 0.99 1.02 PV8*C16 FC/MC/PC43C 0.96 0.96 1.00 PV8*C20 FC/MC/PC43C 1.00 1.00 1.02 P(C,V)9*B12 FC/MC/PC43B 1.00 0.99 1.03 P(C,V)9*B12 FC/MC/PC43C 1.00 0.99 1.03
Coil
T.C. S.C. KW
T.C. S.C. KW
Variable Speed Furnace
P(C,V)9*C16 FC/MC/PC43C 1.00 1.00 1.01 P(C,V)9*C20 FC/MC/PC43C 1.00 1.00 1.03 PV8*C16 FC/MC/PC48C 0.96 0.96 0.98 PV8*C16 FC/MC/PC48D 0.96 0.96 0.98 PV8*C16 UC48D 0.96 0.96 0.98 PV8*C20 FC/MC/PC48C 1.01 1.01 1.00 PV8*C20 FC/MC/PC48D 1.01 1.01 1.00 PV8*C20 UC48D 1.01 1.01 1.00 P(C,V)9*C16 FC/MC/PC48C 1.01 1.01 0.99 P(C,V)9*C16 FC/MC/PC48D 1.01 1.01 0.99 P(C,V)9*C16 UC48D 1.01 1.01 0.99 P(C,V)9*C20 FC/MC/PC48C 1.01 1.01 1.02 P(C,V)9*C20 FC/MC/PC48D 1.01 1.01 1.02 P(C,V)9*C20 UC48D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC/PC48D 1.01 1.01 1.01 P(C,V)9*D20 UC48D 1.01 1.01 1.01 PV8*C20 FC/MC62D 1.01 1.01 1.01 P(C,V)9*C20 FC/MC62D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC62D 1.01 1.01 1.02 PV8*C16 HC42C 0.96 0.96 0.99 PV8*C20 HC42C 1.00 1.00 1.01 P(C,V)9*C16 HC42C 1.00 0.99 1.01 P(C,V)9*C20 HC42C 1.00 1.00 1.03
Coil
T.C. S.C. KW
Johnson Controls Unitary Products 11
Page 12
350154-YTG-B-0408
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH03611 INDOOR COIL MODEL NO. FC62D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1100 1200 1300
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 35.7 38.1 38.5 41.2 45.8 37.2 39.1 38.8 41.7 46.1 38.6 40.1 39.1 42.1 46.3 S.C. 34.5 31.9 27.3 26.9 21.2 36.1 33.4 28.6 27.7 22.1 37.5 35.0 29.9 28.4 22.9
K.W. 1.71 1.74 1.74 1.79 1.82 1.74 1.76 1.76 1.81 1.84 1.78 1.79 1.78 1.84 1.86
T.C. 34.6 36.5 36.7 39.5 43.6 35.9 37.4 37.1 40.0 43.9 37.1 38.2 37.5 40.4 44.2 S.C. 33.6 31.1 26.5 26.0 20.6 34.8 32.6 27.6 27.0 21.4 36.0 34.1 28.8 27.9 22.1
K.W. 1.98 2.00 2.00 2.05 2.07 2.00 2.02 2.01 2.06 2.09 2.04 2.05 2.04 2.09 2.12
T.C. 33.6 35.0 35.0 37.8 41.5 34.6 35.7 35.4 38.3 41.8 35.5 36.4 35.9 38.7 42.0 S.C. 32.6 30.3 25.6 25.2 20.0 33.6 31.8 26.6 26.3 20.6 34.5 33.3 27.7 27.4 21.2
K.W. 2.24 2.26 2.25 2.30 2.33 2.26 2.28 2.27 2.32 2.35 2.30 2.30 2.30 2.34 2.38
T.C. 32.5 33.4 33.2 36.1 39.4 33.3 34.0 33.7 36.6 39.6 34.0 34.5 34.2 37.1 39.8 S.C. 31.6 29.4 24.7 24.3 19.4 32.3 31.0 25.6 25.6 19.9 33.0 32.4 26.6 26.9 20.3
K.W. 2.50 2.52 2.51 2.55 2.59 2.52 2.53 2.53 2.57 2.60 2.56 2.56 2.56 2.59 2.63
