Yokogawa YPP6300 User Manual

Page 1
YPP6300 Pulse Input Rate/Totalizer
Instruction Manual
Pulse, Open Collector, NPN, PNP, TTL, Switch Contact,
Gate Function for Rate Dis play of Slow Pulse Rates
NEMA 4X, IP65 Front
Universal 85-265 VAC, or 12/24 VDC Input Power Models
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Isolated 24 VDC Transmitter Power Supply
Programmable Displays & Function Keys
Sunlight Readable Display Models
Rate Displayed as Units per Second, Minute, Hour, or Day
Total, Grand Total or Non-Resettable Grand Total
9-Digit Totalizer with Total Overflow Feature
K-Factor Calibration or Scale with up to 32-Point Linearization
2 or 4 Relays + Isolated 4-20 mA Output for Rate/Total/Grand Total
External 4-Relays & Digital I/O Expansion Modules
USB, RS-232 & RS-485 Serial Communication Options
Modbus
Configure, Monitor, and Datalog from a PC with
Free PROPLUS Software
®
RTU Communication Protocol Standard
2 Dart Road • Newnan, Georgia 30265 770-253-7000 • 800-888-6400 Fax: 770-251-2088 • www.yokogawa-usa.com
Page 2
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual Disclaimer
The information contained in this document is subject to change without notice. Yokogawa Corporation of America makes no representations or warranties with respect to the contents hereof; and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
WARNING:
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Yokogawa Corporation of America shall not be held liable for damages resulting from such improper use.
WARNING: Risk of electric shock or personal injury.
Limited Warranty
Yokogawa Corporation of America warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Yokogawa Corporation of America’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
All trademarks mentioned in this document are the property of their respective owners.
© 2011-2012 Yokogawa Corporation of America. All rights reserved.
www.yokogawa-usa.com
2
Page 3
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Table of Contents
INTRODUCTION ------------------------------------------------------------- 7 ORDERING INFORMATION ---------------------------------------------- 8 SPECIFICATIONS ----------------------------------------------------------- 9
General ------------------------------------------------------------------------------- 9 Rate Input ------------------------------------------------------------------------- 10 Rate/Totalizer -------------------------------------------------------------------- 11 Relays ------------------------------------------------------------------------------ 13 Isolated 4-20 mA Transmitter Output ------------------------------------ 14 Modbus® RTU Serial Communications ---------------------------------- 15 YPPA1044 Digital Input & Output Expansion Module -------------- 15
COMPLIANCE INFORMATION ---------------------------------------- 16
Safety ------------------------------------------------------------------------------- 16 Electromagnetic Compatibility --------------------------------------------- 16
SAFETY INFORMATION ------------------------------------------------ 17 INSTALLATION ------------------------------------------------------------ 18
Unpacking ------------------------------------------------------------------------- 18 Panel Mounting Instructions ------------------------------------------------ 18 Configuration for 12 or 24 VDC Power Option ------------------------ 20 Transmitter Supply Voltage Selection (P+, P-) ----------------------- 21 Connections ---------------------------------------------------------------------- 21
Connectors Labeling --------------------------------------------------------- 22 Power Connections ---------------------------------------------------------- 22 Signal Connections ---------------------------------------------------------- 23 Modbus RTU Serial Communications ----------------------------------- 25 Relay Connections ----------------------------------------------------------- 25 Switching Inductive Loads -------------------------------------------------- 26 F4 Digital Input Connections ----------------------------------------------- 27 4-20 mA Output Connections ---------------------------------------------- 27 Analog Output Transmitter Power Supply ------------------------------ 27 External Relay & Digital I/O Connections ------------------------------ 28 Interlock Relay Feature ----------------------------------------------------- 29
SETUP AND PROGRAMMING ----------------------------------------- 30
Front Panel Buttons and Status LED Indicators --------------------- 31 Display Functions and Messages ----------------------------------------- 32 Main Menu ------------------------------------------------------------------------ 36 Setting Numeric Values ------------------------------------------------------ 37 Setting Up the Rate/Totalizer Meter (setup) --------------------------- 38
Setting the Input Signal (Input) ------------------------------------------ 39
3
Page 4
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Totalizer Features (total) ---------------------------------- 39 Setting the Input Units or Custom Tags (units) ---------------------- 40 Setting the Decimal Point (dEc pt) -------------------------------------- 41 Programming the Rate/Totalizer (prog) -------------------------------- 41
K-Factor Calibration (Factor) ----------------------------------------- 42 Multi-Point Calibration & Scaling -------------------------------------- 42 PROPLUS Software ------------------------------------------------------ 42 Scaling the Meter (SCALE) ---------------------------------------------- 43 Gate Function (Gate) ---------------------------------------------------- 44 Contact De-Bounce Filter (FiLter) ---------------------------------- 45 Time Base, Total Conversion Factor & Total Reset -------------- 46
Calibrating the Meter with External Source (Cal) ----------------- 47 Setting the Display Parameter & Intensity (dsplay) ----------------- 48 Display Setup Menu --------------------------------------------------------- 49
Setting the Relay Operation (relay) ------------------------------------- 50
Relay Assignment (Assign) ----------------------------------------------- 51 Setting the Relay Action ---------------------------------------------------- 52 Programming Set and Reset Points ------------------------------------- 53 Setting Fail-Safe Operation ------------------------------------------------ 53 Programming Time Delay -------------------------------------------------- 53
Relay and Alarm Operation Diagrams ----------------------------------- 54
High Alarm Operation (Set > Reset) ------------------------------------- 54 Low Alarm Operation (Set < Reset) -------------------------------------- 55 High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 56 Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 57 Alternation Control Operation --------------------------------------------- 58 Rate Relay Sampling Operation ------------------------------------------ 59 Total Relay Sampling Operation ------------------------------------------ 59 Time Delay Operation ------------------------------------------------------- 60
Relay Operation Details ------------------------------------------------------ 61
Overview ------------------------------------------------------------------------ 61 Relays Auto Initialization ---------------------------------------------------- 61 Fail-Safe Operation ---------------------------------------------------------- 61 Front Panel LEDs ------------------------------------------------------------- 62 Latching and Non-Latching Relay Operation -------------------------- 62 Non-Latching Relay (Auto) ------------------------------------------------- 63 Non-Latching Relay (A-nman) --------------------------------------------- 63 Latching Relay (LatcH) ----------------------------------------------------- 63 Latching Relay (Lt-Clr) ---------------------------------------------------- 64 Acknowledging Relays ------------------------------------------------------ 64 Setting Up the Interlock Relay (Force On) Feature ------------------ 65
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 66 Reset Menu (reset) ------------------------------------------------------------ 67
4
Page 5
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Control Menu (Contrl) -------------------------------------------------------- 67 Setting Up the Password (pass) ------------------------------------------- 68
Protecting or Locking the Meter ------------------------------------------- 68 Total Reset Password & Non-Resettable Total ----------------------- 69 Making Changes to a Password Protected Meter -------------------- 70 Disabling Password Protection -------------------------------------------- 70
Advanced Features Menu ---------------------------------------------------- 71
Advanced Features Menu & Display Messages ---------------------- 72 Rounding Feature (round) ------------------------------------------------- 75 Modbus RTU Serial Communications (serial) ---------------------- 75 Select Menu (SElEct) ------------------------------------------------------- 76 Signal Input Conditioning (Functn) -------------------------------------- 76 Multi-Point Linearization (Linear) ---------------------------------------- 77 Low-Flow Cutoff (CutofF) -------------------------------------------------- 78 Analog Output Programming (AoutPr) ---------------------------------- 78 Programmable Function Keys User Menu (user) -------------------- 79 Meter Copy Function (Copy) ----------------------------------------------- 80
METER OPERATION ----------------------------------------------------- 82
Front Panel Buttons Operation -------------------------------------------- 82 Function Keys Operation ---------------------------------------------------- 82 F4 Operation --------------------------------------------------------------------- 83 Maximum/Minimum Readings ---------------------------------------------- 83
TROUBLESHOOTING ---------------------------------------------------- 84
Diagnostics Menu (diag) ----------------------------------------------------- 84
Determining Software Version -------------------------------------------- 84
Reset Meter to Factory Defaults ------------------------------------------- 85
Factory Defaults & User Settings ----------------------------------------- 86
Troubleshooting Tips --------------------------------------------------------- 89 Alphabetical List of Display Functions & Messages --------------- 90
5
Page 6
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Table of Figures
Figure 1: 1/8 DIN Panel Cutout and Mounting ................................... 18
Figure 2: Meter Dimensions - Side View ............................................ 19
Figure 3: Meter Dimensions - Top View ............................................. 19
Figure 4: Jumper Configuration for 12/24 VDC Power ..................... 20
Figure 5: Transmitter Supply Voltage Selection ............................... 21
Figure 6: Connector Labeling for Fully Loaded YPP6300 ................ 22
Figure 7: Power Connections ............................................................. 22
Figure 8: Flowmeter Powered by Internal Power Supply ................. 23
Figure 9: Flowmeter Powered by External Supply ........................... 23
Figure 10: Self-Powered Magnetic Pickup Coil Flowmeter .............. 23
Figure 11: Relay Connections ............................................................ 25
Figure 12: AC and DC Loads Protection ........................................... 26
Figure 13: Low Voltage DC Loads Protection ................................... 26
Figure 14. F4 Digital Input Connections ............................................ 27
Figure 15: 4-20 mA Output Connections ........................................... 27
Figure 16: Expansion Modules & DIN Rail Mounting Kit .................. 28
Figure 17: External Relays Module Connections ............................. 28
Figure 18: Digital I/O Module Connections ....................................... 29
Figure 19: Interlock Connections ....................................................... 29
Figure 20: Acknowledge Relays w/Function Key or Digital Input ... 64
Figure 21: Meter Copy Connection .................................................... 80
Figure 22: 1/8 DIN Panel Cutout Template ........................................ 97
6
Page 7
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
INTRODUCTION
The PROPLUS YPP6300 is a multi purpose, easy to use pulse rate/totalize r ideal for flow rate, total, and control applications . It accepts pulse (e.g. ±40 mV to ±8 V), square wave (0-5 V, 0-12 V, or 0-24 V), open collector, NPN, PNP , TTL or switch contact signals. Three of the front panel buttons can be custom-programmed for specific operation.