T.C. 30.7 31.5 31.2 33.7 37.0 31.5 32.0 31.6 34.2 37.2 32.1 32.6 32.0 34.7 37.4 S.C. 29.9 28.4 23.7 23.6 18.6 30.6 29.6 24.7 24.8 19.0 31.3 30.6 25.7 25.9 19.4 K.W. 2.89 2.90 2.90 2.94 2.97 2.92 2.92 2.91 2.96 2.99 2.95 2.95 2.94 2.98 3.02
T.C. 29.0 29.6 29.2 31.3 34.7 29.7 30.2 29.5 31.8 34.9 30.4 30.7 29.8 32.3 35.0 S.C. 28.3 27.5 22.8 22.9 17.9 29.0 28.2 23.8 23.9 18.2 29.6 28.9 24.8 24.9 18.5 K.W. 3.28 3.28 3.27 3.32 3.35 3.30 3.29 3.29 3.33 3.37 3.33 3.32 3.31 3.35 3.40
T.C. 27.3 27.7 27.2 29.0 32.4 28.0 28.3 27.4 29.5 32.6 28.6 28.8 27.7 30.0 32.7 S.C. 26.7 26.5 21.9 22.2 17.2 27.3 26.8 22.9 23.1 17.4 28.0 27.1 24.0 24.0 17.6 K.W. 3.66 3.65 3.65 3.70 3.73 3.68 3.67 3.66 3.71 3.75 3.71 3.70 3.69 3.73 3.78
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Air Handler Coil
AV36C 0.97 0.97 1.03 MV12B FC/MC/PC43B 0.98 0.98 1.03 MV12B FC/MC/PC43C 0.98 0.98 1.03 MV16C FC/MC/PC43C 0.99 0.99 1.01 MV12D FC/MC/PC48D 0.98 0.98 1.00 MV12D UC48D 0.98 0.98 1.00 MV16C FC/MC/PC48C 0.99 0.99 1.00 MV16C FC/MC/PC48D 0.99 0.99 1.00 MV16C UC48D 0.99 0.99 1.00 MV20D FC/MC/PC48D 1.00 1.00 1.00 MV20D UC48D 1.00 1.00 1.00 MV12D FC/MC62D 1.00 1.00 1.00 MV20D FC/MC62D 1.01 1.01 1.00
Variable Speed Furnace
PV8*A12 FC/MC/PC37A 0.98 0.98 1.05 PV9*A12 FC/MC/PC37A 0.97 0.97 1.07 PV8*B16 FC/MC/PC43B 0.98 0.98 1.02 PV8*B16 FC/MC/PC43C 0.98 0.98 1.02 PV8*C16 FC/MC/PC43C 0.99 0.99 1.02 PV8*C20 FC/MC/PC43C 0.98 0.98 1.04 P(C,V)9*B12 FC/MC/PC43B 0.97 0.97 1.05 P(C,V)9*B12 FC/MC/PC43C 0.97 0.97 1.05
Coil
T.C. S.C. KW
T.C. S.C. KW
Variable Speed Furnace
P(C,V)9*C16 FC/MC/PC43C 0.98 0.98 1.02 P(C,V)9*C20 FC/MC/PC43C 0.98 0.98 1.03 PV8*C16 FC/MC/PC48C 0.99 0.99 1.01 PV8*C16 FC/MC/PC48D 0.99 0.99 1.01 PV8*C16 UC48D 0.99 0.99 1.01 PV8*C20 FC/MC/PC48C 0.99 0.99 1.04 PV8*C20 FC/MC/PC48D 0.99 0.99 1.04 PV8*C20 UC48D 0.99 0.99 1.04 P(C,V)9*C16 FC/MC/PC48C 0.99 0.99 1.02 P(C,V)9*C16 FC/MC/PC48D 0.99 0.99 1.02 P(C,V)9*C16 UC48D 0.99 0.99 1.02 P(C,V)9*C20 FC/MC/PC48C 0.99 0.99 1.03 P(C,V)9*C20 FC/MC/PC48D 0.99 0.99 1.03 P(C,V)9*C20 UC48D 0.99 0.99 1.03 P(C,V)9*D20 FC/MC/PC48D 0.99 0.99 1.02 P(C,V)9*D20 UC48D 0.99 0.99 1.02 PV8*C20 FC/MC62D 1.00 1.00 1.04 P(C,V)9*C20 FC/MC62D 1.00 1.00 1.03 P(C,V)9*D20 FC/MC62D 1.01 1.00 1.02 PV8*C16 HC42C 0.99 0.99 1.02 PV8*C20 HC42C 0.98 0.98 1.04 P(C,V)9*C16 HC42C 0.98 0.98 1.02 P(C,V)9*C20 HC42C 0.98 0.98 1.03