The basic model includes an isolated 24 VDC transmitter po wer supply that can be used to power the input tran smitter or other devices. An addit ional isolated 24 VDC power supply is included with the 4-20 mA outp ut option. standard.
A fully loaded YPP6300 pulse rate/totalizer meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power su pplies. The YPP6 300 capabilities may be enhanced by adding the following external expansion modules: four SPST relays (creating an ei ght-relay rate/tot alizer), two digital I/O m odules with four inp uts and four outputs each, and RS-232, RS-485, and USB communication adapters.
The eight relays can be us ed for alarm indicatio n or process control applic ations. The 4-20 mA isolated output , Modbus RTU serial comm unications, and digital I/ O options make the YPP63 00 an excellent additio n to any system.
A digital input is
7
Page 8
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
ORDERING INFORMATION
Standard Models
85-265 VAC Model
YPP6300-6R0 YPP6300-7R0 No options
YPP 6300-6R2 YPP6300-7R2 2 relays
YPP 6300-6R3 YPP6300-7R3 4-20 mA output
YPP 6300-6R4 YPP6300-7R4 4 relays
YPP 6300-6R5 YPP6300-7R5 2 relays & 4-20 mA output
YPP 6300-6R7 YPP6300-7R7 4 relays & 4-20 mA output
SunBright Display Models
85-265 VAC Model
YPP6300-6H0 YPP6300-7H0 No options
YPP6300-6H2 YPP6300-7H2 2 relays
YPP6300-6H3 YPP6300-7H3 4-20 mA output
YPP6300-6H4 YPP6300-7H4 4 relays
YPP6300-6H5 YPP6300-7H 5 2 relays & 4-20 mA outpu t
YPP6300-6H7 YPP6300-7H 7 4 relays & 4-20 mA outpu t
Accessories
Model Description
YPPA1002 DIN rail mounting kit for two expansion modules
YPPA1004 4 SPST (Form A) relays
YPPA1044 4 digital inputs & 4 digital outputs (2 may be connected)
YPPA1200 Meter copy cable
YPPA1232 RS-232 serial adapter
YPPA1485 RS-485 serial adapter
YPPA8008 USB serial adapter
YPPA7485-I RS-232 to RS-422/485 isolated converter
YPPA7485-N RS-232 to RS-422/485 non-isolated converter
YPPA8232-N USB to RS-232 non-isolated converter
YPPA8485-I USB to RS-422/485 isolated converter
YPPA8485-N USB to RS-422/485 non-isolated converter YPPX6901 Suppressor (snubber): 0.01 µF/470 , 250 VAC
Enclosures
Model Description
YPPA2811 1 Meter Plastic NEMA 4X Enclosure
YPPA2812 2 Meter Plastic NEMA 4X Enclosure
12/24 VDC Model
12/24 VDC Model
Options Installed
Options Installed
8
Page 9
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
DISPLAY INTENSITY
DISPLAY UPDATE RATE
OVERRANGE
DISPLAY ASSIGNM ENT
PROGRAMMING METHODS
RECALIBRATION
MAX/MIN DISPLAY
PASSWORD
NON-VOLATILE MEMORY
POWER OPTIONS
FUSE
ISOLATED TRANSMITTER POWER SUPPLY
Upper display: 0.6" (15 mm) high, red LEDs Lower display: 0.46" (12 mm) high, red LEDs 6 digits: each (-99999 to 999999), with lead zero blanking.
Eight user selectable intensity levels
Rate: 10 per second; up to 1 per 100 se conds (and is a function of Low Gate setting)
Total: 10 per second (fixed)
Display flashes
The Upper and Lower displays may be assi gned to rate, total, grand total, alternate rate & total, max/min, units (lower display only), set points, Modbus input, & more.
Four front panel buttons, digital inputs, PC and PROPLUS software, Modbus registers, or cloning using Copy function.
All ranges are calibrated at the factor y to read frequency in Hz. No recalibration required.
Max/min readings reached by the proce ss are stored until reset by the user or until power to th e meter is cycled.
Three programmable passwords rest rict modification of programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
All programmed settings are stored in non -volatile memory for a minimum of ten years if po wer is lost.
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24 VDC ± 10%, 15 W max
Required external fuse: UL Recognized, 5 A max , slow blow; up to 6 meters may share one 5 A fuse
Terminals P+ & P-: 24 VDC ± 10%. 12/24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal jumper J4).
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA m ax for 5 or 10 VDC supply.
999999
9
Page 10
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
ISOLATION
OVERVOLTAGE CATEGORY
ENVIRONMENTAL
CONNECTIONS
ENCLOSURE
MOUNTING
TIGHTENING TORQUE
OVERALL DIMENSIONS
WEIGHT
WARRANTY
4 kV input/output-to-power line 500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II: Local level with smaller transient overvol tages than Installation Overvoltage Category III.
Operating temperature range: -40 to 65°C Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
Removable screw terminal blocks accept 12 to 2 2 AWG wire, RJ45 for external relays, digital I/O, and s erial communication adapters.
1/8 DIN, high impact plastic, UL 94V-0, co lor: black
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket ass emblies are provided.
Screw terminal connectors: 5 lb-in (0.56 Nm)
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
9.5 oz (269 g)
3 years parts & labor
Rate Input
INPUTS
LOW VOLTAGE MAG PICKUP (Isolated)
MINIMUM INPUT FREQUENCY
MAXIMUM INPUT FREQUENCY
INPUT IMPEDANCE
ACCURACY
TEMPERATURE DRIFT
MULTI-POINT LINE ARIZ ATIO N
Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 5 V @ 40 Hz; Modbus PV (Slave)
Sensitivity: 40 mVp-p to 8Vp-p
0.001 Hz Minimum frequency is dependent on high gate setting.
30,000 Hz (10,000 for low voltage mag pi ckup)
Pulse input: Greater than 300 kΩ @ 1 kHz. Open collector/switch input: 4.7 kΩ pull-up to 5 V.
±0.03% of calibrated span ±1 count
Rate display is not affected by changes in tem perature.
2 to 32 points
10
Page 11
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
LOW-FLOW CUTOFF
DECIMAL POINT
0-999999 (0 disables cutoff function)
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
CALIBRATION
K-FACTOR
CALIBRATION RANGE
FILTER
TIME BASE
GATE
F4 DIGITAL INPUT CONTACTS
F4 DIGITAL INPUT LOGIC LEVELS
May be calibrated using K-factor, internal ca libration, or by applying an external calibration sig nal.
Field programmable K-factor converts i nput pulses to rate in engineering units. May be progra mmed from 0.00001 to 999,999 pulses/unit.
Input 1 signal may be set anywhere in the ran ge of the meter; input 2 signal may be set anywhere ab ove or below input 1 setting.
Minimum input span between any t wo inputs is 10 Hz. An error message will appear if the input 1 a nd input 2 signals are too close together.
Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with lo w speed filter.
Second, minute, hour, or day
Low gate: 0.1-99.9 seconds
High gate: 2.0-999.9 seconds
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Rate/Totalizer
DISPLAY ASSIGNM ENT
RATE DISPLAY INDICATION
TOTAL DISPLAY & TOTAL OVERFLOW
ALTERNATING DISPLAY
The Upper and Lower displays may be assi gned to rate, total, grand total, alternate rate/total, alternate rate/grand total, set points, alternate rate/units , alternate total/units, alternate grand total/units, display Hi, di splay Lo, display Hi/Lo, display modbus, display units (lower displa y) and display Off (lower display).
-99999 to 999999, lead zero blankin g. “R” LED illuminates while displaying rate or frequency.
0 to 999,999; aut omatic lead zero bla nking. “T” LED is illuminated while displaying total or grand total. Up to 999,999,999 with total-overflo w feature. “ displayed to the left of total overflow and LED is illuminated.
Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds.
oF” is
11
Page 12
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
TOTAL DECIMAL POINT
TOTALIZER
TOTALIZER ROLLOVER
TOTAL OVERFLOW
OVERRIDE
TOTALIZER PRESETS
PROGRAMM­ABLE DE LAY ON RELEASE
TOTAL RESET
TOTAL RESET PASSWORD
NON­RESETTABLE TOTAL
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Total decimal point is independent of rate decimal point.
Calculates total based on rate and fi eld programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed.
Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display.
Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
Up to eight, user selectable under setup menu. An y set point can be assigned to total and ma y be programmed anywhere in the range of the meter fo r total alarm indication.
0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total.
If the meter is programmed to reset tota l to zero automatically when the preset is reached, th en a delay will occur before the total is reset.
Via front panel button, external contac t closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communic ations.
Total and grand total passwords may be en tered to prevent resetting the total or grand total from th e front panel.
The grand total can be programmed as a non-resettable total by entering the password “050873 ”.
Once the Grand Total has been programmed
!
Caution!
as “non-resettable” the feature cannot disabled.
be
12
Page 13
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Relays
RATING
NOISE SUPPRESSION
RELAY ASSIGNM ENT
DEADBAND
HIGH OR LOW ALARM
RELAY OPERATION
RELAY RESET
TIME DELAY
FAIL-SAFE OPERATION
AUTO INITIALIZATION
2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for in ductive loads
Noise suppression is recommended for each relay contact switching inductive loads; see page 26 for det ails.
Relays may be assigned to rate, total, or gran d total.
0-100% of span, user programmabl e
User may program any alarm for high or l ow trip point. Unused alarm LEDs and relays may be disable d (turn off).
Automatic (non-latching) Latching (requires manual acknowledge) Sampling (based on time) Alternation control (2 to 8 relays) Off (disable unused relays and enable Int erlock feature) Manual on/off control mode
User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when th e input passes the reset point or total is reset to zero.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (Latching with clear)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
0 to 999.9 seconds, on & off relay time delays Programmable and independent for eac h relay.
Programmable and independent for eac h relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
When power is applied to the meter, relays will reflect the state of the input to the meter.
13
Page 14
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
SCALING RANGE
CALIBRATION
ANALOG OUT PROGRAMMING
ACCURACY
TEMPERATURE DRIFT
ISOLATED TRANSMITTER POWER SUPPLY
EXTERNAL LOOP POWER SUPPLY
OUTPUT LOOP RESISTANCE
35 VDC (external)
Rate/process, total, grand total, max, min , set points 1-8, Modbus input or manual control mo de
1.000 to 23.000 mA for any display range.
Factory calibrated: 0.0 to 1000.0 = 4-20 mA output
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
± 0.1% FS ± 0.004 mA
0.4 µA/°C max from 0 to 65°C ambient,
0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC ± 10%. May be used to power the 4-20 mA output or other devices. Re fer to Figure 6 on page 22 and Figure 15 on page 27.
All models rated @ 40 mA max.
35 VDC maximum
Power supply Minimum Maximum
24 VDC
10 Ω 700 Ω
100 Ω 1200 Ω
14
Page 15
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Modbus® RTU Serial Communications
SLAVE ID
BAUD RATE
TRANSMIT TIME DELAY
DATA
PARITY
BYTE-TO-BYTE TIMEOUT
TURN AROUND DELAY
Note: Refer to the PROPLUS Modbus Register Tables located at www.yokogawa-usa.com for details.
1 – 247 (Meter address)
300 - 19,200 bps
Programmable between 0 and 199 ms
8 bit (1 start bit, 1 or 2 stop bits)
Even, Odd, or None with 1 or 2 stop bits
0.01 – 2.54 second
Less than 2 ms (fixed)
YPPA1044 Digital Input & Output Expansion Module
CHANNELS
SYSTEM
DIGITAL INPUT LOGIC HIGH
DIGITAL INPUT LOGIC LOW
DIGITAL OUTPUT LOGIC HIGH
DIGITAL OUTPUT LOGIC LOW
SOURCE CURRENT
SINK CURRENT
+5 V TERMINAL
4 digital inputs & 4 digital outputs per module
Up to 2 modules for a total of 8 inputs & 8 o utputs
3 to 5 VDC
0 to 1.25 VDC
3.1 to 3.3 VDC
0 to 0.4 VDC
10 mA maximum output current
1.5 mA minimum input current
To be used as pull-up for digital inputs only. Connect normally open contacts across +5 V & DI 1-4.
15
Page 16
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED
UL FILE NUMBER
FRONT PANEL
LOW VOLTAGE DIRECTIVE
Electromagnetic Compatibility
EMISSIONS
Radiated Emissions
AC Mains Conducted Emissions
IMMUNITY
RFI - Amplitude Modulated
Electrical Fast Transients
Electrostatic Discharge
RFI - Conducted
AC Surge
Surge
Power-Frequency Magnetic Field
Voltage Dips
Voltage Interruptions
USA & Canada UL 508 Industrial Control Equipment
E348677
UL Type 4X, NEMA 4X, IP65; panel gasket provided
EN 61010-1:2001 Safety requirements for measurement, con trol, and laboratory use
EN 55022:2006/A1:2007 Class A ITE emissions requirements
Class A
Class A
EN 61326-1:2006 Measurement, control, and laborator y equipment
EN 61000-6-2:2005 EMC heavy industrial generic immunity standar d
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
±2kV AC mains, ±1kV other
±4kV contact, ±8kV air
10V, 0.15-80 MHz, 1kHz 80% AM
±2kV Common, ±1kV Differential
1KV (CM)
3 A/m 70%V for 0.5 period
40%V for 5 & 50 periods 70%V for 25 periods
<5%V for 250 periods
16
Page 17
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Note:
Testing was conducted on YPP6300 meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.yokogawa-usa.com
SAFETY INFORMATION
Warning!
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
17
WARNING: Risk of electric shock or personal injury.
Page 18
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
A
A
INSTALLATION
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications. Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 20.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 for more detail s.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0 .16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Ins ert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Note: See
B
1.772"
(45mm)
Figure 22 on page 97 for 1/8 DIN Panel Cutout Template
3.622" (92 mm)
Square Corners to 0.060"
(1.5mm) Max Radius
Panel Cutout to DIN 43700
Toleran ces:
: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Gasket
Mounting
Bracket
Panel
Mounting
Screw
Removable Connectors
Figure 1: 1/8 DIN Panel Cutout and Mounting
18
Page 19
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Mounting Dimensions
Figure 2: Meter Dimensions - Side View
O
N
C
C
N
+
R
-
N
C
N
O
C
O
N
N
C
N
C
C
C
N
O
Figure 3: Meter Dimensions - Top View
19
Page 20
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Configuration for 12 or 24 VDC Power Option
Do not exceed voltage rating of the selected
Warning!
Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12 V as shown below.
configuration.
J9 CONFIGURATION
+ _
MAIN B OAR D
J9
12 V
24 V
Factory Default
M-LINK
24 VDC 12 VDC POWER
Figure 4: Jumper Configuration for 12/24 VDC Power
20
Page 21
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
Figure 5: Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety
!
Caution!
regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
21
Page 22
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Do not connect any equipment other than Yokogawa’s expansion modules, cables, or meters to the RJ45
Warning!
M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 6: Connector Labeling for Fully Loaded YPP6300
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 6. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
POWER
-
+
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 7: Power Connections
22
Page 23
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Signal Connections
Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminal is the return for the input signals.
The following figures show examples of signal connections.
Setup and programming is performed through the front panel buttons.
Figure 8: Flowmeter Powered by Internal Power Supply
Figure 9: Flowmeter Powered by External Supply
Figure 10: Self-Powered Magnetic Pickup Coil Flowmeter
23
Page 24
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Figure 11: NPN open Collector Input
Figure 12: PNP Sensor Powered by Internal Supply
Figure 13: Switch Input Connections
24
Page 25
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. For interfacing to the PROPLUS, use the YPPA1232 for RS-232, the YPPA1485 for RS-485, or the YPPA8008 for USB. The same port is used for interfacing with all expansion modules (e.g. external relays, digital I/O).
Use the YPPA1200 meter copy cable for meter-to-meter interfacing for cloning purposes (i.e. copying settings from one meter to other meters).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 6. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
RELAY4 RELAY3
4365 21
CNONO NC NC C
Figure 11: Relay Connections
RELAY2 RELAY1
4365 21
CNONO N C NC C
25
Page 26
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
C
C
R
R
Figure 12: AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC
network may also be installed across the load. Experiment for best results.
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
Figure 13: Low Voltage DC Loads Protection
RC Networks Available from Yokogawa
RC networks are available from Yokogawa and should be applied to each relay contact switching an inductive load. Part number: YPPX6901.
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Note:
26
Page 27
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure across F4 and COM, or with an active low signal applied to F4.
Figure 14. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
24 V
MA OUT
-
+
12-35 VDC
Power Supply
RI- I+
132
RELAY1
321
MA OUT
+
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
24 V
RI- I+
132
-
RELAY1
321
-
+
4-20 mA
Input Meter
Figure 15: 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
27
Page 28
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
External Relay & Digital I/O Connections
The relay and digital I/O expansion modules YPPA1004 & YPPA1044 are connected to the meter using the CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the
YPPA1044 must be removed on the second digital I/O module in order for the system to recognize it as module #2.
Do not connect or disconnect the expansion modules with the power on!
Warning!
More detailed instructions are provided with each optional expansion module.
Figure 16: Expansion Modules & DIN Rail Mounting Kit
RLY5 RLY6 RLY7 RLY8
12
NO C NO C NO C NO C
345678
Figure 17: External Relays Module Connections
28
Page 29
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
123456
+5 I1 I2 I3 I4 O1
5 VDC GND
DI 1-4 DO 1-4
78
O2 O3
910
O4 G
Figure 18: Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page
65). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 19: Interlock Connections
29
Page 30
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
SETUP AND PROGRAMMING
The meter has been factory calibrated to read input
frequency in Hz (pulses/sec). The calibration equipment is certified to NIST standards.
Use the K-Factor menu to match the rate/totalizer with
a flowmeter’s k-factor (pulse/unit of measure).
Or use the Scale menu to scale the pulse input
(pulse/sec) without a signal source.
Or use Cal menu to calibrate the rate/totalizer using a
signal source.
Overview
There are two switches, located to the right of the input connector, which must be configured according to the input level and type. Jumper J4 located inside the meter, behind the input signal connector, is used to select the excitation voltage (24 V*, 10 V or 5 V) which is supplied to the P+ and P- wiring terminals.
Setup and programming is done through the front panel buttons.
After power and input signal connections have been completed and verified, apply power to the meter.
Default setting
*
30
Page 31
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Front Panel Buttons and Status LED Indicators
Button Symbol
Note: F4 is a digital input. Alarms 5-8
are enabled when relay expansion module is installed.
Description LED Status
Menu 1-8 Alarm 1 – 8 indicator
Right arrow/F1 R Rate indicator
Up arrow/F2 T Total indicator
Enter/F3 G T Grand Total indicator
M
Total overflow indicator
Manual control relays &/or analog output
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit
or decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or press or hold to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the
advanced features of the meter.