Coil
T.C. S.C. KW
12 Johnson Controls Unitary Products
Page 13
350154-YTG-B-0408
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH04811 INDOOR COIL MODEL NO. FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 950 1000 1050
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 35.4 36.6 36.2 39.8 42.3 36.1 37.2 36.8 40.2 42.9 36.8 37.8 37.4 40.6 43.4 S.C. 34.3 31.8 26.9 27.2 21.7 34.8 32.5 27.6 27.8 22.0 35.3 33.3 28.2 28.5 22.3 K.W. 1.50 1.50 1.49 1.48 1.48 1.50 1.49 1.49 1.48 1.47 1.49 1.49 1.49 1.47 1.47
T.C. 34.0 34.9 34.5 37.8 40.4 34.6 35.4 35.0 38.2 40.9 35.2 36.0 35.5 38.6 41.5 S.C. 32.9 31.0 26.2 26.4 21.0 33.4 31.7 26.8 27.0 21.3 33.9 32.4 27.4 27.6 21.7 K.W. 1.81 1.81 1.81 1.80 1.79 1.81 1.81 1.80 1.79 1.78 1.80 1.80 1.80 1.79 1.78
T.C. 32.5 33.1 32.8 35.7 38.5 33.1 33.7 33.2 36.2 39.0 33.7 34.2 33.6 36.6 39.5 S.C. 31.5 30.2 25.5 25.5 20.3 32.0 30.9 26.0 26.1 20.7 32.5 31.6 26.6 26.7 21.1 K.W. 2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.11 2.11 2.09
T.C. 31.1 31.4 31.1 33.7 36.6 31.7 31.9 31.4 34.2 37.1 32.2 32.4 31.7 34.6 37.6 S.C. 30.1 29.4 24.8 24.7 19.6 30.6 30.1 25.3 25.3 20.0 31.1 30.8 25.8 25.8 20.4 K.W. 2.44 2.44 2.44 2.43 2.41 2.43 2.43 2.43 2.43 2.41 2.43 2.43 2.43 2.42 2.40
T.C. 29.4 29.7 28.9 31.5 34.2 30.0 30.2 29.3 31.9 34.6 30.5 30.7 29.6 32.3 35.0 S.C. 28.5 27.8 23.8 23.8 18.7 28.9 28.5 24.3 24.4 19.1 29.4 29.1 24.8 24.9 19.6 K.W. 2.86 2.87 2.87 2.87 2.84 2.86 2.86 2.86 2.86 2.84 2.86 2.86 2.86 2.85 2.84
T.C. 27.8 28.0 26.9 29.3 31.9 28.4 28.6 27.2 29.7 32.2 28.9 29.1 27.6 30.1 32.5 S.C. 26.9 26.3 22.9 23.0 17.8 27.4 26.9 23.4 23.5 18.3 27.8 27.5 23.9 24.1 18.7 K.W. 3.28 3.28 3.29 3.29 3.26 3.27 3.28 3.28 3.27 3.26 3.27 3.27 3.28 3.27 3.26
T.C. 26.2 26.4 24.8 27.1 29.6 26.7 26.9 25.2 27.5 29.8 27.2 27.5 25.6 27.9 30.0 S.C. 25.4 24.8 21.9 22.1 16.9 25.8 25.4 22.4 22.7 17.4 26.2 26.0 22.9 23.3 17.9 K.W. 3.69 3.70 3.71 3.71 3.67 3.69 3.69 3.70 3.69 3.67 3.69 3.69 3.70 3.68 3.68
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Air Handler Coil
AV/SV48D 0.97 0.97 1.00 AV/SV60D 0.97 0.97 1.00 F4FV060 0.99 0.98 1.01 MV16C FC/MC/PC48C 1.00 1.00 0.99 MV16C FC/MC/PC48D 1.00 1.00 0.99 MV16C UC48D 1.00 1.00 0.99 MV20D FC/MC/PC48D 1.00 1.00 1.00 MV20D UC48D 1.00 1.00 1.00 MV20D FC/MC62D 1.00 1.00 1.00