31
Page 32
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Functions and Messages
The meter displays various func tions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Dis pla y P ara me ter Action/Setting Description
setup
Input
Total
unitS
rate
total
Gtotal
Dec pt
prog
InCAL
factor
sCalE
Cal
Inp 1
Dis 1
Inp 2
Dis 2
Setup
Input Enter Input selection menu
Total
Units
Rate
Total
Grand Total
Decimal point
Program
Input Calibration
K-factor Scaling
Scale
Calibrate
Input 1
Display 1
Input 2
Display 2
Enter Setup menu
Enable or disable totalizer fea tures
Select the display units/tags
Select the display units for rate
Select the display units for total
Select the display units for grand total
Set decimal point for rate, total , grand total
Enter the Program menu
Enter the Input Calibration menu
Programs unit to convert input p ulse to rate in engineering units
Enter the Scale menu
Enter the Calibrate menu
Calibrate input 1 signal or program input 1 value
Program display 1 value
Calibrate input 2 signal or program input 2 value (up to 32 points)
Program display 2 value (up to 32 points)
Error
T tb
Error
Total time base
Error, calibration not successf ul, check signal or programmed value
Program total time base
32
Page 33
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Dis pla y P ara me ter Action/Setting Description
T CF
T rst
GT tb
GT CF
GT rst
Auto
T dly
mAn
dsplay
big
Little
d-Inty
RELaY
Assign
Asign1
Total conversion factor
Total reset
Grand total time base
Grand total conversion factor
Grand total reset
Automatic
Time delay
Manual
Display
Upper display
Lower display
Display intensity
Relay
Assignment
Assign 1 Relay 1 assignment
Program total conversion factor
Program total reset mode: auto or manual
Program grand total time base
Program grand total conversion factor
Program grand total reset mode: auto or manual
Press Enter to set automatic t otal reset
Program time delay for total auto reset
Press Enter to reset total manual ly
Enter the Display menu
Press Enter to assign the Upper di splay parameter (default: PV or rate)
Press Enter to assign the lower di splay parameter (default: total)
Set display intensity level from 1 to 8
Enter the Relay menu
Assign relays to rate, total, grand total, or Modbus
rATE
totAL
G total
RLY 1
Act 1
Rate
Total
Grand total
Relay 1
Action 1
Assign relay to rate
Assign relay to total
Assign relay to grand total
Relay 1 setup
Set relay 1 action
33
Page 34
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Dis pla y P ara me ter Action/Setting Description
Auto
A-nman
LatcH
Lt-CLr
Altern
Sanmpl
OFF
Set 1
RSt 1
RLY 2
FaiLSF
FLS 1
on
off
Automatic
Auto-manual
Latching
Latching­cleared
Alternate
Sampling
Off
Set 1
Reset 1
Relay 2
Fail-safe Enter Fail-safe menu
Fail-safe 1
On
Fail-safe off
Set relay for automatic reset
Set relay for automatic & manu al reset any time
Set relay for latching operation (relays assigned to rate)
Set relay for latching operation with manual reset only after alarm condi tion has cleared (relays assigned to rate)
Set relay for alternation cont rol (relays assigned to rate)
Set relay for sampling operation
Disable relay and front panel s tatus LED (Select Off to enable Interloc k feature)
Program set point 1
Program reset point 1
Relays 2-8 setup
Note: Relays 5-8 are shown, only if expansion relay module is installed.
Set relay 1 fail-safe operation
Enable fail-safe operation
Disable fail-safe operation
DeLAY
DLY 1
On 1
OFF 1
Aout
Dis 1
Delay
Delay 1
On
Off
Analog output
Display 1
Enter relay Time Delay menu
Enter relay 1 time delay setup
Set relay 1 On time delay
Set relay 1 Off time delay
Enter the Analog output scaling menu
Program display 1 value
34
Page 35
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Dis pla y P ara me ter Action/Setting Description
Out 1
Dis 2
Out 2
reset
Rst Hi
Rst Lo
Rst HL
Rst t
Rst Gt
Contrl
Auto
mAn
pass
Pass 1* Password 1*
Total
Gtotal
nonrst
unloc
Output 1
Display 2
Output 2
Reset
Reset high
Reset low
Reset high & low
Reset total
Reset grand total
Control
Automatic
Manual
Password
Total password
Grand total password
Non­resettable
Unlocked
Program output 1 value (e.g. 4. 000 mA)
Program display 2 value
Program output 2 value (e.g. 20.0 00 mA)
Press Enter to access the Reset menu
Press Enter to reset max display
Press Enter to reset min display
Press Enter to reset max & min displays
Press Enter to reset total
Press Enter to reset grand total
Enter Control menu
Press Enter to set meter for a utomatic operation
Press Enter to manually control relays or analog output operation
Enter the Password menu
Set or enter Password 1* (*1, 2, or 3)
Set or enter password for m anual reset
Set or enter password for m anual reset
Non-resettable grand total set aft er entering “050873” for Gtotal password
Program password to lock meter
locd
999999
Locked
Flashing display
Enter password to unlock meter
Overrange condition
35
Page 36
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Main Menu
The main menu consists of the most commonly used functions: Reset,
Control, Setup
Press Menu button to enter Programming Mode then press the Up
arrow button to scroll through the main menu.
, and Password.
Press Menu, at any time, to exit and return to Run Mode. Changes
made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to memory only after pressing
Enter.
The display moves to the next menu every time a setting is
accepted by pressing Enter.
36
Page 37
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
.
V
A
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value.
The digit being changed is displayed brighter than the rest.
Press and hold up arrow to auto-increment the display value. Press the Enter button, at any time, to accept a setting or Menu button to exit without saving changes.
Select
Next Digit
004.000
004.000
dis 1 dis 1 dis 1
Increment
Digital
alue
005
000
ccept
Setting
Next
Setting
37
Page 38
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting Up the Rate/Totalizer Meter (setup)
The Setup menu is used to select:
1. Enable or disable totalizer features
2. Units for Rate, Total, and Grand Total
3. Decimal point position
4. Input Calibration
5. Display parameter and intensity
6. Relay operation
7. 4-20 mA analog output scaling
Press the Enter button to access any menu or press Up arrow button to scroll through choices. Press the Menu button to exit at any time.
38
Page 39
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Input Signal (Input)
There is a switch, located to the right of the input connector, which must be configured according to the input level and type. Jumper J4 located inside the meter, behind the input signal connector, is used to select the excitation voltage (24 V*, 10 V or 5 V) which is supplied to the P+ and P­wiring terminals.
Default setting
*
Enter the Input menu to enable or disable the totalizer features.
Setting the Totalizer Features (total)
Enable or disable the totalizer features by selecting “Yes” or “no” after the input type has been set up. If the totalizer features are disabled, most totalizer features and functions are hidden from the menus.
Note: The totalizer continues working in the background.
39
Page 40
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Input Units or Custom Tags (units)
Enter the input unit or custom tag that will be displayed if alternating rate, total, or grand total and units is selec ted in the is selec ted as the lower displ ay para meter. See the flow chart on page 49 to access the display menu to show the unit or tag on the lower display. The engineering units or custom legends can be set using the following 7-segment character set:
Display Character
0 1 2 3 4 5 6 7 8 9 A b C c d e f g 9 H h I I
j
Notes:
Degree symbol represented by (<) if programming with PROPLUS. The letters “m” and “w” use two 7-segment LEDs each; when selected the
characters to the right are shifted one position. Press and hold up arrow to auto-scroll the characters in the display.
0
1
2
3
4
5
6
7
8
9 A
b
C
c
d
E
F
G
g
H
h
I
i
J
40
units menu, or d unit
Display Character
k l
m
n O o p q r s t u v
uw
x y z
­/ [ ] =
!
K
L
m
n
O
o
P
q
r
S
t
u
V
w
X
Y
Z
-
/ ]
[
=
Degree(<)
Space
Page 41
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Decimal Point (dEc pt)
The decimal point may be set with up to five decimal places or with no decimal point at all. The rate, total, and grand total decimal points are independent.
Pressing the right arrow moves the decimal point one place to the right until no decimal point is displayed, then it moves to the leftmost position.
Pressing the up arrow moves the decimal point to the left.
Programming the Rate/Totalizer (prog)
It is very important that one reads the following information before programming the meter:
The meter has been factory calibrated to read input frequency in Hz
(pulses/sec). The calibration equipment is certified to NIST standards.
Use the K-Factor menu to match the rate/totalizer with a flowmeter’s
k-factor (pulse/unit of measure).
Or use the Scale menu to scale the pulse input (pulse/sec) without a
signal source.
Or use Cal menu to calibrate the rate/totalizer using a signal source.
Program menu contains the following menus:
The
1. K-Factor calibration
2. Scale without a signal source
3. Calibrate with a calibrated signal source
4. Total time base & conversion factor
5. Grand total time base & conversion factor
6. Total reset mode for total & grand total
Note: The Scale, Calibrate, and K-Factor functions are exclusive of each other. The meter uses the last function programmed. Only one of these methods can be employed at a time. The Scale and Calibrate functions can use up to 32 points (default is 2). The number of points should be set in the Advanced menu under the Multi-Point Linearization menu selection prior to scaling and calibration of the meter, see page 77 for details.
The pulse inputs may be calibrated or scaled to any display value within the range of the meter.
(Linear)
41
Page 42
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Additional parameters, not needed for most applications, are programmed in the
, page 71.
Menu
Advanced Features menu; see Advanced Features
K-Factor Calibration (Factor)
The meter may be calibrated using the K-Factor function. Most flowmeter manufacturers provide this information with the device. Enter the
K-Factor (Factor) menu and select the decimal point with highest
resolution possible and program the k-factor value (
i.e. pulses/gal). The
meter will automatically calculate the flow rate using the k-factor and the time base selected.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The number of points for multi-point calibration/scaling is set up in the
Advanced Features menu. Up to 32 linearization points may be selected.
See page 77 for details.
PROPLUS Software
The meter can also be programmed using the PC-based PROPLUS software available for free download at www.yokogawa-usa.com.
Data logging for one meter at the time is available with PROPLUS software. More advanced data acquisition may be accomplished by using any Modbus RTU compliant software.
In order to program the meter using a computer, the meter must be connected using a USB, RS-232 or RS-485 serial adapter, see ORDERING INFORMATION on page 8 for details.
42
Page 43
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Scaling the Meter (SCALE)
The pulse inputs can be scaled to display the process variable in engineering units.
A signal source is not needed to scale the meter; simply program the inputs and corresponding display values.
For instructions on how to program numeric
values see
Setting Numeric Values, page 37.
43
Page 44
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to input 2 during calibration or scaling, allowing the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected
backwards.
2. Minimum input span requirements not maintained.
3. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum allowed input span is 1.0 Hz, which is the minimum diffe rence between input 1 and input 2 signals requi red to complete the calibration or scaling of the meter.