T.C. S.C. KW
Variable Speed Furnace
PV8*C16 FC/MC/PC48C 0.97 0.97 0.98 PV8*C16 FC/MC/PC48D 0.97 0.97 0.98 PV8*C16 UC48D 0.97 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 PV8*C20 FC/MC/PC48D 1.00 1.00 0.99 PV8*C20 UC48D 1.00 1.00 0.99 P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.98 P(C,V)9*C16 FC/MC/PC48D 1.01 1.02 0.98 P(C,V)9*C16 UC48D 1.01 1.02 0.98 P(C,V)9*C20 FC/MC/PC48C 0.99 0.99 1.00 P(C,V)9*C20 FC/MC/PC48D 0.99 0.99 1.00 P(C,V)9*C20 UC48D 0.99 0.99 1.00 P(C,V)9*D20 FC/MC/PC48D 0.99 0.99 1.00 P(C,V)9*D20 UC48D 0.99 0.99 1.00 PV8*C20 FC/MC62D 1.00 1.00 0.99 P(C,V)9*C20 FC/MC62D 1.00 1.00 1.00 P(C,V)9*D20 FC/MC62D 0.99 0.99 1.00 P(C,V)9*D20 HC60D 0.95 0.95 1.00
Coil
T.C. S.C. KW
Johnson Controls Unitary Products 13
Page 14
350154-YTG-B-0408
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH04811 INDOOR COIL MODEL NO. FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1500 1600 1700
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 48.7 49.9 49.0 53.2 56.4 49.6 50.4 49.5 54.4 56.8 50.5 50.9 50.0 55.5 57.2 S.C. 48.0 44.9 38.2 37.9 29.7 48.9 46.3 39.1 39.0 30.3 49.7 47.6 40.0 40.1 30.9 K.W. 2.53 2.57 2.56 2.64 2.71 2.58 2.61 2.61 2.67 2.75 2.64 2.67 2.66 2.72 2.79
T.C. 46.8 47.7 46.8 50.9 53.6 47.6 48.2 47.2 51.8 54.0 48.3 48.8 47.6 52.5 54.4 S.C. 46.2 43.8 37.1 36.8 28.7 46.9 45.0 38.0 37.9 29.3 47.6 46.2 38.9 38.9 29.9 K.W. 2.89 2.91 2.90 2.98 3.05 2.93 2.96 2.95 3.02 3.09 2.99 3.01 3.00 3.07 3.15
T.C. 45.0 45.5 44.5 48.6 50.9 45.6 46.1 44.9 49.1 51.3 46.2 46.6 45.2 49.6 51.6 S.C. 44.3 42.6 35.9 35.7 27.8 44.9 43.7 36.9 36.7 28.4 45.6 44.8 37.8 37.7 28.9 K.W. 3.24 3.26 3.25 3.33 3.40 3.29 3.31 3.29 3.37 3.44 3.34 3.36 3.34 3.42 3.50
T.C. 43.1 43.4 42.2 46.3 48.2 43.5 43.9 42.5 46.5 48.5 44.0 44.4 42.9 46.6 48.8 S.C. 42.4 41.5 34.8 34.6 26.9 43.0 42.4 35.7 35.6 27.4 43.5 43.3 36.7 36.5 27.9 K.W. 3.59 3.61 3.60 3.68 3.75 3.64 3.66 3.64 3.72 3.79 3.69 3.71 3.69 3.77 3.85
T.C. 40.7 41.0 39.6 43.5 45.2 41.2 41.5 39.9 43.7 45.4 41.6 41.9 40.1 43.9 45.6 S.C. 40.1 39.3 33.5 33.5 25.8 40.6 40.1 34.4 34.4 26.3 41.1 40.8 35.4 35.3 26.8 K.W. 4.10 4.12 4.10 4.18 4.25 4.15 4.16 4.14 4.22 4.29 4.21 4.22 4.19 4.27 4.35