Gate Function (Gate)
The gate function is used for displaying slow pulse rates. Using the programmable gate, the meter is able to display pulse rates as slow as 1 pulse every 999.9 seconds (0.001 Hz). The gate function can also be used to obtain a steady display reading with a fluctuating input signal.
The gate function (
Gate) is the first option in the Advanced Features
menu. There are two settings for the Gate, low gate (Lo G) and high gate
Hi G).
(
Low Gate (Lo G)
For most applications, low gate setting should be left at 1.0 second. Increase low gate setting to obtain a steadier rate display. The rate display will update in accordance with the low gate setting, for example if low gate is set at 10.0, the display will update every 10 seconds; changes in rate between updates will not be reflected until next display update.
High Gate (Hi G)
Set the high gate value to correspond to the highest expected pulse period (lowest pulse rate). For instance if the meter must display a rate when there is 1 pulse coming into the meter every 10 seconds, set the high gate to 11.0 seconds. When the signal is removed from the meter, the display will show the last reading for 11 seconds; then it will read zero.
44
Page 45
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Gate Settings
Slow Pulse Rate
Low Gate* (sec) High Gate (sec) Min Freq** (Hz)
1.0 2.0 0.5000
1.0 10.0 0.1000
1.0 20.0 0.0500
1.0 100.0 0.0100
1.0 200.0 0.0050
1.0 400.0 0.0025
1.0 800.0 0.0012
1.0 999.9 0.0010
*The low gate setting corresponds to the display update rate and is used to stabilize the display reading with a fluctuating signal.
**The minimum frequency is dependent on high gate setting.
Contact De-Bounce Filter (FiLter)
The filter function (FiLter) can be used for applications where the meter is set up to count pulses generated by switch contacts. The filter value can be set anywhere between 2 and 50, the higher the value, the greater the filtering.
The filter function (
Filter) is the second option in the Advanced
Features menu. There are two settings, Hi SPd (high speed) and Lo
(low speed), press ENTER when Lo SPd is displayed to enable the
SPd
filter function. Program the filter value, so that there are no extra counts when a contact closure is completed.
Filter Settings
Contact De-Bounce Filter
Filter Setting Speed Setting Max Freq (Hz)
2 Lo SPd 999
4 Lo SPd 499
8 Lo SPd 249
16 Lo SPd 124
32 Lo SPd 62
40 Lo SPd 50
50 Lo SPd 40
N/A Hi SPd 30,000
45
Page 46
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Time Base, Total Conversion Factor & Total Reset
The time base, total conversion factor, and total reset menus are located
Program menu.
in the
The total and grand total have their own independent settings. This means that one can be displaying the value in gallons while the other displays in million gallons, liters, m
3
, etc.
Total & Grand Total Reset
The totals can be programmed for manual or automatic reset. In the automatic reset mode, a programmable time delay is available to reset the total or grand total after the assigned preset is reached.
Non-Resettable Totalizer
The total and grand total can be password-protected to prevent unauthorized resets. The grand total can be programmed as a non-resettable total, see page 69 for details.
46
Page 47
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Calibrating the Meter with External Source (Cal)
To scale the meter without a signal
source refer to
K-Factor Calibration
42 or Scaling the Meter (
(Factor) on page
SCALE) on
page 43
The meter can be calibrated to display the process variable in engineering units by applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter.
The displ ay flashes
while sensing
the inputs
There is no need to warm up the meter before
performing the calibration procedure.
47
Page 48
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Display Parameter & Intensity (dsplay)
The upper display (Big) can be programmed to display:
1. Rate value
2. Total or grand total
3. Relay set points
4. Max & min values
5. Modbus input
6. Display rate and units
7. Rate and total
8. Rate and grand total
9. Total and units
10. Grand total and units
The lower display (
1. Rate value
2. Total or grand total
3. Relay s et p oints
4. Max & min values
5. Engineering units or custom legends
6. Modbus input
7. Off (no display)
8. Display rate and units
9. Rate and total
10. Rate and grand total
11. Total and units
12. Grand total and units
Display Intensity: The meter has eight display intensity levels to give the best performance under various lighting conditio ns. Select intensity 8 for outdoor applications. The default display intensity setting is 8.
Little) can be programmed to display:
48
Page 49
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Setup Menu
After setting up the input and the display, press the Menu button to exit programming and skip the rest of the setup menu. Press the Menu button again and the Up arrow to reach the
Program menu and complete
the scaling or calibration of the meter.
49
Page 50
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Relay Operation (relay)
This menu is used to set up the operation of the relays.
During setup, the relays do not follow the input and
!
Caution!
1. Relay assignment
a. Rate for low and high alarm
b. Total
c. Grand total
d. Modbus input
2. Relay action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
e. Alternation control (automatic reset only)
f. Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
3. Set and reset points
4. Fail-safe operation
a. On (enabled)
b. Off (disabled)
5. Time delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
they will remain in the state found prior to entering the Relay menu.
condition has cleared)
50
Page 51
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Relay Assignment (Assign)
The relays can be assigned to any of the following parameters:
1. Rate for low or high alarm indication
2. Total for alarm indication
3. Grand total for alarm indication
4. Modbus input
51
Page 52
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting the Relay Action
Operation of the relays is programmed in the Action menu. The relays may be set up for any of the following modes of operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
52
Page 53
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Programming Set and Reset Points
High alarm indication: program set point above reset point.
Low alarm indication: program set point below reset point.
The deadband is determined by the difference between set and reset points. Minimum deadband is one display count. If the set and reset points are programmed with the same value, the relay will reset one count below the set point.
Note: Changes are not saved until the reset point has been accepted.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the process variable is within safe limits and the relay coil is de-energized when the alarm condition exists. The fail-safe operation is set independently for each relay. Select
on to enable or select off to disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for each relay between 0 and 999.9 seconds. The relays will transfer only after the condition has been maintained for the corresponding time delay.
On time delay is associated with the set point.
The
Off time delay is associated with the reset point.
The
53
Page 54
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To detect a new alarm condition, the signal must go below the set point, and then go above it.
54
Page 55
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Low Alarm Operation (Set < Reset)
Input
Reset
Set
Relay
LED
energized
on
de-energized
off
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latc hing)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing above Reset (latching with clear)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back “on”, signal must go above set point and then go below it.
55
Page 56
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
High Alarm with Fail-Safe Operation (Set > Reset)
Input
Set
Reset
Relay
LED
energized
off
de-energized
on
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latching)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing below Reset (latching with clear)
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
56
Page 57
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Low Alarm with Fail-Safe Operation (Set < Reset)
Input
Reset
Set
Relay
LED
de-energized
on
energized
off
Automatic (non-latching)
Relay
LED
ACK
pressed
Automatic or Manual (non-latc hing)
Relay
LED
ACK
pressed
Manual (latching)
Relay
LED
ACK
pressed
Manual only after passing above Reset (latching with clear)
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
57
Page 58
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Alternation Control Operation
Input
Relay2 Set
Relay1 Set
Relay1 &
Relay2 Reset
de-energized energized
Pump 1
Pump 2
Input
Relay2 Set
Relay1 Set
Relay1 Reset
58
de-energized energized
Relay2 Reset
Pump 1
Pump 2
Input
Relay2 Set
Relay1 Set
Relay2 Reset
Relay1 Reset
LEDs indicate the relay status
de-energized energized
Pump 2
Pump 1
Page 59
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Rate Relay Sampling Operation
Input
Set
Reset
Relay
LED
Sample
Tim e
Sample
Tim e
Sample
Tim e
When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
Total Relay Sampling Operation
Total
300
200
100
Relay
LED
When the total reaches the preset, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the preset value is added to the total.
Preset = 100
Sample
Time
Sample
Time
Sample
Time
59
Page 60
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Time Delay Operation
The following graphs show the operation of the time delay function.
Input
Set
Reset
<Tdelay <Tdelay >=Tdelay
Relay
*
LED
On Time Delay
Input
Set
Reset
<Tdelay <Tdelay >=Tdelay
Relay
LED
*
Off Time Delay
When the signal crosses the set point, the
On time delay timer starts and
the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the delay timer resets and the relay does not change state. The same principle applies to the
Off time delay.
Note: If “Automatic or Manual” (A-nmAn) reset mode is selected, the LED
follows the reset point and not the relay state when the relay is acknowledged.
On time
60
Page 61
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2 or 4 optional internal relays and/or 4 external relays expansion module. Typical applications include high or low flow alarms and basic batch control. There are four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Alternation Control for up to 8 Relays
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm relays will reflect the state of the input to the meter. The following table indicates how the alarm LEDs and relays will react on power-up based on the set and reset points:
Alarm #
1 HI 1000 500 499 Off 2 LO 700 900 499 On 3 LO 250 400 499 Off 4 HI 450 200 499 On
HI or LO
Alarm
Set
Point
Reset
Point
Power-Up
Reading
Fail-Safe Operation
The following table indicates how the relays behave based on the fail­safe selection for each relay:
Fail-Safe
Selection
Off Open Closed Closed Open
On Closed Open Open Closed
Note: NO = Normally Open, NC = Normally Closed. This refers to the condition of the relay contacts when the power to the meter is off.
Non-Alarm State Alarm State
NO NC NO NC
Relay &
LED
Power Failure
Relays go to non-alarm state Relays go to alarm state
61
Page 62
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Front Panel LEDs
The LEDs on the front panel provide status indication for the following:
LED Status LED Status
1 Alarm 1 5 Alarm 5 2 Alarm 2 6 Alarm 6 3 Alarm 3 7 Alarm 7 4 Alarm 4 8 Alarm 8
The meter is supplied with four alarm points that include front panel LEDs to indicate alarm conditions. This standard feature is particularly useful for alarm applications that require visual-only indication. The LEDs are controlled by the set and reset points programmed by the user. When the display reaches a set point for a high or low alarm, the corresponding alarm LED will turn on. When the display returns to the reset point the LED will go off. The front panel LEDs respond differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and always on during alarm condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflects the status of the relays, regardless of the alarm condition. The following tables illustrate how the alarm LEDs function in relation to the relays and the acknowledge button (Default: F3 key assigned to ACK):
Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or non-latching (automatic reset) operation.