T.C. 38.5 38.7 37.2 40.7 42.4 38.9 39.1 37.3 40.9 42.5 39.3 39.5 37.4 41.2 42.5 S.C. 37.9 37.2 32.3 32.4 24.9 38.4 37.8 33.2 33.3 25.3 38.8 38.4 34.1 34.2 25.7 K.W. 4.60 4.60 4.58 4.67 4.74 4.65 4.65 4.62 4.71 4.78 4.70 4.71 4.67 4.76 4.83
T.C. 36.2 36.4 34.7 37.9 39.6 36.6 36.8 34.7 38.2 39.6 36.9 37.1 34.7 38.4 39.5 S.C. 35.7 35.1 31.1 31.3 23.9 36.1 35.6 32.0 32.2 24.3 36.5 36.0 32.8 33.1 24.6 K.W. 5.09 5.09 5.07 5.16 5.23 5.14 5.14 5.11 5.20 5.27 5.20 5.21 5.16 5.25 5.32
Multipliers for determining the performance with other indoor sections
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Air Handler Coil
AV/SV48D 0.96 0.96 0.99 AV/SV60D 0.96 0.96 0.99 F4FV060 0.96 0.96 0.98 MV16C FC/MC/PC48C 0.99 0.99 0.99 MV16C FC/MC/PC48D 0.99 0.99 0.99 MV16C UC48D 0.99 0.99 0.99 MV20D FC/MC/PC48D 0.99 0.99 1.00 MV20D UC48D 0.99 0.99 1.00 MV20D FC/MC62D 1.00 1.00 1.00
T.C. S.C. KW
Variable Speed Furnace
PV8*C16 FC/MC/PC48C 0.97 0.97 1.01 PV8*C16 FC/MC/PC48D 0.97 0.97 1.01 PV8*C16 UC48D 0.97 0.97 1.01 PV8*C20 FC/MC/PC48C 0.98 0.98 1.02 PV8*C20 FC/MC/PC48D 0.98 0.98 1.02 PV8*C20 UC48D 0.98 0.98 1.02 P(C,V)9*C16 FC/MC/PC48C 0.98 0.98 1.03 P(C,V)9*C16 FC/MC/PC48D 0.98 0.98 1.03 P(C,V)9*C16 UC48D 0.98 0.98 1.03 P(C,V)9*C20 FC/MC/PC48C 0.98 0.98 1.02 P(C,V)9*C20 FC/MC/PC48D 0.98 0.98 1.02 P(C,V)9*C20 UC48D 0.98 0.98 1.02 P(C,V)9*D20 FC/MC/PC48D 0.98 0.98 1.00 P(C,V)9*D20 UC48D 0.98 0.98 1.00 PV8*C20 FC/MC62D 0.99 0.99 1.01 P(C,V)9*C20 FC/MC62D 0.99 0.99 1.02 P(C,V)9*D20 FC/MC62D 0.99 0.99 1.01 P(C,V)9*D20 HC60D 0.95 0.95 1.00
Coil
T.C. S.C. KW
14 Johnson Controls Unitary Products
Page 15
350154-YTG-B-0408
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH06011 INDOOR COIL MODEL NO. FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1100 1150 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 38.1 44.0 43.9 47.7 52.4 39.7 44.2 44.3 48.1 53.0 41.4 44.3 44.7 48.5 53.5 S.C. 37.2 35.7 30.6 30.0 24.5 38.8 36.5 31.2 30.6 24.9 40.4 37.3 31.7 31.2 25.3 K.W. 3.20 1.94 1.94 1.91 1.92 2.79 1.94 1.94 1.91 1.90 2.37 1.95 1.94 1.92 1.88
T.C. 37.5 42.0 42.0 45.7 50.2 39.2 42.4 42.3 46.1 50.8 40.8 42.8 42.7 46.5 51.3 S.C. 36.6 35.0 29.8 29.4 23.8 38.2 35.8 30.4 30.0 24.2 39.8 36.6 30.9 30.6 24.6 K.W. 3.20 2.36 2.36 2.33 2.34 2.78 2.36 2.36 2.34 2.32 2.37 2.37 2.36 2.35 2.31