Relay terminology for following tables
Terminology Relay Condition
On Alarm (Tripped) Off Normal (Reset)
Ack Acknowledged
The On and Off terminology does not refer to the status of the relay’s coil, which depends on the fail-safe mode selected.
Warning!
In latching relay mode, latched relays will reset (unlatch) when power is cycled.
62
Page 63
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Non-Latching Relay (Auto)
Automatic reset only
Condition LED Relay
Normal Off Off Alarm On On Ack (No effect) On On Normal Off Off
In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm finally goes away, the relay automatically resets and the LED also goes off.
Non-Latching Relay (A-nman)
Automatic + manual reset at any time
Condition LED Relay
Normal Off Off Alarm On On Normal Off Off Next Alarm On On Ack On Off Normal Off Off
In this application, the meter is set up for automatic and manual reset at any time (non-latching relay). The LED and the relay automatically reset when the meter returns to the normal condition.
The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm condition still exists. This causes the relay to reset, but the LED stays on until the meter returns to the normal condition.
Latching Relay (LatcH)
Manual reset any time
Condition LED Relay
Normal Off Off Alarm On On Ack Off Off
In this application, the meter is set up for manual reset at any time. Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off the LED.
63
Page 64
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
ACK
Latching Relay (Lt-Clr)
Manual reset only after alarm condition has cleared
Condition LED Relay
Normal Off Off Alarm On On Ack (No effect) On On Normal On On Ack Off Off
In this application, the meter is set up for manual reset only after the signal passes the reset point (alarm condition has cleared). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm is acknowledged after it returns to the normal state, the LED and the relay go off. Notice that the LED remains on, even after the meter returns to the normal condition. This is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the alarm condition.
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual reset:
1. Via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of
the digital inputs and the +5 V terminals on the digital I/O modules, or using the F4 digital input, which is triggered with a contact closure to COM, or with an active low signal (see page
27).
When the ACK button or the assigned digital input is closed, all relays programmed for manual reset are acknowledged.
YPPA1044 Digital I/O Module
1 2 3 4 56 78910
I1 I2 I3 I4
+5
DI 1-4
O1 O2 O3 O4 G
DO 1-4
GND
Figure 20: Acknowledge Relays w/Function Key or Digital Input
64
Page 65
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:
1. Access the
2. In the Advanced features –
inputs to
3. Connect a switch or dry contac t between the +5V terminal and the
corresponding digital input (dI-1 to dI-4) terminal.
Setup – Relay – Action menu and set the action to off.
User menu program any of the digital
Force On any of the internal relays (1-4).
SW2
SW1
123456
+5 I1 I2 I3 I4 O1
5 VDC GND
DI 1-4 DO 1-4
65
78
O2 O3
910
O4 G
Page 66
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off) when SW1 & SW2 switches (above) are closed. If the contacts to these digital inputs are opened, the corresponding front panel LEDs flash indicating this condition. The processes being controlled by the interlock relay will stop, and will re-start only after the interlock relay is re­activated by the digital inputs (switc hes).
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) – i.e. both switches must be closed to trip the relay.
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range selected.
No equipment is needed to scale the analog output; simply program the display values to the corresponding mA output signal.
Analog Output menu is used to program the 4-20 mA output based
The on display values.
For instructions on how to program
numeric values see
Numeric Values
Setting
, page 37.
66
Page 67
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Reset Menu (reset)
The Reset menu is used to reset the totals, maximum or minimum reading (peak or valley) reached by the process; both may be reset at the same time by selecting “reset high & low” (
rst HL).
Control Menu (Contrl)
The Control menu is used to control the 4-20 mA analog output and the relays manually, ignoring the input. Each relay and analog output can be programmed independently for manual control. Selecting automatic control sets all relays and the analog output for automatic operation.
67
Page 68
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Setting Up the Password (pass)
The Password menu is used for programming three levels of security to prevent unauthorized changes to the programmed parameter settings and to program the non-resettable totalizer.
Pass 1: Allows use of function keys and digital i nputs Pass 2: Allows use of function keys, digital inputs a nd editing set/reset points Pass 3: Restricts all programming, functio n keys, and digital inputs. Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total m anually
Protecting or Locking the Meter
Enter the Password menu and program a six-digit password.
For instructions on how to program numeric values see
, page 37.
Values
Setting Numeric
Record the password for future reference. If appropriate, it may be recorded in the space provided.
Model:
Serial Number:
Password 1: __ __ __ __ __ __
Password 2: __ __ __ __ __ __
Password 3: __ __ __ __ __ __
Total __ __ __ __ __ __
GTotal __ __ __ __ __ __
68
Page 69
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Total Reset Password & Non-Resettable Total
The total and the grand total can be password-protected to prevent unauthorized total resets.
The grand total can be programmed as a non-resettable total by entering the password “050873”.
!
Caution!
Once the Grand Total has been programmed as “non­resettable” the feature cannot
be disabled.
69
Page 70
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Making Changes to a Password Protected Meter
If the meter is password protected, the meter will display the message
Locd (Locked) when the Menu button is pressed. Press the Enter button
while the message is being displayed and enter the correct password to gain access the menu. After exiting the programming mode, the meter returns to its password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu and enter the correct password twice, as shown below. The meter is now unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the message password is programmed.
If the password entered is incorrect, the meter displays the message
Locd (Locked) for about two seconds, and then it returns to Run Mode.
To try again, press Enter while the
unLoc (unlocked) and the protection is disabled until a new
Locked message is displayed.
The password may be disabled b y entering a master
Did you forget the password?
password once. If you are authoriz ed to make changes, enter the master password 508655 to unl ock the meter.
70
Page 71
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
71
Page 72
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced
Features
menu in the order they appear in the menu.
Display Parameter Action/Setting
Gate
Lo G
Hi G
filter
Lo Spd
Hi Spd
Round
seriAl
SlaveId
baud
Tr dLY
Parity
t-byt
SelEct
Functn
Linear
No PtS
CutofF
Count
Gate
Low gate
High gate
Filter
Low speed
High speed
Round
Serial
Slave ID
Baud rate
Transmit delay
Parity
Time byte
Select
Signal input conditioning
Linear
Number of points
Cutoff
Count
Enter Gate function menu
Program Low gate value
Program High gate value
Enter the Filter menu
Set the contact de-bounce filter value
Select high speed filter
Set the rounding value for display variables
Set serial communication parameters
Set slave ID or meter address
Select baud rate
Set transmit delay for serial communication
Select parity Even, Odd, or None with 1 or 2 stop bits
Set byte-to-byte timeout
Enter the Select menu (function, cutoff, out)
Select linear only, other functions are not applicable to pulse input
Set meter for linear function and selec t number of linearization points
Set meter for 2 to 32-point linearization
Set low-flow cutoff
Set the totals to count up or down from a set value
72
Page 73
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting
Tot C
Gtot C
AoutPr
Source
O-rang
u-rang
mAx
min
Calib
4 mA
20 mA
user
F1
F2
Total count
Grand total count
Analog output programming
Source
Overrange
Underrange
Maximum
Minimum
Calibrate
4 mA output
20 mA output
User I/O
F1 function key
F2 function key
Set the total to count up to or down from the programmed total value
Set the grand total to count up or do wn from from the programmed grand total value
Program analog output parameters
Select source for the 4-20 mA output
Program mA output for display overrange
Program mA output for display underrange
Program maximum mA output allowed
Program minimum mA output allowed
Calibrate 4-20 mA output (internal reference source used for scaling th e output)
Enter mA output value read by milliamp meter with at least 0.001 mA resolut ion
Enter mA output value read by milliamp meter with at least 0.001 mA resolut ion
Assign function keys and digital I/O
Assign F1 function key
Assign F2 function key
F3
F4
dI I
dO 1
Copy
send
F3 function key
F4 function
Digital input 1
Digital output 1
Copy
Send
Assign F3 function key
Assign F4 function (digital input)
Assign digital input 1 – 8, if expansion modules are connected
Assign digital output 1 – 8, if expansion modules are connected
Enter copy function
Send meter settings to another meter
73
Page 74
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting
done
Diag
Filter
Round
Functn
SCALE
Factor
Gate
Cutoff
T tb
T CF
T rst
Gt tb
Gt Cf
Gt rst
Done
Diagnostics
Filter
Round
Function
Scale
K-factor
Gate
Cutoff
Total time base
Total conver­sion factor
Total reset
Grand total time base
GT conversion factor
Grand total
Copy function completed
Display parameter settings
Display filter selection
Round the display values to the nearest entered multiple
Function selected
Scaling parameter
K-factor value
Gate settings
Cutoff value
Set time period
Set conversion factor
Set reset method
Set grand total time period
Set grand total conversion factor
Set grand total reset method
Dsplay
RELAY
Aout
Aoutpr
SEriaL
LED t
Info
Display
Relays
Analog output
Analog output programming
Serial
LED test
Information
Display assignments
Relay settings
Analog output scaling
Analog output programming
Serial communication settings
Test all LEDs
Display software and S/N information
74
Page 75
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used in addition to the filter function.
Rounding causes the display to round to the nearest value according to the rounding selected. This setting affects the last two digits, regardless of decimal point position.
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an RS-232, RS-485, or USB adapter option is required; see
Information
Warning!
Note: More detailed instructions are provided with each optional serial
on page 8 for details.
Do not connect any equipment other than Yokogawa’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
communications adapter. Note: Refer to the Register Tables located at www.yokogawa-usa.com for details.
Ordering
PROPLUS Modbus
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
The YPP6300 can also be connected to another YPP6300 with a special YPPA1200 cable, allowing the user to copy all the settings from one meter to another, using the
Copy function.
75
Page 76
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Select Menu (SElEct)
The Select menu is used to select the signal input conditioner applied to the input (linear), low-flow cutoff, and analog output programming. The multi-point linearization is part of the linear function selection.
Signal Input Conditioning (Functn)
The Function menu is used to select the signal input conditioner applied to the input: linear, where the multi-point linearization is part of the linear function selection.
Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a display that is linear with respect to the input signal.
76
Page 77
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected under the linear function. display for non-linear signals.
The multi-point linearization can be used to linearize the
77
Page 78
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will display zero below the cutoff value. Programming the cutoff value to zero disables the cutoff feature.
Analog Output Programming (AoutPr)
The Analog Output Programming menu is used to program the behavior of the 4-20 mA output. The following parameters and functions are programmed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Max: Maximum analog output value allowed regardless of input
5. Min: Minimum analog output value allowed regardless of input
6. Calibrate: Calibrate the internal 4-20 mA source reference used to scale the 4-20 mA output
Analog Output Source
The source for generating the 4-20 mA output may be assigned to the rate/process variable, total, grand total, maximum or minimum value reached by the rate/process, one of the set points, or the Modbus PV input.
Analog Output Calibration
To perform the analog output calibration it’s recommended to use a milliamp meter with a resolution of at least 0.1 µA to measure the ou tput current. The values saved internally during this procedure are used for scaling the 4-20 mA output in the
Setup menu.
78
Page 79
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel func tion keys F1, F2, F3, F4 (digital input) and up to eight digital inputs to access most of the menus or to activate functions immediately (e.g. Reset max & min). Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter (e.g. Alarms, relay acknowledgement, etc.).
*If installed
Function Keys & Digital I/O Available Settings
Display Description Display Description
Rst HL
relay
Set 1
Rly d
Rly E
O Hold
d Hold
Big Hi
Big Lo
Big HL
Lit Hi
Lit Lo
Lit HL
Lit gt
Contrl
disabl
AcH
Reset max & min
Relay menu
Set point 1 - 8
Disable relay
Enable relay
Relays & output hold
Display hold
Max on Upper display
Min on Upper display
Max/min Upper display
Max on Lower display
Min on Lower display
Max/min Lower display
Lower display grand total
Control Menu
Disable function key
Acknowledge relays
Reset
Rst t
Rst Gt
Rst Hi
Rst Lo
Dsplay
Big
Little
menu
Right
up
Enter
Alm 1
F on 1
F on 2
F on 3
F on 4
Reset menu
Reset total
Reset grand total
Reset max
Reset min
Display menu
Upper display menu
Lower display menu
Menu button
Right arrow button
Up arrow button
Enter button
Alarm 1 – 8
Force on relay 1
Force on relay 2
Force on relay 3
Force on relay 4
79
Page 80
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
A
Meter Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one meter to other meters requiring exactly the same setup and programming (
i.e. type of input, scaling, decimal point, filter, gate, etc.).
Only the YPP
1200 meter copy cable must be used
for meter-to-meter interfacing.
Warning!
Using standard CAT5 or other cable will cause damage to both meters.
YPPA1200 Meter Copy
Figure 21: Meter Copy Connection
Copy Function Requirements
To successfully copy settings from one meter to another, both meters must have:
1. Same software version
2. Same baud rate setting
See Determining Software Version,
page 84 for instructions.
80
Page 81
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Meter Copy or Cloning Instructions
Do not connect the two meters to
!
Caution!
1. Connect two meters using a YPPA1200 meter copy cable.
Use YPPA1200 meter copy cable only! Using standard CAT5 or other cable will cause
Warning!
2. Do not connect the two meters to the same signal source.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter the
Advanced Features Menu page 71.
5. Scroll to the Enter.
6. The meter displays the message flashes while sending data.
damage to both meters.
Advanced Features menu of the Master meter see
Copy function using the Up arrow button then press
the same signal source while cloning. Internal calibration may be affected.
Send. Press Enter, the display
7. The Clone meter displays the message CPY rC while being programmed then the message done when copying is completed. The meter initializes and returns to Run Mode using the same settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer
Copy Function Requirements above.
to
81
Page 82
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
METER OPERATION
The meter accepts pulses (e.g. ±40mV to ± 8V), square wave (0-5, 0­12V, or 0-24V), open collector NPN, PNP, TTL, or switch contact signals and displays these signals in engineering units from -99999 to 999999.
The dual-line display can be customized by the user to operate in such a way as to satisfy a specific application. Typically the upper display is used for the process variable; while the lower display is used for engineering units, custom legend, total, grand total, or set point indication.
The meter can be set up to display the pulse input on the upper display and the Modbus input on the lower display. The relays and analog output can be programmed to operate from the Modbus PV input.
Front Panel Buttons Operation
Button Symbol
Description
Press to enter or exit Programming Mode, view settings, or exit max/min readings
Press to reset max/min readings or other parameter/function assigned through the
User menu
Press to display max/min readings or other parameter/function assigned through the
User menu
Press to acknowledge relays or other parameters/function assigned through the
User menu
Function Keys Operation
During operation, the programmable function keys operate according to the way they have been programmed in the Advanced Features – User menu.
The table above shows the factory default settings for F1, F2, and F3.
82
Page 83
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact clos ure to COM, or with an active low signal. During operation, F4 operates according to the way is has been programmed in the
Advanced Features – User menu.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or momentarily:
1. Display briefly by assigning to the F1-F3 function keys, F4 (digital input) or to the digital inputs in the
2. Display continuously by assigning either display to max/min through
Display menu.
the
Any of the F1-F3 function keys (buttons), F4 (digital input), and the digital inputs can be programmed to reset the max & min readings. The meters are set at the factory to display the max reading by pressing the Up arrow/F2 button and to use the Right arrow/F1 button to access the
Reset menu.
To display max reading using function key with factory defaults:
1. Press Up arrow/F2 button to display maximum reading since the last reset/power-up.
2. To reset max/min press Right arrow/F1 button to access the Reset menu. The max & min displays are reset to actual values.
3. Press Menu to exit max/min display reading.
To display max/min readings continuously:
Assign either display to Max (d Hi), Min (d Lo), or toggle between Max and Min (
d HL) every 10 seconds.
User menu.
83
Page 84
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
TROUBLESHOOTING
The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see.
If the meter is not working as expected, refer to the and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced Features menu, to
Diagnostics menu see Advanced Features Menu, page 71.
access
It provides an easy way to view the programmed parameter settings for troubleshooting purposes . Press the Enter and the Menu button to exit at any time.
For a description of the diagnostic messages,
Display Messages, page 72.
Menu &
Determining Software Version
To determine the software version of a meter:
1. Go to the
2. Press Up arrow button and scroll to Information menu (
3. Press Enter to access the software number ( version ( displayed. Continue pressing Enter until all the information is displayed.
4. The meter returns to Run Mode after displaying all the settings.
Diagnostics menu (diAG) and press Enter button.
UER) information. Write down the information as it is
button to view the settings
Diagnostics menu
see Advanced Features
Info).
SFT) and
84
Page 85
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See Advanced Features Menu,
page 71.
2. Press Up arrow to go to
3. Press and hold Right arrow for three seconds, press Enter when display flashes Note: If Enter is not pressed within three seconds, the display returns to the
4. The meter goes through an initialization sequence (similar as on power-up), and loads the factory default settings.
Diagnostics menu.
Diagnostics menu
reset.
85
Page 86
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application.
Model: ______________ S/N: _______________ Date: _________
Parameter Display Default Setting User Setting
Input type
Total
Units
Filter
K-factor
Function
Number of points
Input 1
Display 1
Input 2
Display 2
Decimal point
Cutoff value
Display assignment
Upper display
Lower display
Display intensity
Total time base
Total conversion factor
Total reset
Grand total time base
Grand total conversion factor
Grand total reset
Input
yes
units
filter
Factor
Functn
No Pts
InP 1
Dis 1
InP 2
Dis 2
Ddddd.d
CutofF
dSPLAY
big
Little
d-Inty
T tb
T CF
T rst
GT tb
T CF
T rst
Pulse
Total enabled
Rate / total / gr. total pulse / pulse / pulse
Hi Spd
1.000
Linear
2
00000.0
00000.0
10000.0
10000.0
1 place
0.000 (disabled)
Rate/Process
Total value
8
Second
1.000
Manual
Second
1.000
Manual
86
Page 87
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Parameter Display Default Setting User Setting
Relay 1 assignment
Relay 2 assignment
Relay 3 assignment
Relay 4 assignment
Relay 1 action
Relay 1 set point
Relay 1 reset point
Relay 2 action
Relay 2 set point
Relay 2 reset point
Relay 3 action
Relay 3 set point
Relay 3 reset point
Relay 4 action
Relay 4 set point
Relay 4 reset point
Fail-safe relay 1
Fail-safe relay 2
Fail-safe relay 3
Fail-safe relay 4
On delay relay 1
Off delay relay 1
On delay relay 2
Off delay relay 2
On delay relay 3
Off delay relay 3
On delay relay 4
Off delay relay 4
Display 1 analog out
Output 1 value
Asign1
Asign2
Asign3
Asign4
Act 1
Set 1
RSt 1
Act 2
Set 2
RSt 2
Act 3
Set 3
RSt 3
Act 4
Set 4
RSt 4
Fls 1
Fls 2
Fls 3
Fls 4
On 1
Off 1
On 2
Off 2
On 3
Off 3
On 4
Off 4
Dis 1
Out 1
Total
Total
Rate
Rate
Automatic
100.0
000.0
Automatic
200.0
000.0
Automatic
300.0
250.0
Automatic
400.0
350.0
Off
Off
Off
Off
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0
4.000 mA
87
Page 88
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Parameter Display Default Setting User Setting
Display 2 analog out
Output 2 value
Source analog output
Overrange output
Underrange output
Maximum output
Minimum output
Slave ID (Address)
Baud rate
Transmit delay
Parity
Byte-to-byte timeout
F1 function key
F2 function key
F3 function key
F4 function
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Password 1
Password 2
Password 3
Total password
Grand total password
Dis 2
Out 2
Source
O-rang
u-rang
mAx
min
Slave Id
baud
Tr dly
Parity
t-byt
F1
F2
F3
F4
dI 1
dI 2
dI 3
dI 4
dO 1
dO 2
dO 3
dO 4
Pass 1
Pass 2
Pass 3
Total
Gtotal
1000.0
20.000 mA
Rate/process
21.000 mA
3.000 mA
23.000 mA
1.000 mA
247
9600
50 ms
Even
010 (0.1 sec)
Reset max & min
Upper display: Max (Hi)
Acknowledge relays
Acknowledge relays
Menu
Right arrow
Up arrow
Enter
Alarm 1
Alarm 2
Alarm 3
Alarm 4
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
88
Page 89
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Troubleshooting Tips
Symptom Check/Action
No display at all
Not able to change setup or programming, Locd is displayed
Meter displays error message during calibration (Error)
Meter displays
999999
-99999
Display is unstable
Display response is too slow
Display reading is not accurate
Display does not respond to input changes, reading a fixed number
Display alternates between
1. Hi and a number
2. Lo and a number
Relay operation is reversed
Relay and status LED do not respond to signal
Flashing relay status LEDs
Meter not communicating with application programs
If the display locks up or the meter does not respond at all
Other symptoms not described above
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from factory defaults and map changes ahead of time, rather than at random.
Check power at power connector
Meter is password-protected, enter correct six-digit password to unlock
Check:
1. Signal connections
2. Minimum input span requirements Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal connector
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filt er and gate values
Check filter and gate values
Check:
Scaling or calibration
Check:
Display assignment, it might be
displaying max, min, or set point. Press Menu to exit max/min display readings.
Check:
1. Fail-safe in Setup menu
2. Wiring of relay contacts Check:
1. Relay action in Setup menu
2. Set and reset points Relays in manual control mode or rela y interlock switches opened. Check:
1. Serial adapter and cable
2. Serial settings
3. Meter Slave ID and baud rate Cycle the power to reboot the microprocessor.
Call Technical Support for assistance.
89
Page 90
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Alphabetical List of Display Functions & Messages
Display Parameter Action/Setting Description
20 mA
4 mA
999999
AcH
Act 1
Alm 1
Altern
A-nman
Aout
Aoutpr
Asign1
Assign
Auto
Auto
baud
big
Big Hi
Big HL
Big Lo
Cal
20 mA output
4 mA output
Flashing display
Acknowledge Acknowledge relays
Action 1
Alarm 1
Alternate
Auto-manual
Analog output
Analog output programming
Assign 1
Assignment
Automatic
Automatic
Baud rate
Upper display
Max on Upper display
Max/min Upper display
Min on Upper display
Calibrate
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
Overrange condition
Set relay 1 action
Assign digital output to Alarm 1 – 8
Set relay for alternation control (relays assigned to rate)
Set relay for automatic & manual reset any time
Analog output scaling
Analog output programming
Relay 1 assignment
Assign relays to rate, total, or grand total
Press Enter to set meter for automatic operation
For automatic reset
Select baud rate
Press Enter to assign the Upper display parameter (default: PV or rate)
Assign digital input to display max on the Upper display
Assign digital input to toggle max/min o n the Upper display
Assign the digital input to display min on the Upper display
Enter the Calibrate menu
90
Page 91
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting Description
Calib
Contrl
Copy
Count
Cutoff
D Hi
D HL
D Hold
D Lo
D r_u
D unit
Dec pt
DeLAY
dI 1
Diag
d-Inty
Dis 1
Dis 2
disabl
DLY 1
dO 1
done
DSet 1
dsplay
Calibrate
Control
Copy
Count
Cutoff
Display high
Display H&L
Display hold
Display low
Display r-u
Display units
Decimal point
Delay
Digital input 1
Diagnostics
Display intensity
Display 1
Display 2
Delay 1 Enter relay 1 time delay setup
Digital output 1
Done
Display set 1
Display
Calibrate 4-20 mA output (internal reference source used for scaling the output)
Enter Control menu
Enter copy function
Set total and grand total count direction
Cutoff value
Select to display the max
Select to display the max & min toggling
Display hold
Select to display the min
Select to display rate and units
Select to display engineering units or label
Set decimal point for rate, total, grand total
Enter relay Time Delay menu
Assign digital input 1-8, if expansion modules are connected
Display parameter settings
Set display intensity level from 1 to 8
Program display 1 value
Program display 2 value
Disable function key
Assign digital output 1 – 8, if expansion modules are connected
Copy function completed
Select to display set point 1 (1-8)
Enter the Display menu
91
Page 92
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting Description
Enter
Error
F On 1
F1
F2
F3
F4
factor
FaiLSF
filter
FLS 1
Force
Functn
G total
GT CF
GT rst
GT tb
Gtot C
Gtotal
Info
InCAL
Inp 1
Enter
Error
Force On 1
F1 function key
F2 function key
F3 function key
F4 function
K-factor Scaling
Fail-safe
Filter
Fail-safe 1
Force
Function
Grand total
Grand total conversion factor
Grand total reset
Grand total time base
Grand Total Count
Grand total password
Information
Input Calibration
Input 1
Assign digital input to Enter button/F3
Error, calibration not successful, check s ignal or programmed value
Force relay 1 on using digital input (1-8)
Assign F1 function key
Assign F2 function key
Assign F3 function key
Assign F4 function (digital input)
Programs unit to convert input pulse to rate in engineering units
Enter Fail-safe menu
Set noise filter value
Set relay 1 fail-safe operation
Force analog output value for loop break
Select linear only, other functions are not applicable
Assign relay to grand total
Program grand total conversion factor
Program grand total rest mode: auto or manual
Program grand total time base
Set grand total to count up or down
Set or enter password for manual reset
Display software and S/N information
Enter the Input Calibration menu
Calibrate input 1 signal or program in put 1 value
92
Page 93
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting Description
Inp 2
Input
LatcH
LED t
Length
Linear
Lit gt
Lit Hi
Lit HL
Lit Lo
Little
locd
Lt-CLr
mAn
mAx
mbus
menu
min
No PtS
nonrst
O Hold
Input 2
Input
Latching
LED test
Length
Linear
Grand total on Lower display
Max on Lower display
Max/min Lower display
Min on Lower display
Lower display
Locked
Latching-cleared
Manual
Maximum
Modbus
Menu button
Minimum
Number of points
Non-resettable
Relays output hold
Calibrate input 2 signal or program in put 2 value (up to 32 points)
Input selection
Set relay for latching operation (relays assigned to rate)
Test all LEDs
Not applicable
Set meter for linear function and select number of linearization points
Assign the digital input to display the g rand total on the Lower display
Assign digital input to display max on the lower display
Assign the digital input to toggle max/m in on the lower display
Assign digital input to display min on the lower display
To assign the lower display parameters
Enter password to unlock meter
Set relay for latching operation with manual reset only after alarm condition has c leared (relays assigned to rate)
To manually control
Program maximum mA output allowed
Select to display Modbus input or to assign Modbus input as the analog output source
Assign digital input to Menu button
Program minimum mA output allowed
Set meter for 2 to 32-point linearization
Non-resettable grand total set afte r entering “050873” for Gtotal password
Assign digital input to hold all relays state
93
Page 94
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting Description
OFF
OFF 1
On
On 1
O-rang
Out 1
Out 2
pass
Pass 1
Pass 2
Pass 3
prog
Prog E
rATE
RELaY
reset
Right
RLY 1
RLY 2
Rly d
Rly E
RSt 1
Rst Gt
Off
Off
On
On
Overrange
Output 1
Output 2
Password
Password 1
Password 2
Password 3
Program
Programmable exponent
Rate
Relay
Reset
Right arrow
Relay 1
Relay 2
Disable relay
Enable relay
Reset 1
Reset grand total
Disable relay and front panel status LED, turn relays off, program off time delay
Disable relay and front panel status LED, turn relays off, program off time delay
Enable fail-safe operation, turn relays on, program on time delay
Set relay 1 On time delay
Program mA output for display overrange
Program output 1 value (e.g. 4.000 mA)
Program output 2 value (e.g. 20.000 mA)
Enter the Password menu
Set or enter Password 1
Set or enter Password 2
Set or enter Password 3
Enter the Program menu
Set meter for programmable exponent a nd enter exponent value
Assign relay to rate
Enter the Relay menu
To access the Reset menu
Assign digital input to Right arrow button/F1
Relay 1 setup
Relays 2-8 setup
Note: Relays 5-8 are shown, only if expansion relay module is installed.
Assign digital input to disable all relays
Assign digital input to enable all relays
Program reset point 1
To reset grand total
94
Page 95
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting Description
Rst Hi
Rst HL
Rst Lo
Rst t
Sanmpl
sCalE
SelEct
send
seriAl
Set 1
setup
SlavId
Source
T CF
T dly
T rst
T tb
Tot C
Total
Tr dLY
units
unloc
up
u-rang
user
Reset high
Reset high & low
Reset low
Reset total
Sampling
Scale
Select
Send
Serial
Set 1
Setup
Slave ID
Source
Total conversion factor
Time delay
Total reset
Total time base
Total Count
Total
Transmit delay
Units
Unlocked
Up arrow
Underrange
User I/O
Press Enter to reset max display
Press Enter to reset max & min displays
Press Enter to reset min display
Reset total
Set relay for sampling operation
Enter the Scale menu
Enter the Select menu (function, cutoff, output)
Send meter settings to another meter
Set serial communication parameters
Program set point 1
Enter Setup menu
Set Slave ID or meter address
Select source for the 4-20 mA output
Program total conversion factor
Program time delay for total auto reset
Program total rest mode: auto or manual
Program total time base
Set total to count up or down
Enable or disable totalizer features
Set transmit delay for serial communication
Select the display units/tags
Program password to lock meter
Assign digital input to up arrow button/F2
Program mA output for display underrange
Assign function keys and digital I/O
95
Page 96
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
96
Page 97
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Figure 22: 1/8 DIN Panel Cutout Template
97
Page 98
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
Intentionally
Left Blank
98
Page 99
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
NOTES
99
Page 100
Model YPP6300 Pulse Input Rate/Totalizer Instruction Manual
LIM6300YK_B
SFT039 Ver 3.100 & up
08/12
Loading...