T.C. 37.0 40.1 40.0 43.8 48.1 38.6 40.7 40.4 44.2 48.6 40.2 41.3 40.7 44.5 49.1 S.C. 36.1 34.2 29.0 28.7 23.1 37.7 35.0 29.6 29.3 23.5 39.2 35.8 30.1 29.9 23.8 K.W. 3.20 2.78 2.78 2.75 2.76 2.78 2.78 2.78 2.76 2.75 2.37 2.78 2.78 2.77 2.74
T.C. 36.5 38.2 38.1 41.9 45.9 38.1 39.0 38.4 42.2 46.4 39.7 39.8 38.7 42.5 46.9 S.C. 35.6 33.5 28.2 28.1 22.4 37.1 34.3 28.8 28.7 22.7 38.7 35.0 29.3 29.2 23.1 K.W. 3.20 3.19 3.20 3.17 3.17 2.78 3.20 3.20 3.18 3.17 2.37 3.20 3.20 3.19 3.17
T.C. 34.2 35.5 35.3 38.8 42.7 35.4 36.1 35.6 39.1 43.1 36.6 36.7 35.8 39.3 43.5 S.C. 33.4 31.9 26.7 26.8 21.0 34.6 32.6 27.3 27.3 21.4 35.7 33.2 27.8 27.8 21.8 K.W. 3.76 3.75 3.75 3.73 3.73 3.48 3.75 3.75 3.74 3.73 3.20 3.76 3.76 3.75 3.74
T.C. 32.0 32.9 32.6 35.8 39.7 32.8 33.3 32.9 36.0 39.9 33.5 33.7 33.1 36.3 40.2 S.C. 31.3 30.4 25.3 25.4 19.7 32.0 30.9 25.9 25.9 20.1 32.8 31.5 26.4 26.4 20.5 K.W. 4.30 4.29 4.29 4.28 4.28 4.16 4.29 4.29 4.28 4.28 4.02 4.29 4.29 4.29 4.28
T.C. 29.9 30.3 30.0 32.7 36.6 30.2 30.5 30.1 33.0 36.7 30.5 30.6 30.3 33.2 36.9 S.C. 29.2 28.9 23.9 24.1 18.3 29.5 29.3 24.4 24.5 18.8 29.8 29.7 24.9 24.9 19.3 K.W. 4.84 4.82 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Air Handler Coil
AV/SV60D 0.99 0.99 1.00 F4FV060 0.99 0.99 1.02 MV20D FC/MC/PC60D 0.95 0.95 1.00 MV20D UC60D 0.95 0.95 1.00 MV20D FC/MC62D 1.00 1.00 1.00
T.C. S.C. KW
Variable Speed Furnace
PV8*C20 FC/PC60C 0.97 0.97 1.01 PV8*C20 FC/MC/PC60D 0.97 0.97 1.01 PV8*C20 UC60D 0.97 0.97 1.01 P(C,V)9*C20 FC/PC60C 0.96 0.96 1.01 P(C,V)9*C20 FC/MC/PC60D 0.96 0.96 1.01 P(C,V)9*C20 UC60D 0.96 0.96 1.01 P(C,V)9*D20 FC/MC/PC60D 0.95 0.95 1.00 P(C,V)9*D20 UC60D 0.95 0.95 1.00 PV8*C20 FC/MC62D 1.02 1.02 1.01 P(C,V)9*C20 FC/MC62D 1.01 1.01 1.00 P(C,V)9*D20 FC/MC62D 1.00 1.00 1.00 P(C,V)9*D20 HC60D 0.95 0.95 1.00
Coil
T.C. S.C. KW
Johnson Controls Unitary Products 15
Page 16
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH06011 INDOOR COIL MODEL NO. FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
ID CFM 1750 1850 1950
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 57.1 61.0 60.6 66.2 71.1 58.0 61.4 61.2 66.8 72.2 58.8 61.6 61.8 67.3 73.3 S.C. 58.1 53.7 44.6 44.7 36.4 59.0 54.7 46.2 45.8 36.6 59.8 55.6 47.7 46.8 36.8 K.W. 3.20 3.25 3.26 3.32 3.36 3.27 3.32 3.31 3.39 3.44 3.36 3.40 3.38 3.47 3.53
T.C. 55.3 58.5 58.0 63.4 68.2 56.0 58.8 58.4 63.9 68.9 56.7 59.1 58.7 64.3 69.5 S.C. 56.3 52.5 43.9 43.6 34.8 57.0 53.5 44.9 44.6 34.9 57.7 54.5 45.8 45.6 34.9 K.W. 3.69 3.74 3.74 3.80 3.86 3.77 3.80 3.79 3.87 3.93 3.85 3.88 3.86 3.95 4.01
T.C. 53.6 55.9 55.4 60.6 65.3 54.1 56.2 55.5 60.9 65.5 54.6 56.5 55.6 61.2 65.8 S.C. 54.5 51.3 43.2 42.5 33.1 55.1 52.4 43.6 43.5 33.1 55.6 53.4 44.0 44.4 33.0 K.W. 4.19 4.23 4.22 4.29 4.35 4.26 4.29 4.28 4.35 4.41 4.34 4.36 4.35 4.43 4.49
T.C. 51.8 53.3 52.8 57.8 62.4 52.2 53.6 52.7 58.0 62.2 52.6 53.9 52.5 58.2 62.0 S.C. 52.7 50.1 42.5 41.5 31.5 53.1 51.3 42.4 42.3 31.4 53.5 52.4 42.1 43.2 31.2 K.W. 4.69 4.71 4.70 4.77 4.84 4.76 4.77 4.76 4.83 4.90 4.83 4.85 4.83 4.91 4.97
T.C. 48.6 49.8 49.3 53.9 58.3 49.1 50.1 49.3 54.1 58.2 49.5 50.4 49.2 54.2 58.1 S.C. 49.5 47.7 40.5 39.8 30.1 50.0 48.7 40.7 40.6 30.1 50.4 49.6 40.8 41.3 30.1 K.W. 5.39 5.40 5.38 5.46 5.54 5.46 5.47 5.44 5.53 5.60 5.54 5.55 5.52 5.60 5.67
T.C. 45.6 46.3 46.0 50.2 54.3 46.1 46.7 46.0 50.3 54.3 46.5 47.1 46.0 50.4 54.2 S.C. 46.4 45.4 38.6 38.2 28.7 46.9 46.2 39.0 38.9 29.0 47.4 46.9 39.4 39.6 29.1 K.W. 6.06 6.07 6.04 6.13 6.22 6.14 6.14 6.11 6.20 6.28 6.23 6.22 6.19 6.28 6.36
T.C. 42.6 42.8 42.6 46.4 50.3 43.1 43.3 42.7 46.5 50.4 43.5 43.7 42.7 46.5 50.4 S.C. 43.4 43.2 36.6 36.6 27.4 43.9 43.7 37.4 37.2 27.8 44.3 44.1 38.1 37.8 28.2 K.W. 6.74 6.75 6.71 6.80 6.89 6.82 6.82 6.78 6.87 6.96 6.91 6.90 6.86 6.96 7.04
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Air Handler Coil
AV/SV60D 0.96 0.96 0.99 F4FV060 0.96 0.96 0.99 MV20D FC/MC/PC60D 0.96 0.96 0.99 MV20D UC60D 0.96 0.96 0.99 MV20D FC/MC62D 1.00 1.00 1.00
Subject to change without notice. Printed in U.S.A. 350154-YTG-B-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 350154-YTG-A-0108
T.C. S.C. KW
Variable Speed Furnace
PV8*C20 FC/PC60C 0.95 0.95 1.00 PV8*C20 FC/MC/PC60D 0.95 0.95 1.00 PV8*C20 UC60D 0.95 0.95 1.00 P(C,V)9*C20 FC/PC60C 0.93 0.93 0.99 P(C,V)9*C20 FC/MC/PC60D 0.93 0.93 0.99 P(C,V)9*C20 UC60D 0.93 0.93 0.99 P(C,V)9*D20 FC/MC/PC60D 0.93 0.93 0.98 P(C,V)9*D20 UC60D 0.93 0.93 0.98 PV8*C20 FC/MC62D 0.98 0.98 1.01 P(C,V)9*C20 FC/MC62D 0.97 0.97 1.00 P(C,V)9*D20 FC/MC62D 0.97 0.97 0.99 P(C,V)9*D20 HC60D 0.94 0.94 0.98
Coil
T.C. S.C. KW
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Loading...